DTR Lomo Luxury 9-12 ANG
DTR Lomo Luxury 9-12 ANG
Service Manual
Models: GWH09QB-K3DNA1G GWH12QC-K3DNB2G
GWH09QB-K3DNA5G GWH12QC-K3DNB4G
GWH09QB-K3DNA5G GWH12QC-K3DNB6G
GWH09QB-K3DNB2G GWH12QC-K3DNC2G
GWH09QB-K3DNB4G GWH12QC-K3DNC4G
GWH09QB-K3DNB6G (Refrigerant R410A)
GWH09QB-K3DNC2G
GWH09QB-K3DNC4G
GWH12QC-K3DNA1G
GWH12QC-K3DNA5G
Table of Contents
Table of Contents
Service Manual
9. Maintenance.............................................................................................................60
9.1 Error Code List................................................................................................................60
9.2 Procedure of Troubleshooting.........................................................................................68
9.3 Troubleshooting for Normal Malfunction..........................................................................83
10. Exploded View and Parts List...............................................................85
10.1 Indoor Unit.....................................................................................................................85
10.2 Outdoor Unit..................................................................................................................93
11. Removal Procedure........................................................................................95
11.1 Removal Procedure of Indoor Unit................................................................................95
11.2 Removal Procedure of Outdoor Unit...........................................................................100
Appendix:.......................................................................................................................106
Appendix 1: Reference Sheet of Celsius and Fahrenheit...................................................106
Appendix 2: Configuration of Connection Pipe....................................................................106
Appendix 3: Pipe Expanding Method..................................................................................107
Appendix 4: List of Resistance for Temperature Sensor.....................................................108
Table of Contents
Service Manual
GWH09QB-K3DNA1G/I GWH09QB-K3DNB6G/I
GWH12QC-K3DNA1G/I GWH12QC-K3DNB6G/I
GWH09QB-K3DNA5G/I GWH09QB-K3DNB4G/I
GWH12QC-K3DNA5G/I GWH12QC-K3DNB4G/I
GWH09QB-K3DNC2G/I GWH09QB-K3DNC4G/I
GWH12QC-K3DNC2G/I GWH12QC-K3DNC4G/I
GWH09QB-K3DNB2G/I
GWH12QC-K3DNB2G/I
Technical Information 1
Service Manual
Outdoor Unit
GWH09QB-K3DNA1G/O
GWH12QC-K3DNA1G/O
Remote Controller
YV1F7 YAN1F1
GWH09QB-K3DNC2G(CB439000402) YV1F7
All models except
YAN1F1
WIFI
GWH09QB-K3DNC2G(CB439000402)
MODE ON/OFF
FAN SWING
IFEEL X-FAN
2 Technical Information
Service Manual
2. Specifications
2.1 Specification Sheet
Parameter Unit Value
1.GWH09QB-K3DNA1G
1.GWH12QC-K3DNA1G
2.GWH09QB-K3DNB6G
2.GWH12QC-K3DNB6G
3.GWH09QB-K3DNA5G
Model 3.GWH12QC-K3DNA5G
4.GWH09QB-K3DNB4G
4.GWH12QC-K3DNB4G
5.GWH09QB-K3DNC2G
5.GWH12QC-K3DNC2G
6.GWH09QB-K3DNC4G
1.CB419005503 2.CB435000404 1.CB419005403 2.CB435000103
Product Code 3.CB425003503 4.CB434002304 3.CB425003603 4.CB434002103
5.CB439000402 6.CB444001202 5.CB439000101
Rated Voltage V~ 220-240 220-240
Power
Rated Frequency Hz 50 50
Supply
Phases 1 1
Power Supply Mode Outdoor Outdoor
Cooling Capacity(Min~Max) W 2600(450~3230) 3500(600~3960)
Heating Capacity(Min~Max) W 2800(450~4100) 3670(600~5130)
Cooling Power Input(Min~Max) W 805(200~1420) 1084(220~1550)
Heating Power Input(Min~Max) W 755(200~1550) 989(220~1650)
Cooling Current Input A 3.7 5.2
Heating Current Input A 3.4 5.0
Rated Input W 1550 1650
Rated Current A 6.3 6.9
Air Flow Volume(SH/H/M//L/SL) m3/h 560/490/430/330/- 660/540/460/330/-
Dehumidifying Volume L/h 0.8 1.4
EER W/W 3.23 3.23
COP W/W 3.71 3.71
SEER W/W 6.1 6.1
SCOP W/W / /
Application Area m2 12-18 16-24
1.GWH12QC-K3DNA1G/I
1.GWH09QB-K3DNA1G/I2.GWH09QB-K3DNB6G/I
2.GWH12QC-K3DNB6G/I
3.GWH09QB-K3DNA5G/I4.GWH09QB-K3DNB4G/I
Indoor Unit Model 3.GWH12QC-K3DNA5G/I
5.GWH09QB-K3DNC2G/I6.GWH09QB-K3DNC4G/I
4.GWH12QC-K3DNB4G/I
5.GWH12QC-K3DNC2G/I
Fan Type Cross-flow Cross-flow
Fan Diameter Length(DXL) mm Ф98X580 Ф98X633.5
r/
Cooling Speed(SH/H/M//L/SL) 1300/1200/1050/800/- 1350/1200/1050/850/-
min
r/
Heating Speed(SH/H/M//L/SL) 1300/1200/1050/900/- 1300/1150/1000/900/-
min
Fan Motor Power Output W 20 20
Fan Motor RLA A 0.22 0.31
Fan Motor Capacitor μF 1 1.5
Indoor Evaporator Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Unit Evaporator Pipe Diameter mm Φ5 Φ5
Evaporator Row-fin Gap mm 2-1.4 2-1.4
Evaporator Coil Length (LXDXW) mm 584X22.8X266.7 635X22.8X306.3
Swing Motor Model MP24AA MP24BA
Swing Motor Power Output W 1.5 1.5
Fuse Current A 3.15 3.15
Sound Pressure Level(SH/H/M//L/ dB
39/36/32/26/- 39/33/26/-/-
SL) (A)
dB
Sound Power Level(SH/H/M//L/SL) 49/46/42/36/- 49/43/36/-/-
(A)
Dimension (WXHXD) mm 790X275X200 845X289X209
Dimension of Carton Box (LXWXH) mm 863X268X352 918X278X364
Dimension of Package(LXWXH) mm 866X271X367 921X281X379
Net Weight kg 9 10
Gross Weight kg 11 12
Technical Information 3
Service Manual
4 Technical Information
Service Manual
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Technical Information 5
Service Manual
Current(A)
6
7
5
6
5 4
4 3
Condition
3 Condition
Indoor:DB 20°C
Indoor:DB 27°C WB19°C 2 Indoor air flow: Super High
2 Indoor air flow: Super High
Pipe length:4m
Pipe length:4m
1 1 Voltage:230V
Voltage:230V
0 0
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Compressor Speed(rps) Compressor Speed(rps)
Cooling Heating
130 130
120 120
110 110
Capacity ratio(%)
Capacity ratio(%)
100 100
90
90
80
80
70 Condition
70 Condition
Indoor:DB27°C WB19°C 60 Indoor:DB20°C
Indoor air flow: High Indoor air flow: High
60 Pipe length:4m
Pipe length:4m 50
50 40
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 -22 -15 -10 -5 0 5 10
Outdoor temp. (°C) Outdoor temp.(°C)
6 Technical Information
Service Manual
Heating:
Rated heating Pressure of gas pipe Inlet and outlet pipe
Compressor
condition(°C) connecting indoor and temperature of heat Fan speed of Fan speed of
Model frequency
(DB/WB) outdoor unit exchanger indoor unit outdoor unit
(Hz)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
09K 65
20/- 7/6 2.2 to 2.4 70 to 35 2 to 4 Super High High
12K 77
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length:4m.
