Quantum Using Ecostruxure™ Control Expert: Experts and Communication Reference Manual
Quantum Using Ecostruxure™ Control Expert: Experts and Communication Reference Manual
35010574 12/2018
Quantum using
EcoStruxure™
Control Expert
Experts and Communication
Reference Manual
(Original Document)
12/2018
35010574.15
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of
this document on any medium whatsoever without permission of Schneider Electric, given in
writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of
the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at
your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2018 Schneider Electric. All rights reserved.
2 35010574 12/2018
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Part I Software Configuration . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 1 Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mapping a Local Quantum I/O Station . . . . . . . . . . . . . . . . . . . . . . . . 18
Open the Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Chapter 2 Quantum Addressing Modes . . . . . . . . . . . . . . . . . . . . . 21
Flat Addressing—800 Series I/O Modules . . . . . . . . . . . . . . . . . . . . . 22
Topological Addressing—800 Series I/O Modules with Control Expert 23
IODDT Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Quantum IODDTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Addressing Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Discrete I/O Bit Numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
I/O Module Status Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Part II Quantum Remote I/O (RIO) Modules . . . . . . . . . . . . 33
Chapter 3 140 CRP 931 00: Remote I/O (RIO) Head Module (single
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 4 140 CRP 932 00: Remote I/O (RIO) Head Module (dual
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 5 140 CRA 931 00: Remote I/O (RIO) Drop Module (single
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
35010574 12/2018 3
Chapter 6 140 CRA 932 00: Remote I/O (RIO) Drop Module (dual
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Chapter 7 140 NRP 954 00: Fiber Optic Repeater Module
(Multimode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
LED Indicators and Diagnostic Relay Behavior . . . . . . . . . . . . . . . . . . 63
Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Chapter 8 140 NRP 954 01C: Fiber Optic Repeater Module (Single-
mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
LED Indicators and Diagnostic Relay Behavior . . . . . . . . . . . . . . . . . . 83
Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Part III Quantum Distributed I/O (DIO) Drop Modules . . . . . 99
Chapter 9 Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Configuring a Quantum DIO Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Chapter 10 140 CRA 211 10: DIO Drop Module 115/230 VAC (single
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Chapter 11 140 CRA 212 10: DIO Drop Module 115/230 VAC (dual
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
4 35010574 12/2018
Chapter 12 140 CRA 211 20: DIO Drop Module 24 VDC (single
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Chapter 13 140 CRA 212 20: DIO Drop Module 24 VDC (dual
channel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Part IV Modbus Plus Network Option Modules (NOM) . . . . . 137
Chapter 14 140 NOM 211 00: Modbus Plus Option Module . . . . . . . 139
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Chapter 15 140 NOM 212 00: Modbus Plus Option Module . . . . . . . 151
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Chapter 16 140 NOM 252 00: Modbus Plus Option Module 10Base-
FL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Fiber Optic Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Part V Quantum Ethernet Modules . . . . . . . . . . . . . . . . . . . 183
Chapter 17 140 NOE xxx xx: Ethernet Module General Overview . . 185
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Modicon Quantum Ethernet Modules Overview . . . . . . . . . . . . . . . . . 187
Indicators for Ethernet Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
35010574 12/2018 5
Chapter 18 140 NOE 211 x0: TCP/IP 10Base-T Ethernet Module . . . 195
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Chapter 19 140 NOE 251 x0: TCP/IP 10Base-FL Ethernet Module . . 201
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Chapter 20 140 NOE 311 00: SY/MAX 10Base-T Ethernet Module . . 207
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Chapter 21 140 NOE 351 00: SY/MAX 10Base-FL Ethernet Module . 213
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Chapter 22 140 NOE 771 00: TCP/IP 10/100 Ethernet Module . . . . . 219
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
Chapter 23 140 NOE 771 01: TCP/IP 10/100 Ethernet Module . . . . . 225
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Chapter 24 140 NOE 771 10: TCP/IP 10/100 FactoryCast Ethernet
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Chapter 25 140 NOE 771 11: TCP/IP 10/100 FactoryCast Ethernet
Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
6 35010574 12/2018
Chapter 26 140 NWM 100 00: TCP/IP 10/100 FactoryCast HMI
Ethernet Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Part VI Quantum Field Bus Modules . . . . . . . . . . . . . . . . . . 249
Chapter 27 140 EIA 921 00: AS-i Master Communication Module . . 251
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Part VII Quantum Special Purpose / Intelligent Modules . . . . 261
Chapter 28 140 HLI 340 00: High Speed Latch and Interrupt Module 263
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Chapter 29 140 EHC 202 00: High Speed Counter Module . . . . . . . 273
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Controlling and Timing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
Operating Conditions and Examples . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
I/O Map and Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
35010574 12/2018 7
Chapter 30 140 EHC 105 00: High Speed Counter Module . . . . . . . . 317
Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
8 35010574 12/2018
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, service, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.
35010574 12/2018 9
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have
point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on
factors such as the control function required, degree of protection required, production methods,
unusual conditions, government regulations, etc. In some applications, more than one processor
may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and
factors present during setup, operation, and maintenance of the machine and, therefore, can
determine the automation equipment and the related safeties and interlocks which can be properly
used. When selecting automation and control equipment and related software for a particular
application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States
of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as point-
of-operation guarding must be provided. This is necessary if the operator's hands and other parts
of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software
cannot be substituted for or take the place of point-of-operation protection.
10 35010574 12/2018
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation
protection have been installed and are operational before placing the equipment into service. All
interlocks and safeties related to point-of-operation protection must be coordinated with the related
automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation
protection is outside the scope of the Function Block Library, System User Guide, or other
implementation referenced in this documentation.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means
used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not
installed according to local regulations (according to the National Electrical Code in the U.S.A, for
instance). If high-potential voltage testing is necessary, follow recommendations in equipment
documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
35010574 12/2018 11
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English
version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection
and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe
operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment
manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to
the operator. Access to other controls should be restricted to prevent unauthorized changes in
operating characteristics.
12 35010574 12/2018
About the Book
At a Glance
Document Scope
This document is the reference for the networking, communication, and special purpose modules
of the Quantum automation system with Control Expert.
Validity Note
This document is valid for EcoStruxure™ Control Expert 14.0 or later.
The technical characteristics of the devices described in the present document also appear online.
To access the information online:
Step Action
1 Go to the Schneider Electric home page www.schneider-electric.com.
2 In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks (*).
3 If you entered a reference, go to the Product Datasheets search results and click on the
reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click
on the product range that interests you.
4 If more than one reference appears in the Products search results, click on the reference that
interests you.
5 Depending on the size of your screen, you may need to scroll down to see the data sheet.
6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in the present document should be the same as those
characteristics that appear online. In line with our policy of constant improvement, we may revise
content over time to improve clarity and accuracy. If you see a difference between the document
and online information, use the online information as your reference.
Related Documents
You can download these technical publications and other technical information from our website
at https://www.schneider-electric.com/en/download
35010574 12/2018 13
Product Related Information
WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control
systems. Only persons with such expertise should be allowed to program, install, alter, and apply
this product.
Follow all local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
14 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
Software Configuration
35010574 12/2018
Part I
Software Configuration
Software Configuration
Introduction
This part provides information on the Software Configuration of the networking and
intelligent/special purpose modules.
35010574 12/2018 15
Software Configuration
16 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
Module Configuration
35010574 12/2018
Chapter 1
Module Configuration
Module Configuration
Purpose
This chapter provides information on software configuration of the module.
35010574 12/2018 17
Module Configuration
Overview
Use the following dialog to map an existing local Quantum I/O station with a new module.
Step Action
1 Call the Bus Editor
2 Mark a free slot in the local station (left mouse button)
3 Move the mouse pointer over the marked slot
4 Click on the right mouse button
Result: A shortcut menu is opened
18 35010574 12/2018
Module Configuration
Overview
The following dialog box enables you to call the parameter configuration for a module.
An explanation of the individual parameters can be found in the respective module chapters.
Step Action
1 Call the Bus Editor
2 Select the module
3 Click on the right mouse button
Result: A shortcut menu is opened
35010574 12/2018 19
Module Configuration
20 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
Addressing Modes
35010574 12/2018
Chapter 2
Quantum Addressing Modes
Purpose
This chapter provides information on the three different modes Control Expert allows to address
the I/O data from a Quantum I/O module:
Flat Addressing
Topological Addressing
IODDT Addressing
35010574 12/2018 21
Addressing Modes
Introduction
800 series I/O modules follow a system of flat address mapping in Control Expert. To work
properly. each module requires a determinate number of bits and/or words. The IEC addressing
system is equivalent to the 984LL register addressing. Use the following assignments:
0x is now %Mx
1x is now %Ix
3x is now %IWx
4x is now %MWx
The following table shows the relationship between 984LL notation and IEC notation.
Step Action
1 Enter the address range in the configuration screen.
Examples
The following examples show the relationship between 984LL register addressing and IEC
addressing:
000001 is now %M1
100101 is now %I101
301024 is now %IW1024
400010 is now %MW10
22 35010574 12/2018
Addressing Modes
To read Action
input value (rank = 0) from channel 7 of an analog module Enter
located in slot 6 of a local rack: %IW1.6.7[.0]
input value (rank = 0) from channel 7 of an analog module Enter
located in slot 6 of drop 3 of RIO bus 2: %IW\2.3\1.6.7[.0]
’out of range’ value (rank = 1) from channel 7 of an analog Enter
module located in slot 6 of a local rack: %I1.6.7.1[.0]
35010574 12/2018 23
Addressing Modes
IODDT Addressing
IODDT Addressing
An IODDT allows all information (bits and registers) related to a channel to be handled through a
user-defined variable. This variable is defined in the Control Expert data editor by selecting the
appropriate IODDT for the module as a data type and specifying the topological address of the
module using the following syntax:
%CH[\b.e\]r.m.c
where:
b = bus
e = equipment (drop)
r = rack
m = module slot
c = channel
Here is an example of an IODDT for a thermocouple input module in slot 4 of a local rack:
24 35010574 12/2018
Addressing Modes
Quantum IODDTs
Introduction
Control Expert provides a couple of IODDTs which are either generic and can be used for several
I/O modules or belong to one specific module.
NOTE: Deviating from the general description of the data types in the Direct Addressing Data
Instances chapter in the EcoStruxure™ Control Expert Reference Manual, in Quantum IODDTs for
analog modules and expert modules the data type Bool is used for %I and %Q.
T_ANA_IN_VE
T_ANA_IN_VE is used with all channels of the following I/O modules:
ACI 030 00
AII 330 10
ACI 040 00
ACI 040 00
T_ANA_IN_VWE
T_ANA_IN_VWE is used with all channels of the following I/O modules:
ARI 030 10,
AVI 030 00
ATI 030 00
AII 330 00
and
Channels 3 and 4 of AMM 090 00
IODDT for analog input modules supporting Value, Warning and Error
35010574 12/2018 25
Addressing Modes
T_ANA_BI_VWE
T_ANA_BI_VWE is used with the following I/O modules:
Channels 1 and 2 of AMM 090 00
IODDT for bidirectional analog modules supporting Value, Warning and Error
T_CNT_105
T_CNT_105 is used with all channels of the following I/O modules:
EHC 105
Specific IODDT for high speed counter module EHC 105
26 35010574 12/2018
Addressing Modes
Addressing Example
NOTE: For the IODDT the data type T_ANA_IN_VWE is used and the variable My_Temp with the
address %CH1.5.10 was defined.
