Smartstruxure Solution 1.6: Reference Architecture - Multiple Automation Servers

This document discusses the architecture of SmartStruxure Solution 1.6 BACnet systems. Key points include: 1) It uses a client/server model with workstations and webstations as clients, and automation servers and an enterprise server as servers. 2) The enterprise server provides global access and monitoring of alarms, trends, events and historical data from multiple automation servers. 3) Each automation server can connect to up to 127 BACnet devices including IO modules and field controllers via MS/TP, and connect to additional devices via Lonworks, BACnet/IP or Modbus. 4) The system supports up to 250 automation servers and 600 total BACnet devices per

Uploaded by

Fernando Hdz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views5 pages

Smartstruxure Solution 1.6: Reference Architecture - Multiple Automation Servers

This document discusses the architecture of SmartStruxure Solution 1.6 BACnet systems. Key points include: 1) It uses a client/server model with workstations and webstations as clients, and automation servers and an enterprise server as servers. 2) The enterprise server provides global access and monitoring of alarms, trends, events and historical data from multiple automation servers. 3) Each automation server can connect to up to 127 BACnet devices including IO modules and field controllers via MS/TP, and connect to additional devices via Lonworks, BACnet/IP or Modbus. 4) The system supports up to 250 automation servers and 600 total BACnet devices per

Uploaded by

Fernando Hdz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

7/13/2015

SmartStruxure Solution 1.6


BACnet Architecture ES/AS

Reference Architecture - Multiple Automation Servers

StruxureWare Building Operation


Software

Hardware poweredNetwork Server Layer


by StruxureWare Building Operation

Field Controllers
Confidential Property of Schneider Electric 2

1
7/13/2015

System Architecture StruxureWare

> Client / Server system

> Clients
> Workstation
> WebStation

> Servers
> Automation Server
> Enterprise Server

Confidential Property of Schneider Electric 3

Enterprise Server

Live Features
Global view and access
Enterprise Server
Program runtime environment
Centralized alarms and data management
Manage alarms from multiple servers
View extended trend logs from multiple server
View event logs from multiple servers
Store historical data from multiple servers
Capable of monitoring BACnet field bus:
Connects to BACnet field bus through a BACnet/IP router

Confidential Property of Schneider Electric 4

2
7/13/2015

StruxureWare Building Op. Architecture


LonWorks/IP
BACnet/IP
Modbus/IP

AS
IO Modules

Automation IO Modules Automation IO Modules


Power Server Power Server
Supply Supply
b3920
b3850
LONWorks

Modbus
FT-10A

b3867

RTU
b3867

Square D
MNB300 MNB300 Lighting Panel

Variable Speed
SE8000 Drive
SE8000
BACnet
MS/TP

Power
Meter
Confidential Property of Schneider Electric 5
250 Automation Servers and 1 Enterprise Server per system

BACnet Architecture
LonWorks/IP
BACnet/IP
Modbus/IP

AS

•600 BACnet devices total 30000 BACnet


Objects Per ES
b3920 •250 AS w/BACnet fieldbus per ES
b3850
•127 BACnet devices (incl. b3:s) per AS
b3867
b3867 MS/TP
• 2 MS/TP Bus per AS
MNB300 MNB300

SE8000 SE8000
BACnet
MS/TP

Confidential Property of Schneider Electric 6

3
7/13/2015

Some rules… - BACnet

> AS and ES are considered BACnet Devices

> StruxureWare Workstation is certified as a BACnet Operator Workstation

> Max 250 AS

> Max 254 BACnet devices (incl.B3’s) /AS

> Com A and/or Com B for the MSTP port

> MSTP must be daisy chained and terminated

> See Application notes for MS/TP practical limits

Confidential Property of Schneider Electric 7

More rules… - BACnet

> BBMD functionality in both the AS and ES

> BACnet IP router functionality on AS and ES

> Unique Network Numbers

> Unique Device ID’s

> Discovery of 3rd Party Devices

> Default settings are usually default for a reason

> The BACnet Interface Applications Folder is your friend….

Confidential Property of Schneider Electric 8

4
7/13/2015

The AS – what can it do


Examples of Field Bus architecture

10 Lon 64 Lon 64 Lon 10 Lon

127 10 BACnet 31 modbus 127 BACnet


BACnet

31 modbus 31 modbus 31 modbus 127 BACnet