PowerFlex 753 AC Drive

Designed for general purpose applications, the PowerFlex 753 AC drive offers multiple options and features along with the
added benefit of simple integration. The PowerFlex 753 comes standard with built-in I/O making it a cost effective solution
ideal for OEMs and system integrators looking to reduce engineering costs, deliver machines to market faster and meet end-
user demand for more productive and safer machines.

PowerFlex 753 at a glance


Branch circuit
protection supplied Ratings
separately 380…480V: 0.75…270 kW / 1.0…400 Hp / 2.1…477 A
600V: 1.0…300 Hp / 1.7…289 A
690V: 7.5…250 kW / 12…263 A
Isolation Transformers and Input Motor Control • V/Hz Control
Line Reactors are available. • Sensorless Vector Control
See pages 100…108. • Vector Control with FORCE Technology
(with and without encoder)
Integral EMC Filter. External • Interior Permanent Magnet with and without encoder
Common Mode Choke is available. Enclosures • IP00/IP20, NEMA/UL Type Open
See page 98 and 1321 Power • Flange Mount
Conditioning Products Technical
Data, publication 1321-TD001 for
• IP54/NEMA/UL Type 12
LCD Numeric HIM shown (not supplied).
additional information.. Safety • Safe Torque-Off PLe/SIL3 Cat. 3
See page 90 for other options.
• Safe Speed Monitor PLe/SIL3 Cat. 4
Additional • DeviceLogix
Features • Predictive Diagnostics
• Adjustable Voltage Control
• Three option slots for I/O, feedback, safety, auxiliary
Communications
control power, communications
Multiple options for industrial
networks are available. • Indexing
See pages 91 and 92. • Pump Jack and Pump Off for oil well applications
• Pjump and Traverse for Fibers application
• Conformal Coating
Embedded I/O • DC Link Choke
3 Digital Inputs, 1 Relay Output,
• Automatic Device Configuration (1)
1 Transistor Output, 1 Analog Input,
1 Analog Output, 1 PTC Input Certifications • ATEX Certified with appropriate options
See page 93 for additional options. • c-UL-us
• CE
Integral brake transistor on Frames • EAC
1…5, optional on Frames 6…7. • EPRI/SEMI F47
Resistors are available. • FS ISO/EN13849-1 with Safe Torque-Off option
See page 98. • KCC
• Marine (ABS, Lloyd’s Register, and RINA)
• RCM
Output Reactors, Terminators
• RoHS compliant materials
and Reflected Wave Devices • TÜV (2)
are optional. Options See pages 90…109
See pages 98…108. (1) Requires Dual-port EtherNet/IP Option Module (Cat. No. 20-750-ENETR),
firmware V7, Studio 5000 Logix Designer, and Drive Add-On Profiles Version 4.04
or higher.
(2) Certification applies to 20-750-S and 20-750-S1 Safety Options when installed in
drive.
Safety, feedback, and other drive
options are available.
See pages 93…95.

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 55


PowerFlex 753 AC Drive

Additional Information
PowerFlex 750-Series Brochure, publication 750-BR001
PowerFlex 750-Series Technical Data, publication 750-TD001

Catalog Number Explanation


20F 1 A N D 248 A A 0 N N N N N
Input Enclosure Voltage Rating Filtering & Brake
Type Rating Common Mode IGBT
Capacitor
Configuration

Product Selection
IP00/IP20, NEMA/UL Type Open (1)
380…480V AC, Three-Phase Drives
480V AC Input 400V AC Input
Output Amps (2) Normal Heavy Output Amps (2) Normal Heavy
Duty Duty Duty Duty Frame
Cont. 1 Min. 3 Sec. Hp Hp Cat. No. Cont. 1 Min. 3 Sec. kW kW Cat. No. (3) Size
2.1 2.3 3.2 1 0.5 20F11RD2P1AA0NNNNN 2.1 2.3 3.2 0.75 0.37 20F11RC2P1JA0NNNNN 1
3.4 3.7 5.1 2 1.5 20F11RD3P4AA0NNNNN 3.5 3.9 5.3 1.5 0.75 20F11RC3P5JA0NNNNN 1
5 5.5 7.5 3 2 20F11RD5P0AA0NNNNN 5 5.5 7.5 2.2 1.5 20F11RC5P0JA0NNNNN 1
8 8.8 12 5 3 20F11RD8P0AA0NNNNN 8.7 9.6 13.1 4 2.2 20F11RC8P7JA0NNNNN 1
11 12.1 16.5 7.5 5 20F11RD011AA0NNNNN 11.5 12.7 17.3 5.5 4 20F11RC011JA0NNNNN 1
14 15.4 21 10 7.5 20F11RD014AA0NNNNN 15.4 16.9 23.1 7.5 5.5 20F11RC015JA0NNNNN 1
2.1 3.1 3.7 1 1 20F11ND2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11NC2P1JA0NNNNN 2
3.4 5.1 6.1 2 2 20F11ND3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11NC3P5JA0NNNNN 2
5 7.5 9 3 3 20F11ND5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11NC5P0JA0NNNNN 2
8 12 14.4 5 5 20F11ND8P0AA0NNNNN 8.7 13 15.6 4 4 20F11NC8P7JA0NNNNN 2
11 16.5 19.8 7.5 7.5 20F11ND011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11NC011JA0NNNNN 2
14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11ND014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11NC015JA0NNNNN 2
22 (14) 24.2 (21) 33 (33) 15 10 20F11ND022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11NC022JA0NNNNN 2
27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11ND027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11NC030JA0NNNNN 3
34 (27) 37.4 (40.5) 51 (51) 25 20 20F11ND034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11NC037JA0NNNNN 3
40 (34) 44 (51) 60 (61.2) 30 25 20F11ND040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11NC043JA0NNNNN 3
52 (40) 57.2 (60) 78 (78) 40 30 20F11ND052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11NC060JA0NNNNN 4
65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11ND065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11NC072JA0NNNNN 4
77 (65) 84.7 (97.5) 116 (117) 60 50 20F11ND077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11NC085JA0NNNNN 5
96 (77) 106 (116) 144 (144) 75 60 20F11ND096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F11NC104JA0NNNNN 5
125 (96) 138 (144) 188 (188) 100 75 20F1AND125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20F1ANC140JN0NNNNN 6 (4)
156 (125) 172 (188) 234 (234) 125 100 20F1AND156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20F1ANC170JN0NNNNN 6 (4)
186 (156) 205 (234) 279 (281) 150 125 20F1AND186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20F1ANC205JN0NNNNN 6 (4)
248 (186) 273 (279) 372 (372) 200 150 20F1AND248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20F1ANC260JN0NNNNN 6 (4)
302 (248) 332 (372) 453 (453) 250 200 20F1AND302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20F1ANC302JN0NNNNN 7 (4)
361 (302) 397 (453) 542 (544) 300 250 20F1AND361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20F1ANC367JN0NNNNN 7 (4)
415 (361) 457 (542) 623 (650) 350 300 20F1AND415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20F1ANC456JN0NNNNN 7 (4)
477 (361) 525 (542) 716 (650) 400 300 20F1AND477ANONNNNN 477 (367) 525 (551) 716 (684) 270 200 20F1ANC477JNONNNNN 7 (4)
(1) Frames 2…5 are IP20, Frames 6…7 are IP00.
(2) Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
(3) The 11th character determines default Filtering and Common Mode Cap jumper configuration. “J” = Installed, “A” = Removed.
(4) Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