For comparison, the register addressing as used with Concept is added in the last column. As
Concept does not support direct addressing of a bit in a word, the bit extraction has to be performed
in the user program.
35010574 12/2018 27
Addressing Modes
Introduction
The numbering of channels of an I/O module usually starts with 1 and counts up to the maximum
number of supported channels. The software however starts numbering with a 0 for the least
significant bit in a word (LSB). The Quantum I/O modules have their lowest channel mapped to the
most significant bit (MSB).
The following figure shows the mapping of I/O channels related to the bits in a word:.
28 35010574 12/2018
Addressing Modes
35010574 12/2018 29
Addressing Modes
The following illustration shows how one word of the table conveys the status information for two
modules:
30 35010574 12/2018
Addressing Modes
Example
The following example shows a rack and the corresponding I/O status bytes displayed in an
animation table. The drop is configured to start at word %IW100 and allocates 16 words. This
represents the local and expansion rack, and assumes they are 16 slot racks.
If a module does not have have a status byte associated with the module or the slot is empty, then
the byte = 0.
Rack configuration and animation table:
Relation between slot, input word and status byte. The byte related to the module is marked:
35010574 12/2018 31
Addressing Modes
1 If you install a 140 CRP 312 00 remote I/O head module on the local rack instead of a
140 CRP 93• 00 module, the status byte is the ETH_STATUS detailed in the Device DDT Names
topic in the Quantum EIO Remote I/O Modules Installation and Configuration Guide.
32 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
Remote I/O (RIO) Modules
35010574 12/2018
Part II
Quantum Remote I/O (RIO) Modules
Introduction
This part provides information on the following Quantum RIO modules:
NOTE: For detailed information see also Product Related Information, page 14, Modicon Remote
I/O Cable System Planning and Installation Guide
35010574 12/2018 33
Remote I/O (RIO) Modules
34 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 CRP 931 00
35010574 12/2018
Chapter 3
140 CRP 931 00: Remote I/O (RIO) Head Module (single channel)
140 CRP 931 00: Remote I/O (RIO) Head Module (single
channel)
Purpose
This chapter contains information of the 140 CRP 931 00 Module.
35010574 12/2018 35
140 CRP 931 00
Presentation
Function
The Remote I/O Head single channel modules are installed in the same backplane as the system
controlling CPU modules. The RIO head is used to transfer data bi-directionally between the CPU
and RIO drop modules installed in separate backplanes. A coaxial cable network is used to
interconnect the RIO head module and one or more RIO drop modules.
Illustration
The following figure shows the Remote I/O (RIO) module’s parts.
1 LED Area
2 RIO Coax Connector
3 Version Label
4 Model Number, Module Description, Color Code
5 Removable Door
6 Customer Identification Label (Fold label and place it inside door)
NOTE: To mantain CE compliance with the European Directive on EMC (89/336/EEC), the RIO
head module must be connected using quad shielded cable (see the Remote I/O Cable System
Planning and Installation Guide).
36 35010574 12/2018
140 CRP 931 00
Indicators
Illustration
The following figure shows the LED indicators for the RIO Head module.
Description
The following table shows the LED descriptions for the RIO Head module.
35010574 12/2018 37
140 CRP 931 00
Error Codes
38 35010574 12/2018
140 CRP 931 00
35010574 12/2018 39
140 CRP 931 00
Specifications
General Specifications
General Specifications
Connection / Transmission
Connection / Transmission
Diagnostics
Diagnostics
40 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 CRP 932 00
35010574 12/2018
Chapter 4
140 CRP 932 00: Remote I/O (RIO) Head Module (dual channel)
140 CRP 932 00: Remote I/O (RIO) Head Module (dual
channel)
Purpose
This chapter contains information of the 140 CRP 932 00 Module.
35010574 12/2018 41
140 CRP 932 00
Presentation
Function
The Remote I/O Head dual channel modules are installed in the same backplane as the system
controlling CPU modules. The RIO head is used to transfer data bi-directionally between the CPU
and RIO drop modules installed in separate backplanes. A coaxial cable network is used to
interconnect the RIO head module and one or more RIO drop modules.
Illustration
The following figure shows the Remote I/O (RIO) module’s parts.
1 LED Area
2 RIO Coax Connector (Channel A)
3 RIO Coax Connector (Channel B)
4 Version Label
5 Model Number, Module Description, Color Code
6 Removable Door
7 Customer Identification Label (Fold label and place it inside door)
NOTE: To mantain CE compliance with the European Directive on EMC (89/336/EEC), the RIO
head module must be connected using quad shielded cable (see the Remote I/O Cable System
Planning and Installation Guide).
42 35010574 12/2018
140 CRP 932 00
Indicators
Illustration
The following figure shows the LED indicators for the RIO Head module.
Description
The following table shows the LED descriptions for the RIO Head module.
35010574 12/2018 43
140 CRP 932 00
Error Codes
44 35010574 12/2018
140 CRP 932 00
NOTE: Error codes are available in the File and Device info screen (Crash Code field
(see EcoStruxure™ Control Expert, OS Loader, User Manual)) when using OS Loader.
35010574 12/2018 45
140 CRP 932 00
Specifications
General Specifications
General Specifications
Connection / Transmission
Connection / Transmission
Diagnostics
Diagnostics
46 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 CRA 931 00
35010574 12/2018
Chapter 5
140 CRA 931 00: Remote I/O (RIO) Drop Module (single channel)
140 CRA 931 00: Remote I/O (RIO) Drop Module (single
channel)
Purpose
This chapter contains information of the 140 CRA 931 00 Module.
35010574 12/2018 47
140 CRA 931 00
Presentation
Function
The Remote I/O Drop Single Channel modules are used to transfer data bi-directionally over a
coaxial cable network between I/O modules installed in the same (RIO drop) backplane and the
RIO head installed in the CPU backplane.
Illustration
The following figure shows the Remote I/O (RIO) module’s parts.
1 LED Area
2 RIO Coax Connector
3 Version Label
4 Model Number, Module Description, Color Code
5 Removable Door
6 Customer Identification Label (Fold label and place it inside door)
NOTE: To maintain CE compliance with the European Directive on EMC (89/336/EEC), the RIO
Head module must be connected using quad shielded cable (see the Remote I/O Cable System
Planning and Installation Guide).
48 35010574 12/2018
140 CRA 931 00
35010574 12/2018 49
140 CRA 931 00
Indicators
Illustration
The following figure shows the LED indicators for the Drop module.
Description
The following table shows the RIO Drop module LED descriptions.
50 35010574 12/2018
140 CRA 931 00
Error Codes
35010574 12/2018 51
140 CRA 931 00
Specifications
General Specifications
General Specifications
NOTE: You can specify a monitoring time of 3 - 65 535 in this text box. With communication
interruptions with the remote processor, the output modules will maintain their last operating
condition during that time. Once the monitoring time has expired, the output modules will reset to
their default timeout status. The monitoring time does not influence input modules. The CPU will
immediately set the input value to zero.
Connection / Transmission
Connection / Transmission
Diagnostics
Diagnostics
Power Up Runtime
Dual Port Memory Check Executive Checksum
LAN Controller Check RAM Address/Data
52 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 CRA 932 00
35010574 12/2018
Chapter 6
140 CRA 932 00: Remote I/O (RIO) Drop Module (dual channel)
140 CRA 932 00: Remote I/O (RIO) Drop Module (dual
channel)
Purpose
This chapter contains information of the 140 CRA 932 00 Module.
35010574 12/2018 53
140 CRA 932 00
Presentation
Function
The Remote I/O Drop dual Channel modules are used to transfer data bi-directionally over a
coaxial cable network between I/O modules installed in the same (RIO drop) backplane and the
RIO head installed in the CPU backplane.
Illustration
The following figure shows the Remote I/O (RIO) module’s parts.
1 LED Area
2 RIO Coax Connector (Channel A)
3 RIO Coax Connector (Channel B)
4 Version Label
5 Model Number, Module Description, Color Code
6 Removable Door
7 Customer Identification Label (Fold label and place it inside door)
NOTE: To maintain CE compliance with the European Directive on EMC (89/336/EEC), the RIO
Head module must be connected using quad shielded cable (see the Remote I/O Cable System
Planning and Installation Guide).
54 35010574 12/2018
140 CRA 932 00
35010574 12/2018 55
140 CRA 932 00
Indicators
Illustration
The following figure shows the LED indicators for the Drop module:
Description
The following table shows the RIO Drop module LED descriptions:
56 35010574 12/2018
140 CRA 932 00
Error Codes
35010574 12/2018 57
140 CRA 932 00
Specifications
General Specification
General Specification
NOTE: You can specify a monitoring time of 3 - 65 535 in this text box. With communication
interruptions with the remote processor, the output modules will maintain their last operating
condition during that time. Once the monitoring time has expired, the output modules will reset to
their default timeout status. The monitoring time does not influence input modules. The CPU will
immediately set the input values to zero.
Connection / Transmission
Connection / Transmission
Diagnostics
Diagnostics
Power Up Runtime
Dual Port Memory Check Executive Checksum
LAN Controller Check RAM Address/Data
58 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 NRP 954 00
35010574 12/2018
Chapter 7
140 NRP 954 00: Fiber Optic Repeater Module (Multimode)
Purpose
This chapter contains information of the 140 NRP 954 00 Module.
35010574 12/2018 59
140 NRP 954 00
Presentation
Function
The 140 NRP 954 00 fiber optical repeater module provides communication between two or more
RIO nodes or segments of networks over a multimode fiber optic medium. Each repeater contains
one electrical RIO interface and two fiber optic transceivers.
Illustration
The following figure shows the 140 NRP 954 00 (NRP) module parts.
1 Version label
2 Model number, module description, color code
3 LED area
4 Removable door
5 Customer identification label (Fold label and place it inside door)
6 Diagnostic relay port
7 Electrical coaxial port (“F” type connector)
8 Transmitter optical fiber port - FPort 1 Tx (ST type connector)
9 Receiver optical fiber port - FPort 1 Rx (ST type connector)
10 Receiver optical fiber port - FPort 2 Rx (ST type connector)
11 Transmitter optical fiber port - FPort 2 Tx (ST type connector)
60 35010574 12/2018
140 NRP 954 00
CAUTION
CONNECTIVITY COMPLIANCE
To maintain CE compliance with the European Directive on EMC (89/336/EEC), the
140 NRP 954 00 module must be connected using quad shielded cable (see the Remote I/O
Cable System Planning and Installation Guide).
Failure to follow these instructions can result in injury or equipment damage.
35010574 12/2018 61
140 NRP 954 00
Optical Ports
The 140 NRP 954 00 fiber optic repeater module is equipped with two optical ports (FPort1 and
FPort2). One pair of fiber optic cables are connected to one fiber optic port using two low-loss
industrial ST-type connectors (one for the transmitter signal (Tx) and one for the receiver signal
(Rx)).
62 35010574 12/2018
140 NRP 954 00
Illustration
The following figure shows the LED indicators for the 140 NRP 954 00 fiber optic repeater module:
LED Indicators
The following table describes the status LEDs of the 140 NRP 954 00 module:
35010574 12/2018 63
140 NRP 954 00
NOTE: When the 140 NRP 954 00 is not powered, the contacts of the diagnostic relay are open.
