Remote Inverter Access Guide
Remote Inverter Access Guide
Application instructions
for installers
Application instructions - Remote access to the inverter
via web user interface
1 Application
We have provided you with an intuitive web-based user interface for remote configuration of a KACO inverter which is
connected to a network.
Enter the unit’s IP address (e.g. http://192.168.100.13) into the address bar of a common internet browser to gain access
to the user interface.
The web user interface is split into three sections and separated by a selection bar. The area above the selection bar is
used to display the unit and network data. The graphical interface of the inverter is simulated below the selection bar on
the left hand side. The current performance and operating data are displayed on the right hand side. There is also the
option to export data in csv format.
*We recommend using Internet Explorer, Firefox, Google Chrome or Mobile Safari for optimum display.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 2 of 30
Application instructions - Remote access to the inverter
via web user interface
It is only possible to configure the inverter remotely if this function has been activated locally via the inverter’s webserver
menu on the unit.
Figure 3. Access to remote config via the webserver menu interface on the inverter
Figure 5. Remote update activation via the webserver menu interface on the inverter
2 Safety
CAUTION
Setting parameters incorrectly can cause damage
Changes to software parameters can seriously impair the functionality of the unit.
> The activities described in the document may only be carried out by specially trained personnel
with the following qualifications:
- Knowledge about how an inverter functions and operates
- Training in the handling of hazards and risks during the installation and operation of
electrical units and systems
- Education concerning the installation and start-up of electrical units and systems
- Knowledge of applicable standards and directives
> Knowledge and adherence to this document with all safety notices.
CAUTION
Unauthorised access can lead to damage
If unauthorised persons gain access to the system, unit settings could be manipulated which could
seriously impair the functionality and safety of the unit and lead to damage.
> The following functions must only be used on the local network or via a secure VPN connection.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 3 of 30
Application instructions - Remote access to the inverter
via web user interface
NOTEHT
The update can take several minutes. The "Operating" LED flashes during the update process.
The inverter may restart several times.
The following message appears if the DC power supply is too low: "DC power supply too low! Perform
update anyway?".
In this case, select “No” and perform the update with a stable voltage supply.
NOTEHT
The unit-specific and serial number dependent password is required to set “critical” parameters. The
unit-specific password can be obtained from KACO customer service, if necessary.
Login data must be stored in a location which is not accessible to third parties.
ACCESS DATA *)
The two accounts “user” (restricted configuration options) and “installer” (advanced configuration
options) are available for remote access to the unit:
User name: user
Password: Da_3u1B! (initial setting)
User name: installer
Password: Mo_g010rP! (initial setting)
*)
Important: Following initial start-up, you must change the access data via one of the menu items “Change user
password” or “Change installer password” in the Main menu under Functions.
NOTEHT
The functions described in the following chapter are only available on the inverters listed and with the
existing software package (see chapter 5.1).
Configurations and software updates may only be carried out if there is a suitable DC power supply.
DEVICE-SPECIFIC NOTEHT
Modified parameters in the device series blueplanet 15.0-20.0TL3 from Software Version V4.x
are only adopted when the device is restarted, but at the latest on the next day.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 4 of 30
Application instructions - Remote access to the inverter
via web user interface
3 Navigation
The following table will support you during the remote config process using the web user interface and shows you the
input screens behind the “Configuration” link.
Input screens that are marked on the side(user) are only available to installers, service partners and technicians and can
not be accessed by system operators.
Note: In the case of inactive entry or use, the interface is made available for 10 minutes for configuration purposes. Once
this time has elapsed, you must log in again.
Configuration
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 5 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 6 of 30
Application instructions - Remote access to the inverter
via web user interface
Figure 13. View and edit the yield and operating counters
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 7 of 30
Application instructions - Remote access to the inverter
via web user interface
Number of monitored
MPP trackers
Parameter version
Self-test status
Activation status
Clicking the “Back” button will
take you back to the previous
input screen at any time.
Automatic IP address
assignment can be activated
by clicking the “Active” button.
Note: The following fields will be
hidden when the DHCP is activated.
IP address
Subnet mask
Gateway
DNS server
Note: Warning messages*) are
highlighted in the comments box
below.
Set the entries by clicking the
“Set” button.
Figure 17. Configure the network settings *)
Changing these properties can result in the
connection being terminated.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 8 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 9 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 10 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 11 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 12 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 13 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 14 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 15 of 30
Application instructions - Remote access to the inverter
via web user interface
Submenu items – Parameters for the reactive power mode (Not for RPO-inverters)
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 16 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 17 of 30
Application instructions - Remote access to the inverter
via web user interface
buttons.
Enter the minimum and
maximum deactivation
threshold
or set them using the “+/-”
buttons.
Enter the deactivation time or
set it using the “+/-” buttons.
Specify the gradient in % /Hz
or set it using the “+/-”
buttons.
Enter the intentional delay in
Figure 44. Configuring power reduction P(f) sec. or set it using the “+/-”
buttons.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 18 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 19 of 30
Application instructions - Remote access to the inverter
via web user interface
Grid parameters
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 20 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 21 of 30
Application instructions - Remote access to the inverter
via web user interface
“Set” button.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 22 of 30
Application instructions - Remote access to the inverter
via web user interface
“Set” button.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 23 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 24 of 30
Application instructions - Remote access to the inverter
via web user interface
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 25 of 30
Application instructions - Remote access to the inverter
via web user interface
Upload/download
View Documentation of
parameter for Print or PDF-
Export by clicking the Button
Load a parameter set by
clicking the button.
Figure 65. Performing an upload/download Note: Before transferring the
parameter set, the same country
setting must be set on all devices.
Parameters that affect each
other during the first import
can lead to an error message.
In case of error repeat import.
After importing a parameter
set, the correctness of all
parameters must be checked.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 26 of 30
Application instructions - Remote access to the inverter
via web user interface
Software update
NOTEHT
Ensure that the inverter has an active DC power supply when remote access is active. It is only possible to
update all of the inverter’s components to the most current software version in this operating state.
Furthermore, any USB storage media which may be connected to the unit must be removed.
NOTEHT
The update can take several minutes. The "Operating" LED flashes during the update process.
The inverter may restart several times.
The following message appears if the DC power supply is too low: "DC power supply too low! Perform
update anyway?”.
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 27 of 30
Application instructions - Remote access to the inverter
via web user interface
ACCESS DATA
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 28 of 30
Application instructions - Remote access to the inverter
via web user interface
1. Once the update has been completed successfully, check the current software version of all installed components.
» The inverter displays the version of the software that is currently loaded in the upper area of user interface.
5 More information
NOTEHT
Information concerning the specific functionality of menu entries can be found in the operation
manuals on our homepage.
Table 1. KACO inverter series that support all of the functions described
Key
V5.x new Features Features / Functions‘ / Password protection; Features / Functions‘ /
Enhanced Island Detection /Up-/Download’ / Documentation of a
parameter set / Grid parameters / Overvoltage protection
x.yz released
- in preparation Single update Remote update of the inverter possible
APL_remoteaccess_via_
WebGui_Installer_190603 Last updated: 2019-11-26 Page 29 of 30
Carl-Zeiss-Straße 1 · 74172 Neckarsulm · Germany · Phone +49 7132 3818-0 · Fax +49 7132 3818-703 · [email protected] · www.kaco-newenergy.de
Ö3012650-02-171206Yä
The text and figures reflect the current technical state at the time of printing. Subject to technical changes. No liability for printing errors. 3012650-03-190308