0% found this document useful (0 votes)
164 views2 pages

Ficha Tecnica Honeywell C7027a1023

The document describes Honeywell's C7027A, C7035A, and C7044A ultraviolet flame detectors. The detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners. The C7027A and C7035A mount on sighting pipes, while the C7044A uses a simple bracket. All three detectors detect only ultraviolet radiation emitted from flames. They have operating temperature ranges of 0°F to 250°F and can withstand pressures up to 5 psi. The C7035A has a field-replaceable UV sensing tube.

Uploaded by

Controls Burner
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
164 views2 pages

Ficha Tecnica Honeywell C7027a1023

The document describes Honeywell's C7027A, C7035A, and C7044A ultraviolet flame detectors. The detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners. The C7027A and C7035A mount on sighting pipes, while the C7044A uses a simple bracket. All three detectors detect only ultraviolet radiation emitted from flames. They have operating temperature ranges of 0°F to 250°F and can withstand pressures up to 5 psi. The C7035A has a field-replaceable UV sensing tube.

Uploaded by

Controls Burner
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Honeywell

R4126 and R4127lR7255B


R4140IR7249A
R4150IR7259A
R4795lR7290
-Flame Safeguard Primary Controls/
C7027A, C7035A, C7044A Amplifiers
R4075C,D,E/R7249A
MINIPEEPER ULTRAVIOLET R4136C,D/R7249A
dA690G Protectorelay Primary Control
FLAME DETECTOR -R7023C Flame Detector Relay.

l The C7044A is also used with the following 50’ Hz Flame


Safeguard Controls/ Amplifiers:
R434l /R7323
R4343lR7323
R4344IR7323
l The C7027A mounts on a 1 I2 in. sighting pipe by means of an
integral collar.
l The C7035A mounts on a 1 in. sighting pipe by means of an
integral collar. A shield protects the sensing tube.
l The C7035A meets outdoor raintight requirements of Under-
writers Laboratories Inc., NEMA 3, and NEMA 4.
l The C7044A mounts with a simple, l-screw bracket. Sensing
tube enclosed in stainless steel housing.
l The C7044A is suitable for side or end viewing.
THE C7027A, C7035A, AND C7044A DETECT ULTRAVIOLET l Compact size makes the C7027A and C7044A particularly
RADIATION EMITTED FROM ALL FLAMES. THEY ARE USED useful for blast tube mounting.
WITH FLAME SAFEGUARD CONTROLS TO PROVIDE SUPER-
l Properly installed, the C7027A and C7035A are sealed
VISION FOR GAS, OIL, OR COMBINATION GAS-OIL
against pressures as high as 5 psi 134.5 kPa].
BURNERS.
l The C7035A ultraviolet sensing tube is field replaceable. The
q C7027A 0 C7035A 0 C7044A
C7027A and C7044A sensing tubes are not field replaceable-
l The C7027A, C7035A, and C7044A are used with the use on an economical, throwaway basis.
following:
-Flame Safeguard Programmers/ l Two Minipeeper detectors can be wired in parallel for difficult
Amplifiers sighting applications.