64 35010574 12/2018
140 NRP 954 00
Module Connections
35010574 12/2018 65
140 NRP 954 00
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
66 35010574 12/2018
140 NRP 954 00
CAUTION
EQUIPMENT FAILURE
The loss of a single fiber optic repeater in this configuration disables the rest of the network. It is
suggested that the Self Healing Ring configuration be used to avoid this problem.
Failure to follow these instructions can result in injury or equipment damage.
35010574 12/2018 67
140 NRP 954 00
NOTE: The distance between nodes on fiber is limited by the maximum allowable power loss from
end-to-end (3 km over 62.5 µm fiber). Power loss includes the fiber optic cable attenuation,
connector losses at the fiber optic receiver and transmitter ports, and the system margin of 3 dB.
NOTE: At each end of the bus, looping back the unused optical ports with a short fiber helps using
the diagnostics. For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and
140 NRP 954 01C Fiber Optic Repeater Modules User Guide.
68 35010574 12/2018
140 NRP 954 00
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
35010574 12/2018 69
140 NRP 954 00
70 35010574 12/2018
140 NRP 954 00
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
35010574 12/2018 71
140 NRP 954 00
Backplane Integration
Instead of placing each fiber optic repeater modules with its own power supply module(s) in a
standalone backplane, you can take the advantage of the quantum form factor.
The following figure shows two segments of RIO coaxial cable connected point-to-point by two
140 NRP 954 00 fiber optic repeaters placed on the Quantum racks where the RIO head and RIO
drop modules are located:
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
72 35010574 12/2018
140 NRP 954 00
Connectors
The following table shows the connector types
NOTE: All connectors must have a short boot for strain relief.
Termination Kits
The following table shows the termination kits.
35010574 12/2018 73
140 NRP 954 00
DANGER
SEVERE EYE DAMAGE
Do not view the ends of fiber optic cable under magnification while a transmit signal is present on
the cable.
Failure to follow these instructions will result in death or serious injury.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the protective coverings from the optical cable port and optical cable tips until
immediately fiber cable connection to the cable port.
After removing the protective coverings, never touch exposed parts such as the ferrule.
After connecting the fiber cable, retain the protective coverings for future use.
Do not remove the protective covering from the unused connector.
Failure to follow these instructions can result in equipment damage.
Before Starting
Prior to installing 140 NRP 954 00 fiber optic repeater, network cables must be prepared and
installed to the repeater’s site with their connectors.
To prepare optic cables:
Follow the cable manufacturer’s recommendations for routing, installing, and testing the cable.
Take care when terminating the ends of each fiber optic cable in order to minimize loss of optical
signal. Follow the manufacturer’s guidelines for installing optical connectors.
Test the cable for proper attenuation prior to the connection of the fiber optic repeaters. The
cable ends should be accessible at each fiber optic installation site. Allow sufficient cable length
for a service loop and strain reliefs.
Label each cable end to facilitate future maintenance.
To prepare and install coaxial cables, refer to Remote I/O Cable System Planning and Installation
Guide.
74 35010574 12/2018
140 NRP 954 00
Step Action
1 Remove the protective plastic coverings from the cable ports and the tips of the
cable. Snap one of the fiber cable clasps (shipped with the module) over the
cable so that the wider end of the tool is closest to the cable end.
2 Turn the connection ring so that one of the arrows on the side of the ring lines up
with the ridge inside.
35010574 12/2018 75
140 NRP 954 00
General Specifications
Introduction
This section gives the 140 NRP 954 00 fiber optic repeater module specifications.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the following tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
General Specifications
76 35010574 12/2018
140 NRP 954 00
NOTICE
DESTRUCTION OF ADAPTER
Before tightening the locknut to the torque 0.46...0.60 N•m (4.1...5.3 lbf-in) be sure to properly
position the right-angle F adapter connector.
During tightening be sure to maintain the connector securely.
The locknut must be loosened before handling the connector. For this reason, it is
recommended to attach the S908 coaxial cable to the chassis to avoid any mechanical stress
on the right-angle F adapter connector.
Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.
Optical Power (Measured with –13.0...–20.0 dBm average power in 50/125 µm fiber cable
1 m test fiber) –10.0...–16 dBm average power in 62.5/125 µm fiber cable
–4.0...–10.5 dBm average power in 100/140 µm fiber cable
Rise/Fall Time 20 nsec or better
Silence (OFF Leakage) –43 dBm
Reliability
35010574 12/2018 77
140 NRP 954 00
78 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
140 NRP 954 01C
35010574 12/2018
Chapter 8
140 NRP 954 01C: Fiber Optic Repeater Module (Single-mode)
Purpose
This chapter contains information of the 140 NRP 954 01C Module.
35010574 12/2018 79
140 NRP 954 01C
Presentation
Function
The 140 NRP 954 01C fiber optical repeater module provides communication between two or
more RIO nodes or segments of networks over a single-mode fiber optic medium. Each repeater
contains one electrical RIO interface and two fiber optic transceivers.
Illustration
The following figure shows the 140 NRP 954 01C (NRP) module parts.
1 Version label
2 Model number, module description, color code
3 LED area
4 Removable door
5 Customer identification label (Fold label and place it inside door)
6 Diagnostic relay port
7 Electrical coaxial port (“F” type connector)
8 Receiver optical fiber port - FPort 1 Rx (LC type connector)
9 Transmitter optical fiber port - FPort 1 Tx (LC type connector)
10 Receiver optical fiber port - FPort 2 Rx (LC type connector)
11 Transmitter optical fiber port - FPort 2 Tx (LC type connector)
80 35010574 12/2018
140 NRP 954 01C
CAUTION
CONNECTIVITY COMPLIANCE
To maintain CE compliance with the European Directive on EMC (89/336/EEC), the
140 NRP 954 01C module must be connected using quad shielded cable (see the Remote I/O
Cable System Planning and Installation Guide).
Failure to follow these instructions can result in injury or equipment damage.
35010574 12/2018 81
140 NRP 954 01C
Optical Ports
The 140 NRP 954 01C fiber optic repeater module is equipped with two optical ports (FPort1 and
FPort2). One pair of fiber optic cables are connected to one fiber optic port using a duplex LC-type
connector.
82 35010574 12/2018
140 NRP 954 01C
Illustration
The following figure shows the LED indicators for the 140 NRP 954 01C fiber optic repeater
module:
LED Indicators
The following table describes the status LEDs of the 140 NRP 954 01C module:
35010574 12/2018 83
140 NRP 954 01C
NOTE: When the 140 NRP 954 01C is not powered, the contacts of the diagnostic relay are open.
84 35010574 12/2018
140 NRP 954 01C
Module Connections
35010574 12/2018 85
140 NRP 954 01C
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
86 35010574 12/2018
140 NRP 954 01C
CAUTION
EQUIPMENT FAILURE
The loss of a single fiber optic repeater in this configuration disables the rest of the network. It is
suggested that the Self Healing Ring configuration be used to avoid this problem.
Failure to follow these instructions can result in injury or equipment damage.
35010574 12/2018 87
140 NRP 954 01C
NOTE: The total distance between the first and the last fiber optic repeater is limited by the
maximum allowable power loss from end-to-end (16 km over 9/125 µm fiber). Power loss includes
the fiber optic cable attenuation, connector losses at the fiber optic receiver and transmitter ports,
and the system margin of 3 dB.
NOTE: At each end of the bus, looping back the unused optical ports with a short fiber helps using
the diagnostics. For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and
140 NRP 954 01C Fiber Optic Repeater Modules User Guide.
88 35010574 12/2018
140 NRP 954 01C
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
35010574 12/2018 89
140 NRP 954 01C
90 35010574 12/2018
140 NRP 954 01C
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
35010574 12/2018 91
140 NRP 954 01C
Backplane Integration
Instead of placing each fiber optic repeater modules with its own power supply module(s) in a
standalone backplane, you can take the advantage of the quantum form factor.
The following figure shows two segments of RIO coaxial cable connected point-to-point by two
140 NRP 954 01C fiber optic repeaters placed on the Quantum racks where the RIO head and RIO
drop modules are located:
NOTE:
Using 2 optical fiber pairs provides a better service and diagnostics.
Using only one fiber pair, looping back the unused optical ports with a short fiber helps using the
diagnostics.
For more details on the diagnostics, refer to the Modicon 140 NRP 954 00 and 140 NRP 954 01C
Fiber Optic Repeater Modules User Guide.
92 35010574 12/2018
140 NRP 954 01C
DANGER
SEVERE EYE DAMAGE
Do not view the ends of fiber optic cable under magnification while a transmit signal is present on
the cable.
Failure to follow these instructions will result in death or serious injury.
NOTICE
INOPERABLE EQUIPMENT
Do not remove the protective coverings from the optical cable port and optical cable tips until
immediately fiber cable connection to the cable port.
After removing the protective coverings, never touch exposed parts such as the ferrule.
After connecting the fiber cable, retain the protective coverings for future use.
Do not remove the protective covering from the unused connector.
Failure to follow these instructions can result in equipment damage.
Before Starting
Prior to installing 140 NRP 954 01C fiber optic repeater, network cables must be prepared and
installed to the repeater’s site with their connectors.
To prepare optic cables:
Follow the cable manufacturer’s recommendations for routing, installing, and testing the cable.
Take care when terminating the ends of each fiber optic cable in order to minimize loss of optical
signal. Follow the manufacturer’s guidelines for installing optical connectors.
Test the cable for proper attenuation prior to the connection of the fiber optic repeaters. The
cable ends should be accessible at each fiber optic installation site. Allow sufficient cable length
for a service loop and strain reliefs.
Label each cable end to facilitate future maintenance.
To prepare and install coaxial cables, refer to Remote I/O Cable System Planning and Installation
Guide.
35010574 12/2018 93
140 NRP 954 01C
Step Action
1 Remove the dust plugs from the LC connectors of the fiber optic cable as shown in
the following figure. Save the dust plugs for future use.
2 Inspect and clean the fiber optic end faces of the LC connectors.
3 Remove the dust plugs from the LC duplex connector as shown in the following
figure:
4 Immediately attach the fiber optic cable to the LC duplex connector of the module
as shown in the following figure:
94 35010574 12/2018
140 NRP 954 01C
Compatibility Rules
Depending on the PV (Product Version) and SV (Software Version) of the CRA modules, the
140 NRP 954 01C may be incompatible.
The following table gives the compatibility rules between the 140 NRP 954 01C and CRA modules:
(1)
An upgrade of the SV to 2.01 makes the module communication compatible.
NOTE: Upgrading the software version of the CRA module from 2.0 to 2.01 for CRA
modules PV 09 is mandatory before using 140 NRP 954 01C in the RIO network.
(2)
For CRA module with SV ≥2.0, OS update is only possible out of the RIO network.
The 140 CRA 93• 00 firmware upgrade is done through Modbus or Modbus Plus using the Control
Expert OS loader tool. The procedure to follow is described in the Quantum Operating System
Upgrade and Update Procedure.
