Relion® 615 series
Feeder Protection and Control
REF615
Modbus Point List Manual
Document ID: 1MRS756581
Issued: 2014-01-24
Revision: G
Product version: 5.0
© Copyright 2014 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................9
This manual........................................................................................9
Intended audience..............................................................................9
Product documentation.....................................................................10
Product documentation set..........................................................10
Document revision history...........................................................10
Related documentation................................................................11
Symbols and conventions.................................................................11
Symbols.......................................................................................11
Document conventions................................................................11
Functions, codes and symbols....................................................12
Section 2 Modbus data mappings..................................................17
Overview...........................................................................................17
Supported functions in REF615........................................................17
Indications........................................................................................20
Premapped indications................................................................20
Common data 1......................................................................20
LD0.DARREC1 AR state (1)..................................................20
LD0.LEDPTRC1 Global conditioning (1)................................21
LD0.TRPPTRC1 Protection trip conditioning (1)....................21
LD0.TRPPTRC2 Protection trip conditioning (2)....................21
LD0.CMMXU1 Phase current limit supervision (1).................21
LD0.RESCMMXU1 Residual current limit supervision
(1)...........................................................................................22
LD0.RESVMMXU1 Residual voltage limit supervision
(1)...........................................................................................22
LD0.LEDGGIO1 Indication LED states OFF/ColorX..............22
LD0.LEDGGIO1 Indication LED states Color1/Color2...........23
LD0.TCSSCBR1 Trip circuit supervision (1)..........................25
LD0.TCSSCBR2 Trip circuit supervision (2)..........................25
LD0.VMMXU1 Phase voltage limit supervision (1).................25
CTRL.DCSXSWI1 Disconnector (1) mom. position...............25
CTRL.DCSXSWI2 Disconnector (2) mom. position...............26
CTRL.DCSXSWI3 Disconnector (3) mom. position...............26
CTRL.ESSXSWI1 Earth switch (1) mom. position.................26
CTRL.CBCSWI1 Circuit breaker (1) mom. position...............26
CTRL.ESSXSWI2 Earth switch (2) mom. position.................27
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position........27
CTRL.CBCILO1 Circuit breaker (1) enable signals................27
REF615 1
Point List Manual
Table of contents
CTRL.CCBRBRF1 Circuit breaker (1) failure protection........27
CTRL.CBXCBR1 Circuit breaker (1) blocking signals............28
LD0.EFPADM1 Admittance-based earth-fault protection
(1)...........................................................................................28
LD0.EFPADM2 Admittance-based earth-fault protection
(2)...........................................................................................28
LD0.EFPADM3 Admittance-based earth-fault protection
(3)...........................................................................................29
LD0.SSCBR1 Circuit breaker (1) condition monitoring..........29
LD0.PHLPTOC1 Phase overcurrent protection low
stage (1).................................................................................29
LD0.PHHPTOC1 Phase overcurrent protection high
stage (1).................................................................................30
LD0.PHHPTOC2 Phase overcurrent protection high
stage (2).................................................................................30
LD0.PHIPTOC1 Phase overcurrent protection
instantaneous stage (1)..........................................................31
LD0.DEFLPDEF1 Directional earth-fault protection low
stage (1).................................................................................31
LD0.DEFLPDEF2 Directional earth-fault protection low
stage (2).................................................................................31
LD0.DEFHPDEF1 Directional earth-fault protection high
stage (1).................................................................................32
LD0.EFLPTOC1 Non-directional earth-fault protection
low stage (1)...........................................................................32
LD0.EFLPTOC2 Non-directional earth-fault protection
low stage (2)...........................................................................32
LD0.EFHPTOC1 Non-directional earth-fault protection
high stage (1).........................................................................32
LD0.EFIPTOC1 Non-directional earth-fault protection
instantaneous stage (1)..........................................................33
LD0.INTRPTEF1 Transient/intermittent earth-fault
protection (1)..........................................................................33
LD0.PDNSPTOC1 Phase discontinuity protection (1)............33
LD0.NSPTOC1 Negative-sequence overcurrent
protection (1)..........................................................................33
LD0.NSPTOC2 Negative-sequence overcurrent
protection (2)..........................................................................34
LD0.INRPHAR1 Three-phase inrush detection (1)................34
LD0.T1PTTR1 Thermal overload protection (1).....................34
LD0.ARCSARC1 Fault arc protection (1)...............................35
LD0.ARCSARC2 Fault arc protection (2)...............................35
LD0.ARCSARC3 Fault arc protection (3)...............................35
LD0.SEQRFUF1 Fuse failure protection (1)...........................36
CTRL.CCRDIF1 Current circuit failure detection (1)..............36
2 REF615
Point List Manual
Table of contents
LD0.DPHLPDOC1 Three-phase directional overcurrent
protection low stage (1)..........................................................36
LD0.DPHLPDOC2 Three-phase directional overcurrent
protection low stage (2)..........................................................37
LD0.DPHHPDOC1 Three-phase directional overcurrent
protection high stage (1).........................................................37
LD0.DARREC1 Autorecloser (1)............................................38
LD0.PHPTOV1 Phase overvoltage protection (1)..................39
LD0.PHPTOV2 Phase overvoltage protection (2)..................39
LD0.PHPTOV3 Phase overvoltage protection (3)..................40
LD0.PSPTUV1 Positive-sequence undervoltage
protection (1)..........................................................................40
LD0.NSPTOV1 Negative-sequence overvoltage
protection (1)..........................................................................41
LD0.PHPTUV1 Phase undervoltage protection (1)................41
LD0.PHPTUV2 Phase undervoltage protection (2)................41
LD0.PHPTUV3 Phase undervoltage protection (3)................42
LD0.ROVPTOV1 Residual overvoltage protection (1)...........42
LD0.ROVPTOV2 Residual overvoltage protection (2)...........43
LD0.ROVPTOV3 Residual overvoltage protection (3)...........43
LD0.WPWDE1 Wattmetric-based earth-fault protection
(1)...........................................................................................43
LD0.WPWDE2 Wattmetric-based earth-fault protection
(2)...........................................................................................43
LD0.WPWDE3 Wattmetric-based earth-fault protection
(3)...........................................................................................44
LD0.HAEFPTOC1 Harmonics-based earth-fault
protection (1)..........................................................................44
LD0.CMHAI1 Current total demand distortion (1)..................44
LD0.VMHAI1 Voltage total demand distortion (1)..................44
LD0.PH1QVVR1 PQ - Voltage variation signals (1)...............45
CTRL.DCXSWI1 Controllable discon. (1) mom. position
data........................................................................................45
CTRL.DCXSWI2 Controllable discon. (2) mom. position
data........................................................................................46
CTRL.ESXSWI1 Controllable earth switch (1) mom.
position...................................................................................46
LD0.XGGIO130 Physical I/O states (BIO card X130) ...........47
LD0.XGGIO120 Physical I/O states (AIM card X120)............47
LD0.XGGIO110 Physical I/O states (BIO card X110)............48
LD0.XGGIO100 Physical I/O states (PSM card X100)...........48
LD0.XAGGIO130 Physical I/O states (AIM card XA130).......49
LD0.MVGAPC1 Multipurpose binary inputs (1)......................49
LD0.MVGAPC2 Multipurpose binary inputs (2)......................50
LD0.SPCGGIO2 Multipurpose binary output states (2)..........50
REF615 3
Point List Manual
Table of contents
Indications in FE08......................................................................51
LD0.SECRSYN1 Synchrocheck (1).......................................51
LD0.FRPFRQ1 Frequency protection (1)...............................52
LD0.FRPFRQ2 Frequency protection (2)...............................52
LD0.FRPFRQ3 Frequency protection (3)...............................53
LD0.XGGIO130 Physical I/O states (BIO card X130) ...........53
LD0.XGGIO120 Physical I/O states (AIM card X120)............54
LD0.XGGIO110 Physical I/O states (BIO card X110)............54
LD0.XGGIO100 Physical I/O states (PSM card X100)...........55
LD0.XAGGIO130 Physical I/O states (AIM card XA130).......55
Unmapped indications.................................................................56
All premapped 3-phase protection function stages -
operate/phase-dependent objects added...............................56
Common data 2......................................................................56
CTRL.DCSXSWI2 Disconnector (2) mom. position...............57
CTRL.DCSXSWI3 Disconnector (3) mom. position...............57
CTRL.DCXSWI1 Controllable discon. (1) mom. position
data .......................................................................................57
CTRL.DCXSWI2 Controllable discon. (2) mom. position
data .......................................................................................58
CTRL.ESSXSWI2 Earth switch (2) mom. position.................58
CTRL.ESXSWI1 Controllable earth switch (1) mom.