Indoor side noise when blowing Outdoor side noise when blowing
60 58
12K
56
50 54
09K
Noise dB(A)
52
Noise/dB(A)
40 50
09K
12K 48
30
46
44
20
Low Middle High Super High 42
20 30 40 50 60 70 80 90
Indoor fan motor rotating speed Compressor frequency(Hz)
Technical Information 7
Service Manual
W D
09K 12K
168.5 462 159.5 123.5 542 179.5
54 54 35 35
Model W H D
09K 790 275 200
12K 845 289 209 Unit:mm
8 Technical Information
Service Manual
257 712
540
320 776
286
Unit:mm
510
Technical Information 9
Service Manual
Gas pipe
side
Valve
4-Way valve
Discharge
10 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
● Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
TUBE ROOM
TEMP. TEMP. RECEIVER AND
SENSOR SENSOR DISPLAY BOARD AP3
AP1 DISPLAY
θ θ WIFI MODULE
RT1 RT2
TERMINAL
T-SENSOR DISP1 DISP2 WIFI BLOCK
(COM-MANUAL) L
BU BU
CAP N1 N(1)
OUTDOOR UNIT
BK BK
COM-OUT 2
AP2 L
JUMP BN 3 BN
PRINTED CIRCUIT BOARD L
YEGN
CONNECTING
YEGN XT CABLE
SWING-UD
PG PGF
PE
HEALTH-L HEALTH-N EVAPORATOR
M2
M1 RD BU
COLD PLASMA
STEPPING GENERATOR
MOTOR FAN MOTOR
6363222005
Technical Information 11
Service Manual
● Outdoor Unit
GWH12QC-K3DNA1G/O
0$*1(7,&
UXQQLQJVWRSSLQJRUKDVEHHQ
(.9
5,1*
SRZHUHGRIIIRUOHVVWKDQ / / <9
PLQXWHVWRSUHYHQWWKHULVN N57 57 57
N N 97 97
RIHOHFWULFVKRFN
/; /;
%8 ;7 0$*1(7,&5,1* &1 &1 :$<
/ %8 /
,1'22581,7
1 1 1
%. %. / $30DLQ%RDUG
&208
%1 / %1 /
/ $&/
<(*1 <(*1 <(*1 3( 29&&203 +($7 +($7 2)$1
8 9 :
7(50,1$/ 5' 5'
1 %8 %/2&. %8 <( 5'
0$*1(7,&
/ %1%. ;
5,1*
<(*1 (+ (+ <(*1
(/(&75,&$/ / 0
%2; &RPS %RWWRP 3(
32:(5 3( 6$7
9 %DQG %DQG )$1
8 : +HDWHU +HDWHU 02725 3(
<(*1 &203
29(5/2$5'
3( 3527(&725 127(0RWRU
&203 JURXQGRQO\
DSSOLHVWRWKH
0,',62/$7,21 LURQVKHOOPRWRU
6+((7 3(
63610000084
GWH09QC-K3DNA1G/O
UXQQLQJVWRSSLQJRUKDVEHHQ
(.9
5,1*
SRZHUHGRIIIRUOHVVWKDQ / / <9
57 57
PLQXWHVWRSUHYHQWWKHULVN N N N 57
97 97
RIHOHFWULFVKRFN
/; /;
%8 ;7 0$*1(7,&5,1* &1 &1 :$<
/ %8 /
,1'22581,7
1 1 1
%.
%.
&208 $30DLQ%RDUG
%1 / %1 /
/ $&/
<(*1 <(*1 <(*1 3( 29&&203 +($7 +($7 2)$1
8 9 :
7(50,1$/ 5' 5'
1 %8 %/2&. %8 <( 5'
0$*1(7,&
/ %1%. ;
5,1*
These circuit diagrams are subject to change without notice, please refer to the one supplied with the unit.
12 Technical Information
Service Manual
Indoor Unit
● Top view
5 6 7 8 9 10
4 No. Name
Terminal with otdoor unit
1
communication wire
2 Live wire
3 3 Fuse
4 Neutral wire
11
5 Health neutral wire
6 PG motor needle stand
7 Health live wire
2
12 8 Auto button
9 Up&down swing motor
1
PG feedback interface of
10
indoor fan
11 Detecting plate(WIFI)
13 Interface of tube temperature
12
sensor
13 Display interface
14 Jumper cap
14
● Bottom view
High voltag
Technical Information 13
Service Manual
Outdoor Unit
● Top view
No. Name
1 Compressor
3 4
2 Reactor 2
3 Reactor 1
5 4 Chassis electric heating
6 5 Compressor electric heating
6 4-way valve
7 7 DC fan
8 Earthing wire
2 9 Communication wire
10 Neutral wire
11 Live wire
12 Electronic expansion valve
13 Temperature sensor
14 Overloard
8 15 DRED
1
10
11
15 14 13 12
● Bottom view
14 Technical Information
Service Manual
Press this button to turn on the unit. Press this button again to turn off the unit.
Press this button to increase set temperature. Holding it down above 2 seconds rapidly increases set temperature.
In AUTO mode, set temperature is not adjustable.
Technical Information 15
Service Manual
OFF
16 Technical Information
Service Manual
battery
reinstall
remove
Technical Information 17
Service Manual
Note:
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp or wireless telephone; remote controller should be close to
indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you dont use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or theres no display, please replace batteries.
18 Technical Information
Service Manual
1 ON/OFF button
2 MODE button
WIFI
3 FAN button
4 SWING button
1
3 5 TURBO button
2
5 6 ▲/ button
▲
4
6
7 7 SLEEP button
8
9 8 TEMP button
11 10
9 I FEEL button
12 10 LIGHT button
11 CLOCK button
Technical Information 19
Service Manual
Press this button to turn on the unit. Press this button again to turn off the unit.
Press this button to increase set temperature. Holding it down above 2 seconds rapidly increases set temperature.
In AUTO mode, set temperature is not adjustable.
OFF
Caution:
20 Technical Information
Service Manual
12.TURBO button
Technical Information 21
Service Manual
battery
reinstall
remove
22 Technical Information
Service Manual
6.3 Operation of Smart Control (Smart Phone, Tablet PC) For Gree
Operation Instructions
Download and install APP
Scan the following QR code with your smart phone and download Wifi Smart.
Install the App according to its guidance. When successfully installed, your smart phone homepage will show this icon
Configuration
Before operation, please finish the following configuration in order to realize Wifi control and the connection between air conditioner and
intelligent device.
1.Short-distance control setting for air conditioner using wifi hotspotStep 1: Air conditioner wifi is set to AP mode in factory. You can
search the air conditioner wifi hotspot through your smart phone. The name of wifi hotspot is the last 8 numbers of the air conditioner
mac address. Password is 12345678.
Step 2: Open App and the screen will show the air conditioner that you just connected. Click this air conditioner to enter and realize
short-distance control, as shown below. Please refer to "Functions introduction" for specific control methods.