35010574 12/2018 95
140 NRP 954 01C
General Specifications
Introduction
This section gives the 140 NRP 954 01C fiber optic repeater module specifications.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the following tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
General Specifications
96 35010574 12/2018
140 NRP 954 01C
NOTICE
DESTRUCTION OF ADAPTER
Before tightening the locknut to the torque 0.46...0.60 N•m (4.1...5.3 lbf-in) be sure to properly
position the right-angle F adapter connector.
During tightening be sure to maintain the connector securely.
The locknut must be loosened before handling the connector. For this reason, it is
recommended to attach the S908 coaxial cable to the chassis to avoid any mechanical stress
on the right-angle F adapter connector.
Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.
Optical Power (Measured with –8.0...–15.0 dBm average power in 9/125 µm fiber cable
1 m test fiber)
Rise/Fall Time 20 nsec or better
Silence (OFF Leakage) –45 dBm
Reliability
35010574 12/2018 97
140 NRP 954 01C
98 35010574 12/2018
Quantum using EcoStruxure™ Control Expert
DIO Drop Modules
35010574 12/2018
Part III
Quantum Distributed I/O (DIO) Drop Modules
Introduction
This part provides information on the following Quantum DIO modules:
Quantum DIO is implemented over a Modbus Plus network. The CPU or NOM modules may be
the network head via their Modbus Plus ports. Quantum DIO Modbus Plus drop adaptors are
specifically designed to link Quantum I/O modules to the head via twisted pair shielded cable
(Modbus Plus). The DIO drop modules also provide the I/O with power (maximum 3A) from a 24
VDC or a 115/230 VAC source. Each DIO network supports up to 63 distributed drops using
repeaters.
NOTE: In the DIO rack with 140 CRA 211 x0 module, 140 DSI 353 00 module must not be used.
35010574 12/2018 99
DIO Drop Modules
Chapter 9
Software Configuration
Software Configuration
Introduction
A Quantum DIO Drop consists of a standard module rack installed with I/O modules and a
140 CRA 21• •0 Modbus Plus communication module.
A DIO Bus can either be connected to the Modbus Plus connection on the CPU, or to a
140 NOM 2•• 00 communication module.
NOTE: The Quantum DIO Drop Modules 140 CRA 2•• ••• have no health bits.
For this reason the status for a properly functioning DIO Drop is always ZERO and not ONE as it
is for other modules!
Step Action
1 Select the Modbus Plus connection that you want to configure as a DIO Bus from
the Project Browser or in the hardware configuration window.
The following configuration window is opened:
Step Action
2 Activate the DIO Bus check box in the configuration window and confirm your
entry.
A DIO Bus is placed in the Project Browser:
3 Open the DIO Bus and select add module rack and select New Device.
The module rack selection list is opened:
Step Action
4 Select the desired module rack and enter the Modbus Plus address in the
address field. Confirm with OK.
A DIO Drop is placed in the Project Browser. The number set, 12 in our example,
states the Modbus Plus address of the Drop. The Modbus Plus Coupler
140 CRA 21X X0 is automatically entered in slot 1:
5 To continue configuring the RIO Drop you can carry on as with configuring a local
I/O.
Chapter 10
140 CRA 211 10: DIO Drop Module 115/230 VAC (single channel)
140 CRA 211 10: DIO Drop Module 115/230 VAC (single
channel)
Purpose
This chapter contains information of the 140 CRA 211 10 Module.
Presentation
Function
The 140 CRA 211 10 is a single channel Distributed I/O Interface, connected via a twisted pair
Modbus Plus cable network. This DIO Drop Module provides the I/O with power from a 115/230
VAC source.
Illustration
The following figure shows the parts of the distributed I/O (DIO) module.
Indicators
Illustration
The following figure shows the LED panel.
Description
The following table shows the DIO LED indicators and descriptions.
Specifications
General Specifications
General Specifications
Input
Input
Output to Bus
Output to Bus
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Runtime RAM
RAM Address
Executive Checksum
Wiring Diagram
Illustration
The following figure shows the wiring diagram for the 140 CRA 211 10
NOTE: Follow the Power and Grounding Guidelines of the Quantum Hardware Reference Manual
and the Grounding and Electromagnetic Compatibility of PLC Systems manual recommendations.
Chapter 11
140 CRA 212 10: DIO Drop Module 115/230 VAC (dual channel)
140 CRA 212 10: DIO Drop Module 115/230 VAC (dual
channel)
Purpose
This chapter contains information of the 140 CRA 212 10 Module.
Presentation
Function
The 140 CRA 212 10 is a dual channel Distributed I/O Interface, connected via a twisted pair
Modbus Plus cable network. This DIO Drop Module provides the I/O with power from a 115/230
VAC source.
Illustration
The following figure shows the parts of the distributed I/O (DIO) module.
Indicators
Illustration
The following figure shows the LED panel.
Description
The following table shows the DIO LED indicators and descriptions.
Specifications
General Specifications
General Specifications
Input
Input
Output to Bus
Output to Bus
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Runtime RAM
RAM Address
Executive Checksum
Wiring Diagram
Illustration
The following figure shows the wiring diagram for the 140 CRA 212 10
NOTE: Follow the Power and Grounding Guidelines of the Quantum Hardware Reference Manual
and the Grounding and Electromagnetic Compatibility of PLC Systems manual recommendations.
Chapter 12
140 CRA 211 20: DIO Drop Module 24 VDC (single channel)
140 CRA 211 20: DIO Drop Module 24 VDC (single channel)
Purpose
This chapter contains information of the 140 CRA 211 20 Module.
Presentation
Function
The 140 CRA 211 20 is a single channel Distributed I/O Interface, connected via a twisted pair
Modbus Plus cable network. This DIO Drop Module provides the I/O with power from a 24 VDC
source.
Illustration
The following figure shows the parts of the distributed I/O (DIO) module.
Indicators
Illustration
The following figure shows the LED panel.
Description
The following table shows the DIO LED indicators and descriptions.
Specifications
General Specifications
General Specifications
Input
Input
Output to Bus
Output to Bus
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Runtime RAM
RAM Address
Executive Checksum
Wiring Diagram
Illustration
The following figure shows the wiring diagram for the 140 CRA 211 20 module
NOTE: Follow the Power and Grounding Guidelines of the Quantum Hardware Reference Manual
and the Grounding and Electromagnetic Compatibility of PLC Systems manual recommendations.
Chapter 13
140 CRA 212 20: DIO Drop Module 24 VDC (dual channel)
140 CRA 212 20: DIO Drop Module 24 VDC (dual channel)
Purpose
This chapter contains information of the 140 CRA 212 20 Module.
Presentation
Function
The 140 CRA 212 20 is a dual channel Distributed I/O Interface, connected via a twisted pair
Modbus Plus cable network. This DIO Drop Module provides the I/O with power from a 24 VDC
source.
Illustration
The following figure shows the parts of the distributed I/O (DIO) module.
1 LED Area
2 Modbus Plus Connector (Channel A)
3 Modbus Plus Connector (Channel B)
4 Field Wiring Connector
5 Field Wiring Connector Cover
6 Model Number, Module Description, Color Code
7 Removable Door
8 Customer Identification Label (Fold label and place it inside door)
Indicators
Illustration
The following figure shows the LED panel.
Description
The following table shows the DIO LED indicators and descriptions.
Specifications
General Specifications
General Specifications
Input
Input
Output to Bus
Output to Bus
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Runtime RAM
RAM Address
Executive Checksum
Wiring Diagram
Illustration
The following figure shows the wiring diagram for the 140 CRA 212 20 module
NOTE: Follow the Power and Grounding Guidelines of the Quantum Hardware Reference Manual
and the Grounding and Electromagnetic Compatibility of PLC Systems manual recommendations.
Part IV
Modbus Plus Network Option Modules (NOM)
Introduction
This part provides information on the following Quantum Network Option modules:
NOTE: More information is provided in the Modicon Modbus Plus Network, Planning and
Installation Guide (see page 13).
Chapter 14
140 NOM 211 00: Modbus Plus Option Module
Purpose
This chapter contains information of the 140 NOM 211 00 Module.
Presentation
Function
The 140 NOM 211 00 is a single channel Network Option Modul (NOM), connected via a twisted
pair Modbus Plus cable network
Illustration
The following figure shows the parts of the Modbus Plus 140 NOM 211 00 modules.
1 LED Area
2 Comm Parameter Slide Switch
3 Modbus Connector
4 Modbus Plus Connector
5 Model Number, Module Description, Color Code
6 Removable door
7 Customer Identification Label, (Fold label and place it inside door)
NOTE: If the left-hand switch is in the upper position and right-hand switch is set to mem then, as
of firmware version 2.20, bridge mode is deactivated. This means that the network connection
between Modbus and Modbus Plus is locked.
The NOM hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII
mode. When networking controllers, a panel device connected to the NOM Modbus port can
communicate with the controller to which it is conected, as well as log into any nodes on the
Modbus Plus network.
NOTE: If "0," or an address greater than 64 is selected, the Modbus + LED will be "on" steady, to
indicate the selection of an invalid address.
NOTE: If "0," or an address greater than 64 is selected, the Modbus + LED will be "on" steady, to
indicate the selection of an invalid address.
Baud 2,400
Parity Even
Data Bits 7
Stop Bits 1
Device Address Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to
the port; the following comm parameters are set and cannot be changed:
Baud 9,600
Parity Even
Data Bits 8
Stop Bits 1
Device Address Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to
the port in software; the following parameters are valid.
Indicators
Illustration
The following figure shows the Modbus Plus NOM LED indicators.
Description
The following table shows the Modbus Plus NOM LED Descriptions.
Error Codes
Specifications
General Specifications
General Specifications
Power Dissipation 4W
Bus Current required 750 mA (max.)
Communication Ports
Communication Ports
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Processor
Runtime RAM
RAM Address
Executive Checksum
Processor
Chapter 15
140 NOM 212 00: Modbus Plus Option Module
Purpose
This chapter contains information of the 140 NOM 212 00 Module.
Presentation
Function
The 140 NOM 212 00 is a dual channel Network Option Modul (NOM), connected via a twisted pair
Modbus Plus cable network
Illustration
The following figure shows the parts of the Modbus Plus 140 NOM 212 00 modules.
1 LED Area
2 Comm Parameter Slide Switch
3 Modbus Connector
4 Modbus Plus Connector (Chan A)
5 Modbus Plus Connector (Chan B)
6 Model Number, Module Description, Color Code
7 Removable door
8 Customer Identification Label, (Fold label and place it inside door)
NOTE: If the left-hand switch is in the upper position and right-hand switch is set to mem then, as
of firmware version 2.20, bridge mode is deactivated. This means that the network connection
between Modbus and Modbus Plus is locked.
The NOM hardware defaults to bridge mode when the front panel switch is set to RTU or ASCII
mode. When networking controllers, a panel device connected to the NOM Modbus port can
communicate with the controller to which it is conected, as well as log into any nodes on the
Modbus Plus network.
NOTE: If "0," or an address greater than 64 is selected, the Modbus + LED will be "on" steady, to
indicate the selection of an invalid address.
NOTE: If "0," or an address greater than 64 is selected, the Modbus + LED will be "on" steady, to
indicate the selection of an invalid address.
Baud 2,400
Parity Even
Data Bits 7
Stop Bits 1
Device Address Rear panel rotary switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to
the port; the following comm parameters are set and cannot be changed:
Baud 9,600
Parity Even
Data Bits 8
Stop Bits 1
Device Address Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to
the port in software; the following parameters are valid.
