Country of Origin, Construction, Approvals & Fire Performance

This document provides specifications for 2 core heavy duty fire resistant mineral insulated copper clad (MICC) cables manufactured by Wrexham Mineral Cables in the United Kingdom. The cables are approved to exceed 3 hours of fire resistance at 950°C and have a continuous operating temperature range of -40°C to 250°C. They consist of solid copper conductors with highly compressed magnesium oxide insulation and a seamless copper sheath.

Uploaded by

Anand s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views3 pages

Country of Origin, Construction, Approvals & Fire Performance

This document provides specifications for 2 core heavy duty fire resistant mineral insulated copper clad (MICC) cables manufactured by Wrexham Mineral Cables in the United Kingdom. The cables are approved to exceed 3 hours of fire resistance at 950°C and have a continuous operating temperature range of -40°C to 250°C. They consist of solid copper conductors with highly compressed magnesium oxide insulation and a seamless copper sheath.

Uploaded by

Anand s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

2 CORE HEAVY DUTY

Fire Resistant MICC Cable


750V

Country of Origin, Construction, Approvals & Fire Performance


Manufacturer Place of Manufacture
Wrexham Mineral Cables United Kingdom
Cables Manufactured to Cable Type — Known as “Fire Survival Cable”
BSEN 60702-1:2002+A1:2015 Fire Resistant exceeding 3 hours @ 950°C
Continuous Operating Temperature LPCB Product Approval Number
-40°C up to 250°C 333a/01
Applicable Standards
BS5839-1:2017 Enhanced to Clause 26.2, BS EN 50200:2015, Solid Copper Conductors
BS 8434-2:2003 + A2:2009, *BS6387:2013 C,W & Z, BS 8519 & BS 8491 CAT C, BS 60331
Copper Sheath
LPCB Approved Marking on Cables Insulation
WMIC, WMC “Made in the UK” Highly compressed magnesium oxide (Mg0)
Hazardous area cable system ATEX / IEC Ex APPROVED UNDER SIRA LICENCE 1305X & IEC Ex SIR 19.0051X
Apparatus (type of protection ‘d’) Zones 1 & 2, Groups
IIA, IIB and IIC. Zones 20, 21 & 22, groups IIIA, IIIB & IIIC. In compliance with EN 60079
Copper Conductor Plain Annealed to
Seamed Copper Sheath Construction Magnesium Oxide
IEC 60228 Type 1 Solid Insulation (MgO)
Cu - ETP or Cu – FRHC C12200 grade, Cu – DHP
Number of Cores LSZH Outer Sheath
(Optional)
2
* Only cables up to 20mm *

Wrexham Mineral Cables — Wynnstay Technology Park, Ruabon, Wrexham, LL14 6EN, United Kingdom
T: +44 (0) 1978 810789 — E: [email protected]
W: www.wrexhammineralcables.com Page 1 of 3
CDS009 Two Core Heavy Duty (750v) Datasheet Issue E Approved by S. Williams 22.07.21
2 CORE HEAVY DUTY
Fire Resistant MICC Cable
750V
Electrical Properties
Current Rating Bare or Voltage Drop Cables Max Conductor Copper Sheath Earth Fault Loop
Voltage Rating Test Voltage Served Cables Exposed to
Two Core Exposed to Touch Resistance Resistance @ 20°C Impedance Resistance @
(Factory Internal Touch
Heavy Duty D.C Test) 70°C (R1+R2)
MICC Cables (Amps)
(V) (V) Ohms/Km
Bare Served (Per Amp/Per m) Ohms per 1000m @ 20°C Ohms/Km
2H1.5 750 3750 22.5 25 28 12.1 1.51 16.902
2H2.5 750 3750 31 34 17 7.41 1.29 10.903
2H4 750 3750 40.5 45 10 4.61 1.04 7.185
2H6 750 3750 51 57 7 3.08 0.887 5.073
2H10 750 3750 69 77 4.2 1.83 0.690 3.272
2H16 750 3750 92 102 2.6 1.15 0.533 2.220
2H25 750 3750 120 133 1.65 0.727 0.423 1.537

NOTES:
Ambient Temp 30°C Sheath operating temperature 70°C For bare cables exposed to touch,
the tabulated values should be multiplied by 0.9