Technical Information 23
Service Manual
NOTICE:
Please select the encrypt mode "empty" if your wifi has been set without password.
Functions introduction
1.User registration
Purpose: To realize long-distance control
Operation instruction: For the first time login, you have to register a new username. If you already have a username, skip the registration
step and enter email address and password on the "Login Page" to log in. If password is forgotton, you can reset the password.
Operation steps:
(1) Select the sever address
(2) Account login: Slide the page "Device". and enter the page "Menu" on the left. Tap "Login" to enter the page "Register username".
New user must first register a username. Tap "Register”.
(3) Enter your email address. Wait until you receive the verification code. Enter the code and then tap "OK" to log in. Username will
appear. As shown here, the username is "test".
24 Technical Information
Service Manual
(4) If password is forgotten, you can reset the password with your email address.
Tap "Forgot password" and enter the page "Forgot password". Tap "Get verification code" to get a email verification code. Enter a new
password and tap "OK" to log in.
2.Personal settings
Purpose: Set name (device name, preset name, etc.) and images (device image) in order to identify a user easily.
(1) Set device name
After quick configuration, a list of controllable smart devices will be generated. Default name for air conditioner is the last 8 numbers of the
air condtioner mac address.
Step 1: Tap and hold "babyroom" to enter the page "Edit device". Tap "Image" to select the source of image. Select from "Default images"
or "Take photo" or "Choose from photos" and save an image.
Step 2: Tap "Name" to change device name, Save it and the new device name will be shown. enable button Lock device to lock the device
other smart phone cant search the device now. Tap "Temp unit" to change the temperature unit.
Step 3: Tap "Firmware updated" to upgrade the Firmware of the device, Tap"1.8" the device will upgraded auto.
Technical Information 25
Service Manual
Step 2: Choose the time. Tap "Name". As shown in the picture, its name is "baby room". For timer type, select "On". Then select the repeating
days. Save the setting of preset name.
Tap "babyroom" and enter the page of air conditioner control. Tap to turn on the control switch.
26 Technical Information
Service Manual
Tap or to increase or decrease temperature. Tap to change working mode. Tap to enter the page of fan speed
adjustment.
Step 2: Advanced settings Tap to enter advanced settings. You may select "Air", "Dry", "Health", "Light", "Sleep" or "Energy
saving".
(2) Advanced control functions: Set scene; Preset; Link: Infrared control (only applicable to smart phone with infrared emitter)
Set scene: Preset the operation of several smart devices by one tap.
On the page "Home control", tap the image of "Home control" to enter the page "Edit scene".
Technical Information 27
Service Manual
Tap "Add scene" and edit the scene name, for example, "Back home". Add execution devices.
Tap to add commands. On the page "Select execution device", select the air conditioner named "babyroom". Then select "ON" or
"OFF".
Continue to select the next execution device as instructed above. Tap to set the interval.
Tap "Save". Then the scene "Back home" will be in execution. You may view the execution condition of the scene.
28 Technical Information
Service Manual
(3) Preset includes single-device preset and multi-device preset Single-device preset: This can preset a certain device to be On/Off at a
specific time.
On the homepage "Device", take air conditioner "babyroom" as an example.Tap at the bottom of the page "babyroom". Then you will
enter the page "Preset edit".
Slide up and down to set the time. If you want to synchronize the time, tap " synchronize".
Multi-device preset: This can preset multiple devices to execute a command at a specific time.
Please refer to the instructions as how to set preset time, name, timer type and repeating days for a single device.
Tap "Preset device" to select one or more devices. Then return to the page "Device".
Technical Information 29
Service Manual
Tap "Temperature" to enter the page "Select temperature parameter". Slide up or down to adjust temperature. Tap "Upper limit" or
"Lower limit".
Tap "Mode" and "On/Off" to select the status of master device. Then tap "Save".
Step 2: Set time parameter for linkage. Tap "Time parameter" to enter the page "Set time". Slide rightwards to turn on the
setting time.
Tap "Execution time"; Then tap "Start" and "Stop" to set start time and stop time respectively. Tap "OK" at the top right corner to save
the setting.
30 Technical Information
Service Manual
Tap the days below "Repeat" to select the repeating days. Then tap "Save".
Tap the name of device that you want to control. Tap "ON" or "OFF" and then tap "Save" to complete the linkage.
Tap "Save" and then repeat the above steps to set linkage of several scenes.
Technical Information 31
Service Manual
(5) Infrared control (only applicable to smart phone with infrared emitter).
Function: Smart phone can be used as a remote controller.
Tap at the top right corner of the homepage "Device". Select "Infrared" and enter the page "Remote controller". Tap and
slide up to enter the page of advanced functions.
Tap to turn on the device. Tap to select mode. Tap to adjust fan speed and swing angle. Tap "Health", "Energy
saving", "Sleep" etc. to set advanced functions.
Tap "Sleep" to enter the page "Sleep". You can select "Traditional sleep", "Expert sleep" or "DIY sleep". Tap "DIY sleep" and then tap
the left and right arrows to set sleep time. Tap up and down arrows to adjust temperature at a specific sleep time.
4.Menu functions
Menu functions (Share, Set, History, Feedback)
(1) Share: To share quick configuration information and units information, including local export and local import.
For local import, you just need to tap "Local import" and wait for the data download.
Local export
Step 1: Export local data to another smart phone.
Enter "Menu" on the left side and tap "Share" to enter the page "Share". Then tap "Local export".
32 Technical Information
Service Manual
(2) Backup: To keep backup of the quick configuration information and units information, including backup to cloud and backup list on
the cloud.
Backup to cloud
Enter the "Menu" on the left and tap "Backup".
Tap "Backup to cloud" and then tap "Yes". Then wait for the data download.
Select "Backup list on the cloud". Then backup records will appear. Tap "Record" to download data and recover data to local unit.
Technical Information 33
Service Manual
(3) Settings
User can set vibration, message alerts, server, updates, etc. The server setting here must keep the same as the server setting in
"Configuration" mentioned before.
Otherwise, remote control will be invalid.
(4) Feedback
User can feedback suggestions to back-stage management for maintenance and development.
Tap "Feedback". Enter your suggestions and then submit it.
34 Technical Information
Service Manual
Install the App according to its guidance. When successfully installed, your smart phone homepage will show this icon
Configuration
Before operation, please finish the following configuration in order to realize Wifi control and the connection between air conditioner and
intelligent device.
1.Short-distance control setting for air conditioner using wifi hotspotStep 1: Air conditioner wifi is set to AP mode in factory. You can
search the air conditioner wifi hotspot through your smart phone. The name of wifi hotspot is the last 8 numbers of the air conditioner
mac address. Password is 12345678.
Step 2: Open App and the screen will show the air conditioner that you just connected. Click this air conditioner to enter and realize
short-distance control, as shown below. Please refer to "Functions introduction" for specific control methods.
Technical Information 35
Service Manual
NOTICE:
Please select the encrypt mode "empty" if your wifi has been set without password.
Functions introduction
1.User registration
Operation instruction: For the first time login, you have to register a new username. If you already have a username, skip the registration
step and enter email address and password on the "Login Page" to log in. If password is forgotton, you can reset the password.
Operation steps:
(1) Select the sever address
(2) Account login: Slide the page "Device". and enter the page "Menu" on the left. Tap "Login" to enter the page "Register username".