56 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 753 AC Drive

IP00/IP20, NEMA/UL Type Open (continued)


Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For
details, contact your local Rockwell Automation sales office or Allen-Bradley Distributor.

DC Bus terminals are not supplied with AC input Frame 6 and 7 drives.

600V AC, Three-Phase Drives – IP20, NEMA/UL Type 1


Output Amps (1)
Cont. 1 Min. 3 Sec. Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11NE1P7AA0NNNNN 3
2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11NE2P7AA0NNNNN 3
3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11NE3P9AA0NNNNN 3
6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11NE6P1AA0NNNNN 3
9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11NE9P0AA0NNNNN 3
11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11NE011AA0NNNNN 3
17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11NE017AA0NNNNN 3
22 (17) 24 (26) 33 (46) 20 15 20F11NE022AA0NNNNN 3
27 (22) 30 (33) 41 (59) 25 20 20F11NE027AA0NNNNN 4
32 (27) 35 (41) 48 (73) 30 25 20F11NE032AA0NNNNN 4
41 (32) 45 (48) 62 (86) 40 30 20F11NE041AA0NNNNN 5
(1) These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

600…690V AC, Three-Phase Drives – IP00, NEMA/UL Type Open


600V AC Input 690V AC Input
Output Amps (1) Normal Heavy Output Amps (1) Normal Heavy
Duty Duty Duty Duty Frame
Cont. 1 Min. 3 Sec. Hp Hp Cat. No. Cont. 1 Min. 3 Sec. kW kW Cat. No. (2) Size
12 (9.1) 13.2 (13.7) 18 (18) 10 (3) 7.5 20F1ANE012AN0NNNNN 12 (9) 13.2 (13.5) 18 (18) 7.5 5.5 20F1ANF012JN0NNNNN 6 (4)
18 (11.1) 19.8 (16.7) 27 (27) 15 (3) 10 20F1ANE018AN0NNNNN 15 (11.5) 16.5 (17.3) 22.5 (22.5) 11 7.5 20F1ANF015JN0NNNNN 6 (4)
23 (18) 25.3 (27) 34.5 (34.5) 20 (3) 15 20F1ANE023AN0NNNNN 20 (15) 22 (22.5) 30 (30) 15 11 20F1ANF020JN0NNNNN 6 (4)
24 (22) 26.4 (33) 36 (39.6) 20 (3) 20 20F1ANE024AN0NNNNN 23 (20) 25.3 (30) 34.5 (36) 18.5 15 20F1ANF023JN0NNNNN 6 (4)
28 (23) 30.8 (34.5) 42 (42) 25 (3) 20 20F1ANE028AN0NNNNN 30 (23) 33 (34.5) 45 (45) 22 18.5 20F1ANF030JN0NNNNN 6 (4)
33 (28) 36.3 (42) 49.5 (50.4) 30 (3) 25 20F1ANE033AN0NNNNN 34 (30) 37.4 (45) 51 (54) 30 22 20F1ANF034JN0NNNNN 6 (4)
42 (33) 46.2 (49.5) 63 (63) 40 (3) 30 20F1ANE042AN0NNNNN 46 (34) 50.6 (51) 69 (69) 37 30 20F1ANF046JN0NNNNN 6 (4)
53 (42) 58.3 (63) 79.5 (79.5) 50 (3) 40 20F1ANE053AN0NNNNN 50 (46) 55 (69) 75 (82.8) 45 37 20F1ANF050JN0NNNNN 6 (4)
63 (52) 69.3 (78) 94.5 (94.5) 60 50 20F1ANE063AN0NNNNN 61 (50) 67.1 (75) 91.5 (91.5) 55 45 20F1ANF061JN0NNNNN 6 (4)
77 (63) 84.7 (94.5) 116 (116) 75 60 20F1ANE077AN0NNNNN 82 (61) 90.2 (91.5) 123 (123) 75 55 20F1ANF082JN0NNNNN 6 (4)
99 (77) 109 (116) 149 (149) 100 75 20F1ANE099AN0NNNNN 98 (82) 108 (123) 147 (148) 90 75 20F1ANF098JN0NNNNN 6 (4)
125 (99) 138 (149) 188 (188) 125 100 20F1ANE125AN0NNNNN 119 (98) 131 (147) 179 (179) 110 90 20F1ANF119JN0NNNNN 6 (4)
144 (125) 158 (188) 216 (225) 150 125 20F1ANE144AN0NNNNN 142 (119) 156 (179) 213 (214) 132 110 20F1ANF142JN0NNNNN 6 (4)
192 (144) 211 (216) 288 (288) 200 150 20F1ANE192AN0NNNNN 171 (142) 188 (213) 257 (257) 160 132 20F1ANF171JN0NNNNN 7 (4)
242 (192) 266 (288) 363 (363) 250 200 20F1ANE242AN0NNNNN 212 (171) 233 (257) 318 (318) 200 160 20F1ANF212JN0NNNNN 7 (4)
289 (242) 318 (318) 434 (436) 300 250 20F1ANE289AN0NNNNN 263 (212) 289 (289) 395 (395) 250 200 20F1ANF263JN0NNNNN 7 (4)
(1) These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
(2) The 11th character determines default Filtering and Common Mode Cap jumper configuration. “J” = Installed, “A” = Removed.
(3) Alternate 600V ratings when connected to drives 60 Hp and greater in common DC input applications with uncontrolled front ends.
(4) Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 57


