Rectangular & Circular Types: Rsa, Casa & Cbsa: Duct Ventilation Air Conditioning Co. (W.L.L.)
Rectangular & Circular Types: Rsa, Casa & Cbsa: Duct Ventilation Air Conditioning Co. (W.L.L.)
MADE IN QATAR
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Table Of Contents
Sound Attenuators / General
Page
Introduction 3
Acoustic Design 4
Definitions 5
2
Sound Attenuators
Introduction
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
INTRODUCTION
DVAC Sound Attenuators are designed to achieve the required performances as set out
in the ASTM Standards E477-06a for Prefabricated Attenuators.
DVAC Sound Attenuators are licensed to bear the AMCA Seal for Prefabricated Silencer
Sound & Air Performance.
The ratings shown herein are based on tests and procedures performed in accordance with
AMCA PUBLICATION 1011 and comply with the requirements of the AMCA Certified Ratings
Program.
AMCA Certified Ratings Seal applies to Dynamic Insertion Loss, Airflow Generated Noise and
Pressure Drop.
Models RSA3', RSA4', RSA5', RSA6', RSA7' & RSA8' are certified and their Certified
Performance is indicated in pages 16---21.
3
Sound Attenuators
Acoustic Design
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
It is correct, though impracticable, to propose that noise can be controlled at any of these stages. In the case of the fan,
for example, the manufacturer has already produced a quiet design within the constraints of commercial prudence
and the office worker is unlikely to take too kindly to a suggestion that the wearing of ear protectors is a satisfactory
means of combating the air-conditioning noise! This leaves us with having to control the noise during the transmission.
Noise control Engineers have two weapons with which to combat noise - mass and absorption - usually applied
in a combination. The term mass, for example, meaning the plantroom built of heavy weight materials and absorption
being the splitter attenuators strategically located to acoustically seal the ducts where they penetrate the mass barrier.
During the design stage, the common pitfalls should be avoided, these include:
1. Right angle bends and take-offs.
2. Ineffective expansions and contractions.
3. Incorrectly located dampers, heater batteries and cooling coils.
4. Fans located above lightweight ceilings or immediately above or below the most sensitive rooms.
In addition some acoustic assessment should be carried out in order to ensure that realistic space is allowed for attenuators
and that they are positioned effectively.
4
Sound Attenuators
Definitions
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
DIRECT SPL
SOUND POWER LEVEL (SWL) Noise which is transmitted directly from a source (i.e. a grille or
diffuser) without reflection.
A theoretical assessment of sound produced at source calculated
from the measured Sound Pressure Levels at known distances
from the source under known acoustic conditions. REVERBERANT SPL
A level which depends only on the source and is independent
of the environment or location. The Sound Power Level of a fan Noise which is transmitted by reflection of room surfaces.
is therefore very useful information since any level quoted can
be compared directly with data from any other manufacturer.
REVERBERATION TIME
A measurement of the acoustic “reflectiveness” of a room.
SOUND PRESSURE LEVEL (SPL)
A measured Sound Level which is an indication only of the noise INSERTION LOSS
produced at source since environmental factors such as reverbe-
ration and distance from the source have affected the measurement. A measure of the noise reduction capability of an attenuator
The Sound Pressure Level of a fan is not very useful since (sometimes of a partition) so named after the method of testing
environmental factors apparent when the unit was measured may where a section of ductwork is replaced by an attenuator between
or may not be present in the actual location of the plant. two test rooms. One room contains the noise source and the other
the sound level measuring equipment. The difference in recorded
noise level is said to be the insertion loss due to the insertion of
the attenuator in the system.
DECIBEL (dB)
Commonly, the unit used to measure sound. It is used to quantify REGENERATED NOISE
both Sound Pressure Level and Sound Power Level.
Noise in addition to that produced by the fan, caused by air
passing over fixed duct elements such as blades on grilles,
dampers, air turns, splitters in attenuators, etc.., is not normally
CRITERIA a problem on low velocity systems and is not dealt within
this booklet.