position data...........................................................................59
LD0.DIAGLCCH1 Ethernet supervision (1)............................59
LD0.EFHPTOC2 Earth-fault protection high stage (2)...........59
LD0.FRPFRQ4 Frequency protection (4)...............................60
LD0.HREFPDIF1 High-impedance restricted earth-fault
detection (1)...........................................................................60
LD0.HREFPDIF2 High-impedance restricted earth-fault
detection (2)...........................................................................60
LD0.IL1TCTR1 3-phase CT supervision (1)...........................61
LD0.MAPGAPC1 Multipurpose analog protection
function (1).............................................................................61
LD0.MAPGAPC2 Multipurpose analog protection
function (2).............................................................................61
LD0.MAPGAPC3 Multipurpose analog protection
function (3).............................................................................61
LD0.MAPGAPC4 Multipurpose analog protection
function (4).............................................................................62
LD0.MAPGAPC5 Multipurpose analog protection
function (5).............................................................................62
LD0.MAPGAPC6 Multipurpose analog protection
function (6).............................................................................62
LD0.MAPGAPC7 Multipurpose analog protection
function (7).............................................................................62
4 REF615
Point List Manual
Table of contents
LD0.MAPGAPC8 Multipurpose analog protection
function (8).............................................................................63
LD0.MAPGAPC9 Multipurpose analog protection
function (9).............................................................................63
LD0.MAPGAPC10 Multipurpose analog protection
function (10)...........................................................................63
LD0.MAPGAPC11 Multipurpose analog protection
function (11)...........................................................................63
LD0.MAPGAPC12 Multipurpose analog protection
function (12)...........................................................................64
LD0.MAPGAPC13 Multipurpose analog protection
function (13)...........................................................................64
LD0.MAPGAPC14 Multipurpose analog protection
function (14)...........................................................................64
LD0.MAPGAPC15 Multipurpose analog protection
function (15)...........................................................................64
LD0.MAPGAPC16 Multipurpose analog protection
function (16)...........................................................................65
LD0.MAPGAPC17 Multipurpose analog protection
function (17)...........................................................................65
LD0.MAPGAPC18 Multipurpose analog protection
function (18)...........................................................................65
LD0.MDSOPT1 Generic operation time supervision (1)........65
LD0.MVGAPC1 Multipurpose binary inputs, MOM-only
or latch use (1).......................................................................66
LD0.MVGAPC2 Multipurpose binary inputs, MOM-only
or latch use (2).......................................................................66
LD0.PHIZ1 High impedance fault detection (1)......................67
LD0.PHLPTOC2 Phase overcurrent protection low
stage (2).................................................................................67
LD0.RESTCTR1 Io CT supervision (1)..................................68
LD0.RESTCTR2 Io CT supervision (2)..................................68
LD0.RESTVTR1 Uo VT supervision (1).................................68
LD0.SCERFLO1 Fault locator (1)...........................................68
LD0.SPCGGIO1 Multipurpose binary output states (1)..........69
LD0.TRPPTRC3 Protection trip conditioning (3)....................70
LD0.TRPPTRC4 Protection trip conditioning (4)....................70
LD0.TRPPTRC5 Protection trip conditioning (5)....................70
LD0.UL1TVTR1 3-phase VT supervision (1)..........................70
LD0.UL1TVTR2 3-phase VT supervision (2)..........................71
LD0.VMMXU2 Phase voltage limit supervision (2).................71
LD0.XARGGIO130 Alarm/warning.........................................71
LD0.XRGGIO130 Alarm/warning...........................................72
Registers..........................................................................................72
Premapped registers...................................................................72
REF615 5
Point List Manual
Table of contents
User definable registers [Alt.1], visible on 3x and 4x..............72
User definable bits [Alt.2], visible on 0x,1x,3x and 4x............73
SSR1 System status register (1) device health......................73
SSR2 System status register (2) IED mode and state...........74
SSR3 System status register (3) data available 1 (client-
dependent).............................................................................74
SSR4 System status register (4) data available 2 (client-
dependent - user-definable)...................................................75
SSR5 System status register (5) device alive register...........75
SSR6 System status register (6) control command
status (client-dependent)........................................................76
LD0.DARREC1 Autorecloser values (1).................................76
LD0.CMMXU1 Phase current measurements (1) ..................77
LD0.RESCMMXU1 Residual current measurement (1) ........77
LD0.RESVMMXU1 Residual voltage measurement (1) ........77
LD0.CMSQI1 Sequence of current measurements (1) .........77
LD0.T1PTTR1 Thermal protection values (1)........................78
LD0.HAEFMHAI1 Current harmonics (1) ..............................78
LD0.VMMXU1 Voltage measurements (1) ............................78
LD0.VMSQI1 Sequence of voltage measurements (1) .........79
LD0.PEMMXU1 Three-phase power measurements (1)........79
LD0.FMMXU1 Frequency measurement (1)..........................79
LD0.SECRSYN1 Synchrocheck (1).......................................79
Indication bits mirrored in registers........................................80
LD0.PEMSTA1 Power measurement demand values
(1) ..........................................................................................80
LD0.VMSTA1 Voltage demand values (1) ............................80
LD0.RESVMSTA1 Residual voltage demand value (1) ........81
LD0.RESCMSTA1 Residual current demand value (1) .........82
LD0.CMSTA1 Phase current demand values (1) ..................82
CTRL.CBCSWI1 Circuit breaker operation counter (1) .........83
LD0.ARCSARCx1 Fault arc counters ....................................83
LD0.DARREC1 Autorecloser counters (1).............................84
LD0.PEMMTR1 Three-phase energy measurements
(1)...........................................................................................84
System diagnostic values.......................................................85
LD0.SSCBR1 Circuit-breaker condition monitoring
values (1)................................................................................85
LD0.PH1QVVR1 Short duration voltage variations (1)...........85
LD0.CMHAI1 Current total demand distortion (1)..................86
LD0.VMHAI1 Voltage total demand distortion (1)..................87
Active parameter setting group - read and write....................87
Control structure 1..................................................................88
Control structure 2..................................................................88
6 REF615
Point List Manual
Table of contents
Control structure 3..................................................................88
Control structure 4..................................................................88
Control structure 5..................................................................89
Control structure 6..................................................................89
Control structure 7..................................................................89
Control structure 8..................................................................89
Device ID string......................................................................90
IED Real-time clock (in local time mode) - read and
write (synchronize).................................................................90
IED real-time clock (in UTC time mode) - read and write
(synchronize)..........................................................................90
Time and reason for latest IED reset......................................91
Event record structure............................................................91
Fault record structure header.................................................95
Fault record data....................................................................96
Unmapped registers....................................................................97
LD0.MDSOPT1 Generic operation time supervision (1)........97
LD0.MVI4GAPC1 Multipurpose analog values (1).................97
LD0.SCA4GAPC1 Multipurpose analog values (1)................98
LD0.SCERFLO1 Fault locator (1)...........................................98
LD0.VMMXU2 Voltage measurements (2).............................98
LD0.XARGGIO130 RTD input values....................................99
Controls............................................................................................99
CTRL.CBCSWI1 Circuit breaker (1) control................................99
Reset, acknowledge and trigger points (A)................................100
LD0.LPHD1 IED warm reset (1)................................................101
LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops..................101
LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops..................101
LD0.SPCGGIO1 Multipurpose binary outputs (1) .....................101
LD0.SPCGGIO2 Multipurpose binary outputs (2) .....................102
CTRL.DCCSWI1 Disconnector (1) control................................103
CTRL.DCCSWI2 Disconnector (2) control................................103
CTRL.ESCSWI1 Earth switch (1) control..................................104
Section 3 Glossary.......................................................................105
REF615 7
Point List Manual
8
1MRS756581 G Section 1
Introduction
Section 1 Introduction
1.1 This manual
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
REF615 9
Point List Manual
Section 1 1MRS756581 G
Introduction
1.3 Product documentation
1.3.1 Product documentation set
deinstallation & disposal
Decommissioning,
Commissioning
Maintenance
Engineering
Planning &
Installation
Operation
Quick start guide purchase
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual c
Communication protocol manual c
IEC 61850 Engineering guide
Point list manual
GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V1 EN
Figure 1: The intended use of documents during the product life cycle
Product series- and product-specific manuals can be downloaded
from the ABB Website http://www.abb.com/relion.
1.3.2 Document revision history
Document revision/date Product version History
A/2008-07-02 1.1 First release
B/2009-03-04 2.0 Content updated to correspond to the
product version
C/2009-07-03 2.0 Content updated
D/2010-06-11 3.0 Content updated to correspond to the
product version
E/2012-05-11 4.0 Content updated to correspond to the
product version
F/2013-02-21 4.0 FP1 Content updated to correspond to the
product version
G/2014-01-24 5.0 Content updated to correspond to the
product version
10 REF615
Point List Manual
1MRS756581 G Section 1
Introduction
Download the latest documents from the ABB Website
http://www.abb.com/substationautomation.
1.3.3 Related documentation
Name of the document Document ID
Modbus Communication Protocol Manual 1MRS756468
1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons.
To navigate between the options, use and .
• Menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
REF615 11
Point List Manual
Section 1 1MRS756581 G
Introduction
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
• This document assumes that the parameter setting visibility is "Advanced".
1.4.3 Functions, codes and symbols
Table 1: Functions included in the IED
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage
PHLPTOC2 3I> (2) 51P-1 (2)
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage
PHHPTOC2 3I>> (2) 51P-2 (2)
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage
Three-phase directional overcurrent protection, DPHLPDOC1 3I> -> (1) 67-1 (1)
low stage
DPHLPDOC2 3I> -> (2) 67-1 (2)
Three-phase directional overcurrent protection,
DPHHPDOC1 3I>> -> (1) 67-2 (1)
high stage
Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)
EFLPTOC2 Io> (2) 51N-1 (2)
Non-directional earth-fault protection, high stage EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earth-fault protection,
EFIPTOC1 Io>>> (1) 50N/51N (1)
instantaneous stage
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
DEFLPDEF2 Io> -> (2) 67N-1 (2)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Admittance based earth-fault protection1) EFPADM1 Yo> -> (1) 21YN (1)
EFPADM2 Yo> -> (2) 21YN (2)
EFPADM3 Yo> -> (3) 21YN (3)
Wattmetric based earth-fault protection1) WPWDE1 Po> -> (1) 32N (1)
WPWDE2 Po> -> (2) 32N (2)
WPWDE3 Po> -> (3) 32N (3)
Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
Harmonics based earth-fault protection1) HAEFPTOC1 Io>HA (1) 51NHA (1)
Non-directional (cross-country) earth-fault
EFHPTOC1 Io>> (1) 51N-2 (1)
protection, using calculated Io
Table continues on next page
12 REF615
Point List Manual
1MRS756581 G Section 1
Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46 (1)
NSPTOC2 I2> (2) 46 (2)
Phase discontinuity protection PDNSPTOC1 I2/I1> (1) 46PD (1)
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)
ROVPTOV2 Uo> (2) 59G (2)
ROVPTOV3 Uo> (3) 59G (3)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
PHPTUV2 3U< (2) 27 (2)
PHPTUV3 3U< (3) 27 (3)
Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)
PHPTOV2 3U> (2) 59 (2)
PHPTOV3 3U> (3) 59 (3)
Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)
FRPFRQ2 f>/f<,df/dt (2) 81 (2)
FRPFRQ3 f>/f<,df/dt (3) 81 (3)
FRPFRQ4 f>/f<,df/dt (4) 81 (4)
Three-phase thermal protection for feeders,
T1PTTR1 3Ith>F (1) 49F (1)
cables and distribution transformers
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> (1) 87NH (1)
protection
51BF/51NBF
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1)
(1)
Three-phase inrush detector INRPHAR1 3I2f> (1) 68 (1)
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
TRPPTRC2 Master Trip (2) 94/86 (2)
TRPPTRC3 Master Trip (3) 94/86 (3)
TRPPTRC4 Master Trip (4) 94/86 (4)
TRPPTRC5 Master Trip (5) 94/86 (5)
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Table continues on next page
REF615 13
Point List Manual
Section 1 1MRS756581 G
Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Multi-purpose protection2) MAPGAPC1 MAP (1) MAP (1)
MAPGAPC2 MAP (2) MAP (2)
MAPGAPC3 MAP (3) MAP (3)
MAPGAPC4 MAP (4) MAP (4)
MAPGAPC5 MAP (5) MAP (5)
MAPGAPC6 MAP (6) MAP (6)
MAPGAPC7 MAP (7) MAP (7)
MAPGAPC8 MAP (8) MAP (8)
MAPGAPC9 MAP (9) MAP (9)
MAPGAPC10 MAP (10) MAP (10)
MAPGAPC11 MAP (11) MAP (11)
MAPGAPC12 MAP (12) MAP (12)
MAPGAPC13 MAP (13) MAP (13)
MAPGAPC14 MAP (14) MAP (14)
MAPGAPC15 MAP (15) MAP (15)
MAPGAPC16 MAP (16) MAP (16)
MAPGAPC17 MAP (17) MAP (17)
MAPGAPC18 MAP (18) MAP (18)
Fault locator SCEFRFLO1 FLOC (1) 21FL (1)
High impedance fault detection PHIZ1 HIF (1) HIZ (1)
Power quality
Current total demand distortion CMHAI1 PQM3I (1) PQM3I (1)
Voltage total harmonic distortion VMHAI1 PQM3U (1) PQM3V (1)
Voltage variation PHQVVR1 PQMU (1) PQMV (1)
Control
Circuit-breaker control CBXCBR1 I <-> O CB (1) I <-> O CB (1)
Disconnector control I <-> O DCC
DCXSWI1 I <-> O DCC (1)
(1)
I <-> O DCC
DCXSWI2 I <-> O DCC (2)
(2)
Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1)
Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Auto-reclosing DARREC1 O -> I (1) 79 (1)
Synchronism and energizing check SECRSYN1 SYNC (1) 25 (1)
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM (1) CBCM (1)
Table continues on next page
14 REF615
Point List Manual
1MRS756581 G Section 1
Introduction
Function IEC 61850 IEC 60617 IEC-ANSI
Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)
TCSSCBR2 TCS (2) TCM (2)
Current circuit supervision CCRDIF1 MCS 3I (1) MCS 3I (1)
Fuse failure supervision SEQRFUF1 FUSEF (1) 60 (1)
Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1)
Measurement
Disturbance recorder RDRE1 DR (1) DFR (1)
LOADPROF LOADPROF
Load profile record LDPMSTA1
(1) (1)
Three-phase current measurement CMMXU1 3I (1) 3I (1)
Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)
Residual current measurement RESCMMXU1 Io (1) In (1)
RESCMMXU2 Io (2) In (2)
Three-phase voltage measurement VMMXU1 3U (1) 3V (1)
VMMXU2 3U (2) 3V (2)
Residual voltage measurement RESVMMXU1 Uo (1) Vn (1)
Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)
Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1)
X130 (RTD)
RTD/mA measurement XRGGIO130 X130 (RTD) (1)
(1)
Frequency measurement FMMXU1 f (1) f (1)
IEC 61850-9-2 LE (Voltage sharing)3) SMVSENDER SMVSENDER SMVSENDER
1) One of the following can be ordered as an option: Admittance based E/F, Wattmetric based E/F or
Harmonics based E/F. The option is an addition to the existing E/F of the original configuration. The
optional E/F has also a predefined configuration in the IED. The optional E/F can be set on or off.
