0% found this document useful (0 votes)
62 views4 pages

SCDF Circular 20060412 - Additional Fire Safety Requiements For Super High-Rise Residential Buildings

The document outlines additional fire safety requirements for super high-rise residential buildings in Singapore, defined as those exceeding 40 storeys. Key requirements include the establishment of refuge floors at 20-storey intervals, enhanced fire lift specifications, and provisions for water-mist gun access. Compliance is mandatory for all new constructions and applicable retroactively to ongoing developments.

Uploaded by

Derek Ong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views4 pages

SCDF Circular 20060412 - Additional Fire Safety Requiements For Super High-Rise Residential Buildings

The document outlines additional fire safety requirements for super high-rise residential buildings in Singapore, defined as those exceeding 40 storeys. Key requirements include the establishment of refuge floors at 20-storey intervals, enhanced fire lift specifications, and provisions for water-mist gun access. Compliance is mandatory for all new constructions and applicable retroactively to ongoing developments.

Uploaded by

Derek Ong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Our Ref: Page 1 of 4

Our Ref: CD/FSSD/12/01/03/04 DID: 68481409


€ € FAX: 68481493
€ €
12 Apr 2006

Registrar, Board of Architects (BOA)


Registrar, Professional Engineers Board (PEB)
President, Singapore Institute of Architects (SIA)
President, Institution of Engineers, Singapore (IES)
President, Association of Consulting Engineers, Singapore (ACES)

Dear Sirs

ADDITIONAL FIRE SAFETY REQUIREMENTS FOR SUPER HIGH-RISE RESIDENTIAL


BUILDINGS

With the continuous growth of Singapore’s population, high demand for


residential properties, and the limited land space of this island nation, urban
planners and designers are pushing the limits in building height upwards. Such a
trend has begun to emerge even in our public residential developmental
programme.

2. This has given rise to greater fire safety concerns with skyscraping residential
buildings, as they pose greater difficulties in mitigating efforts required of
emergency responders as well as evacuation of the occupants. Henceforth,
residential buildings that go beyond 40 storeys will be labeled as Super High-rise
Residential Buildings. SCDF has reviewed the current Fire Code requirements and
has identified the following additional requirements that would enhance fire safety
in super high-rise residential buildings:-

a. The creation of refuge floor/holding area at 20-storey intervals.

b. Facilitate the use of water-mist gun by providing water feeding points.

c. Larger capacity fire-lift to ferry men and equipment thus facilitating


the rapid deployment in super high-rise buildings.

3. Attached are details of these additional requirements. All new super high-
rise residential buildings shall comply with these additional requirements with
immediate effect. For developments that are currently in the making, these
requirements will also be made in retrospect, as SCDF had separately conveyed
the requirements to the QPs and developers concerned.

4. Please convey the contents of this circular to members of your


Institution/Association/Board.€ The circular is also available in CORENET-e-Info:
http://www.corenet.gov.sg/einfo.
€
5. For any inquiry or clarification, please contact Ms Kwan Lian Sian at tel. no. :
68481456 or e-mail address: [email protected]
€

http://www.corenet.gov.sg/eInfo/circulars/HTMLandPDF/SCDF_2006041201.html 6/19/2006
Our Ref: Page 2 of 4

€
Yours faithfully

€(transmitted via e-mail)


€
Ding Tuen Cheng
Secretary, FSSD Standing Committee
for Commissioner
Singapore Civil Defence Force

cc
All members of FSSD Standing Committee
President, REDAS
President, IFE
President, SISV
CEO, BCA
CEO, URA
CEO, HDB
CEO, PSA
CEO, JTC
CE, LTA
CE, PSB – (Attn : Ms Tan Chiew Wan/Mr. Lau Keong Ong)
GM, SPRING Singapore – (Attn : Mr. Teo Nam Kuan)

ADDITIONAL FIRE SAFETY REQUIREMENTS FOR SUPER HIGH-RISE


RESIDENTIAL BUILDING

A. DEFINITION

1. Refuge Floor - A floor designated for holding occupants in a super high-rise


residential buildings.

2. Holding Area – A designated circulation area/space on the refuge floor for temporary
assembly of occupants during fire emergency.

3. Super High-Rise Building – Building having more than 40 storeys/levels

B. PROVISION OF REFUGE FLOOR

1. Super high-rise residential building shall be provided with at least one refuge
floor at an interval of not more than 20 storeys.

2. The refuge floor shall comply with the following requirements:

a. It shall be of masonry construction having fire resistance rating not less than
2 hours.

http://www.corenet.gov.sg/eInfo/circulars/HTMLandPDF/SCDF_2006041201.html 6/19/2006
Our Ref: Page 3 of 4

b. At least 50% of the gross floor area of the refuge floor shall be designated as
holding area.

c. There shall be no commercial activities in the holding area, however, it can


be used as space for physical exercises or children playground. All
equipment placed within the holding area shall be made / constructed of
non-combustible materials.

d. The size of the holding area shall be adequate to accommodate at least half
the total occupant load of all storeys above and below the refuge floor,
basing on 0.3m² per person.

e. The holding area shall be separated from other areas of the refuge floor by
compartment wall having fire resistance rating not less than 2 hours. Link
of the holding area with other occupied rooms/areas shall be via an external
corridor, or a smoke-stop lobby complying with Cl. 2.2.13(b) of the Fire
Code.

f. The holding area shall be naturally ventilated with permanent openings on


at least 2 sides of external walls. Height of opening shall not be less than
1200mm high and the total area of ventilation openings shall not be less than
25% of the floor area of the holding area.

g. All parts of the holding area shall be within 9m of any ventilation opening.

h. Ventilation opening shall be located at least 1.5m horizontally and 3m


vertically above adjoining unprotected openings.

i. Sprinkler system shall be provided for the refuge floor if there is any non-
residential room located on the same floor.

j. Escape routes leading to the holding area shall be through smoke-stop/fire


fighting lobby or external corridor.

k. A sign depicting “REFUGE FLOOR” shall be displayed inside the staircase


and on wall immediately outside the staircase at the refuge floor. The sign of
lettering size not less 50mm shall be displayed at a height of 1500mm above
the landing/finished floor level.

l. Emergency lighting shall be provided to cover all areas of the holding area.
Such lighting shall be connected to secondary power supply, i.e. generator,
battery, etc, and shall be able to provide a horizontal luminance at floor level
of not less than 5 lux. The delay between the failure of the electrical supply
to normal lighting and the energization of the emergency lighting for
occupied areas shall not exceed 15 seconds.

C. PROVISION OF FIRE LIFT

1. The fire lift car shall have a clear area/space of not less than 1.7m (depth) x 1.5m
(width).

2. The clear area/space (unobstructed by door swings) of fire fighting lobby shall not
be less than 6m².

http://www.corenet.gov.sg/eInfo/circulars/HTMLandPDF/SCDF_2006041201.html 6/19/2006
Our Ref: Page 4 of 4

3. Two-way voice communication system shall be provided at the fire fighting lift
lobby serving the refuge floor.

D. PROVISION OF QUICK COUPLING FOR SCDF’S WATER MIST GUN

1. At least one number of quick coupling shall be provided on every habitable floor.
The remotest point of the floor shall be within 45m of the quick coupling.

2. The quick coupling shall be connected to domestic water riser or hose-reel pipe at
the height between 1m and 1.6m and shall be located along common corridor or
within the smoke-stop/fire fighting lobby.

3. The design and installation of the quick coupling shall meet the specifications
stipulated by SCDF.