Noise Levels which are subjectively or objectively acceptable
in a given environment.
The most commonly used Criteria are Noise Criteria Curves (NC OCTAVE BANDS
Levels), Noise Rating Curves (NR Levels) and dB (A).
Subdivisions of the Frequency range each identified by its mid
( O r centre) frequency. By international agreements these
comprise 63, 125, 250, 500, 1k, 4k, and 8kHz.
DUCTBORN NOISE
Noise which is transmitted along ductworks, both upstream and FREQUENCY (Hz)
downstream of a fan.
The pitch of sound; the number of sound pressure waves arriving
at a fixed point per second.
5
Sound Attenuators
Roomside Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
ROOMSIDE CALCULATION
PART 1 PART 2
How to find the In-duct SWL of the fan: Investigate the duct system between the fan and the
critical noise outlet
A) Using the fan manufacturer’s catalogue information, obtain
the In-duct Sound Power Level at the mid-frequency Octave The “critical” noise outlet in the duct system is usually the noise
Bands of interest, or calculate the approximate In-duct Sound outlet closest to the fan using the following information assess
Power Level from Table 1. The total duct attenuation:
In both cases the approximate duty of the fan needs to be known.
These figures are inserted in line a. B) Straight unlined ducts provide a degree of attenuation.
Some manufacturers present noise data as a Sound Pressure This is frequency dependent and varies with the minimum
Level which needs to be converted by applying the relevant duct dimension and duct length.
correction factor.
Approximate attenuation per meter run is shown in Table 2.
To avoid noise breakout problems the duct attenuation taken
should be limited to approximately 15dB. Bends provide
attenuation as shown in Tables 3a and 3b. Duct and bend
attenuation figures should be entered against line “b”.
Table 1: In-duct SWL of the Fan Table 2: The attenuation of straight unlined rectangular ducts -
dB per meter
Overall sound power level dB re 10-12 watts
130
Octave centre frequency, fm in Hz
120
63 125 250 500 1k 2k 4k 8k
110 S 0-200 0.6 0.6 0.45 0.3 0.3 0.3 0.3 0.3
201-400 0.6 0.6 0.45 0.3 0.2 0.2 0.2 0.2
100
401-800 0.6 0.6 0.3 0.15 0.15 0.15 0.15 0.15
80
0-250 0 0 0 0 1 2 3 3
251-500 0 0 0 1 2 3 3 3
S 501-1000 0 0 1 2 3 3 3 3
1001-2000 0 1 2 3 3 3 3 3
6
Sound Attenuators
Roomside Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
ROOMSIDE CALCULATION
PART 2 (cont’d.)
C) At low frequencies some of the sound power on reaching 2. By multiple reflections off the room surfaces and room
the critical noise outlet is reflected back along the duct. contents, which will depend upon the size of the room and
The degree of attenuation due to this phenomenon is dependent the reverberation time, known as the Reverberant Sound
on frequency and the total area of the outlet. The attenuation Pressure Level.
from Table 4 is inserted in line “c”
To estimate the Direct Sound Pressure Level.
D) The total duct attenuation is obtained from lines “b” & “c” and
is inserted in line “d”. F) Calculate the percentage of the total sound leaving the critical
noise outlet. This is approximately equal to the percentage of
E) The Sound Power Level leaving the critical outlet is obtained the fan air volume which passes through the critical outlet.
from: e=a-d
Table 5 gives the factors to be inserted in line “f”.
PART 3
G) Estimate the distance between the nearest listening position
Calculate the Room Effect
and the critical outlet and, using Table 6, insert the distance
In a room the sound pressure waves will reach the listener along factors in line “g”. Unless the specification states otherwise,
two paths: the commonly applied distance is 1.5 meters.