New user must first register a username. Tap "Register”.
(3) Enter your email address. Wait until you receive the verification code. Enter the code and then tap "OK" to log in. Username will
appear. As shown here, the username is "test".
36 Technical Information
Service Manual
(4) If password is forgotten, you can reset the password with your email address.
Tap "Forgot password" and enter the page "Forgot password". Tap "Get verification code" to get a email verification code. Enter a new
password and tap "OK" to log in.
2.Personal settings
Purpose: Set name (device name, preset name, etc.) and images (device image) in order to identify a user easily.
(1) Set device name
After quick configuration, a list of controllable smart devices will be generated. Default name for air conditioner is the last 8 numbers of the
air condtioner mac address.
Step 1: Tap and hold "babyroom" to enter the page "Edit device". Tap "Image" to select the source of image. Select from "Default images"
or "Take photo" or "Choose from photos" and save an image.
Step 2: Tap "Name" to change device name, Save it and the new device name will
be shown. enable button Lock device to lock the device,other smart phone cant search the device now. Tap "Temp unit" to change the
temperature unit.
Step 3: Tap "Firmware updated" to upgrade the Firmware of the device, Tap"1.8" the device will upgraded auto.
Technical Information 37
Service Manual
Step 2: Choose the time. Tap "Name". As shown in the picture, its name is "baby room". For timer type, select "On". Then select the
repeating days. Save the setting of preset name.
Tap "babyroom" and enter the page of air conditioner control. Tap to turn on the control switch.
38 Technical Information
Service Manual
Tap or to increase or decrease temperature. Tap to change working mode. Tap to enter the page of fan speed
adjustment.
Step 2: Advanced settings Tap to enter advanced settings. You may select "Air", "Dry", "Health", "Light", "Sleep" or "Energy saving".
(2) Advanced control functions: Set scene; Preset; Link: Infrared control (only applicable to smart phone with infrared emitter)
Set scene: Preset the operation of several smart devices by one tap.
On the page "Device", tap the image of "Device" to enter the page "Edit scene".
Technical Information 39
Service Manual
Tap "Add scene" and edit the scene name, for example, "Back home". Add execution devices.
Tap to add commands. On the page "Select execution device", select the air conditioner named "babyroom". Then select "ON" or
"OFF".
Continue to select the next execution device as instructed above. Tap to set the interval.
Tap "Save". Tap the scene picture displayed in "Home control" home page to send the command. Then the scene "Back home" will be in
execution. You may view the execution condition of the scene.
40 Technical Information
Service Manual
Slide up and down to set the time. If you want to synchronize the time, tap " synchronize".If such "Hint" interface hasnt appeared,
please skip this operation procedure.
Multi-device preset: This can preset multiple devices to execute a command at a specific time.
Please refer to the instructions as how to set preset time, name, timer type and repeating days for a single device.
Tap "Preset device" to select one or more devices. Then return to the page "Home control".
Technical Information 41
Service Manual
(4) Link(This function is applicable to partial of models)
set in the master device, slave devices will execute commands to realize devices Select a master device. When the environment
has satisfied the parameters as linkage.
Step 1: Set the parameters of master device (Select master device, select environment parameters, select master device status).
Tap at the top right corner of the homepage "Device". Select "Link" and enter the page "Add linkage". Tap "Device parameter"
to enter the page "Select device". Take "baby room" as an example. Tap "baby room".
Tap "Temperature" to enter the page "Select temperature parameter". Slide up or down to adjust temperature. Tap "Upper limit" or
"Lower limit".
Tap "Mode" and "On/Off" to select the status of master device. Then tap "Save".
Step 2: Set time parameter for linkage. Tap "Time parameter" to enter the page "Set time". Slide rightwards to turn on the
setting time.
Tap "Execution time"; Then tap "Start" and "Stop" to set start time and stop time respectively. Tap "OK" at the top right corner to save
the setting.
42 Technical Information
Service Manual
Tap the days below "Repeat" to select the repeating days. Then tap "Save".
Tap the name of device that you want to control. Tap "ON" or "OFF" and then tap "Save" to complete the linkage.
Technical Information 43
Service Manual
Tap "Save" and then repeat the above steps to set linkage of several scenes.
(5) Infrared control (only applicable to smart phone with infrared emitter).
Function: Smart phone can be used as a r emote controller.
Tap at the top right corner of the homepage "Device". Select "Infrared" and enter the page "Remote controller". Tap and slide
up to enter the page of advanced functions.
Tap to turn on the device. Tap t o select mode. Tap to adjust fan speed . Tap "Health", "Energy saving", "Sleep" etc.
to set advanced functions.
Tap "Sleep" to enter the page "Sleep". You can select "Traditional sleep", "Expert sleep" or "DIY sleep". Tap "DIY sleep" and then tap the left
and right arrows to set sleep time. Tap up and down arrows to adjust temperature at a specific sleep time.
4.Menu functions
Menu functions (Share, Set, History, Feedback)
(1) Share: To share quick configuration information and units information, including local export and local import.
For local import, you just need to tap "Local import" and wait for the data download.
Local export
Step 1: Export local data to another smart phone.
Enter "Menu" on the left side and tap "Share" to enter the page "Share". Then tap "Local export".
44 Technical Information
Service Manual
(2) Backup: To keep backup of the quick configuration information and units information, including backup to cloud and backup list on
the cloud.
Backup to cloud
Enter the "Menu" on the left and tap "Backup".
Tap "Backup to cloud" and then tap "Yes". Then wait for the data download.
Technical Information 45
Service Manual
Select "Backup list on the cloud". Then backup records will appear. Tap "Record" to download data and recover data to local unit.
(3) Settings
User can set vibration, message alerts, server, updates, etc. The server setting here must keep the same as the server setting in
"Configuration" mentioned before.
Otherwise, remote control will be invalid.
(4) Feedback
User can feedback suggestions to back-stage management for maintenance and development.
Tap "Feedback". Enter your suggestions and then submit it.
46 Technical Information
Service Manual
2. Other control
(1) Buzzer
Upon energization or availably operating the unit or remote controller, the buzzer will give out a beep.
(2) Auto button
If press this auto button when turning off the unit, the complete unit will operate at auto mode. Indoor fan operates at auto fan speed
and swing function is turned on. Press this auto button at ON status to turn off the unit.
(3) Auto fan
Heating mode: During auto heating mode or normal heating ode, auto fan speed will adjust the fan speed automatically according to
ambient temperature and set temperature.
(4) Sleep
After setting sleep function for a period of time, system will adjust set temperature automatically.
(5) Timer function:
General timer and clock timer functions are compatible by equipping remote controller with different functions.
(6) Memory function
memorize compensation temperature, off-peak energization value.
Memory content: mode, up&down swing, light, set temperature, set fan speed, general timer (clock timer cant be memorized).
After power recovery, the unit will be turned on automatically according to memory content.
(7) Health function
During operation of indoor fan, set health function by remote controller. Turn off the unit will also turn off health function.
Turn on the unit by pressing auto button, and the health is defaulted ON.
Technical Information 47
Service Manual
48 Technical Information
Service Manual
● Outdoor Unit
1. Cooling mode:
Working condition and process of cooling mode:
① When Tindoor ambient temperature≥Tpreset, unit enters into cooling mode. Indoor fan, outdoor fan and compressor start operation.
