6.
6 Design of Column Jacketing
Existing size of column = (360 × 360) mm
Unsupported length = 3.83 m
Now, Before Retrofit:
Ultimate axial load (𝑃𝑢 ) = 1036.834 kN
Existing main reinforcement in column =
(𝐴𝑠𝑐 ) = 8 − 16𝑚𝑚𝜙 = 1608.5 𝑚𝑚2
Concrete grade by NDT = M20
𝑓𝑐𝑘 = 20 𝑀𝑃𝑎 :Before Retrofitting
𝑑 ′ = 60 mm
Now,
Capacity of column = 𝑃𝑐 = 0.4 𝑓𝑐𝑘 (𝐴𝑔𝑟𝑜𝑠𝑠 − 𝐴𝑠𝑐 ) + 0.67 𝑓𝑦 𝐴𝑠𝑐 = 961.25 kN-m < 𝑃𝑢
∴ Hence, retrofitting is necessary.
After retrofitting:
Ultimate axial load on column (𝑃𝑢 ) = 1215.55 kN
Along major axis:
𝑀𝑢𝑥 = 200.5316 kN-m
𝑀𝑢𝑦 = −75.977 kN-m
And,
2 + 𝑀 2 = 246.608 kN-
Ultimate moment for design purpose, 𝑀𝑢 = 1.15 × √𝑀𝑢𝑥 𝑢𝑦
m
Check for eccentricities:
Effective length of column (𝑙𝑒 ) = 0.65 × 3.83 = 2.4895 𝑚
Then,
𝑙 𝑒
Slenderness Ratio (𝑆. 𝑅. ) = 0.56 = 4.445 < 12
𝑙 𝐷
Minimum eccentricity along major axis, 𝑒𝑥 = 500 + 30 = 26.326 mm > 20 mm
𝑙 𝛽
Minimum eccentricity along minor axis, 𝑒𝑦 = 500 + 30 = 26.3267 mm > 20 mm
Now, Minimum eccentricity in field condition:
0.05 𝐷 = 28 𝑚𝑚 > 𝑒min (OK)
Assuming effective cover = 𝑑 ′ = 60 𝑚𝑚
So,
“SEISMIC VULNERABILITY EVALUATION AND RETROFITTING OF EXISTING RCC STRUCTURE”
By [Sandesh, Shiyam, Shlok, Sonam, Subash, Swastik] | 117
𝑑′ 60
= 560 = 0.107
𝐷
𝑃𝑢 𝑀𝑢
And, 𝑓 = 0.165; 𝑓 = 0.07
𝑐𝑘 𝐵𝐷 𝑐𝑘 𝐵𝐷
Then,
𝑑′
Using P-M interaction chart for = 0.1
𝐷
𝑃
From chart 44, 𝑓 = 0.03
𝑐𝑘
𝑝 = 0.6% but min = 0.8%, max = 6%
Provide, 𝑝 = 0.8%
0.8
𝐴𝑠𝑐 = 100 × 560 × 560 = 2510 𝑚𝑚2
Check for biaxial bending:
Higher reinforcement. Since, there is large deficiencies in upper columns, we provide:
𝐴𝑠𝑐 = 7690.618 𝑚𝑚2
𝑑
𝑝 = 2.45 %, 𝐷 = 0.107
𝑝
𝑓𝑦 = 415 MPa, 𝑓 = 0.122
𝑐𝑘
𝑝𝑢
Now, 𝑓 = 0.165
𝑐𝑘 𝐵𝐷
𝑀𝑢𝑥,1
Then, 𝑓 2 = 0.16
𝑐𝑘 𝐵𝐷
𝑀𝑢𝑥,1 = 561.971 kN-m
For square column:
𝑀𝑢𝑦,1 = 561.971 kN-m
So, 𝑃𝑢𝑧 = 0.45 𝑓𝑐𝑘 𝐴𝑐 + 0.75 × 𝑓𝑦 × 𝐴𝑠𝑐
= 0.45 × 20 × (560 × 560 − 7690.618) + 0.75 × 415 × 7690.618
= 5146.889 kN
Then,
𝑃𝑢
= 0.235 > 0.2
𝑃𝑢𝑧
< 0.8
𝑃
So, 𝛼𝑛 = 0.667 + 1.667 × 𝑃 𝑢 = 0.667 + 1.667 × 0.235 = 1.058
𝑢𝑧
Then,
𝛼𝑛 𝛼𝑛
𝑀 𝑀
Check: (𝑀 𝑢𝑥 ) + (𝑀 𝑢𝑦,1) ≤1
𝑢𝑥,1 𝑢𝑦
200.5316 1.058 75.977 1.058
or, ( 561.971 ) + (561.971) ≤1
“SEISMIC VULNERABILITY EVALUATION AND RETROFITTING OF EXISTING RCC STRUCTURE”
By [Sandesh, Shiyam, Shlok, Sonam, Subash, Swastik] | 118
or, 0.456 ≤ 1 (OK)
Then: Provide 𝑝 = 2.45% reinforcement.
For Jacketing:-
4
Area of steel required = 3 × (𝐴𝑠𝑡,𝑟𝑒𝑞𝑢𝑖𝑟𝑒𝑑 − 𝐴𝑠𝑡,𝑒𝑥𝑖𝑠𝑡𝑖𝑛𝑔 )
4
= 3 × (7690.618 − 1608.5)
= 8109.49 mm2
Then,
Provide 12 − 30 𝑚𝑚 𝜙 as longitudinal bars,
8 𝑚𝑚 bars as lateral stirrups = 150 mm c/c.
After retrofitting
“SEISMIC VULNERABILITY EVALUATION AND RETROFITTING OF EXISTING RCC STRUCTURE”