-18
-17
-16
-15
-14
-13
-12
-10
-11
6
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
10
2
5 0
9
1 2 3 4 5 10 20 50 100
8 4 1 Metres
-12
-13
-14
-15
-16
-17
-18
-19
-20
-21
-22
-23
-24
-25
-26
-27
-28
-29
-30
5000
-11
6 2
0
5
1
10000 4 1 1.5 2 3 4 5 6 7 8 9
Metres
7
Sound Attenuators
Roomside Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
ROOMSIDE CALCULATION
PART 3 (cont’d.)
H) By examining Table 7, select the location type (A or B or C) To estimate the Reverberant Sound Pressure Level.
which is closest to matching the position of the critical outlet
in the room using the charts for the chosen location, type and K) For the fan system in question, calculate the percentage
outlet area, insert the factors obtained in line “h” of the sound emerging from all the noise outlets in the room
served by the fan.
Note: These figures are positive and to avoid possible confusion,
the positive sign should also be inserted in line “h”.
This approximates to the percentage of the fan air volume serving
the room under investigation.
I) The factors tabulated at each Octave Band in lines “f”, “g” & “h”
are now added together in line “i”, to give the total Direct actors,
remembering that the factors in line “h” are positive. Using Table 8 insert the factor in line “k”.
J) The direct sound pressure level in the room is equal to the sum
of the Sound Power Level leaving the Critical Outlet in line “e”
and the Total Direct Factors shown in line “i”.
Type Junction of three room surfaces Type Junction of two Octave Type Centre of one
B room surfaces Centre B room surface
A = + 9 throughout frequency
Outlet area, cm2 in Hz Outlet area, cm2
B C 10 100 1000 10000 10 100 1000 10000 100000
+6 +7 +8 63 +3 +4 +5 +6 +7
A
+6 +7 +8 125 +3 +4 +5 +6 +7 +8
+6 +7 +8 +9 250 +3 +4 +5 +6 +7 +8 +9
+6 +7 +8 +9 500 +3 +4 +5 +6 +7 +8 +9
+7 +8 +9 1k +4 +5 +6 +7 +8 +9
+7 +8 +9 2k +5 +6 +7 +8 +9
+7 +8 +9 4k +7 +8 +9
+8 +9 8k +8 +9
-18
-17
-16
-15
-14
-13
-12
-10
-11
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1 2 3 4 5 10 20 50 100
Percentage
8
Sound Attenuators
Roomside Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
ROOMSIDE CALCULATION
PART 3 (cont’d.)
L) The amount of reflection or absorption of the sound emerging from N) The Reverberant Sound Pressure Level (line “o”) in the room
the noise outlets, depends upon the volume and the reverberation is equal to the sum of the Sound Pressure Level leaving the
time (which is a function of the amount of absorption) of the room. Critical Outlet (line “e”) and the Total Reverberant Factors
(line “n”)
Tables 9 and 10 give factors related to these which are inserted
in lines “l” and “m” respectively. O) To arrive at the Combined Sound Pressure Level, it is necessary
to logarithmically sum the Reverberant Sound Pressure Level
M) The factors tabulated at each Octave Band in lines “k”, “l” & “m” and the Direct Sound Pressure Level.
are now added together in line “n”, to give the Total Reverberant
Factor. This can be simplified by using Table 11.
The combined Pressure level can then be entered in line “p”.
-16
-18
-19
-20
-21
-22
-23
-24
-10
-12
-13
-14
-15
-17
-25
-25
-27
-28
-11
+9
+8
+7
+6
+5
+4
+3
+2
+1
-1
-2
-3
-4
-5
-6
-7
-8
-9
0
Average furnishing
Table 10: Reverberation Limited furnishing
Time factors, dB No furnishing
Very hard surfaces, high ceilings
+10
+11
-10
-11
+1
+2
+3
+4
+5
+6
+7
+8
+9
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
0.1 +3
2.3 +2
4,5,6,7,8,9 +1
10+ +0
9
Sound Attenuators
Roomside Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
ROOMSIDE CALCULATION
PART 4
How to find the Required Insertion Loss R) The Attenuator can now be selected to meet the parameters
of Insertion Loss, Physical Size and the Pressure Loss.