Current Carrying Capacity LSZH or Bare and Exposed to Touch MICC Resistance, Reactance & Impedance
Two Core Heavy Duty Single Phase A.C or D.C — 2 Core Cables
Resistance R (Ω /Km) Reactance X Impedance Z (Ω /Km)
MICC Cables Cable Type
Ref C * (Amps) Ref E, F & G ** (Amps) (Ω /Km)
30c 70c 105c 30c 70c 105c
2H1.5 25 26
2H1.5 12.575 14.477 16.141 0.101 12.576 14.478 16.142
2H2.5 34 36
2H4 45 47 2H2.5 7.701 8.886 9.885 0.094 7.702 8.866 9.885
2H6 57 60 2H4 4.791 5.516 6.150 0.088 4.792 5.516 6.150
2H10 77 82 2H6 3.200 3.685 4.109 0.083 3.201 3.686 4.110
2H16 102 109 2H10 1.902 2.190 2.441 0.079 1.904 2.191 2.442
2H25 133 142 2H16 1.195 1.376 1.534 0.075 1.198 1.378 1.536
* Clipped direct ** In free air, perforated cable tray horizontal or vertical 2H25 0.756 0.870 0.970 0.073 0.759 0.873 0.973

Wrexham Mineral Cables — Wynnstay Technology Park, Ruabon, Wrexham, LL14 6EN, United Kingdom
T: +44 (0) 1978 810789 — E: [email protected]
W: www.wrexhammineralcables.com Page 2 of 3
CDS009 Two Core Heavy Duty (750v) Datasheet Issue E Approved by S. Williams 22.07.21
2 CORE HEAVY DUTY
Fire Resistant MICC Cable
Mechanical Properties 750V
Cable Diameter Conductor Copper Nominal Mean Serving Approx Weight per Minimum Bend
Two Core (mm) Diameter Sheath Mean Insulation Thickness (LSZH 1000m Radius (6 Times
Heavy Duty Thickness Thickness Optional Outer (Kg) Diameter of
MICC Cables (mm) (Mg0) Covering) Cable)
Bare Served (mm) Bare Served
(mm2) (mm) (mm)
2H1.5 7.9 9.6 1.5 0.54 1.3 0.75 247 284 47.4
2H2.5 8.7 10.4 2.5 0.57 1.3 0.75 280 335 52.2
2H4 9.8 11.5 4 0.61 1.3 0.75 365 415 58.8
2H6 10.9 12.6 6 0.65 1.3 0.75 463 510 65.4
2H10 12.7 14.4 10 0.71 1.3 0.75 635 725 76.2
2H16 14.7 16.4 16 0.78 1.3 0.75 855 918 88.2
2H25 17.1 19.4 25 0.85 1.3 1.00 1185 1285 102.6

Product Part Codes


WMC Cable WMC Cable Seal Kits Shrouds Shrouds Lockwasher Bare LSZH Bare Two LSZH Two
IEC Ex & ATEX Approved WRLM
Part Code for Part Code WRPS Plain (PVC) (LSZH) Single Single Way Clips Way Clips
Cable Gland or
Two Core Bare or CC for LSZH or WRLWS
Clips Clips (Saddles) (Saddles)
Heavy MICC Served or WRPSL E/T Serrated (P Clips) (P Clips) 1 Clip 1 Clip
Duty CCM MICC Washer 1 Clip 1 Clip every every
MICC every every 0.4m 0.4m
Cables WRLM/ 0.4m 0.4m
WRGM
Cable Size Cable Size WRPS/ WRHG WRHGMM WRLWS
Followed By Followed By *** **** WRPSL *** **** *** **** *** **** WRC WRCHL WRS WRSFL
2H1.5 BARE/* LSF/**/* 2H1.5/20 2H1.5/20 2H1.5 20/** 20/** 20 20 20 20 30 37/** 342 382/**
2H2.5 BARE/* LSF/**/* 2H2.5/20 2H2.5/20 2H2.5 20/** 20/** 20 20 20 20 34 40/** 342 422/**
2H4 BARE/* LSF/**/* 2H4/20 2H4/25 2H4 20/** ! 20 25 20 25 37 43/** 422 462/**
2H6 BARE/* LSF/**/* 2H6/20 2H6/25 2H6 20/** ! 20 25 20 25 43 47/** 462 502/**
2H10 BARE/* LSF/**/* 2H10/25 2H10/32 2H10 ! ! 25 32 25 32 47 54/** 502 529/**
2H16 BARE/* LSF/**/* 2H16/25 2H16/40 2H16 ! ! 25 40 25 40 54 63/** 592 702/**
2H25 BARE/* LSF/**/* 2H25/32 2H25/40 2H25 ! ! 32 40 32 40 67 75/** 702 757/**

D or C depending on drum or coil | ** Cable colour e.g. RD = RED, OE = ORANGE, BK = BLACK, WE = WHITE
Seal choice: *** Represents Standard seal (WRPS) requirements **** Represents E/T seal (WRPSL) requirements (Only available up to 50mm2)

Wrexham Mineral Cables — Wynnstay Technology Park, Ruabon, Wrexham, LL14 6EN, United Kingdom
T: +44 (0) 1978 810789 — E: [email protected]
W: www.wrexhammineralcables.com Page 3 of 3
CDS009 Two Core Heavy Duty (750v) Datasheet Issue E Approved by S. Williams 22.07.21