PowerFlex 753 AC Drive

Flange Mount
Front = IP20, NEMA/UL Type Open, Back/Heatsink = IP66, NEMA/UL Type 4X

380...480V AC, Three-Phase Drives


480V AC Input 400V AC Input
Output Amps (1) Normal Heavy Output Amps (1) Normal Heavy
Duty Duty Duty Duty Frame
Cont. 1 Min. 3 Sec. Hp Hp Cat. No. Cont. 1 Min. 3 Sec. kW kW Cat. No. (2) Size
2.1 3.1 3.7 1 1 20F11FD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11FC2P1JA0NNNNN 2
3.4 5.1 6.1 2 2 20F11FD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11FC3P5JA0NNNNN 2
5 7.5 9 3 3 20F11FD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11FC5P0JA0NNNNN 2
8 12 14.4 5 5 20F11FD8P0AA0NNNNN 8.7 13 15.6 4 4 20F11FC8P7JA0NNNNN 2
11 16.5 19.8 7.5 7.5 20F11FD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11FC011JA0NNNNN 2
14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11FD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11FC015JA0NNNNN 2
22 (14) 24.2 (21) 33 (33) 15 10 20F11FD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11FC022JA0NNNNN 2
27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11FD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11FC030JA0NNNNN 3
34 (27) 37.4 (40.5) 51 (51) 25 20 20F11FD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11FC037JA0NNNNN 3
40 (34) 44 (51) 60 (61.2) 30 25 20F11FD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11FC043JA0NNNNN 3
52 (40) 57.2 (60) 78 (78) 40 30 20F11FD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11FC060JA0NNNNN 4
65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11FD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11FC072JA0NNNNN 4
77 (65) 84.7 (97.5) 116 (117) 60 50 20F11FD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11FC085JA0NNNNN 5
96 (77) 106 (116) 144 (144) 75 60 20F11FD096AA0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F11FC104JA0NNNNN 5
Note: Frames 6…7 require a user installed flange kit with an IP00, NEMA/UL Type Open drive.
(1) Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
(2) The 11th character determines default Filtering and Common Mode Cap jumper configuration. “J” = Installed, “A” = Removed.

600V AC, Three-Phase Drives


Output Amps (1)
Cont. 1 Min. 3 Sec. Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11FE1P7AA0NNNNN 3
2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11FE2P7AA0NNNNN 3
3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11FE3P9AA0NNNNN 3
6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11FE6P1AA0NNNNN 3
9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11FE9P0AA0NNNNN 3
11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11FE011AA0NNNNN 3
17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11FE017AA0NNNNN 3
22 (17) 24 (26) 33 (46) 20 15 20F11FE022AA0NNNNN 3
27 (22) 30 (33) 41 (59) 25 20 20F11FE027AA0NNNNN 4
32 (27) 35 (41) 48 (73) 30 25 20F11FE032AA0NNNNN 4
41 (32) 45 (48) 62 (86) 40 30 20F11FE041AA0NNNNN 5
52 (41) 57 (62) 78 (111) 50 40 20F11FE052AA0NNNNN 5
(1) These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