P) The specification will usually give a criterion; where one is not Insertion Loss Figures are placed in line “s” as a final check.
given, Table 12 can be used.
The above analysis method takes no account of regenerated
The required or selected criterion is inserted in line “q”. noise from the attenuators or ductwork elements.
Q) If the Combined Sound Pressure Level exceeds the Criterion Similarly, it is not possible to deal with the method of selecting
in any Octave Band, then the difference is the Insertion Loss attenuators for high pressure systems which commonly have
terminal devices that generate noise and often have some
required from the attenuator (line “r”).
attenuation capability.
To allow for the possible addition of noise from other sources, a safety
margin of typically 3dB may be added.
Table 12: Recommended design criteria for various area functions (according to CIBSE)
SITUATION NC
Concert halls, opera halls, studios for sound reproduction, live theatres (>500 seats) 20
Bedrooms in private homes, live theatres (<500 seats), cathedrals and large churches,
25
television studios, large conference and lecture rooms (>50 people)
Living rooms in private homes, board rooms, top management offices, conference and
lecture rooms (20-50 people), multi-purpose halls, churches (medium and small), libraries,
30
bedrooms in hotels, etc., banqueting rooms, operating theatres, cinemas, hospital private
rooms, large courtrooms
Public rooms in hotels, etc., ballrooms, hospital open wards, middle management and small
offices, small conference and lecture rooms (<20 people), school classrooms, small courtrooms, 35
museums, libraries, banking halls, small restaurants, cocktail bars, quality shops
Toilets and washrooms, large open offices, drawing offices, reception areas (offices), halls,
corridors, lobbies in hotels, hospitals, etc., laboratories, recreation rooms, post offices, 40
large restaurants, bars and night clubs, department stores, shops, gymnasia
Kitchens in hotels, hospitals, etc., laundry rooms, computer rooms, accounting machine rooms,
45
Cafeteria, supermarkets, swimming pools, covered garages in hotels, offices, etc., bowling alleys
10
Sound Attenuators
Roomside Calculation Sheet
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
CALCULATION SHEET
Customer Name :
Project Name : 63 125 250 500 1k 2k 4k 8k
Fan Duty :
Type :
System : In-duct Sound Power a
Duct / Bend Width x Height Length / Angle Type
b
Selection Code: NC 55 74 67 62 58 56 54 53 52
NR 55 79 70 63 58 55 52 50 49
NC 50 71 64 58 54 51 49 48 47
NR 50 75 65 59 53 50 47 45 43
NC 45 67 60 54 49 46 44 43 42
NR 45 71 61 54 48 45 42 40 38
NC 40 64 57 50 45 41 39 38 37
NR 40 67 57 49 44 40 37 35 33
NC 35 60 52 45 40 36 34 33 32
NR 35 63 52 45 39 35 32 30 28
NC 30 57 48 41 35 31 29 28 27
NR 30 59 48 40 34 30 27 25 23
NC 25 54 44 37 31 27 24 22 21
NR 25 55 44 35 29 25 22 20 18
NC 20 51 40 33 26 22 19 17 16
NR 20 51 39 31 24 20 17 14 13
11
Sound Attenuators
Rectangular
Test Method
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
1- GENERAL
The Sound Attenuator is mainly used to reduce FCU and AHU noise to obtain the
required noise level; It offers many advanced features including as standard,
Aerodynamic Splitters, Side Liners, Slide on Flanges and Protective Acoustic Infill
with Galvanized Perforated Sheet.
DVAC Sound Attenuators have been tested and certified in accordance with ASTM
E477-06a, dynamic insertion loss and self noise acoustic performance data were
obtained in AMCA (USA) test facility, using the duct-to-room reverberant test facility
with air flowing through the Silencers.