Indoor fan operates according to set fan speed.
② When Tindoor ambient temperature≤Tpreset-2℃ , compressor stops operation and outdoor fan will stop 30s later. Indoor fan operates
according to set fan speed.
③ When Tpreset-2℃< Tindoor ambient temperature < Tpreset, unit operates according to the previous status.
Under cooling mode, 4-way valve is not energized. Temperature setting range is 16~30℃ . If compressor stops because of malfunction
in cooling mode, indoor fan and swing motor will work according to the original status.
2. Drying mode
(1) Working condition and process of drying mode
① When Tindoor ambient temperature > Tpreset, unit will be in drying mode. Outdoor fan and compressor start operation while indoor
fan will operate at low fan speed.
② When Tpreset-2℃ ≤Tindoor ambient temperature≤Tpreset, unit operates according to the previous status.
③ When Tindoor ambient temperature < Tpreset-2℃ , compressor stops operation and outdoor fan will stop 30s later.
(2) Under drying mode, 4-way valve is not energized. Temperature setting range is 16~30℃ .
(3) Protection function: same as in cooling mode.
3. Fan mode
(1) Under this mode, indoor fan can select different fan speed (except Turbo) or auto fan speed. Compressor, outdoor fan and 4-way
valve all stop operation.
(2) In fan mode, temperature setting range is 16~30℃ .
4. Heating mode
Working condition and process of heating mode:
① When Tpreset-(Tindoor ambient temperature-Tcompensation)≥1℃ , unit enters into heating mode. Compressor, outdoor fan and 4-way
valve start operation.
② When -2℃< Tpreset-(Tindoor ambient temperature-Tcompensation) < 1℃ , unit operates according to the previous
status.
③ When Tpreset-(Tindoor ambient temperature-Tcompensation)≤-2℃ , compressor stops operation and outdoor fan will stop 30s later.
Indoor fan will be in residual-heat blowing status.
④ When unit is turned off under heating mode or changed to other modes from heating mode, 4-way valve will be power-off 2min after
compressor stops working (compressor is in operation status under heating mode).
⑤ When Toutdoor ambient temperature > 30℃ , compressor stops operation immediately. Outdoor fan will stop 30s later.
⑥ Under the condition that compressor is turned on, when unit is changed to heating mode from cooling or drying mode, 4-way valve
will be energized in 2~3mins delay.
Note: Tcompensation is determined by IDU and ODU. If IDU controls the compensation temperature, then Tcompensation is
determined according to the value sent by IDU to ODU; If IDU does not control the compensation temperature, then Tcompensation will
default to 3℃ by the ODU.
5. Freon recovery mode
After the Freon recovery signal from IDU is received, cooling at rated frequency will be forcibly turned on to recover Freon.
Indoor unit will display Fo. If any signal from remote controller is received, unit will exit from Freon recovery mode and indoor unit stops
displaying Fo.
6. Compulsory defrosting
If unit is turned on under heating mode and set temperature is 16℃ (by remote controller), press “+, -, +, -, +, -” within 5s, unit will enter
into compulsory defrosting mode and send the signal to ODU. When the compulsory defrosting signal from ODU is received, IDU will exit
from the compulsory defrosting mode and stop sending the signal to ODU.
After ODU receives the compulsory defrosting code, it will start compulsory defrosting. Defrosting frequency and opening
angle will be the same as in normal defrosting mode. When compulsory defrosting is finished, the complete unit resumes
original status.
Technical Information 49
Service Manual
7. Auto mode
Auto mode is determined by controller of IDU. See IDU logic for details.
8. 8OC heating
Set temperature is 8OC. Display board of IDU displays 8OC. Under this mode, “Cold air prevention” function is shielded.
If compressor is operating under this mode, fan speed will adjust according to auto fan speed; if compressor stops operation
under this mode, indoor fan will be in residual-heat blowing status.
When power on, communication light will be blinking in a normal way (after receiving a group of correct signals,
blinking stops for 0.2s~0.3s). If theres no communication, communication light will be always on. If other ODU has
malfunction, communication light will be on for 1s and off for 1s in a circular way.
50 Technical Information
Service Manual
Warnings
cient fixing bolt must be installed; make sure the installation
support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur-
ing installation.
Electrical Safety Precautions: 6. Make sure no foreign objects are left in the unit after fin-
ishing installation.
1. Cut off the power supply of air conditioner before
checking and maintenance. Refrigerant Safety Precautions:
2. The air condition must apply specialized circuit and
prohibit share the same circuit with other appliances. 1. Avoid contact between refrigerant and fire as it generates
3. The air conditioner should be installed in suitable poisonous gas; Prohibit prolong the connection pipe by
location and ensure the power plug is touchable. welding.
4. Make sure each wiring terminal is connected firmly 2. Apply specified refrigerant only. Never have it mixed with
during installation and maintenance. any other refrigerant. Never have air remain in the refrigerant
5. Have the unit adequately grounded. The grounding line as it may lead to rupture or other hazards.
wire cant be used for other purposes. 3. Make sure no refrigerant gas is leaking out when
6. Must apply protective accessories such as protective installation is completed.
boards, cable-cross loop and wire clip. 4. If there is refrigerant leakage, please take sufficient
7. The live wire, neutral wire and grounding wire of measure to minimize the density of refrigerant.
power supply must be corresponding to the live wire, 5. Never touch the refrigerant piping or compressor without
neutral wire and grounding wire of the air conditioner. wearing glove to avoid scald or frostbite.
8. The power cord and power connection wires cant be
pressed by hard objects. Improper installation may lead to fire hazard, explosion,
9. If power cord or connection wire is broken, it must be electric shock or injury.
replaced by a qualified person.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
R410A
8. Installation
8.1 Installation Dimension Diagram
At least 15cm
Space to the wall
At least 15cm
At least 15cm
cm
3 00 At least 250cm
st
lea tio
n
At tr uc
obs
o the
et
ac
Sp
Space to the obstruction
At least 50cm
he
t ot
e ion
ac t
Sp truc
s st
ob
t lea
A cm
30
Space to th
e wall
on At least 50cm
u cti c m
str 200
ob a st Space to the ob
o the t le struction
et A
ac
Sp
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Left Right
Φ55mm Φ55mm
Open-end
Rear piping hole Rear piping hole wrench
Union nut
Pipe joint Union nut Pipe
Fig.1 Torque wrench Pipe
Indoor Outdoor Refer to the following table for wrench moment of force:
(4) Put wiring cover back and then tighten the screw.
Drain hose
Outlet pipe (5) Close the panel.
Note:
(1) All wires of indoor unit and outdoor unit should be
Tape connected by a professional.
Outlet Drain hose
pipe Fig.9
Fig.8 (2) If the length of power connection wire is insufficient, please
contact the supplier for a new one. Avoid extending the wire by
Note: yourself.
(1) Add insulating pipe in the indoor drain hose in order to (3) For the air conditioner with plug, the plug should be
prevent condensation. reachable after finishing installation.
(2) The plastic expansion particles are not provided. (4) For the air conditioner without plug, an air switch must be
(As show in Fig.10) installed in the line. The air switch should be all-pole parting
and the contact parting distance should be more than 3mm.
