25HCD3

Comfort™ 13 Heat Pump


with Puronr Refrigerant
1---1/2 to 5 Nominal Tons

Heating Check Chart

HEATING CHECK CHART


For use with units using R-410A refrigerant
FIELD OPERATING PRESSURE CHARGING TABLE FIXED RESTRICTOR (HIGH
PRESSURE @ VAPOR VALVE, SUCTION PRESSURE @ SUCTION SERVICE PORT)
INDOOR OUTDOOR TEMP. ºF DRY BULB/WET BULB
UNIT DRY
BULB 60/57 50/47 40/38 30/28 20/18 10/9 0/-1
HIGH 310 292 275 257 238 226 213
60º SUCT 115 102 89 76 63 53 43
HIGH 355 334 313 292 271 257 242
70º
018 SUCT 121 107 93 78 64 54 44
HIGH 403 376 349 328 307 291 275
80º
SUCT 127 110 93 79 66 55 45
60º HIGH 348 319 290 269 249 235 221
SUCT 120 102 83 74 64 55 45
HIGH 388 354 320 300 281 267 252
024 70º SUCT 124 106 88 77 65 56 46
80º HIGH 428 394 361 338 316 301 287
SUCT 128 111 94 80 66 57 48
HIGH 368 337 307 282 257 239 221
60º
SUCT 127 110 93 77 61 49 38
HIGH 410 377 344 319 293 273 254
030 70º
SUCT 130 112 94 78 62 50 38
HIGH 455 420 385 358 331 307 284
80º
SUCT 132 114 96 79 63 51 39
60º HIGH 363 337 310 286 262 246 230
SUCT 123 108 93 79 65 55 44
HIGH 404 377 350 324 298 280 262
036 70º SUCT 126 111 95 81 66 56 45
80º HIGH 453 420 387 363 338 318 297
SUCT 129 113 96 82 67 57 46
60º HIGH 316 299 282 264 246 235 223
SUCT 109 98 86 73 59 50 41
HIGH 358 338 317 298 278 267 255
042 70º
SUCT 112 100 87 74 60 51 42
HIGH 404 380 355 338 321 306 291
80º
SUCT 116 102 88 76 63 53 43
60º HIGH 332 306 280 261 242 233 223
SUCT 106 90 74 63 52 45 38
HIGH 377 350 323 303 283 270 256
048 70º
SUCT 110 95 79 68 56 48 40
HIGH 409 386 363 341 318 305 291
80º
SUCT 116 102 87 72 57 49 41
HIGH 327 303 279 263 246 232 218
60º SUCT 105 91 77 66 54 45 35
HIGH 369 340 310 292 274 263 251
060 70º SUCT 108 94 79 68 58 47 36
80º HIGH 410 381 352 336 320 303 286
SUCT 111 97 83 72 60 49 38
* If PressureGuardTM kit is installed, it will not allow pressures to stabilize at these
conditions. To check the charge at these ambients operate in cooling or lower the
indoor dry bulb temperature.
CAUTION
1. Compressor damage may occur if system is over-charged.
2. Carefully recover refrigerant from this unit before final disposal or when servicing.
3. Never vent refrigerant to atmosphere. Use approved recovery equipment.
OPERATION
To check system operation during Heating or Cooling cycle use the appropriate table.
Table indicates whether a correct relationship exists between system operating pressure
and air temperature entering indoor and outdoor units. If pressure and temperature do not
match on chart, system refrigerant charge may not be correct or other system abnormalities
may exist. Do not use table to adjust refrigerant charge.
When charging is necessary during heating season, weigh in total charge as indicated on
unit rating plate. Rating plate charge is for systems with 15 ft. of line-set.
Adjust charge 0.6 oz of refrigerant per foot of 3/8" liquid connecting tubing.
Remove any refrigerant remaining in system before recharging if the
system has lost complete charge, evacuate and recharge by weight.

3 3 8 7 1 9 -1 0 1 R E V . A 338719-101 REV. A

Fig. 1 – 25HCD3 1--1/2 -- 5 Tons


Copyright 2013 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 02/13 Catalog No: 25HCD3---1HCC