2- TEST METHOD
The Laboratory method used in conducting these tests is ASTM Standard E477-06a,
entitled “Standard Method of Testing Duct Liner materials and Prefabricated Silencers
for Acoustical and Airflow Performance”. Sound pressure level data was obtained
using a Brüel and Kjær Pulse Frequency Analyzer.
The Intertech 16,640 cu. Ft. (470 m³) reverberation room is qualified in accordance
with ANSI S12.51 for sound measurement from 50 to 10,000 hertz.
The following notes relate to the data submitted in the data pages:
Notes:
1- Sound Power Level data denoted with a double asterisk has reached ambient levels in the test room
or is determined by instruments limitations. Actual levels are less than or equal to the levels indicated.
The generated sound data has been corrected for end reflection.
Sound power level data denoted with a single asterisk has reached ambient levels and is being corrected.
2- Insertion Loss Data denoted with a single asterisk has been corrected to take into consideration the effect
of the generated Sound Pressure Level approaching the sound pressure level obtained during the insertion
loss portion of the test. In some cases, the insertion loss may be higher than shown. Insertion loss data
denoted with a double asterisk has reached the maximum allowable correction and is not corrected.
12
Sound Attenuators
Rectangular
- Materials
- Construction
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) - Performance
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
13
Sound Attenuators
Installation Guidelines
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
INSTALLATION GUIDELINES
A- Radius Bend
L1 & L2 ΔP FACTOR
Airflow
Deq X 3.0 1.00 Downstream
Silencer
Deq X 2.0 1.25
L2
Radius Bend with
Deq X 1.0 1.75
Turning Vanes
L1
Deq X 0.5 3.00
upstream
Silencer
Deq X 3.0 1.00
Radius Bend
without Deq X 2.0 1.50 NOTE: Silencer splitters should be parallel
Turning Vanes to the plane of the Radius Bend
Deq X 1.0 2.00
L1 L2 ΔP ACTOR
L1 L2
C- Transitions
ΔP FACTOR
15° 30°
Upstream Downstream
Airflow
With 15º included angle (7.5º slope) 1.00 1.00 Silencer
With 60º included angle (30º slope) 1.50 1.00 Silencer between Upstream and Downstream Transitions
14
Sound Attenuators
Installation Guidelines
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
INSTALLATION GUIDELINES
L2
L2
Centrifugal Discharge Airflow
Fan Silencer
Discharge Airflow
Silencer
15°
L1
Intake
Silencer
L1 = Not less than 0.75 X Deq of inlet silencer L2 = Fan wheel diameter for every 1000 fpm of exit velocity
NOTES:
1. For Circular Ducts: “Deq” = Duct Diameter. For Square or Rectangular Ducts: “Deq” = (4/∏ ) x area
2. ΔP Factor is multiplier relative to silencer laboratory tested pressure drop data.
3. Unless noted otherwise, ΔP Factors do not include pressure losses of other components (Transitions, Elbows, Dump Losses, etc..)
which must be calculated separately.
4. The ΔP Factors shown are subject to minimum Duct runs of 5 x Deq after Outlet Silencers and 2.5 x Deq before Inlet Silencers.