Drain hose
8. Bind up Pipe
(1) Bind up the connection pipe, power cord and drain hose
Insulating pipe
Fig.10 with the band.(As show in Fig.14)
7. Connect Wire of Indoor Unit (2) Reserve a certain length of drain hose and power cord
(1) Open the panel, remove the screw on the wiring cover and for installation when binding them. When binding to a certain
then take down the cover.(As show in Fig.11) degree, separate the indoor power and then separate the drain
hose.(As show in Fig.15)
Panel Screw (3) Bind them evenly.
(4) The liquid pipe and gas pipe should be bound separately at
the end.
2. Leakage Detection
The drain hos (1) With leakage detector:
can't raise
upwards Check if there is leakage with leakage detector.
Wall (2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
Fig.25 and keep the soap water for more than 3min. If there are air
U-shaped curve
bubbles coming out of this position, theres a leakage.
Fig.24
Drain hose
Note:
8.8 Check after Installation and Test
(1) The through-wall height of drain hose shouldnt be higher Operation
than the outlet pipe hole of indoor unit.(As show in Fig.25) 1. Check after Installation
(2) Slant the drain hose slightly downwards. The drain hose Check according to the following requirement after finishing
cant be curved, raised and fluctuant, etc.(As show in Fig.26) installation.
(3) The water outlet cant be placed in water in order to drain NO. Items to be checked Possible malfunction
smoothly.(As show in Fig.27) Has the unit been The unit may drop, shake or
1
installed firmly? emit noise.
Have you done the It may cause insufficient cooling
2
refrigerant leakage test? (heating) capacity.
Is heat insulation of It may cause condensation and
The drain hose can't be fluctuant 3
pipeline sufficient? water dripping.
It may cause condensation and
The water outlet 4 Is water drained well?
water dripping.
can't be placed
The drain hose in water Is the voltage of power
can't be fluctuant
The water supply according to the It may cause malfunction or
outlet can't be 5
fluctuant Fig.27 voltage marked on the damage the parts.
nameplate?
Fig.26 Is electric wiring and
It may cause malfunction or
6 pipeline installed
damage the parts.
correctly?
8.7 Vacuum Pumping and Leak 7
Is the unit grounded
It may cause electric leakage.
securely?
Detection Does the power cord It may cause malfunction or
8
1. Use Vacuum Pump follow the specification? damage the parts.
(1) Remove the valve caps on the liquid valve and gas valve Is there any obstruction It may cause insufficient cooling
9
and the nut of refrigerant charging vent. in air inlet and air outlet? (heating).
(2) Connect the charging hose of piezometer to the refrigerant The dust and
charging vent of gas valve and then connect the other charging sundries caused It may cause malfunction or
10
hose to the vacuum pump. during installation are damaging the parts.
(3) Open the piezometer completely and operate for 10-15min removed?
to check if the pressure of piezometer remains in -0.1MPa. The gas valve and liquid
It may cause insufficient cooling
(4) Close the vacuum pump and maintain this status for 1-2min 11 valve of connection pipe
(heating) capacity.
to check if the pressure of piezometer remains in -0.1MPa. If are open completely?
the pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve 2. Test Operation
and gas valve completely with inner hexagon spanner. (1) Preparation of test operation
(6) Tighten the screw caps of valves and refrigerant charging ● The client approves the air conditioner installation.
vent.(As show in Fig.28) ● Specify the important notes for air conditioner to the client.
Liquid valve Piezometer Lo Hi
(2) Method of test operation
Gas valve ● Put through the power, press ON/OFF button on the remote
Refrigerant charging Valve cap controller to start operation.
vent ● Press MODE button to select AUTO, COOL, DRY, FAN and
Nut of refrigerant HEAT to check whether the operation is normal or not.
Charging vent
● If the ambient temperature is lower than 16℃ , the air
Vacuum pump
conditioner cant start cooling.
Inner hexagon
Fig.28 spanner
Close
Open
9. Maintenance
9.1 Error Code List
Display Method of Outdoor
Display Method of Indoor Unit
Unit
Indicator has 3 kinds of
Indicator Display (during
Malfunction display status and during
NO. Dual-8 blinking, ON 0.5s and OFF blinking, ON 0.5s and OFF A/C status Possible Causes
Name
Code 0.5s) 0.5s
Display
Operation Cool Heating Yellow Red Green
Indicator Indicator Indicator Indicator Indicator Indicator
Compressor
Min Showing during min. cooling or
23 P0
frequence in min. heating test
test state
Compressor
rated Showing during nominal cooling or
24 P1
frequence in nominal heating test
test state
Compressor
maximum Showing during max. cooling or
25 P2
frequence in max. heating test
test state
Compressor
intermediate Showing during middle cooling or
26 P3
frequence in middle heating test
test state
Module OFF 3S
33 temperature H5 and blink
is too high 10 times
Indoor unit
OFF 3S
and outdoor compressor and Outdoor fan Indoor unit and outdoor unit doesnt
39 LP and blink
unit doesnt motor cant work match
16 times
match
During cooling and drying
operation, compressor will stop
Failure start- while indoor fan will operate;
40 LC Refer to the malfunction analysis
up During heating operation, the
complete unit will stop
operation.
Normal
contino-
41 communica-
usly
tion
OFF 3S
and blink
once Defrosting will occur in heating
OFF 3S mode. Compressor will operate
(during
42 Defrosting and blink Its the normal state
blinking, while indoor fan will stop
twice
ON 10s operation.
and OFF
0.5s)
Frequency OFF 3S
47 limiting and blink
(power) 13 times
Compressor OFF 3S
48 is open- and blink
circuited once
The
temperature OFF 3S
49 for turning and blink
on the unit is 8 times
reached
Frequency
OFF 3S
limiting
50 and blink
(module 11 times
temperature)
Malfunction
1.Power supply is abnormal;
of zero-cross
51 U8 The complete unit stops 2.Detection circuit of indoor control
detection
mainboard is abnormal.
circuit
Malfunction
52 of detecting JF
plate(WIFI )
If malfunction occurs,corresponding code will display and the unit will resume normal until protection or
malfunction disappears.
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
No Is malfunction Yes
eliminated
Yes
No Is malfunction Yes
eliminated
No Is malfunction Yes
eliminated
No
Measure the voltage of this foot to
neutral wire on the mainboard Replace PG motor
No
No Is malfunction Yes
eliminated
End
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
(4) Malfunction of Zero-crossing Inspection Circuit Malfunction of the IDU Fan Motor U8
Main detection points:
● Instant energization afte de-energization while the capacitordischarges slowly?
● The zero-cross detectioncircuit of the mainboard is defined abnormal?
Malfunction diagnosis process:
Start
Yes
End
Start
Yes
Is malfunction
eliminated
The end
Outdoor unit:
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
No
Yes
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
Yes
End
(2) IPM Protection, Out-of-step Fault, Compressor Phase Overcurrent (AP1 below refers to the outdoor control panel)
Main check points:
●Is the connection between control panel AP1 and compressor COMP secure? Loose? Is the connection in correct order?
●Is the voltage input of the machine within normal range? (Use AC voltmeter to measure the voltage between terminal L and N on the
wiring board XT)
●Is the compressor coil resistance normal? Is the insulation of compressor coil against the copper tube in good condition?
●Is the working load of the machine too high? Is the radiation good?
●Is the charge volume of refrigerant correct?