Indicators
Illustration
The following figure shows the Modbus Plus NOM LED indicators.
Description
The following table shows the Modbus Plus NOM LED Descriptions.
Error Codes
Specifications
General Specifications
General Specifications
Communication Ports
Communication Ports
2 Modbus Plus network For dual connectivity on a single Modbus Plus network. These
(RS-485) port (9-pin ports handle identical versions of all inbound and outbound
connector) transactions and keep track of the data paths used for these
transactions
1 Modbus (RS-232) serial A bridge mode capability in the module permits a panel device
port (9-pin connector) connected to this port to access nodes on the Modbus Plus
network or to access the local PLC directly without having to go
out onto the network.
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Processor
Runtime RAM
RAM Address
Executive Checksum
Processor
Chapter 16
140 NOM 252 00: Modbus Plus Option Module 10Base-FL
Purpose
This chapter contains information of the 140 NOM 252 00 Module.
Presentation
Overview
The Modbus Plus on Fiber module provides connectivity to Modbus Plus nodes by fiber cable.
There are many benefits that result from the use of fiber optics. Some of these benefits include:
Longer distances between nodes (up to 3 km), thereby, increasing the total length of the
network.
Fiber optic medium is not susceptible to the effects of electromagnetic interference, RF
interference, and lightning.
Intrinsically safe links that are required in many hazardous industrial environments.
Total electrical isolation between terminal points on the link
Illustration
The following figure shows the parts of the Modbus Plus 140 NOM 252 00 module.
1 LED Area
2 Modbus Connector
3 Comm Parameter Slide Switch
4 Port 2 TX and RX Connectors
5 Port 1 TX and RX Connectors
6 Model Number, Module Description, Color Code
7 Removable door
8 Customer Identification Label, (Fold label and place it inside door)
Setting the slide switch to the top position assigns ASCII functionality to the port; the following
comm parameters are set and cannot be changed.
Baud 2,400
Parity Even
Data Bits 7
Stop Bits 1
Device Address Rear panel rotary
switch setting
Setting the slide switch to the middle position assigns remote terminal unit (RTU) functionality to
the port; the following comm parameters are set and cannot be changed:
Baud 9,600
Parity Even
Data Bits 8
Stop Bits 1
Device Address Rear panel rotary switch setting
Setting the slide switch to the bottom position gives you the ability to assign comm parameters to
the port in software; the following parameters are valid.
NOTE: If "0" or an address greater than 64 is selected, the Modbus + LED will be "on" steady, to
indicate the selection of an invalid address.
Modbus Connector
The NOM 252 00 module is equipped with an RS-232 port (see below) located on the front of the
module. This port uses an eight-position RJ45 (phone jack-type) connector.
NOTE: A D-shell adapter is available from Modicon for NOM 252 00-to-computer connections: a
(110 XCA 20 300) 9-pin adapter for PC-AT type computers (see the illustration pinout table below).
Pinouts Figures
The following figures show the 9-pin adapter front view (left) and side view (right).
Indicators
Illustration
The following figure shows the Modbus Plus on Fiber LED indicators.
Description
The following table shows the Modbus Plus on fiber LED descriptions.
Step Action
1 Remove the protective plastic coverings from the cable ports and the tips of the
cable. Snap one of the fiber cable clasps (shipped with the module) over the
cable so that the wider end of the tool is closest to the cable end.
2 Turn the connection ring so that one of the arrows on the side of the ring lines up
with the ridge inside.
Point-to-Point Configuration
This type of configuration (see below) allows communication over the distance of up to 3 km
through harsh industrial environments.
Bus Configuration
This type of configuration is used when it is required to connect a number of fiber nodes and can
be used to increase the distance of a standard Modbus Plus network by changing to a fiber
medium. This kind of network allows the connection of up to 32 Quantum NOM 252 nodes over the
distance of 5 km.
The following illustrations show the NOM 252 00 module in a mixed fiber optic/twisted pairs bus
configuration network and a straight fiber optic bus configuration network.
NOTE: The loss of a single node in this configuration disables the rest of the network.
NOTE: The distance between nodes on fiber is limited by the maximum allowable power loss from
end-to-end (3 km over 62.5 mm fiber). Power loss includes the fiber optic cable attenuation,
connector losses at the Fiber Optic Receiver and Transmitter ports, and the system margin of 3 dB.
In this configuration, the end NOM 252 00 in this configuration will have the FRNGoff LED active.
It also displays the Cable B Framing error in the MBPSTAT (in ladder logic).
Tree Configuration
Using tree configurations allows for greater flexibility in the layout of Modbus Plus and NOM 252
00 networks. The following illustrations are samples tree configurations. Additional repeaters may
be connected in order to extend communication between electrical links.
Network Status
The information about the condition of the network is presented in the form of Network Status. This
information indicates the loss of connection (the first break in the self-healing ring) and is similar to
the way the existing 140 NOM 212 00 reports the loss of the redundant cable.
The break in the fiber cable will be detected by the module not receiving the signal from the cable
break side. The incident will be reported by MBPSTAT as a Cable B Framing error. This condition
also activates the FRNGoff LED on the module front.
Connectors
The following table shows the connector types
NOTE: All connectors must have a short boot for strain relief.
Termination Kits
The following table shows the termination kits.
Cables
It is recommended that you use 62.5/125 mm cable (such as AMP 503016-1, AMP 502986-1, or
equivalent) with a maximum attenuation of 3.5 dB/km in most of the configurations.
NOTE: Modicon recommends using the 52-0370-000 cable.
NOTE: All cables must have a maximum cable diameter of not more than 3 mm at the terminal
side.
Connections
The following information discusses connecting the NOM 252 00 on fiber cable, adding a new
mode to the network, and repairing the break in the cable.
NOTE: When a new network is assembled, it is recommended that you connect all cables before
powering up the system. Connect fiber optic cables as described previously in this section.
Calculations
Use the following formula to calculate the number of NOM 252 00 modules in a fiber network:
Step Action
1 The total allowable pulse width distortions and jitter are limited to 20% of the bit
period and is 200 nsec for the full fiber optic network.
2 The jitter contributed by the NOM 252 is 5 nsec max.
3 Jitter contributed by fiber optic repeaters (if used) is 40 nsec.
4 Use the following formula to determine the number (N) of chained repeaters:
where "L" is the total cable length (km), and "X" is the jitter (added by the fiber
optic cable) in nsec/km:
X = 3 ns/km for 50/125 micron meters
5 ns/km for 62.5/125 micron meters
7.5 ns/km for 100/140 micron meters
Specifications
General Specifications
General Specifications
Communication Ports
Communication Ports
Diagnostics
Diagnostics
Power Up RAM
RAM Address
Executive Checksum
Processor
Runtime RAM
RAM Address
Executive Checksum
Optical Transmission
Optical Transmission
Optical Power (Measured -12.8 ... -19.8 dBm average power in 50/125 micron fiber cable
with 1 m test fiber) -9.0 ... -16 dBm average power in 62.5/125 micron fiber cable
-3.5 ... -10.5 dBm average power in 100/140 micron fiber cable
Rise/Fall Time 20 ns or better
Silence (OFF leakage) -43 dBm
Part V
Quantum Ethernet Modules
Introduction
This part provides information about the different Ethernet modules of the Quantum product series.
Chapter 17
140 NOE xxx xx: Ethernet Module General Overview
At a Glance
This chapter contains general information about the 140 NOE ••• •• and 140 NWM 100 00 Ethernet
modules.
General Information
Introduction
This part provides information on the following Quantum Ethernet Modules:
Overview
The following information provides overviews of all Modicon Quantum Ethernet modules.
General Description
The Modicon Quantum Ethernet module, shown below, is one of the latest models in a line of
Modicon Quantum Ethernet TCP/IP modules designed to make it possible for a Modicon Quantum
PLC to communicate with devices over an Ethernet network. The electronics for the Ethernet
modules are contained in a standard Modicon Quantum single-width case that takes up one slot in
a Modicon Quantum backplane. The module, which is capable of being hot swapped, can be
plugged into any available slot in the backplane.
The NOE 771 x0 and NOE 771 x1 modules provide real-time peer-to-peer communications and
I/O scanning and a Modbus/TCP server. The included HTTP services provide maintenance and
configuration utilities to the module.
Front View
The following figure shows the front of the NOE 771 00 Ethernet module as an example for all
Ethernet modules.
NOTE: In the detailed description of the key features, only modules in the NOE family are named.
The features are also available for the 140 NWM 100 00 module, depending on the listed
properties in the above table.
NOTE: In Control Expert software, the 140 NWM 100 00 module is set in the TCP/IP Regular
Network family, although it belongs to the TCP/IP FactoryCast network family. So, the services
listed above (I/O scanning, Global Data, address server, Bandwidth monitoring) are not supported
by the module. However, they can be selected in the TCP/IP regular network configuration in
Control Expert. (Even if they are configured, those services won't work with the module.)
Component Description
LED Indicator Panel Indicates the operating status of the module, and the fiber optic
(see page 192) or Ethernet communications network to which it is connected.
IP Address Area Provides a writable area to record the module’s assigned IP
address.
Global Address Label Indicates the module’s global Ethernet MAC address assigned
at the factory.
100 BASE-FX Connector Provides an MT-RJ socket for connection to a 100-megabit
fiber-optic Ethernet cable.
10/100 BASE-T Connector Provides an RJ45 socket for connection to a shielded, twisted
pair Ethernet cable.
Illustration
The following figure shows the NOE 771 00 LED indicators as a placeholder for all other Ethernet
modules:
Description
The following table shows the LED descriptions:
Chapter 18
140 NOE 211 x0: TCP/IP 10Base-T Ethernet Module
Purpose
This chapter contains information of the 140 NOE 211 x0 Module.
NOTE: For detailed information see also Product Related Information, page 14, User Guide for the
Quantum NOE 211/251 Ethernet Module
Presentation
Function
The Ethernet TCP/IP module for twisted pair cabling provides an interface to Ethernet networks for
the Quantum Automation Series system.
Illustration
The following figure shows the Ethernet TCP/IP NOE 211 x0 module.
Indicators
Illustration
The following figure shows the NOE 211 x0 LED indicators.
Description
The following table shows the NOE 211 x0 LED descriptions.
Specifications
Specifications Table
Specifications Table
Power Dissipation 5W
Bus Current required 1A
Protocol Ethernet ports transmit and receive Modbus commands
encapsulated in TCP/IP protocol.
Ports One 10BASE-T Ethernet network (RJ-45) port.
Data Transfer Frequency 10 Mbps
Compatibility with All, V2.0 at a minimum
Quantum Controllers
Factory Cast 140 NOE 211 10 only
Installation
Installation Example
The following example shows the steps for discovering the default IP network address.
Step Action
1 Locate the global address label on the front panel of the module.
CAUTION
UNEXPECTED EQUIPMENT BEHAVIOR
Do not connect this module to your network until you have ensured that its IP
address will be unique on the network.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
UNEXPECTED EQUIPMENT BEHAVIOR
The cable for an Ethernet module must be routed through an Ethernet hub for the
network to function properly. Do not connect the module directly to another device.
Failure to follow these instructions can result in injury or equipment damage.