I SPEClFlCATlOhiS I
STANDARD MODELS C7035A MINIPEEPER ULTRAVIOLET FLAME DETECTOR
DETECTION: Detects ultraviolet radiation only.
C7027A MINIPEEPER ULTRAVIOLET FLAME DETECTOR AMBIENT OPERATING TEMPERATURE RATINGS: 0 F to 250 F
DETECTION: Detects ultraviolet radiation only. [-18 C to +121 C], or -40 F to +250 F [-40 C to +121 Cl, depending
AMBIENT OPERATING TEMPERATURE RATINGS: 0 F to +215 F on the model.
[-18 C to +102 C], or -40 F to +215 F r-40 C to +102 C], depending
MAXIMUM PRESSURE RATING: 5 psi [34.5 kPa].
on the model.
MOUNTING: Collarwith standard 1 in. internal threadsfor mounting
MAXIMUM PRESSURE RATING: 5 psi [34.5 kPa].
on a 1 in. sighting pipe. (The DIN approved C7035A1064 has l-1 1
MOUNTING: Collar with standard l/2 in. internal threads for
BSRPl threads.)
mounting on a l/2 in. sighting pipe.
WIRING CONNECTIONS: Two, 6 ftt1.83 m], color-coded, NEC Class
WIRING CONNECTIONS: Two, 6 ft [1.83 m], color-coded, NEC Class
1 leadwires. (One model is available with leadwires rated for
1 leadwires. (One model is available with 24 ft [7.32 m] leadwires.)
400 F [204.4 C], and one model is available with 12 ft
Rear of detector has a clamp type connector for l/2 in. flexible
[3.66 m] leadwires.) Rear of detector has 112-14 NPSM internal
metallic conduit. (Models are available with l/2 in. internally
threads for connecting to a conduit. (The DIN approved
threaded spud connector instead of the clamp.)
C7035A1064 has l/2-14 BSP-F threads.)
DIMENSIONS: See Fig. 1.
DIMENSIONS: See Fig. 2.
REPLACEMENT PART: 129685 Flange Gasket NOTE: The UV
WEIGHT: 6 oz [0.17 kg].
sensing tube is not field replaceable.
REPLACEMENT PARTS:
129808 Flange Gasket.
129464M Ultraviolet Sensing Tube, 0 F to250 F I-18 C to+121 C].
129464N Ultraviolet Sensing Tube, -40 F to +250 F [-40 C to
+121 C].

C7027A AND C7035A


APPROVALS:
UNDERWRITERS LABORATORIES INC. LISTED: File No.
MP268; Guide No. MCCZ.
CANADIAN STANDARDS ASSOCIATION CERTIFIED: File No.
LR1620; Guide No. 140-A-2.
FACTORY MUTUAL APPROVED.
FIG. I- INSTALLATION DIMENSIONS OF THE C7027A, IN in. [mm DIN APPROVED MODELS: C7027A1056, C7035A1049, and
IN BRACKETS]. C7035A1064.

D.A. Form Number 65-0062


12-66e cHoneywell Inc. 1986
AMBIENT OPERATING TEMPERATURE RATINGS: 0 F to 215 F [-I8
c to +102 C].
MOUNTING: Bracket (included in 4074 BVK Bag Assembly), se-
cured by two 8-32 RHIS (European M-4) screws (not included).
WIRING CONNECTIONS: Two, 6 ft [1.83 ml, color-coded, NEC Class
1 leadwires. Rear of detector has a clamp type connector for l/2
inch flexible metallic conduit.
DIMENSIONS: See Fig. 3.
WEIGHT: 10 oz to.28 kg].

TABLE I-FLAME SIGNAL

I PLUG-IN I I MINIMUM I
FLAME ACCEPTABLE MAXIMUM
SIGNAL FLAME STEADY CURRENT
FLAME AMPLIFIER SAFEGUARD CURRENT EXPECTED
DETECTOR Ipsrplsl CONTROL(S) lmicroampl (microamp)
C7027A R7249A R4075C,D,E; 3-112 7-l 12
C7035A, or R4139C,D;
FIG. 2- INSTALLATTON DIMENSIONS OFTHEC7035A, IN in. [mm C7944A R4149
IN BRACKETS].
R7255B IT4128 R4127 4 a
1 R7259A i R4150 1 4 I a
C7044A MINIPEEPER ULTRAVIOLET FLAME DETECTOR 1 R7299A 1 R4795A.D 1 l-112 I 2-114
DETECTION: Detects ultraviolet radiation only. Housing has 2
openings to permit viewing from either its end or its side. Side None RA999G, l-1/2 2-l/4
viewing is 1 / 8 as sensitive as end viewing. R7023C

6 FOOT 11.83 METREJ


LEADWIRES (21

FIG. 3-INSTALLATION DIMENSIONS OF THE C7044A, IN in. [mm IN BRACKETS].

PRINTED IN U.S.A.