2) For example, used for RTD/mA based protection or analog GOOSE
3) Only available with redundant Ethernet communication modules
REF615 15
Point List Manual
16
1MRS756581 G Section 2
Modbus data mappings
Section 2 Modbus data mappings
2.1 Overview
This document describes the Modbus data points and structures available in the
IED. The point lists describe a superset of all data available through the standard
configuration/s including the optional functionalities.
The majority of the Modbus data points are valid for all standard configurations.
Some data points are standard configuration-dependent or optional application-
dependent and thus not available in each IED. The unavailable, that means, unused,
data points always return value 0 when they are read. The configuration-dependent
and optional data do not overlap.
2.2 Supported functions in REF615
Table 2: Supported functions
Function IEC 61850 A B C D E F G H J K L N
FE01 FE02 FE03 FE04 FE05 FE06 FE07 FE08 FE09 FE10 FE11 FE12
Protection1)
Three-phase non-
directional overcurrent PHLPTOC 1 1 1 1 1 1 1 2
protection, low stage
Three-phase non-
directional overcurrent PHHPTOC 2 2 2 2 2 2 1 1
protection, high stage
Three-phase non-
directional overcurrent
PHIPTOC 1 1 1 1 1 1 1 1 1 1 1 1
protection, instantaneous
stage
Three-phase directional
overcurrent protection, low DPHLPDOC 2 2 2 1 2 2
stage
Three-phase directional
overcurrent protection, high DPHHPDOC 1 1 1 1 1 1
stage
Non-directional earth-fault
EFLPTOC 2 2) 2 2) 2 2) 2 2) 2 2)
protection, low stage
Non-directional earth-fault
EFHPTOC 1 2) 1 2) 1 2) 1 2) 1 2)
protection, high stage
Non-directional earth-fault
protection, instantaneous EFIPTOC 1 2) 1 2) 1 2) 1 2) 1 2)
stage
Directional earth-fault
DEFLPDEF 2 2)3) 2 2)3) 2 2)4) 2 2)4) 2 2)5) 2 2)4) 1 2)4) 2 6)7) 2 2)4)
protection, low stage
Directional earth-fault
DEFHPDEF 1 2)3) 1 2)3) 1 2)4) 1 2)4) 1 2)5) 1 2)4) 1 2)4) 1 2)7) 1 2)4)
protection, high stage
Admittance-based earth- (3) (3) (3) (3) (3) (3) (3) (3)
EFPADM
fault protection 8) 2)3)8) 2)3)8) 2)4)8) 2)4)8) 2)7)8) 2)4)8) 2)7)8) 2)4)8)
Table continues on next page
REF615 17
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
Function IEC 61850 A B C D E F G H J K L N
FE01 FE02 FE03 FE04 FE05 FE06 FE07 FE08 FE09 FE10 FE11 FE12
Wattmetric-based earth- (3) (3) (3) (3) (3) (3) (3) (3)
WPWDE
fault protection 8) 2)3)8) 2)3)8) 2)4)8) 2)4)8) 2)7)8) 2)4)8) 2)7)8) 2)4)8)
Transient/intermittent earth-
INTRPTEF 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 4)9) 1 7)9) 1 4)9)
fault protection
Harmonics-based earth- (1) (1) (1) (1) (1) (1)
HAEFPTOC
fault protection 8) 8)9) 8)9) 8)9) 8)9) 8)9) 8)9)
Non-directional (cross-
country) earth-fault
EFHPTOC 1 6) 1 6) 1 6) 1 6) 1 6) 1 6) 1 6)
protection, using calculated
Io
Negative-sequence
NSPTOC 2 2 2 2 2 2 2 2 2 2 2 2
overcurrent protection
Phase discontinuity
PDNSPTOC 1 1 1 1 1 1 1 1 1 1 1
protection
Residual overvoltage
ROVPTOV 3 3) 3 3) 3 4) 3 4) 3 7) 3 4) 34) 2 4) 3 7) 3 4)
protection
Three-phase undervoltage
PHPTUV 3 3 3 3 2 3 3
protection
Three-phase overvoltage
PHPTOV 3 3 3 3 2 3 3
protection
Positive-sequence
PSPTUV 1 1 1 1 1
undervoltage protection
Negative-sequence
NSPTOV 1 1 1 1 1
overvoltage protection
Frequency protection FRPFRQ 3 3 3 4 4
Three-phase thermal
protection for feeders,
T1PTTR 1 1 1 1 1 1 1 1 1 1 1
cables and distribution
transformers
High impedance-based
restricted earth-fault HREFPDIF 1 10)
protection
Circuit breaker failure
CCBRBRF 1 1 1 1 1 1 1 1 1 1 1 1
protection
Three-phase inrush
INRPHAR 1 1 1 1 1 1 1 1 1 1 1 1
detector
2(5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5) 2 (5)
Master trip TRPPTRC 2 11) 2 11) 11) 11) 11) 11) 11) 11) 11) 11)
Arc protection ARCSARC (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) (3)
Multi-purpose protection 12) MAPGAPC 18 18 18 18 18 18 18 18 18 18 18 18
Fault locator SCEFRFLO (1) (1) (1)
High impedance fault
PHIZ 1 1 1 1 1 1 1
detection
Power quality
Current total demand
CMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage total harmonic
VMHAI (1) 13) (1) 13) (1) 13) (1) 13)
distortion
Voltage variation PHQVVR (1) 13) (1) 13) (1) 13) (1) 13)
Control
Circuit-breaker control CBXCBR 1 1 1 1 1 1 1 1 1 1 1 1
Disconnector control DCXSWI 2 2 2 2 2 2 2 2 2 2
Earthing switch control ESXSWI 1 1 1 1 1 1 1 1 1 1
Disconnector position
DCSXSWI 3 3 3 3 3 3 3 3 3 3
indication
Earthing switch indication ESSXSWI 2 2 2 2 2 2 2 2 2 2
Autoreclosing DARREC (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1)
Synchronism and
SECRSYN 1 1 1 1
energizing check
Table continues on next page
18 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
Function IEC 61850 A B C D E F G H J K L N
FE01 FE02 FE03 FE04 FE05 FE06 FE07 FE08 FE09 FE10 FE11 FE12
Condition monitoring
Circuit-breaker condition
SSCBR 1 1 1 1 1 1 1 1 1 1
monitoring
Trip circuit supervision TCSSCBR 2 2 2 2 2 2 2 2 2 2 2 2
Current circuit supervision CCRDIF 1 1 1 1 1 1 1 1
Fuse failure supervision SEQRFUF 1 1 1 1 1 1 1 1
Runtime counter for
MDSOPT 1 1 1 1 1 1 1 1 1 1 1 1
machines and devices
Measurement
Disturbance recorder RDRE 1 1 1 1 1 1 1 1 1 1 1 1
Load profile record LDPMSTA 1 1 1 1 1 1 1 1 1 1
Three-phase current
CMMXU 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Sequence current
CSMSQI 1 1 1 1 1 1 1 1 1 1 1 1
measurement
Residual current
RESCMMXU 1 1 1 1 1 1 1 1 1 2 1 1
measurement
Three-phase voltage
VMMXU 1 1 1 2 2 2 1 2
measurement
Residual voltage
RESVMMXU 1 1 1 1 1 1 1 1
measurement
Sequence voltage
VSMSQI 1 1 1 1 1 1 1 1
measurement
Three-phase power and
PEMMXU 1 1 1 1 1 1 1 1
energy measurement
RTD/mA measurement XRGGIO130 (1) (1) (1) (1) (1) (1) (1)
Frequency measurement FMMXU 1 1 1 1 1 1 1 1
IEC 61850-9-2 LE (Voltage
(1) (1) (1) (1) (1) (1) (1) (1)
sharing) 14)
1, 2, ... = number of included instances
() = optional
1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
2) Io selectable by parameter, “Io measured” as default
3) “Uo measured” is always used.
4) Uo selectable by parameter, "Uo measured" as default
5) Uo calculated and negative sequence voltage selectable by parameter, “Uo calculated” as default
6) Io selectable by parameter, “Io calculated” as default
7) “Uo calculated” is always used.
8) One of the following can be ordered as an option: admittance-based E/F, wattmetric-based E/F or harmonics-based E/F. The option is
an addition to the existing E/F of the original configuration. The optional E/F has also a predefined configuration in the IED. The optional
E/F can be set on or off.
9) “Io measured” is always used.
10) “IoB measured” is always used.
11) Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC
option is selected additionally, ARCSARC is connected to the corresponding master trip input in the configuration.
12) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
13) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
14) Only available with COM0031-COM0034
REF615 19
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3 Indications
Table 3: Explanations of the indications table columns
Column name Description
BitA Default 0X and 1X bit address for the data.
RegA Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850 Original IED data object identification. Described in the IEC 61850 format as
name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the value states.