58 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 753 AC Drive

IP54, NEMA/UL Type 12

380…480V AC, Three-Phase Drives


480V AC Input 400V AC Input
Output Amps (1) Normal Heavy Output Amps (1) Normal Heavy
Duty Duty Duty Duty Frame
Cont. 1 Min. 3 Sec. Hp Hp Cat. No. Cont. 1 Min. 3 Sec. kW kW Cat. No. (2) Size
2.1 3.1 3.7 1 1 20F11GD2P1AA0NNNNN 2.1 3.1 3.7 0.75 0.75 20F11GC2P1JA0NNNNN 2
3.4 5.1 6.1 2 2 20F11GD3P4AA0NNNNN 3.5 5.2 6.3 1.5 1.5 20F11GC3P5JA0NNNNN 2
5 7.5 9 3 3 20F11GD5P0AA0NNNNN 5 7.5 9.0 2.2 2.2 20F11GC5P0JA0NNNNN 2
8 12 14.4 5 5 20F11GD8P0AA0NNNNN 8.7 13 15.6 4 4 20F11GC8P7JA0NNNNN 2
11 16.5 19.8 7.5 7.5 20F11GD011AA0NNNNN 11.5 17.2 20.7 5.5 5.5 20F11GC011JA0NNNNN 2
14 (11) 15.4 (16.5) 21 (21) 10 7.5 20F11GD014AA0NNNNN 15.4 (11.5) 16.9 (17.3) 23.1 (23.1) 7.5 5.5 20F11GC015JA0NNNNN 2
22 (14) 24.2 (21) 33 (33) 15 10 20F11GD022AA0NNNNN 22 (15.4) 24.2 (23.1) 33 (33) 11 7.5 20F11GC022JA0NNNNN 2
27 (22) 29.7 (33) 40.5 (40.5) 20 15 20F11GD027AA0NNNNN 30 (22) 33 (33) 45 (45) 15 11 20F11GC030JA0NNNNN 3
34 (27) 37.4 (40.5) 51 (51) 25 20 20F11GD034AA0NNNNN 37 (30) 40.7 (45) 55.5 (55.5) 18.5 15 20F11GC037JA0NNNNN 3
40 (34) 44 (51) 60 (61.2) 30 25 20F11GD040AA0NNNNN 43 (37) 47.3 (55.5) 64.5 (66.6) 22 18.5 20F11GC043JA0NNNNN 3
52 (40) 57.2 (60) 78 (78) 40 30 20F11GD052AA0NNNNN 60 (43) 66 (66) 90 (90) 30 22 20F11GC060JA0NNNNN 4
65 (52) 71.5 (78) 97.5 (97.5) 50 40 20F11GD065AA0NNNNN 72 (60) 79.2 (90) 108 (108) 37 30 20F11GC072JA0NNNNN 5
77 (65) 84.7 (97.5) 116 (117) 60 50 20F11GD077AA0NNNNN 85 (72) 93.5 (108) 128 (130) 45 37 20F11GC085JA0NNNNN 5
96 (77) 106 (116) 144 (144) 75 60 20F1AGD096AN0NNNNN 104 (85) 114 (128) 156 (156) 55 45 20F1AGC104JN0NNNNN 6 (3)
125 (96) 138 (144) 188 (188) 100 75 20F1AGD125AN0NNNNN 140 (104) 154 (156) 210 (210) 75 55 20F1AGC140JN0NNNNN 6 (3)
156 (125) 172 (188) 234 (234) 125 100 20F1AGD156AN0NNNNN 170 (140) 187 (210) 255 (255) 90 75 20F1AGC170JN0NNNNN 6 (3)
186 (156) 205 (234) 279 (281) 150 125 20F1AGD186AN0NNNNN 205 (170) 226 (255) 308 (308) 110 90 20F1AGC205JN0NNNNN 6 (3)
248 (186) 273 (279) 372 (372) 200 150 20F1AGD248AN0NNNNN 260 (205) 286 (308) 390 (390) 132 110 20F1AGC260JN0NNNNN 7 (3)
302 (248) 332 (372) 453 (453) 250 200 20F1AGD302AN0NNNNN 302 (260) 332 (390) 453 (468) 160 132 20F1AGC302JN0NNNNN 7 (3)
361 (302) 397 (453) 542 (544) 300 250 20F1AGD361AN0NNNNN 367 (302) 404 (453) 551 (551) 200 160 20F1AGC367JN0NNNNN 7 (3)
415 (361) 457 (542) 623 (650) 350 300 20F1AGD415AN0NNNNN 456 (367) 502 (551) 684 (684) 250 200 20F1AGC456JN0NNNNN 7 (3)
(1) Some drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
(2) The 11th character determines default Filtering and Common Mode Cap jumper configuration. “J” = Installed, “A” = Removed.
(3) Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 59


PowerFlex 753 AC Drive

IP54, NEMA/UL Type 12 (continued)


Frames 3, 4 and 5 are 600V only drives. Frames 6 and 7 are dual voltage drives and can be operated at 600V or 690V AC.
Important: Frames 3, 4, and 5 must NOT be used in common DC input sharing applications with Frame 6 or larger drives. For
details, contact your local Rockwell Automation sales office or Allen-Bradley Distributor.

DC Bus terminals are not supplied with AC input Frame 6 and 7 drives.

600V AC, Three-Phase Drives


Output Amps (1)
Cont. 1 Min. 3 Sec. Normal Duty Hp Heavy Duty Hp Cat. No. Frame Size
1.7 (0.9) 1.9 (1.4) 2.6 (2.6) 1 0.5 20F11GE1P7AA0NNNNN 3
2.7 (1.7) 3.0 (2.6) 4.1 (4.6) 2 1 20F11GE2P7AA0NNNNN 3
3.9 (2.7) 4.3 (4.1) 5.9 (7.3) 3 2 20F11GE3P9AA0NNNNN 3
6.1 (3.9) 6.7 (5.9) 9.2 (10.5) 5 3 20F11GE6P1AA0NNNNN 3
9 (6.1) 9.9 (9.2) 13.5 (16.5) 7.5 5 20F11GE9P0AA0NNNNN 3
11 (9) 12.1 (13.5) 16.5 (24.3) 10 7.5 20F11GE011AA0NNNNN 3
17 (11) 18.7 (16.5) 25.5 (29.7) 15 10 20F11GE017AA0NNNNN 3
22 (17) 24 (26) 33 (46) 20 15 20F11GE022AA0NNNNN 3
27 (22) 30 (33) 41 (59) 25 20 20F11GE027AA0NNNNN 4
32 (27) 35 (41) 48 (73) 30 25 20F11GE032AA0NNNNN 4
41 (32) 45 (48) 62 (86) 40 30 20F11GE041AA0NNNNN 5
(1) These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.