Fault diagnosis process:
Energize and
switch on
Yes
Use ohmmeter to
measure the resistance
between the three If the Replace the
terminals on compressor resistance is No compressor
COMP, and compare the normal? COMP
measurements with the
compressor resistance on
Service Manual.
No
Use ohmmeter to
measure the resistance Resistance higher
between the two than 500MΩ?
terminals of compressor
COMP and copper tube.
Yes
Replace the
control panel
AP1
END
(3) High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is outdoor ambient temperature in normal range?
●Are the outdoor and indoor fans operating normally?
●Is the heat dissipation environment inside and outside the unit good?
Fault diagnosis process:
No
No
Yes
Replace the
outdoor fan
End
(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:
Yes
Yes
Yes
No
No
Replace the
compressor
Yes
End
(5) Out of step diagnosis for the compressor (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Is the system pressure too high?
●Is the input voltage too low?
Fault diagnosis process:
No
Is stop time of the No Check if the fan terminal Replace the fan
Is the outdoor fan working
compressor longer than OFAN is connected correctly capacitor C1
normally?
3 minutes?
Yes
Yes Replace the
outdoor fan
Is the outdoor unit blocked Yes
Remove foreign objects
by foreign objects?
Are the wires for the compressor connected
correctly? Is connection sequence right? No
Is the connection made in clockwise
direction?
Replace the
No control panel AP1
Connect the Yes
wires correctly
Yes
If the fault is eliminated?
No
No Replace the
compressor
Replace the
compressor
End
End
(6) Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
Yes
No
Replace the
control panel
AP1
No
End
(7) Power factor correct or (PFC) fault (a fault of outdoor unit) (AP1 hereinafter refers to the control board of the outdoor unit)
Mainly detect:
●Check if the reactor (L) of the outdoor unit and the PFC capacitor are broken
Fault diagnosis process:
Start
No
The capacitor is
Yes short circuited and Restart the unit If the fault is eliminated? Yes
Is the resistance around zero?
the capacitor
should be repla-
ced
No
Yes Yes
Whether there is any damage Replace the reactor Restart the unit If the fault is eliminated?
or short-circuit?
No
Yes
End
(8) Communication malfunction: (following AP1 for outdoor unit control board)
Mainly detect:
●Is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged?
●Detect the indoor and outdoor units connection wire and indoor and outdoor units inside wiring is connect well or not, if is there any
damage?
Fault diagnosis process:
Start
No
If the fault is eliminated?
No
Replace the main board
of the indoor unit
Yes
Yes Yes
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesnt rotate motor to have the fan run normally eliminated
No No
Yes No
Is there blockage inside the system? Yes Flush the heat exchangers with high
(Filth blockage, ice plug, greasy Is malfunction Yes
blockage, the cut off valve hasnt been pressure nitrogen eliminated
opened completely)
No No
No
End
31
MODE ON/OFF
FAN SWING
IFEEL X-FAN
A1
/B6
/C2
dis
pla
y
A5
/B4
dis
pla
y
C4
dis
pla
y
30
The component picture is only for reference please refer to the actual product.
Part Code
Description
NO. GWH09QB-K3DNA1G/I(WIFI) GWH12QC-K3DNA1G/I(WIFI) Qty
Product Code CB419N05503 CB419N05403
1 Front Panel Assy 20022493 20022493 1
2 Display Board 30565231 30565231 1
3 Front Case Assy 20022489 20022489 1
4 Helicoid Tongue 26112436 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 00000100093 00000100093 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212180 1
10 Cold Plasma Generator 1114001602 1114001602 1
11 Evaporator Assy 01100100245 01100100245 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 1501214603 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000203585 10000203585 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021901 4202021905 1
23 Main Board 30145096 30145101 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510468 30510468 1
30 Capacitor CBB61S 33010747 33010747 1
31 Detecting plate(WIFI ) 30110144 30110144 1
Part Code
Description
NO. GWH09QB-K3DNB6G/I GWH12QC-K3DNB6G/I Qty
Product Code CB435N00404 CB435N00103
1 Front Panel Assy 20000300050T 20000300049T 1
2 Display Board 30565281 30565281 1
3 Front Case Assy 00000200040 00000200045 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212179 1
10 Cold Plasma Generator 1114001602 1114001602 1
11 Evaporator Assy 01002000044 01100100245 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000203603 10000204251 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021904 4202021914 1
23 Main Board 30145096 30145101 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510468 30510468 1
30 Capacitor CBB61S 33010747 3301074712 1
31 Detecting plate(WIFI ) 30110154 30110144 1
Part Code
Description
NO. GWH09QB-K3DNA5G/I)(WIFI) GWH12QC-K3DNA5G/I(WIFI) Qty
Product Code CB425N03503 CB425N03603
1 Front Panel Assy 00000300036 00000300022 1
2 Display Board 30565260 30565260 1
3 Front Case Assy 2002249501 00000200022 1
4 Helicoid Tongue 26112508 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 00000100093 1
7 Drainage Hose 0523001408 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212179 1
10 Cold Plasma Generator 1114001602 1114001602 1
11 Evaporator Assy 01002000044 01100100245 1
12 Wall Mounting Frame 01252043 01252484 1
13 Cross Flow Fan 10352059 10352056 1
14 Fan Motor 150120874 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000203159 10000204562 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021901 4202021905 1
23 Main Board 30145096 30145101 1
24 Electric Box Cover Sub-Assy 01402065 01402065 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510468 30510468 1
30 Capacitor CBB61S 33010747 3301074712 1
31 Detecting plate(WIFI ) 30110154 30110144 1
Part Code
Description
NO. GWH09QB-K3DNB4G/I(WIFI) GWH09QB-K3DNC2G/I(WIFI) Qty
Product Code CB434N02304 CB439N00402
1 Front Panel Assy 00000200040 00000200040 1
2 Display Board 30565260 30565281 1
3 Front Case Assy 00000200040 00000200040 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 20162010 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212180 1
10 Cold Plasma Generator 1114001603 1114001603 1
11 Evaporator Assy 01002000044 01002000044 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000203105 10000203603 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021904 4202021904 1
23 Main Board 30145096 30145096 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510474 30510468 1
30 Capacitor CBB61S 33010747 33010747 1
31 Detecting plate(WIFI ) 30110154 30110154 1
Part Code
Description
NO. GWH09QB-K3DNC4G/I(WIFI) GWH09QB-K3DNB2G/I(WIFI) Qty
Product Code CB444N01202 CB432N02204
1 Front Panel Assy 00000200040 20000300019S 1
2 Display Board 30565260 30565260 1
3 Front Case Assy 00000200040 00000200040 1
4 Helicoid Tongue 26112508 26112508 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 20162010 20162010 1
7 Drainage Hose 0523001408 0523001408 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212180 1
10 Cold Plasma Generator 1114001603 1114001603 1
11 Evaporator Assy 01002000044 01002000044 1
12 Wall Mounting Frame 01252043 01252043 1
13 Cross Flow Fan 10352059 10352059 1