15
Sound Attenuators
Rectangular
Type RSA - Model: RSA3'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 13. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
16
Sound Attenuators
Rectangular
Type RSA - Model: RSA4'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 15. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
17
Sound Attenuators
Rectangular
Type RSA - Model: RSA5'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 17. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
18
Sound Attenuators
Rectangular
Type RSA - Model: RSA6'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 19. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
19
Sound Attenuators
Rectangular
Type RSA - Model: RSA7'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 21. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
20
Sound Attenuators
Rectangular
Type RSA - Model: RSA8'-20-10
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Table 23. Dynamic Insertion Loss (DIL) Ratings: Forward (+) / Reverse (-) Flow, dB
Octave Band 1 2 3 4 5 6 7 8
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
21
Sound Attenuators
Rectangular
Airflow Performance (Type: RSA)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Face Velocity (fpm) 350 500 625 750 875 1000 1125 1250 1375 1500 1625 1750 1875 2000
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
22
Sound Attenuators
Rectangular
Weights (Type: RSA)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Height (in) 12 12 18 21 24 12 18 20 24 28 32 36
Silencers Size
Width (mm) 300 600 600 600 600 900 900 900 900 900 900 900
Height (mm) 300 300 450 525 600 300 450 500 600 700 800 900
Silencers Length
Weight = 10%
ft mm
lbs 39 67 84 92 101 95 117 125 139 154 168 183
3' 900
kg 18 30 38 42 46 43 53 57 63 70 76 83
lbs 52 88 110 121 130 125 153 163 182 201 220 239
4' 1200
kg 24 40 50 55 59 57 70 74 83 91 100 109
lbs 64 110 136 150 171 155 190 202 228 248 272 295
5' 1500
kg 29 50 62 68 78 70 86 92 104 113 124 134
lbs 77 131 162 178 197 185 226 240 268 295 323 351
6' 1800
kg 35 60 74 81 90 84 103 109 122 134 147 160
lbs 89 152 188 207 226 215 263 279 311 342 375 407
7' 2100
kg 40 69 85 94 103 98 120 127 141 155 170 185
lbs 102 173 215 235 255 244 299 317 354 390 426 463
8' 2400
kg 46 79 98 107 116 111 136 144 161 177 194 210
Height (in) 12 18 21 24 30 36 42 48 12 18 24 30 36 42 48 54 60
Silencers Size
Width (mm) 1200 1200 1200 1200 1200 1200 1200 1200 1500 1500 1500 1500 1500 1500 1500 1500 1500
Height (mm) 300 450 525 600 750 900 1050 1200 300 450 600 750 900 1050 1200 1350 1500
Silencers Length
Silencers Weight = 10%
ft mm
lbs 123 150 164 178 205 233 261 289 150 184 217 250 283 316 350 383 540
3' 900
kg 56 68 75 81 93 106 119 131 68 84 99 114 129 143 159 174 245
lbs 161 197 215 232 269 304 340 376 198 240 283 326 369 411 454 497 663
4' 1200
kg 73 90 98 105 122 138 155 171 90 109 129 148 168 186 206 226 301
lbs 200 244 265 287 331 374 419 463 245 297 350 402 454 507 559 612 788
5' 1500
kg 91 111 120 130 150 170 190 210 111 135 159 183 206 230 254 278 358
lbs 238 290 316 342 394 446 498 550 292 354 416 478 540 602 664 726 912
6' 1800
kg 108 132 144 155 179 203 226 250 133 161 189 217 245 273 302 330 415
lbs 276 337 367 397 456 516 576 636 339 411 482 554 625 697 769 840 912
7' 2100
kg 125 153 167 180 207 235 262 289 154 187 219 252 284 316 350 382 415
lbs 315 383 417 451 519 587 655 723 386 467 549 630 711 792 873 954 1,035
8' 2400
kg 143 174 190 205 236 267 298 329 175 212 250 286 323 359 397 434 470
Forward Flow (+) / Reverse Flow (-). Aero-acoustic performance data based on NVLAP accredited
laboratory tests conducted in strict accordance with ASTM E477-06a.
23
Sound Attenuators - Materials
- Construction
Circular - Casing Thickness
Types: CASA & CBSA
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
24
Sound Attenuators - Connectors
Circular
Types: CASA & CBSA
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
100 25 x 3 130 4
125 25 x 3 155 4
∅ D ∅d 150 25 x 3 180 5
200 25 x 3 225 6
250 25 x 3 275 6
300 25 x 3 325 8
L
400 30 x 3 430 8
450 30x30x3 480 8
500 30x30x3 530 8
CIRCULAR SOUND ATTENUATOR - TYPE: CBSA
The Inlet and Outlet connections can either be Plug-Type Spigot 550 40x40x4 590 12
600 40x40x4 640 12
Or Flanged having an additional sound-absorbing pod fitted in the 700 40x40x4 740 12
center with a galvanized perforated sheet covering and coned end
to reduce pressure loss.