600…690V AC, Three-Phase Drives


600V AC Input 690V AC Input
Output Amps (1) Normal Heavy Output Amps (1) Normal Heavy
Duty Duty Duty Duty Frame
Cont. 1 Min. 3 Sec. Hp Hp Cat. No. Cont. 1 Min. 3 Sec. kW kW Cat. No. (2) Size
12 (9.1) 13.2 (13.7) 18 (18) 10 (3) 7.5 20F1AGE012AN0NNNNN 12 (9) 13.2 (13.5) 18 (18) 7.5 5.5 20F1AGF012JN0NNNNN 6 (4)
18 (11.1) 19.8 (16.7) 27 (27) 15 (3) 10 20F1AGE018AN0NNNNN 15 (11.5) 16.5 (17.3) 22.5 (22.5) 11 7.5 20F1AGF015JN0NNNNN 6 (4)
23 (18) 25.3 (27) 34.5 (34.5) 20 (3) 15 20F1AGE023AN0NNNNN 20 (15) 22 (22.5) 30 (30) 15 11 20F1AGF020JN0NNNNN 6 (4)
24 (22) 26.4 (33) 36 (39.6) 20 (3) 20 20F1AGE024AN0NNNNN 23 (20) 25.3 (30) 34.5 (36) 18.5 15 20F1AGF023JN0NNNNN 6 (4)
28 (23) 30.8 (34.5) 42 (42) 25 (3) 20 20F1AGE028AN0NNNNN 30 (23) 33 (34.5) 45 (45) 22 18.5 20F1AGF030JN0NNNNN 6 (4)
33 (28) 36.3 (42) 49.5 (50.4) 30 (3) 25 20F1AGE033AN0NNNNN 34 (30) 37.4 (45) 51 (54) 30 22 20F1AGF034JN0NNNNN 6 (4)
42 (33) 46.2 (49.5) 63 (63) 40 (3) 30 20F1AGE042AN0NNNNN 46 (34) 50.6 (51) 69 (69) 37 30 20F1AGF046JN0NNNNN 6 (4)
53 (42) 58.3 (63) 79.5 (79.5) 50 (3) 40 20F1AGE053AN0NNNNN 50 (46) 55 (69) 75 (82.8) 45 37 20F1AGF050JN0NNNNN 6 (4)
63 (52) 69.3 (78) 94.5 (94.5) 60 50 20F1AGE063AN0NNNNN 61 (50) 67.1 (75) 91.5 (91.5) 55 45 20F1AGF061JN0NNNNN 6 (4)
77 (63) 84.7 (94.5) 116 (116) 75 60 20F1AGE077AN0NNNNN 82 (61) 90.2 (91.5) 123 (123) 75 55 20F1AGF082JN0NNNNN 6 (4)
99 (77) 109 (116) 149 (149) 100 75 20F1AGE099AN0NNNNN 98 (82) 108 (123) 147 (148) 90 75 20F1AGF098JN0NNNNN 6 (4)
125 (99) 138 (149) 188 (188) 125 100 20F1AGE125AN0NNNNN 119 (98) 131 (147) 179 (179) 110 90 20F1AGF119JN0NNNNN 6 (4)
144 (125) 158 (188) 216 (225) 150 125 20F1AGE144AN0NNNNN 142 (119) 156 (179) 213 (214) 132 110 20F1AGF142JN0NNNNN 6 (4)
192 (144) 211 (216) 288 (288) 200 150 20F1AGE192AN0NNNNN 171 (142) 188 (213) 257 (257) 160 132 20F1AGF171JN0NNNNN 7 (4)
242 (192) 266 (288) 363 (363) 250 200 20F1AGE242AN0NNNNN 212 (171) 233 (257) 318 (318) 200 160 20F1AGF212JN0NNNNN 7 (4)
289 (242) 318 (318) 434 (436) 300 250 20F1AGE289AN0NNNNN 263 (212) 289 (289) 395 (395) 250 200 20F1AGF263JN0NNNNN 7 (4)
(1) These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at either rating.
(2) The 11th character determines default Filtering and Common Mode Cap jumper configuration. “J” = Installed, “A” = Removed.
(3) Alternate 600V ratings when connected to drives 60 Hp and greater in common DC input applications with uncontrolled front ends.
(4) Also available with internal Brake IGBT (20F1xxxxxxx A xxxxxx).

60 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 753 AC Drive

Approximate Dimensions and Weights


Dimensions are in mm (in.) - weights are in kg (lb)

IP00/IP20, NEMA/UL Type Open


Frame H W D Weight
1 400.5 (15.77) 110.0 (4.33) 211.0 (8.31) 6.00 (12.75)
2 424.2 (16.70) 134.5 (5.30) 212.0 (8.35) 7.80 (17.2)
3 454.0 (17.87) 190.0 (7.48) 212.0 (8.35) 11.80 (26.1)
4 474.0 (18.66) 222.0 (8.74) 212.0 (8.35) 13.60 (30.0)
5 550.0 (21.65) 270.0 (10.63) 212.0 (8.35) 20.40 (45.0)
6 665.5 (26.20) 308.0 (12.13) 346.4 (13.64) 38.60 (85.0)
7 881.5 (34.70) 430.0 (16.93) 349.6 (13.76) 72.60…108.90
(160.0…240.0)

IP54, NEMA/UL Type 12


Frame H W D Weight (1)
2 543.2 (21.39) 215.3 (8.48) 222.2 (8.75) 8.00 (17.0)
3 551.0 (21.69) 268.0 (10.55) 220.1 (8.67) 12.00 (26.0)
4 571.0 (22.48) 300.0 (11.81) 220.1 (8.67) 14.00 (30.0)
5 647.0 (25.47) 348.0 (13.70) 220.1 (8.67) 20.00 (45.0)
6 1298.3 (51.11) 609.4 (23.99) 464.7 (18.30) 91.00 (200.0)
7 1614.0 (63.54) 609.4 (23.99) 464.7 (18.30) 162.00 (357.0)
(1) Weights are approximate. Refer to the PowerFlex 750-Series Technical Data for detailed weight information.