2.3.1 Premapped indications
2.3.1.1 Common data 1
Table 4: Common data 1
BitA RegA IEC 61850 name SA name Description Values
CTRL.LLN0
2720 170.00 .Loc.stVal - Remote/Local state 0/1=Rem/Loc
2721 170.01 .LocRem.stVal.Station - Station state 1=Station
DR.RDRE1
2722 170.02 .RcdMade.stVal - DR recording made 1=Made
2723 170.03 .mcd
LD0.LLN0
2726 170.06 .SetSeld.stVal Settings reserved 1=Reserved
2727 170.07 .mcd
2728 170.08 .SetChg.stVal Settings changed 1=Changed
2729 170.09 .mcd
2.3.1.2 LD0.DARREC1 AR state (1)
Table 5: LD0.DARREC1 AR state (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DARREC1
2724 170.04 .AROn.stVal AR_ON AutoRecloser state 0/1=Off/On
20 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.3 LD0.LEDPTRC1 Global conditioning (1)
Table 6: LD0.LEDPTRC1 Global conditioning (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.LEDPTRC1
2736 171.00 .Str.general - Global start 1=Start
2737 171.01 .mcd
2738 171.02 .Op.general - Global operate 1=Operate
2739 171.03 .mcd
2.3.1.4 LD0.TRPPTRC1 Protection trip conditioning (1)
Table 7: LD0.TRPPTRC1 Protection trip conditioning (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC1
2740 171.04 .Op.general - Op.Input signal 1=Operate
2741 171.05 .mcd
2742 171.06 .Tr.general - Trip output signal 1=Trip
2743 171.07 .mcd
2.3.1.5 LD0.TRPPTRC2 Protection trip conditioning (2)
Table 8: LD0.TRPPTRC2 Protection trip conditioning (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC2
2744 171.08 .Op.general - Op.Input signal 1=Operate
2745 171.09 .mcd
2746 171.10 .Tr.general - Trip output signal 1=Trip
2747 171.11 .mcd
2.3.1.6 LD0.CMMXU1 Phase current limit supervision (1)
Table 9: LD0.CMMXU1 Phase current limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.CMMXU1
2752 172.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2753 172.01 .mcd
2754 172.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2755 172.03 .mcd
2756 172.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
Table continues on next page
REF615 21
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
2757 172.05 .mcd
2758 172.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2759 172.07 .mcd
2.3.1.7 LD0.RESCMMXU1 Residual current limit supervision (1)
Table 10: LD0.RESCMMXU1 Residual current limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESCMMXU1
2760 172.08 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2761 172.09 .mcd
2762 172.10 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2763 172.11 .mcd
2.3.1.8 LD0.RESVMMXU1 Residual voltage limit supervision (1)
Table 11: LD0.RESVMMXU1 Residual voltage limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESVMMXU1
2764 172.12 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2765 172.13 .mcd
2766 172.14 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2767 172.15 .mcd
2.3.1.9 LD0.LEDGGIO1 Indication LED states OFF/ColorX
These LED indication points interpret the case when an indication signal is wired
to either the OK or ALARM input of the LED function block. The default color for
ALARM is red and green for OK. Colors can, however, be reconfigured with a
setting parameter.
22 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
LEDx
Signal
OK
ALARM
RESET
LEDx
OK
Signal
ALARM
RESET
GUID-775477F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN
Figure 2: Signal wired to either OK or Alarm input
Table 12: LD0.LEDGGIO1 Indication LED states OFF/ColorX
BitA RegA IEC 61850 name SA name Description Values
LD0.LEDGGIO1
2768 173.00 .ISCSO1.stVal - LED 1 state 0/1=Off/Color
2769 173.01 .ISCSO2.stVal - LED 2 state 0/1=Off/Color
2770 173.02 .ISCSO3.stVal - LED 3 state 0/1=Off/Color
2771 173.03 .ISCSO4.stVal - LED 4 state 0/1=Off/Color
2772 173.04 .ISCSO5.stVal - LED 5 state 0/1=Off/Color
2773 173.05 .ISCSO6.stVal - LED 6 state 0/1=Off/Color
2774 173.06 .ISCSO7.stVal - LED 7 state 0/1=Off/Color
2775 173.07 .ISCSO8.stVal - LED 8 state 0/1=Off/Color
2776 173.08 .ISCSO9.stVal - LED 9 state 0/1=Off/Color
2777 173.09 .ISCSO10.stVal - LED 10 state 0/1=Off/Color
2778 173.10 .ISCSO11.stVal - LED 11 state 0/1=Off/Color
2779 173.11 <reserved> 0
2.3.1.10 LD0.LEDGGIO1 Indication LED states Color1/Color2
These LED indication points interpret the case when a signal is wired to both the
OK and ALARM inputs, but inverted to the other. This means that the LED toggles
between red and green colors. The default color for ALARM is red and green for
OK. Colors can, however, be reconfigured with a setting parameter.
REF615 23
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
LEDx
Signal
OK
ALARM
RESET
NOT
GUID-2AE4D47A-2BBD-4422-A81C-CF2EB7473379 V1 EN
Figure 3: Signal wired to both OK and ALARM inputs – inverted to the other
If the OK and ALARM inputs are wired to separate indication
signals, the LED will have three legal states and cannot be
expressed with one bit only. In this case, it is possible to combine
this LED bit interpretation with the corresponding value from the
other LED state interpretation.
LEDx
Signal 1
OK
Signal 2
ALARM
RESET
GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN
Figure 4: Separate signals wired to OK and ALARM inputs
Table 13: LD0.LEDGGIO1 Indication LED states Color1/Color2
BitA RegA IEC 61850 name SA name Description Values
LD0.LEDGGIO1
3520 220.00 .ISCSO1.stVal - LED 1 state 0/1=Color1/2
3521 220.01 .ISCSO2.stVal - LED 2 state 0/1=Color1/2
3522 220.02 .ISCSO3.stVal - LED 3 state 0/1=Color1/2
3523 220.03 .ISCSO4.stVal - LED 4 state 0/1=Color1/2
3524 220.04 .ISCSO5.stVal - LED 5 state 0/1=Color1/2
3525 220.05 .ISCSO6.stVal - LED 6 state 0/1=Color1/2
3526 220.06 .ISCSO7.stVal - LED 7 state 0/1=Color1/2
3527 220.07 .ISCSO8.stVal - LED 8 state 0/1=Color1/2
3528 220.08 .ISCSO9.stVal - LED 9 state 0/1=Color1/2
3529 220.09 .ISCSO10.stVal - LED 10 state 0/1=Color1/2
3530 220.10 .ISCSO11.stVal - LED 11 state 0/1=Color1/2
3531 220.11 <reserved> 0
24 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.11 LD0.TCSSCBR1 Trip circuit supervision (1)
Table 14: LD0.TCSSCBR1 Trip circuit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR1
2780 173.12 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2781 173.13 .mcd
2.3.1.12 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 15: LD0.TCSSCBR2 Trip circuit supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR2
2782 173.14 .CirAlm.stVal ALARM Supervision alarm 1=Alarm
2783 173.15 .mcd
2.3.1.13 LD0.VMMXU1 Phase voltage limit supervision (1)
Table 16: LD0.VMMXU1 Phase voltage limit supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.VMMXU1
2784 174.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2785 174.01 .mcd
2786 174.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2787 174.03 .mcd
2788 174.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2789 174.05 .mcd
2790 174.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2791 174.07 .mcd
2.3.1.14 CTRL.DCSXSWI1 Disconnector (1) mom. position
Table 17: CTRL.DCSXSWI1 Disconnector (1) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI1 POSITION
2792 174.08 .Pos.stVal.Close - Close bit 1=Close
2793 174.09 .Pos.stVal.Open - Open bit 1=Open
2794 174.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
REF615 25
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.15 CTRL.DCSXSWI2 Disconnector (2) mom. position
Table 18: CTRL.DCSXSWI2 Disconnector (2) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI2 POSITION
2795 174.11 .Pos.stVal.Close - Close bit 1=Close
2796 174.12 .Pos.stVal.Open - Open bit 1=Open
2797 174.13 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.16 CTRL.DCSXSWI3 Disconnector (3) mom. position
Table 19: CTRL.DCSXSWI3 Disconnector (3) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI3 POSITION
2798 174.14 .Pos.stVal.Close - Close bit 1=Close
2799 174.15 .Pos.stVal.Open - Open bit 1=Open
2800 175.00 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.17 CTRL.ESSXSWI1 Earth switch (1) mom. position
Table 20: CTRL.ESSXSWI1 Earth switch (1) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI1 POSITION
2801 175.01 .Pos.stVal.Close - Close bit 1=Close
2802 175.02 .Pos.stVal.Open - Open bit 1=Open
2803 175.03 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.18 CTRL.CBCSWI1 Circuit breaker (1) mom. position
Table 21: CTRL.CBCSWI1 Circuit breaker (1) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2804 175.04 .Pos.stVal.Close - Close bit 1=Close
2805 175.05 .Pos.stVal.Open - Open bit 1=Open
2806 175.06 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
26 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.19 CTRL.ESSXSWI2 Earth switch (2) mom. position
Table 22: CTRL.ESSXSWI2 Earth switch (2) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI2 POSITION
2807 175.07 .Pos.stVal.Close - Close bit 1=Close
2808 175.08 .Pos.stVal.Open - Open bit 1=Open
2809 175.09 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
2.3.1.20 CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
Table 23: CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCSWI1 POSITION
2816 176.00 .Pos.stVal.Close Close bit 1=Close
2817 176.01 .mcd
2818 176.02 .Pos.stVal.Open Open bit 1=Open
2819 176.03 .mcd
2820 176.04 < reserved >
2821 176.05 < reserved >
2822 176.06 .Pos.stSeld SELECTED CB selected for control 1=Selected
2823 176.07 .mcd
2.3.1.21 CTRL.CBCILO1 Circuit breaker (1) enable signals
Table 24: CTRL.CBCILO1 Circuit breaker (1) enable signals
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBCILO1
2824 176.08 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
2825 176.09 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
2.3.1.22 CTRL.CCBRBRF1 Circuit breaker (1) failure protection
Table 25: CTRL.CCBRBRF1 Circuit breaker (1) failure protection
BitA RegA IEC 61850 name SA name Description Values
CTRL.CCBRBRF1
2828 176.12 .Str.general CB_FAULT_AL Timer running 1=Running
2829 176.13 .mcd