800 40x40x4 840 16
900 40x40x4 940 16
1000 40x40x4 1040 16
b
25
Sound Attenuators
Software Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
SOFTWARE CALCULATION
2) Duct Dimension,
5) Type of Silencer.
1- OUTPUT DATA
There are Several Options to make
selection of silencers.
26
Sound Attenuators
Software Calculation
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
SOFTWARE CALCULATION
2- OUTPUT DATA
The Selected Silencer is followed up
with data sheet containing the
following output calculations:
- Size, W/H/L
- Number of Baffles
- Gap between Baffles
- Output Noise Level
- Losses
NTS
3- OUTPUT DATA 2 Splitters with 3 equal gaps of 167mm
1200
300
27
Selection Order Form
Item Qty Duct Size (mm) Volume Flow Distance Noise Fan In Duct Sound Power Level
Reference Rate Between Level Static
Fan to 1st. Desired Pressure
Grille
Width Height Diam. CFM L/S (m) Pa 63 Hz 125 Hz 250 Hz 500 Hz 1k 2k 4k 8k
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
28
Selection Data
Sound Attenuators
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Remarks :
Selection Order Form
Item Qty Duct Size (mm) Volume Flow Distance Noise Fan
Reference Rate Between Level Static
Fan to 1st. Desired Pressure In Duct Sound Pressure Level
Grille
Width Height Diam. CFM L/S (m) Pa 63 Hz 125 Hz 250 Hz 500 Hz 1k 2k 4k 8k D (m)
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)
29
Selection Data
Sound Attenuators
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Remarks :
Sound Attenuators
Instructions For: Maintenance & Cleaning
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Duct Silencers installed inside the buildings are designed to be With the increasing global focus on environmental safety,
essentially maintenance-free for the life of the product. The same building air quality has become very important. The growing
method and routine used for periodic cleaning of the ducts will also number of lawsuits is an indication of this problem. Poor air quality
apply to the duct silencers. The acoustic media used in the duct is proven to affect the health of workers everywhere.
silencers is protected by the perforated metal liner so it will not According to environmental experts nationwide, many building
erode during normal duct cleaning with vacuum equipment. air problems begin in the ducts.
Carbon-containing dirt and moisture found in building ductwork
and air-conditioning drip pans breed bacteria and mold.
2- Duct Silencers Installed Outdoors These contaminants float throughout the air handling system in
the building. The first and least expensive step to eliminating these
Silencers exposed to the outdoors should have all external joints problems is to clean the building air handling system.
and seams caulked with suitable sealant. Wherever possible,
Silencers should be shielded from exposure to moisture from
rain or snow by providing suitable hoods, louvers or dampers.
Occasional exposure of the silencers to moisture will not affect
the longevity or the acoustical performance, provided that the water 2- Why Should we clean our Ductwork?
evaporates after exposure. If water is retained inside the silencer
module casing or baffles, premature rusting may occur. A) Human Health Concerns, Energy Management and Indoor
Environmental concerns will be addressed.
To prevent this, drain holes should be provided in the silencer
casing at all locations where water can collect. B) Allergy & Asthma sufferers can be helped.
Duct Silencers installed Outdoor should be inspected at 6-month C) Indoor cleaning can be reduced
Intervals. Silencers specified for outdoor locations require all seams D) Remove unwanted indoor pollutants; mold, fungus, bacteria
to be caulked with mastic sealant for waterproofing, and all exposed and mites.
welds to be coated with zinc-rich paint for rust proofing.
Inspect the condition of the joints and replace loose or damaged
sealant. Inspect the welds and casings for signs of rusting. Remove
visible rust using a wire brush and re-coat with zinc-rich spray paint.
30
Sound Attenuators
Tel: +974 44 500 118 - 44 500 119 - Fax: +974 44 500 117 - Doha, State Of Qatar
Remarks:
31
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)