Flange Mount
Frame H W D1 D2 Weight (1)
2 481.8 (18.97) 206.2 (8.12) 148.3 (5.84) 63.7 (2.51) 8.00 (17.0)
3 515.0 (20.28) 260.0 (10.24) 127.4 (5.02) 84.6 (3.33) 12.00 (26.0)
4 535.0 (21.06) 292.0 (11.50) 127.4 (5.02) 84.6 (3.33) 14.00 (30.0)
5 611.0 (24.06) 340.0 (13.39) 127.4 (5.02) 84.6 (3.33) 20.00 (45.0)
6 665.5 (26.20) 308.0 (12.13) 208.4 (8.20) 138.0 (5.43) 38.00 (84.0)
7 875.0 (34.45) 430.0 (16.93) 208.4 (8.20) 138.0 (5.43) 96.00 (212.0)
(1) Weights are approximate. Refer to the PowerFlex 750-Series Technical Data for detailed weight information.

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 61


PowerFlex 7-Class and AFE Options
Human Interface Modules

Blank Plate 20-HIM-A3 20-HIM-A5 20-HIM-A6


20-HIM-C3S 20-HIM-C5S 20-HIM-C6S

Used with PowerFlex Drive


Description Cat. No. 70 753/755 AFE
No HIM (Blank Plate), Handheld/Local (Drive Mount) 20-HIM-A0 ✓ ✓ ✓
LCD Display, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A3 ✓ ✓
LCD Display, Programmer Only, Handheld/Local (Drive Mount) 20-HIM-A5 ✓ ✓
Enhanced, LCD, Full Numeric Keypad, Handheld/Local (Drive Mount) 20-HIM-A6 ✓ ✓ ✓
Remote (Panel Mount) LCD Display, Full Numeric Keypad (1) (2) 20-HIM-C3S ✓ ✓
Remote (Panel Mount) LCD Display, Programmer Only (1) (2) 20-HIM-C5S ✓ ✓
Enhanced, LCD, Full Numeric Keypad (1) (2) 20-HIM-C6S ✓ ✓ ✓
(1) IP66, NEMA Type 4X/12−for indoor use only.
(2) Includes a 1202-C30 interface cable (3 m/9.8 ft) for connection to drive.

Human Interface Module (HIM) Accessories


Used with PowerFlex Drive
Description Cat. No. 70 753/755 AFE
Bezel Kit for LCD HIMs, NEMA Type 1 (1) 20-HIM-B1 ✓ ✓ ✓
PowerFlex HIM Interface Cable, 1 m (3.3 ft) (2) 20-HIM-H10 ✓ ✓ ✓
Comm Option Cable Kit (Male-Male)
0.33 m (1.1 ft) 1202-C03 ✓ ✓ ✓
1 m (3.3 ft) 1202-C10 ✓ ✓ ✓
3 m (9.8 ft) 1202-C30 ✓ ✓ ✓
9 m (29.5 ft) 1202-C90 ✓ ✓ ✓
Cable Kit (Male-Female) (3)
0.33 m (1.1 ft) 1202-H03 ✓ ✓ ✓
1 m (3.3 ft) 1202-H10 ✓ ✓ ✓
3 m (9.8 ft) 1202-H30 ✓ ✓ ✓
9 m (29.5 ft) 1202-H90 ✓ ✓ ✓
DPI™ Cable Kit with Connectors, Tools and 100 m (328 ft) Cable 1202-CBL-KIT-100M ✓ ✓ ✓
DPI Cable Connector Kit 1202-TB-KIT-SET ✓ ✓ ✓
DPI/SCANport™ One to Two Port Splitter Cable 1203-S03 ✓ ✓ ✓
(1) Includes a 1202-C30 interface cable (3 m/9.8 ft) for connection to drive.
(2) Required only when HIM is used as handheld or remote.
(3) Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 m (32.8 ft).

90 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 7-Class and AFE Options

Communication Option Kits


Used with PowerFlex Drive
Description Cat. No. 70 753/755 AFE
BACnet/IP Option Module 20-750-BNETIP ✓
BACnet® MS/TP RS485 Communication Adapter 20-COMM-B ✓ ✓
Coaxial ControlNet™ Option Module 20-750-CNETC ✓
ControlNet™ Communication Adapter (Coax) 20-COMM-C ✓ ✓ (1) ✓
DeviceNet™ Option Module 20-750-DNET ✓
DeviceNet™ Communication Adapter 20-COMM-D ✓ ✓ (1) ✓
Dual-port EtherNet/IP Option Module 20-750-ENETR ✓
EtherNet/IP™ Communication Adapter 20-COMM-E ✓ ✓ (1) ✓
Dual-port EtherNet/IP™ Communication Adapter 20-COMM-ER ✓ ✓
HVAC Communication Adapter 20-COMM-H ✓ ✓ (1) ✓
CANopen® Communication Adapter 20-COMM-K ✓ ✓ (1) ✓
LonWorks® Communication Adapter 20-COMM-L ✓ ✓ (1) ✓
Modbus/TCP Communication Adapter 20-COMM-M ✓ ✓ (1) ✓
Profibus DPV1 Option Module 20-750-PBUS ✓
Single-port Profinet I/O Option Module 20-750-PNET ✓
Dual-port Profinet I/O Option Module 20-750-PNET2P ✓
PROFIBUS™ DP Communication Adapter 20-COMM-P ✓ ✓ (1) ✓
ControlNet™ Communication Adapter (Fiber) 20-COMM-Q ✓ ✓ (1) ✓
Remote I/O Communication Adapter (2) 20-COMM-R ✓ ✓ (1) ✓
RS485 DF1 Communication Adapter 20-COMM-S ✓ ✓ (1) ✓
External Communications Kit Power Supply 20-XCOMM-AC-PS1 ✓ ✓ ✓
DPI External Communications Kit 20-XCOMM-DC-BASE ✓ ✓ ✓
External DPI I/O Option Board(3) 20-XCOMM-IO-OPT1 ✓ ✓ ✓
Compact I/O Module (3 Channel) 1769-SM1 ✓ ✓ ✓
(1) Requires a Communication Carrier Card (20-750-20COMM or 20-750-20COMM-F1). Refer to PowerFlex 750-Series Legacy Communication Compatibility for details.
(2) This item has Silver Series status.
(3) For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 91