2830 176.14 .OpEx.general TRBU Fail, external trip 1=Ext.trip
Table continues on next page
REF615 27
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
2831 176.15 .mcd
2832 177.00 .OpIn.general TRRET Internal re-trip 1=Re-trip
2833 177.01 .mcd
2.3.1.23 CTRL.CBXCBR1 Circuit breaker (1) blocking signals
Table 26: CTRL.CBXCBR1 Circuit breaker (1) blocking signals
BitA RegA IEC 61850 name SA name Description Values
CTRL.CBXCBR1
2834 177.02 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
2835 177.03 .mcd
2836 177.04 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2837 177.05 .mcd
2838 177.06 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
2839 177.07 .mcd
2.3.1.24 LD0.EFPADM1 Admittance-based earth-fault protection (1)
Table 27: LD0.EFPADM1 Admittance-based earth-fault protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFPADM1
2840 177.08 .Str.general START Stage start 1=Start
2841 177.09 .mcd
2842 177.10 .Op.general OPERATE Stage operate 1=Operate
2843 177.11 .mcd
2.3.1.25 LD0.EFPADM2 Admittance-based earth-fault protection (2)
Table 28: LD0.EFPADM2 Admittance-based earth-fault protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFPADM2
2844 177.12 .Str.general START Stage start 1=Start
2845 177.13 .mcd
2846 177.14 .Op.general OPERATE Stage operate 1=Operate
2847 177.15 .mcd
28 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.26 LD0.EFPADM3 Admittance-based earth-fault protection (3)
Table 29: LD0.EFPADM3 Admittance-based earth-fault protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFPADM3
2860 178.12 .Str.general START Stage start 1=Start
2861 178.13 .mcd
2862 178.14 .Op.general OPERATE Stage operate 1=Operate
2863 178.15 .mcd
2.3.1.27 LD0.SSCBR1 Circuit breaker (1) condition monitoring
Table 30: LD0.SSCBR1 Circuit breaker (1) condition monitoring
BitA RegA IEC 61850 name SA name Description Values
LD0.SSCBR1
2848 178.00 .OpnAlm.stVal TRV_T_OP_ALM Opn travel time alarm 1=Alarm
2849 178.01 .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
2850 178.02 .SprChaAlm.stVal SPR_CHR_ALM Spring charge alarm 1=Alarm
2851 178.03 .OpNumAlm.stVal OPR_ALM CB operations alarm 1=Alarm
2852 178.04 .OpNumLO.stVal OPR_LO CB operations lockout 1=Lockout
2853 178.05 .LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
2854 178.06 .PresAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
2855 178.07 .PresLO.stVal PRES_LO Low pressure lockout 1=Lockout
2856 178.08 .APwrAlm.stVal IPOW_ALM Lyt alarm 1=Alarm
2857 178.09 .APwrLO.stVal IPOW_LO Lyt lockout 1=Lockout
2858 178.10 .CBLifAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
2.3.1.28 LD0.PHLPTOC1 Phase overcurrent protection low stage (1)
Table 31: LD0.PHLPTOC1 Phase overcurrent protection low stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHLPTOC1
2880 180.00 .Str.general START General start 1=Start
2881 180.01 .mcd
2882 180.02 .Str.phsA phsA start 1=Start
2883 180.03 .mcd
2884 180.04 .Str.phsB phsB start 1=Start
2885 180.05 .mcd
2886 180.06 .Str.phsC phsC start 1=Start
Table continues on next page
REF615 29
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
2887 180.07 .mcd
2888 180.08 .Op.general OPERATE General operate 1=Operate
2889 180.09 .mcd
2.3.1.29 LD0.PHHPTOC1 Phase overcurrent protection high stage (1)
Table 32: LD0.PHHPTOC1 Phase overcurrent protection high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC1
2890 180.10 .Str.general START General start 1=Start
2891 180.11 .mcd
2892 180.12 .Str.phsA phsA start 1=Start
2893 180.13 .mcd
2894 180.14 .Str.phsB phsB start 1=Start
2895 180.15 .mcd
2896 181.00 .Str.phsC phsC start 1=Start
2897 181.01 .mcd
2898 181.02 .Op.general OPERATE General operate 1=Operate
2899 181.03 .mcd
2.3.1.30 LD0.PHHPTOC2 Phase overcurrent protection high stage (2)
Table 33: LD0.PHHPTOC2 Phase overcurrent protection high stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC2
2900 181.04 .Str.general START General start 1=Start
2901 181.05 .mcd
2902 181.06 .Str.phsA phsA start 1=Start
2903 181.07 .mcd
2904 181.08 .Str.phsB phsB start 1=Start
2905 181.09 .mcd
2906 181.10 .Str.phsC phsC start 1=Start
2907 181.11 .mcd
2908 181.12 .Op.general OPERATE General operate 1=Operate
2909 181.13 .mcd
30 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.31 LD0.PHIPTOC1 Phase overcurrent protection instantaneous stage (1)
Table 34: LD0.PHIPTOC1 Phase overcurrent protection instantaneous stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHIPTOC1
2910 181.14 .Str.general START General start 1=Start
2911 181.15 .mcd
2912 182.00 .Str.phsA phsA start 1=Start
2913 182.01 .mcd
2914 182.02 .Str.phsB phsB start 1=Start
2915 182.03 .mcd
2916 182.04 .Str.phsC phsC start 1=Start
2917 182.05 .mcd
2918 182.06 .Op.general OPERATE General operate 1=Operate
2919 182.07 .mcd
2.3.1.32 LD0.DEFLPDEF1 Directional earth-fault protection low stage (1)
Table 35: LD0.DEFLPDEF1 Directional earth-fault protection low stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DEFLPTOC1
2920 182.08 .Str.general START Stage start 1=Start
2921 182.09 .mcd
2922 182.10 .Op.general OPERATE Stage operate 1=Operate
2923 182.11 .mcd
2.3.1.33 LD0.DEFLPDEF2 Directional earth-fault protection low stage (2)
Table 36: LD0.DEFLPDEF2 Directional earth-fault protection low stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.DEFLPTOC2
2924 182.12 .Str.general START Stage start 1=Start
2925 182.13 .mcd
2926 182.14 .Op.general OPERATE Stage operate 1=Operate
2927 182.15 .mcd
REF615 31
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.34 LD0.DEFHPDEF1 Directional earth-fault protection high stage (1)
Table 37: LD0.DEFHPDEF1 Directional earth-fault protection high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DEFHPTOC1
2928 183.00 .Str.general START Stage start 1=Start
2929 183.01 .mcd
2930 183.02 .Op.general OPERATE Stage operate 1=Operate
2931 183.03 .mcd
2.3.1.35 LD0.EFLPTOC1 Non-directional earth-fault protection low stage (1)
Table 38: LD0.EFLPTOC1 Non-directional earth-fault protection low stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFLPTOC1
2932 183.04 .Str.general START Stage start 1=Start
2933 183.05 .mcd
2934 183.06 .Op.general OPERATE Stage operate 1=Operate
2935 183.07 .mcd
2.3.1.36 LD0.EFLPTOC2 Non-directional earth-fault protection low stage (2)
Table 39: LD0.EFLPTOC2 Non-directional earth-fault protection low stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFLPTOC2
2936 183.08 .Str.general START Stage start 1=Start
2937 183.09 .mcd
2938 183.10 .Op.general OPERATE Stage operate 1=Operate
2939 183.11 .mcd
2.3.1.37 LD0.EFHPTOC1 Non-directional earth-fault protection high stage (1)
Table 40: LD0.EFHPTOC1 Non-directional earth-fault protection high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFHPTOC1
2940 183.12 .Str.general START Stage start 1=Start
2941 183.13 .mcd
2942 183.14 .Op.general OPERATE Stage operate 1=Operate
2943 183.15 .mcd
32 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.38 LD0.EFIPTOC1 Non-directional earth-fault protection instantaneous
stage (1)
Table 41: LD0.EFIPTOC1 Non-directional earth-fault protection instantaneous stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFIPTOC1
2944 184.00 .Str.general START Stage start 1=Start
2945 184.01 .mcd
2946 184.02 .Op.general OPERATE Stage operate 1=Operate
2947 184.03 .mcd
2.3.1.39 LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1)
Table 42: LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.INTRPTEF1
2948 184.04 .Str.general START Stage start 1=Start
2949 184.05 .mcd
2950 184.06 .Op.general OPERATE Stage operate 1=Operate
2951 184.07 .mcd
2.3.1.40 LD0.PDNSPTOC1 Phase discontinuity protection (1)
Table 43: LD0.PDNSPTOC1 Phase discontinuity protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PDNSPTOC1
2952 184.08 .Str.general START Stage start 1=Start
2953 184.09 .mcd
2954 184.10 .Op.general OPERATE Stage operate 1=Operate
2955 184.11 .mcd
2.3.1.41 LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
Table 44: LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOC1
2956 184.12 .Str.general START Stage start 1=Start
2957 184.13 .mcd
2958 184.14 .Op.general OPERATE Stage operate 1=Operate
2959 184.15 .mcd
REF615 33
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.42 LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
Table 45: LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOC2
2960 185.00 .Str.general START Stage start 1=Start
2961 185.01 .mcd
2962 185.02 .Op.general OPERATE Stage operate 1=Operate
2963 185.03 .mcd
2.3.1.43 LD0.INRPHAR1 Three-phase inrush detection (1)
Table 46: LD0.INRPHAR1 Three-phase inrush detection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.INRPHAR1
2964 185.04 .Str.general BLK2H General start 1=Start
2965 185.05 .mcd
2966 185.06 .Str.phsA phsA start 1=Start
2967 185.07 .mcd
2968 185.08 .Str.phsB phsB start 1=Start
2969 185.09 .mcd
2970 185.10 .Str.phsC phsC start 1=Start
2971 185.11 .mcd
2.3.1.44 LD0.T1PTTR1 Thermal overload protection (1)
Table 47: LD0.T1PTTR1 Thermal overload protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.T1PTTR1
2972 185.12 .Str.general START General start 1=Start
2973 185.13 .mcd
2974 185.14 .AlmThm.general ALARM Thermal alarm 1=Alarm
2975 185.15 .mcd
2976 186.00 .Op.general OPERATE General operate 1=Operate
2977 186.01 .mcd
34 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.45 LD0.ARCSARC1 Fault arc protection (1)
Table 48: LD0.ARCSARC1 Fault arc protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.ARCSARC11
2978 186.02 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2979 186.03 .mcd
LD0.ARCPTRC11
2982 186.06 .Op.general OPERATE Stage operate 1=Operate
2983 186.07 .mcd
2.3.1.46 LD0.ARCSARC2 Fault arc protection (2)
Table 49: LD0.ARCSARC2 Fault arc protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.ARCSARC21
2984 186.08 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2985 186.09 .mcd