Chapter 19
140 NOE 251 x0: TCP/IP 10Base-FL Ethernet Module
Purpose
This chapter contains information of the 140 NOE 251 x0 Module.
NOTE: For detailed information see also Product Related Information, page 14, User Guide for the
Quantum NOE 211/251 Ethernet Module
Presentation
Function
The Ethernet TCP/IP modules for fiber optic cabling provide an interface to Ethernet networks for
the Quantum Automation Series system.
Illustration
The following figure shows the Ethernet TCP/IP NOE 251 x0 module.
Indicators
Illustration
The following figure shows the NOE 251 x0 LED indicators.
Description
The following table shows the NOE 251 x0 LED descriptions.
Specifications
Specifications Table
Specifications Table
Power Dissipation 5W
Bus Current required 1A
Protocol Ethernet ports transmit and receive Modbus commands
encapsulated in TCP/IP protocol
Ports One 10BASE-FL Ethernet network (ST-style) port.
Data Transfer Frequency 10 Mbps
Compatibility with All, V2.0 at a minimum
Quantum Controllers
Factory Cast 140 NOE 251 10 only
Installation
Installation Example
The following example shows the steps for discovering the default IP network address.
Step Action
1 Locate the global address label on the front panel of the module.
CAUTION
UNEXPECTED EQUIPMENT BEHAVIOR
Do not connect this module to your network until you have ensured that its IP
address will be unique on the network.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
UNEXPECTED EQUIPMENT BEHAVIOR
The cable for an Ethernet module must be routed through an Ethernet hub for the
network to function properly. Do not connect the module directly to another device.
Failure to follow these instructions can result in injury or equipment damage.
Chapter 20
140 NOE 311 00: SY/MAX 10Base-T Ethernet Module
Purpose
This chapter contains information of the 140 NOE 311 00 Module.
NOTE: For detailed information see also Product Related Information, page 14, Quantum Sy/Max
Ethernet Network Option Module Guide
Presentation
Function
The Quantum SY/MAX Ethernet module for twisted pair cabling provides an interface for the
Quantum Automation Series system to SY/MAX devices via Ethernet.
Illustration
The following figure shows the NOE 311 00 SY/MAX Ethernet module.
SY/MAX Addressing
Be sure that the module is assigned a unique SY/MAX drop number during configuration.
WARNING
UNEXPECTED APPLICATION BEHAVIOR
Do assign a unique SY/MAX drop number during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Indicators
Illustration
The following figure shows the NOE 311 00 LED indicators.
Description
The following figure shows the NOE 311 00 LED descriptions.
Specifications
General Specification
General Specification
Cable Type
Cable Type
Wire Size
Wire Size
Topology
Topology
Connector
Connector
Chapter 21
140 NOE 351 00: SY/MAX 10Base-FL Ethernet Module
Purpose
This chapter contains information of the 140 NOE 351 00 Module.
NOTE: For detailed information see also Product Related Information, page 14, Quantum Sy/Max
Ethernet Network Option Module Guide
Presentation
Function
The Quantum SY/MAX Ethernet module for fiber optic cabling provides an interface for the
Quantum Automation Series system to SY/MAX devices via Ethernet.
Illustration
The following figure shows the NOE 351 00 SY/MAX Ethernet module.
SY/MAX Addressing
Be sure that the module is assigned a unique SY/MAX drop number during configuration.
WARNING
UNEXPECTED APPLICATION BEHAVIOR
Do assign a unique SY/MAX drop number during configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Indicators
Illustration
The following figure shows the NOE 351 00 LED indicators.
Description
The following figure shows the NOE 351 00 LED descriptions.
Specifications
General Specification
General Specification
Chapter 22
140 NOE 771 00: TCP/IP 10/100 Ethernet Module
Purpose
This chapter contains information of the 140 NOE 771 00 Module.
NOTE: For detailed information see also Product Related Information, page 14, User Guide for the
Quantum NOE 771 Ethernet Module
Presentation
Function
The Quantum 140 NOE 771 00,10/100 Ethernet module is the latest model in a line of Quantum
Ethernet TCP/IP modules designed to make it possible for a Quantum Programmable Logic
Controller (PLC) to communicate with devices over an Ethernet network.
Illustration
The following figure shows the front of the NOE 771 00 Ethernet module.
Component Description
LED indicator Panel Indicates the operating status of the module, and the fiber optic and
Modbus communications networks it is connected to. (See
Indicators, page 223)
IP Address Writable Provides a writable area to record the module’s assigned IP
Area address.
Global Address Label Indicates the module’s global Ethernet MAC address assigned at
the factory.
100 BASE-FX Provides an MT-RJ receptacle for connection to a 100 megabit fiber
Connector optic Ethernet cable.
10/100BASE-T Provides an RJ-45 receptacle for connection to a shielded, twisted
Connector pair Ethernet cable.
Indicators
Illustration
The following figure shows the 140 NOE 771 00 LED indicators.
Description
The following table shows the 140 NOE 771 00 LED descriptions.
Specifications
Specifications Table
Specifications Table
Chapter 23
140 NOE 771 01: TCP/IP 10/100 Ethernet Module
Purpose
This chapter contains information of the 140 NOE 771 01 Module.
Presentation
Function
The Ethernet TCP/IP module for twisted pair cabling provides an interface to Ethernet networks for
the Quantum Automation Series system.
Illustration
The following figure shows the Ethernet TCP/IP 140 NOE 771 01 module.
Indicators
Illustration
The following figure shows the 140 NOE 771 01 LED indicators.
Description
The following table shows the 140 NOE 771 01 LED descriptions.
Specifications
Specifications Table
Specifications Table
Chapter 24
140 NOE 771 10: TCP/IP 10/100 FactoryCast Ethernet Module
Purpose
This chapter contains information about the 140 NOE 771 10 Module.
Presentation
Function
The Quantum 140 NOE 771 10,10/100 Ethernet module is the latest model in a line of Quantum
Ethernet TCP/IP modules designed to make it possible for a Quantum Programmable Logic
Controller (PLC) to communicate with devices over an Ethernet network.
Illustration
The following figure shows the front of the NOE 771 10 Ethernet module.
Component Description
LED indicator Panel Indicates the operating status of the module, and the fiber optic and
Modbus communications networks it is connected to. (See
Indicators in this
IP Address Writable Provides a writable area to record the module’s assigned IP
Area address.
Global Address Label Indicates the module’s global Ethernet MAC address assigned at
the factory.
100 BASE-FX Provides an MT-RJ receptacle for connection to a 100 Megabit fiber
Connector optic Ethernet cable.
10/100BASE-T Provides an RJ-45 receptacle for connection to a shielded, twisted
Connector pair Ethernet cable.
Indicators
Illustration
The following figure shows the NOE 771 10 LED indicators.
Description
The following table shows the NOE 771 10 LED descriptions.
Specifications
Specifications Table
Specifications Table
Chapter 25
140 NOE 771 11: TCP/IP 10/100 FactoryCast Ethernet Module
Purpose
This chapter contains information about the 140 NOE 771 11 Module.
Presentation
Function
The Ethernet TCP/IP module for twisted pair cabling provides an interface to Ethernet networks for
the Quantum Automation Series system.
Illustration
The following figure shows the Ethernet TCP/IP 140 NOE 771 11 module.
Indicators
Illustration
The following figure shows the 140 NOE 771 11 LED indicators.
Description
The following table shows the 140 NOE 771 11 LED descriptions.
Specifications
Specifications Table
Specifications Table
Chapter 26
140 NWM 100 00: TCP/IP 10/100 FactoryCast HMI Ethernet Module
Purpose
This chapter contains information about the 140 NWM 100 00 Module.
Presentation
Function
The Ethernet TCP/IP module for twisted pair cabling provides an interface to Ethernet networks for
the Quantum Automation Series system.
Illustration
The following figure shows the Ethernet TCP/IP 140 NWM 100 00 module.
Indicators
Illustration
The following figure shows the 140 NWM 100 00 LED indicators.
Description
The following table shows the 140 NWM 100 00 LED descriptions.
Specifications
Specifications Table
Specifications Table
Part VI
Quantum Field Bus Modules
Chapter 27
140 EIA 921 00: AS-i Master Communication Module
Purpose
This chapter contains information on the 140 EIA 921 00 AS-i master communications module.
NOTE: For detailed information see also Product Related Information, page 14, Modicon Quantum
AS-i Master Module EIA 921 00
Presentation
Function
The Quantum AS-i Master Module provides AS-i communications between the bus master module
and the sensor/actuator slaves. One master module can control 31 slaves. Multiple master
modules can be used in a single control system.
These sensor/actuators can be in the local CPU, an RIO, or a DIO drop adapter.
NOTE: This module is not available to directly exploit analog slaves (profile 7.1, 7.2, 7.3, 7.4) on
an AS-i bus.
For detailed information see Modicon Quantum AS-i Master Module EIA 921 00 book Product
Related Information, page 14
Illustration
Front view of the AS-i module with LED Matrix detail and legend numbers:
Legend
The following table provides a description of the functions of the equipment LEDs.
Item Description
1 Display block comprising 4 status indicator lamps (LEDs) for displaying the
module operating modes:
B (green, 1 LED): Indicates, when on, data exchange between module and
slave.
Active (green, 2 LEDs): when on, indicates AS-i module being services by
the local CPU, RIO, or DIO drop adapter.
F (red, 1 LED): indicates, when on steady, module fault. Flashing shows
external I/O fault (could indicate slave with address 0 or an AS-i bus
configuration fault.
2 Display block of 32 indicator lamps (0 - 31, green) for diagnostics of the AS-i bus
and display of the state of each slave connected to the bus.
3 AS-i (red): ON shows AS-i line not properly powered. Flashing shows automatic
addressing enabled and a slave is "prévu" but not connected. OFF shows
normal module function.
4 SLV/BUS (green): ON shows the LEDs 0-31 are in BUS display mode. Displays
the slaves on the bus.
5 I/O Status (green): On shows the LEDs 0-31 are in SLV display mode. Displays
the state of a selected slave.
6 Mode (Push Button): provides local diagnostics of the AS-i bus. Press this
button longer than 1 sec. to change the mode. In slave mode use the Address
Push Button to scroll among the 32 addresses.
7 Address (Push Button): Pressing this button (in slave mode) scrolls through the
slaves. Press longer than 1 sec. to reverse direction of the scroll.
8 AS-i Channel cable connector - connects module to AS-i cable and AS-i power
supply.
Indicators
Ilustration
Diagram of the LED display:
Description
LED Diagnostics
State of Indicator Lamps:
Operating in Protected æ
Mode (normal). Displaying
Outputs.
Operating in Protected æ
Mode (normal). Displaying
Inputs.
Fault on AS-i bus (self- Replace the faulty slave with a
programming possible). new identical slave.
Wiring Diagram
Specifications
AS-i Specifications
Specifications for the 140 EIA 921 00 AS-i module:
Master profile M2
Bus length 100m max, no repeaters
I/O 124 IN / 124 OUT
# slaves 31 max.
Power supply 30VDC @ 120mA max.
Scan time 156 msec x (n+2) if n < 31
156 msec x (n+1) if n = 31
Transmission 167 kbits/sec
Polarity reversal Non-destructive
Bus current required 250mA max.
Power dissipation 2.5W max.