PowerFlex 7-Class and AFE Options

PowerFlex 750-Series Legacy Communication Compatibility


Most legacy communication adapters (20-COMM) can be used with the PowerFlex 753/755. However, the restrictions stated
below do apply.
Frame 1 - It is recommended that the 20-750-20COMM-F1 Communication Carrier Card only be installed in Port 4. Port 5 will
not be accessible when this module is installed.
Frames 2 and larger - It is recommended that the 20-750-20COMM Communication Carrier Card be installed in Port 6. Using
Port 4 or 5 will make the adjacent left port inaccessible to other option modules and may interfere with network cable
connections.
Adapter Accesses Ports 0…6
for I/O Connections Accesses Ports 7 and Higher Supports Drive Add-on Supports Asian-
Cat. No. Type (Implicit and Explicit Messaging) (I/O, Explicit Messaging) Profiles Languages(1)
20-COMM-B BACnet MS/TP Not Compatible
20-COMM-C ControlNet (Coax) ✓ v3.001 (2) ✓ v3.001 (2) ✓ (3) ✓ v3.001 (2)
20-COMM-D DeviceNet ✓ (4) Not Compatible
20-COMM-E EtherNet/IP ✓ v4.001 (2) ✓ v4.001 (2) ✓ (3) ✓ v4.001 (2)
20-COMM-H RS-485 HVAC ✓ v2.009 (5) (2)
20-COMM-K CANopen ✓ v1.001 (2) Not Compatible
20-COMM-L LonWorks ✓ v1.007 (2)

20-COMM-M Modbus/TCP ✓ v2.001 (2) ✓ v2.001 (2) ✓ v2.001 (2)


Not Compatible
20-COMM-P ControlNet (Fiber) ✓ v1.006 (2) ✓ v1.006 (2) Not Compatible
20-COMM-Q PROFIBUS DP ✓ v3.001 (2) ✓ v3.001 (2) ✓ (3) ✓ v3.001 (2)
20-COMM-R (6) Remote I/O ✓ (4)
Not Compatible
20-COMM-S RS-485 DF1 ✓ (4)
(1) Chinese, Japanese, and Korean languages are supported at the time of publication.
(2) Requires this adapter firmware version or higher.
(3) Requires firmware version v1.05 or higher of the drive Add-on Profiles for Studio 5000 Logix Designer software.
(4) Controller must be capable of reading/writing 32-bit floating point (REAL) values.
(5) Supports all three modes of operation (RTU, P1, N2).
(6) This item has Silver Series status.

Communication Accessories
Used with PowerFlex Drive
Description Cat. No. 70 753/755 AFE
Serial Null Modem Adapter 1203-SNM ✓ ✓ ✓
Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables 1203-SSS ✓ ✓ ✓
Universal Serial Bus™ (USB) Converter includes 2m USB, 20-HIM-H10 and 22-HIM-H10 Cables 1203-USB ✓ ✓ ✓
ControlNet T-tap Straight 1786-TPS ✓
Communication Carrier Card for PowerFlex 750-Series Frame 1 drives 20-750-20COMM-F1 ✓
Communication Carrier Card for PowerFlex 750-Series Frame 2 or higher drives 20-750-20COMM ✓

92 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 7-Class and AFE Options

I/O Option Kits


Used with PowerFlex Drive
Description Cat. No. 70 753/755 AFE
ATEX Option Module with 1 Thermosensor Input Connection (requires 11-Series I/O Module below) 20-750-ATEX ✓ (1)
24V DC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In and 2 Relay Outputs 20-750-1132C-2R ✓ (1)
24V DC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In, 1 Relay and 2 Transistor Outputs 20-750-1133C-1R2T ✓ (1)
115V AC 11-Series I/O Module with 1 Analog In, 1 Analog Out, 3 Digital In and 2 Relay Outputs 20-750-1132D-2R ✓ (1)
24V DC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262C-2R ✓ (1)
115V AC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs 20-750-2262D-2R ✓ (1)
24V DC 22-Series I/O Module with 2 Analog In, 2 Analog Out, 6 Digital In, 3 Digital Out, 1 Relay and 20-750-2263C-1R2T ✓ (1)
2 Transistor Outputs
(1) I/O option kits are not allowed in CIP motion mode.

Safety Options
Used with PowerFlex Drive
Description Cat. No. 70 753/755
DriveGuard Safe Torque-Off 20A-DG01 ✓
Safe Torque-Off 20-750-S ✓ (1)
Safe Speed Monitor 20-750-S1 ✓ (1) (2)
(1) Drive can accommodate only one option.
(2) Requires the Dual Incremental Encoder or Universal Feedback Option. Also requires the 20-750-EMCSSM1-F8 EMC Option Kit with Frame 8…9 drives.

Feedback Options
Used with PowerFlex Drive
Description Cat. No. 70 753/755
5V/12V Encoder (1) 20A-ENC-1 ✓
Incremental Encoder 20-750-ENC-1 ✓(2)
Dual Incremental Encoder 20-750-DENC-1 ✓(2)
Universal Feedback (includes Stegmann, Heidenhain, SSI, Biss, 5V Incremental) 20-750-UFB-1 ✓ (3)
(1) Works only with PowerFlex 70 Enhanced Control.
(2) Homing and registration functions are not supported when using this device with Studio 5000 Logix Designer embedded motion instructions. To use these functions, the Universal Feedback Board (20-750-UFB-1) must
be used.
(3) PowerFlex 755 only.