14 Fan Motor 150120874 150120874 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000203105 10000203105 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021904 4202021904 1
23 Main Board 30145096 30145096 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510474 30510474 1
30 Capacitor CBB61S 33010747 33010747 1
31 Detecting plate(WIFI ) 30110154 30110154 1
Part Code
Description
NO. GWH12QC-K3DNB4G/I(WIFI) GWH12QC-K3DNC2G/I(WIFI) Qty
Product Code CB434N02103 CB439N00100
1 Front Panel Assy 00000200045 00000200045 1
2 Display Board 30565260 30565281 1
3 Front Case Assy 00000200045 00000200045 1
4 Helicoid Tongue 26112436 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 00000100093 00000100093 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212179 24212179 1
10 Cold Plasma Generator 1114001603 1114001603 1
11 Evaporator Assy 01100100245 01100100245 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 1501214603 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521210701 1521210701 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000204877 10000204251 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202021914 4202021914 1
23 Main Board 30145101 30145101 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510474 30510474 1
30 Capacitor CBB61S 3301074712 3301074712 1
31 Detecting plate(WIFI ) 30110144 30110144 1
Part Code
Description
NO. GWH12QC-K3DNB2G/I(WIFI) GWH12QC-K3DNC4G/I(WIFI) Qty
Product Code CB432N02103 CB444N01302
1 Front Panel Assy 20000300018S 20000300019S 1
2 Display Board 30565260 30565260 1
3 Front Case Assy 00000200045 00000200045 1
4 Helicoid Tongue 26112436 26112436 1
5 Left Axile Bush 10512037 10512037 1
6 Rear Case assy 00000100093 00000100093 1
7 Drainage Hose 05230014 05230014 1
8 Ring of Bearing 26152022 26152022 1
9 Evaporator Support 24212180 24212180 1
10 Cold Plasma Generator 1114001603 1114001603 1
11 Evaporator Assy 01100100245 01100100245 1
12 Wall Mounting Frame 01252484 01252484 1
13 Cross Flow Fan 10352056 10352056 1
14 Fan Motor 1501214603 1501214603 1
15 Connecting pipe clamp 2611216401 2611216401 1
16 Rubber Plug (Water Tray) 76712012 76712012 1
17 Stepping Motor 1521212901 1521212901 1
18 Crank 73012005 73012005 1
19 Electric Box Assy 10000204877 10000204879 1
20 Axile Bush 10542036 10542036 1
21 Terminal Board 42011233 42011233 1
22 Jumper 4202300104 4202021904 1
23 Main Board 30145101 30145101 1
24 Electric Box Cover Sub-Assy 0140206501 0140206501 1
25 Shield Cover of Electric Box Cover 01592150 01592150 1
26 Electric Box Cover 20112207 20112207 1
27 Power Cord / / /
28 Connecting Cable 4002052317 4002052317 0
29 Remote Controller 30510474 30510474 1
30 Capacitor CBB611A 3301074712 3301074712 1
31 Detecting plate(WIFI ) 30110144 30110144
The component picture is only for reference please refer to the actual product.
Part Code
Description
NO. GWH09QB-K3DNA1G/O GWH12QC-K3DNA1G/O Qty
Product Code CB419W05501 CB419W05401
1 Electric Box Assy 10000100118 10000100120 1
2 Electric Box Sub-Assy 10000500049 10000500051 1
3 Main Board 30138000453 30138000456 1
4 Reactor 43130184 43130184 1
5 Terminal Board 42010313 42010313 1
6 Wire Clamp 71010003 71010003 1
7 Front Grill 22413027 22413027 1
8 Front Panel Assy 0153304802 0153304802 1
9 Axial Flow Fan 10333004 10333004 1
10 Chassis Sub-assy 0280330401P 02803304P 1
11 Fan Motor 1501308506 1501308506 1
12 Top Cover Sub-Assy 01253073 01253073 1
13 Motor Support 01703104 0170310401 1
14 Condenser Assy 01100200141 01100200142 1
15 Rear Grill 01473009 01473009 1
16 Electric Expand Valve Fitting 4300876701 4300876701 1
17 Electronic Expansion Valve 07135228 07135228 1
18 Valve 07100003 07100003 1
19 Big Handle 262334332 262334332 1
20 Cut off Valve Assy 07133474 07133474 1
21 Valve Support 0171314201P 0171314201P 1
22 Right Side Plate Sub-Assy 0130317801 0130317801 1
23 4-Way Valve Assy 03015200074 03015200075 1
24 Clapboard Sub-Assy 0123338502 0123338502 1
25 Magnet Coil 4300040050 4300040050 1
26 Compressor and Fittings 0010322402 0010322402 1
27 Electrical Heater 7661281401 7661281401 1
28 Drainage Connecter 06123401 06123401 1
29 Electrical Heater (Chassis) 7651000414 7651000414 1
Step Procedure
A1/B6/C2display
Screws Panel
a A1/B6/C2 display: Screw off the 2 Front panel
screws that are locking the display board.
Separate the display board from the front
panel.
C4 display: Screw off the 2 screws that
are locking the display board.
This display can be disassembled only
after removing the front case (refer to step
5 of disassembly).
C4display Panel rotation
A5/B4 display: Screw off the 2 Screws
screws that are locking the display board.
Groove
A5/B4 display
b Separate the panel rotation shaft from
the groove fixing the front panel and then
removes the front panel.
Screws
Step Procedure
Note: Screws
The position of detection board(WIFI)
may be different for -different models.
Detecting plate
(WIFI)
For 12K For 09K
Note:
1.Open the screw caps before removing
the screws around the air outlet.
2.The quantity of screws fixing the front
case sub-assy is different for different
models.
Screw
Clasps
Vertical
louver
Clasps Vertical
louver
Step Procedure
Electric box
Shield cover of electric
box sub-assy
Indoor tube
temperature
Grounding screw sensor Electric box assy
b ① Take off the water retaining sheet.
Remove the cold plasma generator by
screwing off the locking screw on the
generator.
② Take off the indoor tube temperature Cold plasma
sensor. generator
③ Screw off 1 grounding screw. Wiring
④ Remove the wiring terminals of motor and terminal
stepping motor. Screw
of motor
⑤ Remove the electric box assy.
Water retaining Wiring
sheet terminal
of stepping
motor
Screw
Main board
c Twist off the screws that are locking
each lead wire and rotate the electric
box assy.
Twist off the screws that are locking the
wire clip. Loosen the power cord and
remove its wiring terminal. Lift up the
main board and take it off.
Power cord
Screw
Wire clip
Step Procedure
Groove
Bottom case
c First remove the left side of the evaporator
from the groove of bottom case and then
remove the right side from the clasp on
the bottom case.
Clasp
Evaporator assy
Connection pipe
Step Procedure
Motor clamp
Cross flow
b Remove the screws at the connection Screw
place of cross flow blade and motor; lift Holder Motor
the motor and cross flow blade upwards sub-assy
to remove them.
Remove the bearing holder sub-assy.
Remove the screw fixing step motor and
then remove the step motor.
Screws
Step motor
Step Procedure
Big handle
Screws
Top panel
Remove the screws fixing top panel and
then remove the top panel.
Screw
Front grille
Step Procedure
Screws
Screws
Front cover
Screws
Nut
Step Procedure
Screws 2
Screws 1
Screws 2
Step Procedure
9. Remove motor
Motor
Screws
Screws
Step Procedure
Liquid valve
Screws
Gas valve
Screws
Valve support
Screws
Step Procedure
Note:
Protect the ports of discharge pipe and
suction pipe to avoid foreign objects to
enter it.
Compressor
Foot nuts
Condenser
Screw
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(℃) Celsius(℃) Celsius(℃)
temperature (℉) temperature (℉) temperature (℉)
(℉) (℉) (℉)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor (15K)
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)