Installation Local, RIO, DIO
Parameter Configuration
PARAMETERS 0
AS-i SLAVE 2-31 see AS-i SLAVE 1
Part VII
Quantum Special Purpose / Intelligent Modules
Introduction
This part provides information of the Quantum Special Purpose / Intelligent Modules
Chapter 28
140 HLI 340 00: High Speed Latch and Interrupt Module
140 HLI 340 00: High Speed Latch and Interrupt Module
Purpose
The following chapter provides information of the Quantum 140 HLI 340 00 Module.
Presentation
Function
The High Speed Latch and Interrupt 24 VDC 16x1 Sink / Source input module accepts 24 VDC
inputs and is for use with 24 VDC sink/source input devices.
Illustration
The following figure shows the 140 HLI 340 00 module and its components.
NOTE: The field wiring terminal strip (Modicon #140 XTS 002 00) must be ordered separately. (The
terminal strip includes the removable door and label.)
NOTE: The tightening torque must be between 0.5 Nm and 0.8 Nm.
NOTICE
DESTRUCTION OF ADAPTER
Before tightening the locknut to the torque 0.50...0.80 Nm, be sure to properly position the
right-angle F adapter connector.
During tightening, be sure to maintain the connector securely.
Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.
Indicators
Illustration
The following table shows the LED indicators for the 140 HLI 340 00 module.
Descriptions
The following table shows the LED descriptions for the 140 HLI 340 00 module.
NOTE: Due to the speed of the module, LED indications do not represent the state of the input
signal, when the input signal is a short duration pulse.
Specifications
General Specifications
General Specifications
Indicators
Indicators
Maximum Input
Absolute Maximum Input Voltage
Continuous 30 Vdc
Input Protection
Input Protection
Isolation
Isolation
Response
Response
OFF - ON 30 μs (max)
ON - OFF 130 μs (max)
Fuses
Fuses
Internal None
External User discretion
Module Keying
Field Wiring Terminal Strip/Module Keying
Wiring Diagram
Illustration
NOTE: Either shielded or unshielded signal cables may be used (the user should consider using
shielded wire in a noisy environment). Shielded types should have a shield tied to earth ground
near the signal ground.
N / C = Not Connected.
NOTE: The tightening torque must be between 0.5 Nm and 0.8 Nm.
NOTICE
DESTRUCTION OF ADAPTER
Before tightening the locknut to the torque 0.50...0.80 Nm, be sure to properly position the
right-angle F adapter connector.
During tightening, be sure to maintain the connector securely.
Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.
Addressing
Flat Addressing
This module requires either 16 contiguous %I references or one %IW word. For a description of
how to access the input points, please refer to Discrete I/O Bit Numbering, page 28.
Topological Addressing
The following tables show the topological addresses for the 140HLI34000 module.
Topological addresses in Bit Mapping format:
Parameter Configuration
Module Placement
The 140 HLI 340 00 High Speed Interrupt module’s functionality depends on its location.
The following list shows the available modes depending on the location:
Local Rack: High Speed Inputs, Latch Inputs, Interrupts,
Remote Rack: High Speed Inputs.
NOTE: The 140 HLI 340 00 module cannot be connected to a secondary rack.
Parameter Description
Chapter 29
140 EHC 202 00: High Speed Counter Module
Purpose
The following chapter provides information of the Quantum 140 EHC 202 00 High Speed Counter
Module.
Presentation
Function
The 140 EHC 202 00 is a two-channel module best suited for high-speed counting applications up
to 500 kHz or for applications that require a quadrature counter interface.
Operating Modes
The following operating modes are possible:
16-bit counters on one or both channels with two outputs, configurable for incremental or
quadrature mode
32-bit counter that uses both channels with two outputs, configurable for incremental or
quadrature mode
32-bit counters on one or both channels with no outputs, configurable for incremental or
quadrature mode
16-bit counters on one or both channels with no outputs, in rate-sample mode for incremental
or quadrature encoders
Outputs
Two FET output switches exist for each counter. They turn on when the counter reaches
programmed setpoint or maximum values in up-count/down-count operations.
The outputs can be turned off by changes in counter values, software commands, or a hard wired
reset from the field.
Each of the outputs can be configured as follows:
Output latched on at setpoint
Output latched on at a terminal count
Output timed on at setpoint, with a time range of 0 ... 16 383 ms (only one of the four possible
outputs can be configured for this mode)
Output timed on at a terminal count, with a time range of 0 ... 16 383 ms (only one of the four
possible outputs can be configured for this mode)
Inputs
Single ended or differential
Illustration
The following figure shows the EHC 102 module and its components.
NOTE: The field wiring terminal strip (Modicon #140 XTS 002 00) must be ordered separately. (The
terminal strip includes the removable door and label.)
Specifications
General Specifications
General Specifications
Counter Inputs
Counter inputs
Discrete Inputs
Discrete inputs
Input threshold
Input threshold
Discrete Outputs
Discrete outputs
Timing Diagrams
The following figure shows the EHC20200 timing diagrams.
NOTE: The timing parameter limits are measures at the module field terminal connector at the logic
low threshold level.
Functions
COUNT UP
The input counter is reset to zero if the count direction input is UP and a preset (hardware or
software) or Load Value command is sent to the module.
When counting in the UP direction, the input counter increments to the maximum value, the next
input pulse sets the counter to zero and it continues counting back up to the maximum value.
COUNT DOWN
The input counter is set to maximum count if the count direction is down and a preset (hardware
or software) or Load Value command is sent to the module.
When counting in the DOWN direction, the input counter is decremented from the maximum value
to zero. The next pulse resets the input counter to the Maximum value and the increment down
starts again.
REMOVE ENABLE
This function disables the input counter, causing it to stop incrementing and hold the count
accumulated prior to disabling.
OUTPUTS
When configured in the count mode, outputs will turn on for defined times when setpoints or
maximum values have been reached.
No output assertion in two, 32 bit counter mode or rate sample.
Programmed ON time for outputs can be set for one channel, one output and one trigger point only.
In a running controller, latched outputs are turned off only by a hardware RESET input. If no reset
is provided, the outputs latched on will turn off when the controller is stopped.
OUTPUT COIL MODE available values:
SETPOINT: ON when set point is reached, back to 0 automatically when the reference is
exceeded.
LATCHED SETPOINT: ON when you reach the set point, it remains ON until no hardware reset
applied (input).
TERMINAL COUNT: ON when it exceeds the max.
LATCHED TERMINAL: ON when it exceeds the max and will be maintained as long as no
hardware reset (input).
TIMED SETPOINT: ON from a set point and held ON during a defined time.
TIMED TERMINAL: ON when it exceeds the max and held ON for a defined time.
COUNTER PRESET
This is both a hardware and software function. In the event that both methods are used, the last
one executed has precedence.
An input counter will be automatically preset whenever a new maximum value or rate sample time
is loaded.
COUNTER ENABLE
Both hardware and software enables are required for an input counter to operate. An input counter
will be automatically software enabled whenever a new maximum value is loaded or a preset
(hardware or software) is sent to it.
QUADRATURE MODE
When the module is configured for quadrature mode operation, the counter requires encoder
pulses on inputs A and B.
In quadrature mode, all input signal edges are counted. A 60 count/revolution encoder will produce
a count of 240 for one shaft rotation.
Rate Sample
rate sample, the module must be:
Configured for pulse or quadrature mode.
Configured for Rate Sample mode.
Loaded with the Rate Sample time value.
Enabled to count, using hardwired input and software control bits.
Pulse Count
Count pulses, the module must be:
Configured for pulse or quadrature mode.
Configured for counter display: two, 16 bit, one, 32 bit, or two, 32 bit counters.
Loaded with the maximum count.
Enabled to count, using hardwired input and software control bits.
Addressing
Flat Addressing
The 140EHC20200 high speed counter requires six contiguous 16-bit input words (%IW) and six
contiguous 16-bit output words (%QW).
Topological Addressing
where:
b = bus
e = equipment (drop)
r = rack
m = module slot
Overview
The 140 EHC 202 00 high speed counter requires six contiguous output (4X) and six contiguous
input (3X) registers in the I/O map.
The 4X registers perform the same configuration tasks as in the Parameter Configuration. Also,
the preset and the enable inputs connected to the field wiring terminal block perform the same
functions as those software command control bits. When both methods are used to:
Preset a counter – the last preset executed has precedence.
Enable/disable a counter – it will only be enabled when both the hardware enable input and
software enable control bit are in the enable state.
For simple applications, the parameter configuation rather than the I/O mapped registers can be
used to configure the module. Parameter configuration is only possible while the PLC is stopped.
The selected parameters take effect when the PLC is set to run. For applications that require that
module parameters be changed while the system is running, user logic can modify the I/O map-
assigned registers to override the previously selected parameters.
When using either parameter configuration or I/O map registers, the maximum values specified in
the Load Values Command section are the largest values that can be used by the module.
The I/O Mapped registers discussed in this section are 4X output registers that:
Preset and enable/disable input counters.
Load setpoint and maximum values to define output turn on points.
Set mode of operation, count, or rate sample.
Enable output switches and configures their mode of operation.
3X input registers that:
Hold count or rate sample data.
Display field power status.
Echo 4X command data after the command is executed by the module.
Commands
There are four command that can be performed. Each uses one or more of both types of registers
assigned to the module. In addition to the command definition byte, the first 4X register for all
commands contain control bits to preset and enable/disable counters of either channel.
Command 1 - CONFIGURES
Command 1 uses three 4X registers and six 3X registers (see below).
The following figure shows the 4X and 3X registers for command 1.
NOTE: 4X register formats for the commands are described first. The 3X register contents after
issuing Command 1 or 2 are listed after the 4X register description for Command 2, since the
responses are the same for both. The 3X responses for Commands 3 and 4 immediately follow
those commands.
NOTE: When Command 0 (4X = 00XX) or any other undefined commands are asserted in the 4X
register, the 3X registers will contain the count inputs if in count mode (same as Command 3) and
the rate sample values when in rate-sample mode (same as Command 4).
The following figure shows the 4x + 1 output register for command 1 (4X+1).
NOTE: The Output ON time specified in the Command 2 registers may be used by only one of the
four outputs. When more than one output is set to mode 5 or 6, the module firmware will operate
the first one encountered, and disable the other outputs set to modes 5 or 6.
NOTE: Zero set into any 4X register pair for 32 bit values or any 4X register means no change.
NOTE: Zero set into any 4X register pair for 32 bit values or any 4X register means no change.
NOTE: Zero set into any 4X register or any 4X register pair for 32 bit values means no change.
Command 3, READ INPUT COUNTER, Output Register Format (4X = 03XX hex)
The following figure shows the 4X register for command 3.
Command 4, READ RATE SAMPLE or READ LAST COUNT VALUE BEFORE MOST RECENT PRESET,
Output Register Format (4X = 04XX hex)
The following figure shows the 4x counters for command 4.
COUNT UP Example
Field connections for this example are illustrated in the EHC 202 wiring diagrams 1-4. The
maximum allowable Vref value is 30 VDC. Input pulse on-off threshold levels for the 5 ... 24 VDC
Vref range are listed in the module specification table. The minimum differential input is 1.8 V.
The following user logic:
Configures the module to count up from zero.
Turns an output on for one count at a setpoint value of 50.
Continues counting to 100.
Rolls over to zero and turn on a second output for one count.
Repeats the operation.