PowerFlex 750-Series Option Kits

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 93


PowerFlex 7-Class and AFE Options

Used with PowerFlex Drive


Description Frame Cat. No. 70 753/755
Auxiliary Power Supply 24V Aux Power Supply 1…7 (1) 20-750-APS ✓
DC Bus Bar Option Kit DC Bus Bars for 380…480V AC drives 6 20-750-DCBB1-F6 ✓
7 20-750-DCBB1-F7 ✓
DC Bus Bars for 600…690V AC drives 6 20-750-DCBB2-F6 ✓
7 20-750-DCBB2-F7 ✓
DC Bus Connection Kit Connects the drive DC bus terminals to the cabinet bus rails. 8…10 20-750-BUS1A-F8 ✓
EMC Option Kit EMC Plate with Core for 380…480V AC drives 1 20-750-EMC1-F1 ✓
2 20-750-EMC1-F2 ✓
3 20-750-EMC1-F3 ✓
EMC Plate with Core for 600V AC drives 3 20-750-EMC3-F3 ✓
EMC Plate with Cores for 380…480V AC drives 4 20-750-EMC1-F4 ✓
5 20-750-EMC1-F5 ✓
EMC Plate with Cores for 600V AC drives 4 20-750-EMC3-F4 ✓
5 20-750-EMC3-F5 ✓
EMC Core for 380…480V AC drives 1 20-750-EMC2-F1 ✓
2 20-750-EMC2-F2 ✓
3 20-750-EMC2-F3 ✓
EMC Core for 600V AC drives 3 20-750-EMC4-F3 ✓
EMC Cores for 380…480V AC drives 4…5 20-750-EMC2-F45 ✓
EMC Cores for 600V AC drives 4 20-750-EMC4-F4 ✓
5 20-750-EMC4-F5 ✓
EMC Plate with Cores for 600…690V AC drives 6 20-750-EMC3-F6 ✓
7 20-750-EMC3-F7 ✓
EMC Plate with Cores for 600…690V AC drives (IP54 Only) 6 20-750-EMC5-F6 ✓
7 20-750-EMC5-F7 ✓
EMC Core – Inverter-mounted output, for 380…690V AC input and DC input 8…10 20-750-EMCCM1-F8 ✓
drives.
EMC Core – Cabinet-mounted input, for 380…690V Common 8…10 20-750-CBPEMCCM1-F8 ✓
DC Input drives only.
EMC Core – Cabinet-mounted input, for 380…690V AC input drives only. 8…10 20-750-EMCCM1-F9 ✓
EMC Cores – Required when using the Safe Speed Monitor option 20-750-S1 8…10 20-750-EMCSSM1-F8 ✓
with 380…690V drives.
Door Shielding Kit 10 20-750-EMCDK1-F10 ✓
Exhaust Hood Exhaust Hood – IP20, NEMA/UL Type 1 drives. 8 20-750-HOOD1-F8 ✓
Flange Adapter Kit Converts Open Type drive to external heatsink (flange) with 2 20-750-FLNG1-F2 ✓
NEMA/UL Type 1 integrity backside. 3 20-750-FLNG1-F3 ✓
This kit is for use with IP20, NEMA/UL Type 0 drives and will
4 20-750-FLNG1-F4 ✓
not provide an air-tight or water-tight seal. Where sealing is
required (e.g. contaminated, dirty or wet environments), a drive with an “F” 5 20-750-FLNG1-F5 ✓
enclosure option must be used.
Converts Open Type drive to external heatsink (flange) with 6 20-750-FLNG4-F6 ✓
NEMA/UL Type 4X/12 integrity backside. 7 20-750-FLNG4-F7 ✓
L Bus Bar Kit Includes three L-brackets 8…10 20-750-LBRKT1 ✓
NEMA/UL Type 1 Option NEMA/UL Type 1 Kit 1 20-750-NEMA1-F1 ✓
Kit 2 20-750-NEMA1-F2 ✓
3 20-750-NEMA1-F3 ✓
4 20-750-NEMA1-F4 ✓
5 20-750-NEMA1-F5 ✓
6 20-750-NEMA1-F6 ✓
7 20-750-NEMA1-F7 ✓
Power Terminal Extension Allows connection of two parallel leads to the AC terminals. 6 20-750-ACTE1-F6 ✓
continued

94 Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015


PowerFlex 7-Class and AFE Options

PowerFlex 750-Series Option Kits (continued)


Used with PowerFlex Drive
Description Frame Cat. No. 70 753/755
Power Terminal Guard Provides additional protection against contact with the power terminals. 6 20-750-PTG1-F6 ✓
7 20-750-PTG1-F7 ✓
Remote Control POD Hardware, fiber-optic, and power supply cables to remotely mount the 8…10 20-750-RPD1-F8 ✓
Mounting Kit control POD up to 23 m (75 ft) from the drive.
Roll-Out Cart A wheeled roll-out cart that facilitates drive installation and removal. 8…10 20-750-CART1-F8 ✓
Required for Frame 8 and larger drives.
(1) Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.

Other Options
Used with PowerFlex Drive
Description Cat. No. 70 753/755
115V AC Interface AK-M9-115VAC-1 ✓
Frame E Flange Gasket AK-M9-GASKET1-E4 ✓
Service Connection Board (1) SK-M9-SCB1 ✓
(1) Provides temporary DPI/HIM connection for NEMA/UL Type 1 and Flange drives with cover removed.

Rockwell Automation Publication PFLEX-SG002I-EN-P - May 2015 95