LD0.ARCPTRC21
2988 186.12 .Op.general OPERATE Stage operate 1=Operate
2989 186.13 .mcd
2.3.1.47 LD0.ARCSARC3 Fault arc protection (3)
Table 50: LD0.ARCSARC3 Fault arc protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.ARCSARC31
2990 186.14 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected
2991 186.15 .mcd
LD0.ARCPTRC31
2994 187.02 .Op.general OPERATE Stage operate 1=Operate
2995 187.03 .mcd
REF615 35
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.48 LD0.SEQRFUF1 Fuse failure protection (1)
Table 51: LD0.SEQRFUF1 Fuse failure protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.SEQRFUF1
2996 187.04 .Str.general FUSEF_U Start 1=Start
2997 187.05 .mcd
2998 187.06 .Str3Ph.general FUSEF_3PH 3-phase start 1=Start
2999 187.07 .mcd
2.3.1.49 CTRL.CCRDIF1 Current circuit failure detection (1)
Table 52: CTRL.CCRDIF1 Current circuit failure detection (1)
BitA RegA IEC 61850 name SA name Description Values
CTRL.CCRDIF1
3002 187.10 .Alm.stVal ALARM Alarm 1=Alarm
3003 187.11 .mcd
3004 187.12 .Op.general FAIL Failure operate 1=Operate
3005 187.13 .mcd
2.3.1.50 LD0.DPHLPDOC1 Three-phase directional overcurrent protection
low stage (1)
Table 53: LD0.DPHLPDOC1 Three-phase directional overcurrent protection low stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DPHLPTOC1
3006 187.14 .Str.general START General start 1=Start
3007 187.15 .mcd
3008 188.00 .Str.phsA phsA start 1=Start
3009 188.01 .mcd
3010 188.02 .Str.phsB phsB start 1=Start
3011 188.03 .mcd
3012 188.04 .Str.phsC phsC start 1=Start
3013 188.05 .mcd
3014 188.06 .Op.general OPERATE General operate 1=Operate
3015 188.07 .mcd
36 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.51 LD0.DPHLPDOC2 Three-phase directional overcurrent protection
low stage (2)
Table 54: LD0.DPHLPDOC2 Three-phase directional overcurrent protection low stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.DPHLPTOC2
3016 188.08 .Str.general START General start 1=Start
3017 188.09 .mcd
3018 188.10 .Str.phsA phsA start 1=Start
3019 188.11 .mcd
3020 188.12 .Str.phsB phsB start 1=Start
3021 188.13 .mcd
3022 188.14 .Str.phsC phsC start 1=Start
3023 188.15 .mcd
3024 189.00 .Op.general OPERATE General operate 1=Operate
3025 189.01 .mcd
2.3.1.52 LD0.DPHHPDOC1 Three-phase directional overcurrent protection
high stage (1)
Table 55: LD0.DPHHPDOC1 Three-phase directional overcurrent protection high stage (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DPHHPTOC1
3026 189.02 .Str.general START General start 1=Start
3027 189.03 .mcd
3028 189.04 .Str.phsA phsA start 1=Start
3029 189.05 .mcd
3030 189.06 .Str.phsB phsB start 1=Start
3031 189.07 .mcd
3032 189.08 .Str.phsC phsC start 1=Start
3033 189.09 .mcd
3034 189.10 .Op.general OPERATE General operate 1=Operate
3035 189.11 .mcd
REF615 37
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.53 LD0.DARREC1 Autorecloser (1)
Table 56: LD0.DARREC1 Autorecloser (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DARREC1
3040 190.00 .PrgRec.stVal INPRO AR in progess 1=In progress
3041 190.01 .mcd
3042 190.02 .PrgRec1.stVal INPRO_1 1st shot in progess 1=In progress
3043 190.03 .mcd
3044 190.04 .PrgRec2.stVal INPRO_2 2nd shot in progess 1=In progress
3045 190.05 .mcd
3046 190.06 .PrgRec3.stVal INPRO_3 3rd shot in progess 1=In progress
3047 190.07 .mcd
3048 190.08 .PrgRec4.stVal INPRO_4 4th shot in progess 1=In progress
3049 190.09 .mcd
3050 190.10 .PrgRec5.stVal INPRO_5 5th shot in progess 1=In progress
3051 190.11 .mcd
3052 190.12 .SucRec.stVal SUC_RECL Successful AR 1=Success
3053 190.13 .mcd
3054 190.14 .UnsRec.stVal UNSUC_RECL Unsuccessful AR 1=Unsuccess
3055 190.15 .mcd
3056 191.00 < reserved >
3057 191.01 < reserved >
3058 191.02 < reserved >
3059 191.03 < reserved >
3060 191.04 .LO.stVal LOCKED Lockout status 1=Lockout
3061 191.05 .mcd
3062 191.06 .RdyRec.stVal READY Reclose ready 1=Ready
3063 191.07 .mcd
3064 191.08 .ActRec.stVal ACTIVE Reclose active 1=Active
3065 191.09 .mcd
3066 191.10 .PrgDsr.stVal DISCR_INPRO Discr.time in progress 1=In progress
3067 191.11 .mcd
3068 191.12 .PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
3069 191.13 .mcd
3070 191.14 .FrqOpAlm.stVal FRQ_OP_ALM Frequent op. Alarm 1=Alarm
3071 191.15 .mcd
3072 192.00 .RclTmStr.stVal Reclaim time started
3073 192.01 .mcd
3074 192.02 .ProCrd.stVal Protection coordination 1=In progress
3075 192.03 .mcd
Table continues on next page
38 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3076 192.04 .CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
3077 192.05 .mcd
3078 192.06 .Op.general CLOSE_CB Operate (close XCBR) 1=Close CB
3079 192.07 .mcd
3080 192.08 .OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
3081 192.09 .mcd
3082 192.10 .UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
3083 192.11 .mcd
3084 192.12 .WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal
3085 192.13 .mcd
2.3.1.54 LD0.PHPTOV1 Phase overvoltage protection (1)
Table 57: LD0.PHPTOV1 Phase overvoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTOV1
3088 193.00 .Str.general START General start 1=Start
3089 193.01 .mcd
3090 193.02 .Str.phsA phsA start 1=Start
3091 193.03 .mcd
3092 193.04 .Str.phsB phsB start 1=Start
3093 193.05 .mcd
3094 193.06 .Str.phsC phsC start 1=Start
3095 193.07 .mcd
3096 193.08 .Op.general OPERATE General operate 1=Operate
3097 193.09 .mcd
2.3.1.55 LD0.PHPTOV2 Phase overvoltage protection (2)
Table 58: LD0.PHPTOV2 Phase overvoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTOV2
3098 193.10 .Str.general START General start 1=Start
3099 193.11 .mcd
3100 193.12 .Str.phsA phsA start 1=Start
3101 193.13 .mcd
3102 193.14 .Str.phsB phsB start 1=Start
3103 193.15 .mcd
3104 194.00 .Str.phsC phsC start 1=Start
Table continues on next page
REF615 39
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3105 194.01 .mcd
3106 194.02 .Op.general OPERATE General operate 1=Operate
3107 194.03 .mcd
2.3.1.56 LD0.PHPTOV3 Phase overvoltage protection (3)
Table 59: LD0.PHPTOV3 Phase overvoltage protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTOV3
3108 194.04 .Str.general START General start 1=Start
3109 194.05 .mcd
3110 194.06 .Str.phsA phsA start 1=Start
3111 194.07 .mcd
3112 194.08 .Str.phsB phsB start 1=Start
3113 194.09 .mcd
3114 194.10 .Str.phsC phsC start 1=Start
3115 194.11 .mcd
3116 194.12 .Op.general OPERATE General operate 1=Operate
3117 194.13 .mcd
2.3.1.57 LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
Table 60: LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PSPTUV1
3118 194.14 .Str.general START General start 1=Start
3119 194.15 .mcd
3120 195.00 .Str.phsA phsA start 1=Start
3121 195.01 .mcd
3122 195.02 .Str.phsB phsB start 1=Start
3123 195.03 .mcd
3124 195.04 .Str.phsC phsC start 1=Start
3125 195.05 .mcd
3126 195.06 .Op.general OPERATE General operate 1=Operate
3127 195.07 .mcd
40 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.58 LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
Table 61: LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOV1
3128 195.08 .Str.general START General start 1=Start
3129 195.09 .mcd
3130 195.10 .Str.phsA phsA start 1=Start
3131 195.11 .mcd
3132 195.12 .Str.phsB phsB start 1=Start
3133 195.13 .mcd
3134 195.14 .Str.phsC phsC start 1=Start
3135 195.15 .mcd
3136 196.00 .Op.general OPERATE General operate 1=Operate
3137 196.01 .mcd
2.3.1.59 LD0.PHPTUV1 Phase undervoltage protection (1)
Table 62: LD0.PHPTUV1 Phase undervoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTUV1
3138 196.02 .Str.general START General start 1=Start
3139 196.03 .mcd
3140 196.04 .Str.phsA phsA start 1=Start
3141 196.05 .mcd
3142 196.06 .Str.phsB phsB start 1=Start
3143 196.07 .mcd
3144 196.08 .Str.phsC phsC start 1=Start
3145 196.09 .mcd
3146 196.10 .Op.general OPERATE General operate 1=Operate
3147 196.11 .mcd
2.3.1.60 LD0.PHPTUV2 Phase undervoltage protection (2)
Table 63: LD0.PHPTUV2 Phase undervoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTUV2
3148 196.12 .Str.general START General start 1=Start
3149 196.13 .mcd
3150 196.14 .Str.phsA phsA start 1=Start
Table continues on next page
REF615 41
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3151 196.15 .mcd
3152 197.00 .Str.phsB phsB start 1=Start
3153 197.01 .mcd
3154 197.02 .Str.phsC phsC start 1=Start
3155 197.03 .mcd
3156 197.04 .Op.general OPERATE General operate 1=Operate
3157 197.05 .mcd
2.3.1.61 LD0.PHPTUV3 Phase undervoltage protection (3)
Table 64: LD0.PHPTUV3 Phase undervoltage protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHPTUV3
3158 197.06 .Str.general START General start 1=Start
3159 197.07 .mcd
3160 197.08 .Str.phsA phsA start 1=Start
3161 197.09 .mcd
3162 197.10 .Str.phsB phsB start 1=Start
3163 197.11 .mcd
3164 197.12 .Str.phsC phsC start 1=Start
3165 197.13 .mcd
3166 197.14 .Op.general OPERATE General operate 1=Operate
3167 197.15 .mcd
2.3.1.62 LD0.ROVPTOV1 Residual overvoltage protection (1)
Table 65: LD0.ROVPTOV1 Residual overvoltage protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV1
3168 198.00 .Str.general START General start 1=Start
3169 198.01 .mcd
3170 198.02 .Op.general OPERATE General operate 1=Operate
3171 198.03 .mcd
42 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.63 LD0.ROVPTOV2 Residual overvoltage protection (2)
Table 66: LD0.ROVPTOV2 Residual overvoltage protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV2
3172 198.04 .Str.general START General start 1=Start
3173 198.05 .mcd
3174 198.06 .Op.general OPERATE General operate 1=Operate
3175 198.07 .mcd
2.3.1.64 LD0.ROVPTOV3 Residual overvoltage protection (3)
Table 67: LD0.ROVPTOV3 Residual overvoltage protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV3
3176 198.08 .Str.general START General start 1=Start
3177 198.09 .mcd
3178 198.10 .Op.general OPERATE General operate 1=Operate
3179 198.11 .mcd
2.3.1.65 LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