In this example, block moves are used to load the operating parameters into the module. This
requires pre-defined tables be established. Register values are in HEX format.
400201 0243 LOAD VALUES command, disable Counter 2, preset and enable
Counter 1
400202 0064 Counter 1 maximum count, count after which Output 1B turns on
400203 0032 Counter 1 setpoint, count when Output 1A turns on
400204 0000 Counter 2 maximum count (not used in this example)
400205 0000 Counter 2 setpoint (not used in this example)
400206 0000 Output assert time (Not used in this example, one output only, fused
Zeros in the 4X registers also mean no change. Setpoint, maximum count and assert time can only
be set to zero using the parameter configuration. When the registers in this example are echoed,
zeros will appear but the actual content in the module will be unchanged from previous values. In
this example, Counter 2 is disabled and its outputs and timed assert have not been selected.
Registers 400204 - 6 have no meaning.
After the module executes the Configure and Load Value’s commands, they are echoed in the I/O
mapped 3X registers except for the command register’s low 8 bits. Command execution time by
the module is 1 ms. Actual time between the 4X register block move and the echo response display
in the 3X registers is dependent on User Logic and hardware configuration. An echo of the
Configuration command registers would appear as follows:
Response Table
The following table shows the echo response for the configuration command.
Register Value
300001 0100
300002 0000
300003 3100
300004 0000
300005 0000
300006 0000
When this command is issued, the content of the input pulse counter is retrieved. The 3X register
content would appear as follows:
Response table
The following table shows the content of the registers.
400201 0243 LOAD VALUES command, disable Counter 2, preset and enable
Counter 1
400202 XXXX Counter 1 Rate Sample Time in milliseconds
400203 0000 Counter 2 Rate Sample Time in milliseconds (Not used in this
example)
400204 0000 Not used by this command
400205 0000
400206 0000
NOTE: Command echoes are the same as described in the Pulse Input Count Up/Down examples.
When this command is issued, the input pulse counter content is retrieved. The 3X register content
is the count over the time period selected in the Load Values registers 4X + 1 and 4X + 2. The 3X
response to the Read-Rate Sample command in register 40301 is as follows.
Response Table
The following table shows the responses to the read rate sample command.
In modules prior to V02.00, when Rate Sample mode was selected, input was always handled as
if it were generated by a pulse encoder. For example, 60 count per revolution encoders, either
pulse or quadrature types, would give a rate of 60 for a one-second revolution when the interval
was set for one second.
NOTE: Beginning with V2.00 modules, if a quadrature type encoder is used to provide count input
and Pulse/Quadrature Input Counter 1 and 2, bits 9 or 10, are set to 1, the module will detect all
edges.
The result is four times the rate sample value as would be accumulated with an equivalent pulse
encoder input. In the example in the above paragraph, the rate sample would be equal to 240.
Encoder type selection is set using Command 1, CONFIGURE (01XX), 4X+1 register, bits 9 or 10
(see the description of Command 1 in this section).
If the Encoder Type select bits are set to 0, either type of encoder will produce the Rate Sample,
as did versions of the module that were lower than V02.00.
Indicators
Illustration
The following figure shows the LED indicators for the EHC20200 High Speed Counter module.
Descriptions
The following table shows the LED descriptions for the EHC 202 00 high speed counter.
Wiring
Signal overview
The following table shows the signal descriptions of the wiring diagram.
Parameter Description/Usage
INPUT A Single ended or differential count input or Phase A for quadrature mode.
Single ended (active low only) uses Input 1A+ and/or Input 2A+.
Input 1A- and/or Input 2A- are not connected. Differential input encoders use
both plus (+) and minus (-) inputs.
INPUT B Direction level for non-quadrature devices or Phase B for quadrature mode.
Direction inputs for non-quadrature input devices are: Count Up = High
Voltage Level; Count Down = Low Voltage Level
For single ended Input devices, only Input 1B+ and/or Input 2B+ are used.
Input 1B- and 2B- are not connected. Differential input encoders use both
plus (+) and minus (-) inputs.
PRESET C Presets count register(s). Low level causes preset.
For single ended Preset inputs, only Preset 1C+ and/or Preset 2B+ are
used. Preset 1C- and 2C- are not connected. Differential input encoders use
both plus (+) and minus (-) inputs.
OUTPUT RESET 0 Low level resets Outputs 1A, 1B, 2A, and 2B to OFF if latched.
For single ended Reset inputs, only Reset 10+ and/or Reset 20+ are used.
Reset 10- and 20- are not connected. Differential input encoders use both
plus (+) and minus (-) inputs.
ENABLE Low level enables counting.
For single ended Enable inputs, only Enable 1+ and/or Enable 2+ are used.
Enable 1- and 2- are not connected. Differential input encoders use both
plus (+) and minus (-) inputs.
VREF Field input device power source connection. Also, connect any unused (+)
inputs to the group VREF terminal or the one in use (30 Vdc max).
Group A = Terminal 17
Group B = Terminal 37
Group A and Group B VREF supplies can be different voltage levels.
LO FILTER SEL Enables the internal 200 Hz filter when connected to Return Terminal 39.
OUTPUT Internal FET switches connect the output supply wired to Terminal 40 to the
Output 1A, 1B, 2A, 2B terminals at output assert times.
POWER SUPPLY External 24 Vdc power supply (+) connection. Required for the module
interface and for Outputs 1A, 1B, 2A, and 2B.
RETURN External 24 Vdc power supply (-) connection. Required for the module
interface and for Outputs 1A, 1B, 2A, and 2B.
Miscellaneous Information
Field wire to Counter 2 inputs and outputs, when configured for one, 32 bit counter with output
assertion. The unused Counter 1 must have its + (plus) inputs connected to VREF+.
Input counts and parameters are not maintained in the module at power down. The rewrite of
parameters at power up must be done with either user logic or Modzoom-type preset panel
selections.
The 200 Hz filter for each counter can be activated by strapping the Lo Filter Sel terminal to the
Return terminal. This function provides noise immunity for low frequency applications and can also
be used for relay debounce.
Wiring diagram 1
Basic wiring diagram showing single ended pulse input, counting up and constant enable.
Terminal 7 Output Reset tied high, not required; outputs not used
Terminal 11 Hardware enabled
Terminal 15, 16 Outputs 1A and 1B operate relays
Terminal 17 Required VRef+ connection
Terminals 21, 23, 25, 27, 31, 37 Counter 2 not used. These terminals must be connected VRef+
Terminal 39 Required Output Supply Return
Terminal 40 Required Output Supply
N/C not connected
Wiring Diagram 2
Wiring diagram showing differential pulse input, counting up and constant enable.
Wiring Diagram 3
Wiring diagram showing quadratur input with constant enable.
Wiring Diagram 4
Wiring diagram showing differential quadrature input with constant enable.
Maintenance
Fuses
Fuses
NOTE: Turn off power to the module and remove the field wiring terminal strip to gain access to
the fuse.
Parameter Configuration
Overview
This section provides information on the parameters, accessible in the Parameter Configuration
Screen.
NUMBER OF COUNTERS
This part of the parameter configuration screen depends on the choice made in the field: NUMBER
OF COUNTERS. Therefore you find four tables accordingly.
This table shows the parameters configuration screen for the entry: 2x16 WITH OUTPUT
This table shows the parameters configuration screen for the entry: 1x32 WITH OUTPUT
This table shows the parameters configuration screen for the entry: 1x32 NO OUTPUT
This table shows the parameters configuration screen for the entry: RATE SAMPLE MODE
Chapter 30
140 EHC 105 00: High Speed Counter Module
Purpose
The following chapter provides information of the Quantum 140 EHC 105 00 High Speed Counter
Module.
Presentation
Function
The 140 EHC 105 00 is a highspeed counter module. It utilizes five equivalent, independently
usable counters with the following functions:
32bit event counter with 6 modes
Event counter with parallel set point output activation
Event counter with parallel set point output activation and fast Final Set Point
Event counter with serial set point activation
Event counter with serial set point activation and fast final set point
Event counter with timed set point output activation
Event counter with latched set point output avtivation
Illustration
The following figure shows the EHC 105 module and its components.
NOTE: The field wiring terminal strip (Modicon #140 XTS 002 00) must be ordered separately. (The
terminal strip includes the removable door and label.)
Specifications
General Specifications
General Specifications
NOTE: The 5Cx and 24Cx counter inputs may be used alternatively.
Counter Inputs
Counter Inputs
Discrete Inputs
Discrete Inputs
Input Threshold
Input Threshold
Discrete Outputs
Discrete Outputs
Indicators
Illustration
The following table shows the LED indicators for the EHC 105 module.
Description
The following table shows the LED descriptions for the EHC 105 module
Wiring
Parameter Configuration
Overview
This section provides information on the parameters, accessible in the Parameter Configuration
Screen.
Counters
This table shows the parameters for the counters with its values
Glossary
H
HTTP
A domain name given to a specific computer on a network and used to address that computer.
Index
0-9 C
140CRA21110, 99 channel data structure for analog modules
140CRA21120, 99 T_ANA_BI_VWE, 24, 26
140CRA21210, 99 T_ANA_IN_VE, 24, 25
140CRA21220, 99 T_ANA_IN_VWE, 24, 25
140CRA93100, 33 T_CNT_105, 24
140CRA93200, 33 configuring discrete I/O modules, 17
140CRP93100, 33 connector types, for fiber optic links, 73
140CRP93200, 33
140EHC10500, 261
140EHC20200, 261 E
140EIA92100, 249 error codes
140HLI34000, 261 140CRA93100, 51
140NOE211x0, 183 140CRA93200, 57
140NOE251x0, 183 140CRP93100, 38
140NOE31100, 183 140CRP93200, 44
140NOE35100, 183 140NOM21100, 147
140NOE77100, 183 140NOM21200, 159
140NOE77101, 183
140NOE77110, 183
140NOE77111, 183 F
140NOM21100, 137 fiber optic cable
140NOM21200, 137 connecting, 75, 94
140NOM25200, 137 termination kits, 73
140NRP95400, 33
general specifications, 76
140NRP95401C, 33 N
general specifications, 96 NOE771xx
140NWM10000, 183 run LED status, 242
NRP95400
bus topology, 67
A connecting, 75
addressing, 21, 285 hot standby systems example, 71
flat, 22 materials for fiber optic links, 72
IODDT, 24 point-to-point topology, 66
RIO topologies, 65
self-healing ring topology, 70
B termination kits, 73
bus topology, 67, 87 tree topology, 69
NRP95401C
bus topology, 87
compatibilty, 95
connecting, 94
hot standby systems example, 91
materials for fiber optic links, 92
point-to-point topology, 86
RIO topologies, 85
self-healing ring topology, 90
tree topology, 89
P
point-to-point topology, 66, 86
R
RIO fiber optic network
bus topology, 67, 87
point-to-point topology, 66, 86
self-healing ring topology, 70, 90
tree topology, 69, 89
S
self-healing ring topology, 70, 90
services
140NOE77100, 189
140NOE77101, 189
140NOE77110, 189
140NOE77111, 189
140NWM10000, 189
status bytes, 29
T
T_ANA_BI_VWE, 26
T_ANA_IN_VE, 25
T_ANA_IN_VWE, 25
T_CNT_105, 26
termination kits, 73
tree topology, 69, 89