Table 68: LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.WPSDE1
3296 206.00 .Str.general START Stage start 1=Start
3297 206.01 .mcd
3298 206.02 .Op.general OPERATE Stage operate 1=Operate
3299 206.03 .mcd
2.3.1.66 LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
Table 69: LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.WPSDE2
3300 206.04 .Str.general START Stage start 1=Start
3301 206.05 .mcd
3302 206.06 .Op.general OPERATE Stage operate 1=Operate
3303 206.07 .mcd
REF615 43
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.67 LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
Table 70: LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.WPSDE3
3304 206.08 .Str.general START Stage start 1=Start
3305 206.09 .mcd
3306 206.10 .Op.general OPERATE Stage operate 1=Operate
3307 206.11 .mcd
2.3.1.68 LD0.HAEFPTOC1 Harmonics-based earth-fault protection (1)
Table 71: LD0.HAEFPTOC1 Harmonics-based earth-fault protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.HAEFPTOC1
3312 207.00 .Str.general START Stage start 1=Start
3313 207.01 .mcd
3314 207.02 .Op.general OPERATE Stage operate 1=Operate
3315 207.03 .mcd
2.3.1.69 LD0.CMHAI1 Current total demand distortion (1)
Table 72: LD0.CMHAI1 Current total demand distortion (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.CMHAI1
3316 207.04 .Alm.stVal ALARM 1=Alarm
3317 207.05 .mcd
2.3.1.70 LD0.VMHAI1 Voltage total demand distortion (1)
Table 73: LD0.VMHAI1 Voltage total demand distortion (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.VMHAI1
3318 207.06 .Alm.stVal ALARM 1=Alarm
3319 207.07 .mcd
44 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.71 LD0.PH1QVVR1 PQ - Voltage variation signals (1)
Table 74: LD0.PH1QVVR1 PQ - Voltage variation signals (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PH1QVVR1
3328 208.00 .VarStrGen.stVal - Variation event detected 1=Detected
3329 208.01 .mcd
3330 208.02 .VarEnd.stVal - Variation event ended 1=Ended
3331 208.03 .mcd
3332 208.04 .SwlOp.stVal - Swell event detected 1=Detected
3333 208.05 .mcd
3334 208.06 .DipOp.stVal - Dip event detected 1=Detected
3335 208.07 .mcd
3336 208.08 .IntrOp.stVal - Interruption event detected 1=Detected
3337 208.09 .mcd
2.3.1.72 CTRL.DCXSWI1 Controllable discon. (1) mom. position data
Table 75: CTRL.DCXSWI1 Controllable discon. (1) mom. position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI1 POSITION
3472 217.00 .Pos.stVal.Close - Close bit 1=Close
3473 217.01 .Pos.stVal.Open - Open bit 1=Open
3474 217.02 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3475 217.03 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO1
3476 217.04 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3477 217.05 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI1
3478 217.06 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3479 217.07 .mcd
3480 217.08 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3481 217.09 .mcd
3482 217.10 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
3483 217.11 .mcd
REF615 45
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.73 CTRL.DCXSWI2 Controllable discon. (2) mom. position data
Table 76: CTRL.DCXSWI2 Controllable discon. (2) mom. position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI2 POSITION
3484 217.12 .Pos.stVal.Close - Close bit 1=Close
3485 217.13 .Pos.stVal.Open - Open bit 1=Open
3486 217.14 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3487 217.15 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO2
3488 218.00 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3489 218.01 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI2
3490 218.02 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3491 218.03 .mcd
3492 218.04 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3493 218.05 .mcd
3494 218.06 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
3495 218.07 .mcd
2.3.1.74 CTRL.ESXSWI1 Controllable earth switch (1) mom. position
Table 77: CTRL.ESXSWI1 Controllable earth switch (1) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.ESXSWI1 POSITION
3496 218.08 .Pos.stVal.Close - Close bit 1=Close
3497 218.09 .Pos.stVal.Open - Open bit 1=Open
3498 218.10 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3499 218.11 .Pos.stSeld - Control selected 1=Selected
CTRL.ESCILO1
3500 218.12 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3501 218.13 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.ESXSWI1
3502 218.14 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3503 218.15 .mcd
3504 219.00 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3505 219.01 .mcd
3506 219.02 .ItlByPss.stVal ITL_BYPASS Interlock bypass 1=Bypass
3507 219.03 .mcd
46 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.1.75 LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 78: LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO130
3184 199.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On
3185 199.01 .mcd
3186 199.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On
3187 199.03 .mcd
3188 199.04 .Ind3.stVal X130-Input 3 State 0/1=Off/On
3189 199.05 .mcd
3190 199.06 .Ind4.stVal X130-Input 4 State 0/1=Off/On
3191 199.07 .mcd
3192 199.08 .Ind5.stVal X130-Input 5 State 0/1=Off/On
3193 199.09 .mcd
3194 199.10 .Ind6.stVal X130-Input 6 State 0/1=Off/On
3195 199.11 .mcd
3264 204.00 .SPCSO1.stVal X130-Output 1 State 0/1=Off/On
3265 204.01 .mcd
3266 204.02 .SPCSO2.stVal X130-Output 2 State 0/1=Off/On
3267 204.03 .mcd
3268 204.04 .SPCSO3.stVal X130-Output 3 State 0/1=Off/On
3269 204.05 .mcd
2.3.1.76 LD0.XGGIO120 Physical I/O states (AIM card X120)
Table 79: LD0.XGGIO120 Physical I/O states (AIM card X120)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO120
3200 200.00 .Ind1.stVal X120-Input 1 State 0/1=Off/On
3201 200.01 .mcd
3202 200.02 .Ind2.stVal X120-Input 2 State 0/1=Off/On
3203 200.03 .mcd
3204 200.04 .Ind3.stVal X120-Input 3 State 0/1=Off/On
3205 200.05 .mcd
3206 200.06 .Ind4.stVal X120-Input 4 State 0/1=Off/On
3207 200.07 .mcd
REF615 47
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.1.77 LD0.XGGIO110 Physical I/O states (BIO card X110)
Table 80: LD0.XGGIO110 Physical I/O states (BIO card X110)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO110
3216 201.00 .Ind1.stVal X110-Input 1 State 0/1=Off/On
3217 201.01 .mcd
3218 201.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On
3219 201.03 .mcd
3220 201.04 .Ind3.stVal X110-Input 3 State 0/1=Off/On
3221 201.05 .mcd
3222 201.06 .Ind4.stVal X110-Input 4 State 0/1=Off/On
3223 201.07 .mcd
3224 201.08 .Ind5.stVal X110-Input 5 State 0/1=Off/On
3225 201.09 .mcd
3226 201.10 .Ind6.stVal X110-Input 6 State 0/1=Off/On
3227 201.11 .mcd
3228 201.12 .Ind7.stVal X110-Input 7 State 0/1=Off/On
3229 201.13 .mcd
3230 201.14 .Ind8.stVal X110-Input 8 State 0/1=Off/On
3231 201.15 .mcd
3232 202.00 .SPCSO1.stVal X110-Output 1 State 0/1=Off/On
3233 202.01 .mcd
3234 202.02 .SPCSO2.stVal X110-Output 2 State 0/1=Off/On
3235 202.03 .mcd
3236 202.04 .SPCSO3.stVal X110-Output 3 State 0/1=Off/On
3237 202.05 .mcd
3238 202.06 .SPCSO4.stVal X110-Output 4 State 0/1=Off/On
3239 202.07 .mcd
2.3.1.78 LD0.XGGIO100 Physical I/O states (PSM card X100)
Table 81: LD0.XGGIO100 Physical I/O states (PSM card X100)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO100
3248 203.00 .SPCSO1.stVal X100-Output 1 State 0/1=Off/On
3249 203.01 .mcd
3250 203.02 .SPCSO2.stVal X100-Output 2 State 0/1=Off/On
3251 203.03 .mcd
3252 203.04 .SPCSO3.stVal X100-Output 3 State 0/1=Off/On
Table continues on next page
48 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3253 203.05 .mcd
3254 203.06 .SPCSO4.stVal X100-Output 4 State 0/1=Off/On
3255 203.07 .mcd
3256 203.08 .SPCSO5.stVal X100-Output 5 State 0/1=Off/On
3257 203.09 .mcd
3258 203.10 .SPCSO6.stVal X100-Output 6 State 0/1=Off/On
3259 203.11 .mcd
2.3.1.79 LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 82: LD0.XAGGIO130 Physical I/O states (AIM card XA130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XAGGIO130
3280 205.00 .Ind1.stVal XA130-Input 1 State 0/1=Off/On
3281 205.01 .mcd
3282 205.02 .Ind2.stVal XA130-Input 2 State 0/1=Off/On
3283 205.03 .mcd
3284 205.04 .Ind3.stVal XA130-Input 3 State 0/1=Off/On
3285 205.05 .mcd
3286 205.06 .Ind4.stVal XA130-Input 4 State 0/1=Off/On
3287 205.07 .mcd
2.3.1.80 LD0.MVGAPC1 Multipurpose binary inputs (1)
Table 83: LD0.MVGAPC1 Multipurpose binary inputs (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MVGAPC1
3536 221.00 .Q1.stVal Input 1 0/1=Off/On
3537 221.01 .mcd
3538 221.02 .Q2.stVal Input 2 0/1=Off/On
3539 221.03 .mcd
3540 221.04 .Q3.stVal Input 3 0/1=Off/On
3541 221.05 .mcd
3542 221.06 .Q4.stVal Input 4 0/1=Off/On
3543 221.07 .mcd
3544 221.08 .Q5.stVal Input 5 0/1=Off/On
3545 221.09 .mcd
3546 221.10 .Q6.stVal Input 6 0/1=Off/On
3547 221.11 .mcd
Table continues on next page
REF615 49
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3548 221.12 .Q7.stVal Input 7 0/1=Off/On
3549 221.13 .mcd
3550 221.14 .Q8.stVal Input 8 0/1=Off/On
3551 221.15 .mcd
2.3.1.81 LD0.MVGAPC2 Multipurpose binary inputs (2)
Table 84: LD0.MVGAPC2 Multipurpose binary inputs (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.MVGAPC2
3552 222.00 .Q1.stVal Input 1 0/1=Off/On
3553 222.01 .mcd
3554 222.02 .Q2.stVal Input 2 0/1=Off/On
3555 222.03 .mcd
3556 222.04 .Q3.stVal Input 3 0/1=Off/On
3557 222.05 .mcd
3558 222.06 .Q4.stVal Input 4 0/1=Off/On
3559 222.07 .mcd
3560 222.08 .Q5.stVal Input 5 0/1=Off/On
3561 222.09 .mcd
3562 222.10 .Q6.stVal Input 6 0/1=Off/On
3563 222.11 .mcd
3564 222.12 .Q7.stVal Input 7 0/1=Off/On
3565 222.13 .mcd
3566 222.14 .Q8.stVal Input 8 0/1=Off/On
3567 222.15 .mcd
2.3.1.82 LD0.SPCGGIO2 Multipurpose binary output states (2)
Table 85: LD0.SPCGGIO2 Multipurpose binary output states (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.SPCGGIO2
3632 227.00 .SPCS01.stVal Ouput state 1 0/1=Off/On
3633 227.01 .mcd
3634 227.02 .SPCS02.stVal Ouput state 2 0/1=Off/On
3635 227.03 .mcd
3636 227.04 .SPCS03.stVal Ouput state 3 0/1=Off/On
3637 227.05 .mcd
3638 227.06 .SPCS04.stVal Ouput state 4 0/1=Off/On
Table continues on next page
50 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3639 227.07 .mcd
3640 227.08 .SPCS05.stVal Ouput state 5 0/1=Off/On
3641 227.09 .mcd
3642 227.10 .SPCS06.stVal Ouput state 6 0/1=Off/On
3643 227.11 .mcd
3644 227.12 .SPCS07.stVal Ouput state 7 0/1=Off/On
3645 227.13 .mcd
3646 227.14 .SPCS08.stVal Ouput state 8 0/1=Off/On
3647 227.15 .mcd
3648 228.00 .SPCS09.stVal Ouput state 9 0/1=Off/On
3649 228.01 .mcd
3650 228.02 .SPCS10.stVal Ouput state 10 0/1=Off/On
3651 228.03 .mcd
3652 228.04 .SPCS11.stVal Ouput state 11 0/1=Off/On
3653 228.05 .mcd
3654 228.06 .SPCS12.stVal Ouput state 12 0/1=Off/On
3655 228.07 .mcd
3656 228.08 .SPCS13.stVal Ouput state 13 0/1=Off/On
3657 228.09 .mcd
3658 228.10 .SPCS14.stVal Ouput state 14 0/1=Off/On
3659 228.11 .mcd
3660 228.12 .SPCS15.stVal Ouput state 15 0/1=Off/On
3661 228.13 .mcd
3662 228.14 .SPCS16.stVal Ouput state 16 0/1=Off/On
3663 228.15 .mcd
2.3.2 Indications in FE08
2.3.2.1 LD0.SECRSYN1 Synchrocheck (1)
Table 86: LD0.SECRSYN1 Synchrocheck (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.SECRSYN1
3184 199.00 .SynPrg SYNC_INPRO Synch. in progress 1=In progress
3185 199.01 .mcd
3186 199.02 .FailCmd CMD_FAIL_AL Close request fail 1=Failed
3187 199.03 .mcd
3188 199.04 .FailSyn CL_FAIL_AL Close cmd fail 1=Failed
3189 199.05 .mcd
REF615 51
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.2.2 LD0.FRPFRQ1 Frequency protection (1)
Table 87: LD0.FRPFRQ1 Frequency protection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC1
3200 200.00 .Str.general START Stage 1 start 1=Start
3201 200.01 .mcd
LD0.FRPTOF1 Overfrequency
3202 200.02 .Op.general OPR_OFRQ Operate 1=Operate
3203 200.03 .mcd
LD0.FRPTUF1 Underfrequency
3204 200.04 .Op.general OPR_UFRQ Operate 1=Operate
3205 200.05 .mcd
LD0.FRPFRC1 Frequency gradient
3206 200.06 .Op.general OPR_FRG Operate 1=Operate
3207 200.07 .mcd
2.3.2.3 LD0.FRPFRQ2 Frequency protection (2)
Table 88: LD0.FRPFRQ2 Frequency protection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC2
3208 200.08 .Str.general START Stage 2 start 1=Start
3209 200.09 .mcd
LD0.FRPTOF2 Overfrequency
3210 200.10 .Op.general OPR_OFRQ Operate 1=Operate
3211 200.11 .mcd
LD0.FRPTUF2 Underfrequency
3212 200.12 .Op.general OPR_UFRQ Operate 1=Operate
3213 200.13 .mcd
LD0.FRPFRC2 Frequency gradient
3214 200.14 .Op.general OPR_FRG Operate 1=Operate
3215 200.15 .mcd
52 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.2.4 LD0.FRPFRQ3 Frequency protection (3)
Table 89: LD0.FRPFRQ3 Frequency protection (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC3
3216 201.00 .Str.general START Stage 3 start 1=Start
3217 201.01 .mcd
LD0.FRPTOF3 Overfrequency
3218 201.02 .Op.general OPR_OFRQ Operate 1=Operate
3219 201.03 .mcd
LD0.FRPTUF3 Underfrequency
3220 201.04 .Op.general OPR_UFRQ Operate 1=Operate
3221 201.05 .mcd
LD0.FRPFRC3 Frequency gradient
3222 201.06 .Op.general OPR_FRG Operate 1=Operate
3223 201.07 .mcd
2.3.2.5 LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 90: LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO130
3344 209.00 .Ind1.stVal X130-Input 1 State 0/1=Off/On
3345 209.01 .mcd
3346 209.02 .Ind2.stVal X130-Input 2 State 0/1=Off/On
3347 209.03 .mcd
3348 209.04 .Ind3.stVal X130-Input 3 State 0/1=Off/On
3349 209.05 .mcd
3350 209.06 .Ind4.stVal X130-Input 4 State 0/1=Off/On
3351 209.07 .mcd
3352 209.08 .Ind5.stVal X130-Input 5 State 0/1=Off/On
3353 209.09 .mcd
3354 209.10 .Ind6.stVal X130-Input 6 State 0/1=Off/On
3355 209.11 .mcd
3424 214.00 .SPCSO1.stVal X130-Output 1 State 0/1=Off/On
3425 214.01 .mcd
3426 214.02 .SPCSO2.stVal X130-Output 2 State 0/1=Off/On
3427 214.03 .mcd
3428 214.04 .SPCSO3.stVal X130-Output 3 State 0/1=Off/On
3429 214.05 .mcd
REF615 53
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.2.6 LD0.XGGIO120 Physical I/O states (AIM card X120)
Table 91: LD0.XGGIO120 Physical I/O states (AIM card X120)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO120
3360 210.00 .Ind1.stVal X120-Input 1 State 0/1=Off/On
3361 210.01 .mcd
3362 210.02 .Ind2.stVal X120-Input 2 State 0/1=Off/On
3363 210.03 .mcd
3364 210.04 .Ind3.stVal X120-Input 3 State 0/1=Off/On
3365 210.05 .mcd
3366 210.06 .Ind4.stVal X120-Input 4 State 0/1=Off/On
3367 210.07 .mcd
2.3.2.7 LD0.XGGIO110 Physical I/O states (BIO card X110)
Table 92: LD0.XGGIO110 Physical I/O states (BIO card X110)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO110
3376 211.00 .Ind1.stVal X110-Input 1 State 0/1=Off/On
3377 211.01 .mcd
3378 211.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On
3379 211.03 .mcd
3380 211.04 .Ind3.stVal X110-Input 3 State 0/1=Off/On
3381 211.05 .mcd
3382 211.06 .Ind4.stVal X110-Input 4 State 0/1=Off/On
3383 211.07 .mcd
3384 211.08 .Ind5.stVal X110-Input 5 State 0/1=Off/On
3385 211.09 .mcd
3386 211.10 .Ind6.stVal X110-Input 6 State 0/1=Off/On
3387 211.11 .mcd
3388 211.12 .Ind7.stVal X110-Input 7 State 0/1=Off/On
3389 211.13 .mcd
3390 211.14 .Ind8.stVal X110-Input 8 State 0/1=Off/On
3391 211.15 .mcd
3392 212.00 .SPCSO1.stVal X110-Output 1 State 0/1=Off/On
3393 212.01 .mcd
3394 212.02 .SPCSO2.stVal X110-Output 2 State 0/1=Off/On
3395 212.03 .mcd
3396 212.04 .SPCSO3.stVal X110-Output 3 State 0/1=Off/On
Table continues on next page
54 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
3397 212.05 .mcd
3398 212.06 .SPCSO4.stVal X110-Output 4 State 0/1=Off/On
3399 212.07 .mcd
2.3.2.8 LD0.XGGIO100 Physical I/O states (PSM card X100)
Table 93: LD0.XGGIO100 Physical I/O states (PSM card X100)
BitA RegA IEC 61850 name SA name Description Values
LD0.XGGIO100
3408 213.00 .SPCSO1.stVal X100-Output 1 State 0/1=Off/On
3409 213.01 .mcd
3410 213.02 .SPCSO2.stVal X100-Output 2 State 0/1=Off/On
3411 213.03 .mcd
3412 213.04 .SPCSO3.stVal X100-Output 3 State 0/1=Off/On
3413 213.05 .mcd
3414 213.06 .SPCSO4.stVal X100-Output 4 State 0/1=Off/On
3415 213.07 .mcd
3416 213.08 .SPCSO5.stVal X100-Output 5 State 0/1=Off/On
3417 213.09 .mcd
3418 213.10 .SPCSO6.stVal X100-Output 6 State 0/1=Off/On
3419 213.11 .mcd
2.3.2.9 LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 94: LD0.XAGGIO130 Physical I/O states (AIM card XA130)
BitA RegA IEC 61850 name SA name Description Values
LD0.XAGGIO130
3440 215.00 .Ind1.stVal XA130-Input 1 State 0/1=Off/On
3441 215.01 .mcd
3442 215.02 .Ind2.stVal XA130-Input 2 State 0/1=Off/On
3443 215.03 .mcd
3444 215.04 .Ind3.stVal XA130-Input 3 State 0/1=Off/On
3445 215.05 .mcd
3446 215.06 .Ind4.stVal XA130-Input 4 State 0/1=Off/On
3447 215.07 .mcd
REF615 55
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3 Unmapped indications
Unmapped indications are indication data that have no initial Modbus mapping
locations, but can be added to the user-definable Modbus area using the
Communication Management tool in PCM600. If Modbus events are enabled for
these indication signals, the event identification is the user-definable area address.
2.3.3.1 All premapped 3-phase protection function stages - operate/phase-
dependent objects added
Table 95: All premapped 3-phase protection function stages - operate/phase-dependent objects added
BitA RegA IEC 61850 name SA name Description Values
LD0.xxxxxxxx (various)
.Op.phsA phsA operate 1 = Operate
.mcd
.Op.phsB phsB operate 1 = Operate
.mcd
.Op.phsC phsC operate 1 = Operate
.mcd
2.3.3.2 Common data 2
Table 96: Common data 2
BitA RegA IEC 61850 name SA name Description Values
LD0.LPHD1
.OutOv.stVal Internal ind. overflow 1=Overflow
.mcd
.OutOv1.stVal Internal meas. overflow 1=Overflow
.mcd
.ChgFlg.stVal Configuration changed 1=Changed
.mcd
.FacSet.stVal Factory settings in use 1=In use
.mcd
LD0.GNRLLTMS1
.TmChSt1.stVal Time synch. status 0/1=Down/Up
.mcd
LD0.IHMI1
.LocClk.stVal Local time 1=Local time
.mcd
LD0.DIAGLCCH1.ChLiv
.ChLiv.stVal Ethernet chn live 1=Live
Table continues on next page
56 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
.mcd
.RedChLiv.stVal Redundant ethernet chn live 1=Live
.mcd
LD0.GSAL1
.AuthAcsA.stVal Viewer accesses IED 1=Accesses
.mcd
.AuthAcsB.stVal Operator accesses IED 1=Accesses
.mcd
.AuthAcsC.stVal Engineer accesses IED 1=Accesses
.mcd
.AuthAcsD.stVal Admin accesses IED 1=Accesses
.mcd
2.3.3.3 CTRL.DCSXSWI2 Disconnector (2) mom. position
Table 97: CTRL.DCSXSWI2 Disconnector (2) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI2 POSITION
.Pos.stVal.Close Close bit 1=Close
.Pos.stVal.Open Open bit 1=Open
.Pos.stVal.Fault Fault bit 1=Pos(00/11)
2.3.3.4 CTRL.DCSXSWI3 Disconnector (3) mom. position
Table 98: CTRL.DCSXSWI3 Disconnector (3) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCSXSWI3 POSITION
.Pos.stVal.Close Close bit 1 = Close
.Pos.stVal.Open Open bit 1 = Open
.Pos.stVal.Fault Fault bit 1 = Pos(00/11)
2.3.3.5 CTRL.DCXSWI1 Controllable discon. (1) mom. position data
Table 99: CTRL.DCXSWI1 Controllable discon. (1) mom. position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI1 POSITION
.Pos.stVal.Close Close bit 1 = Close
.Pos.stVal.Open Open bit 1 = Open
.Pos.stVal.Fault Fault bit 1 = Pos(00/11)
Table continues on next page
REF615 57
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
.Pos.stSeld Control selected 1 = Selected
CTRL.DCCILO1
.EnaOpn.stVal ENA_OPEN Open enabled 1 = Enabled
.EnaCls.stVal ENA_CLOSE Close enabled 1 = Enabled
CTRL.DCXSWI1
.BlkOpn.stVal BLK_OPEN Open blocked 1 = Blocked
.mcd
.BlkCls.stVal BLK_CLOSE Close blocked 1 = Blocked
.mcd
.ItlByPss.stVal ITL_BYPASS Interlock bypass 1 = Bypass
.mcd
2.3.3.6 CTRL.DCXSWI2 Controllable discon. (2) mom. position data
Table 100: CTRL.DCXSWI2 Controllable discon. (2) mom. position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI2 POSITION
.Pos.stVal.Close Close bit 1 = Close
.Pos.stVal.Open Open bit 1 = Open
.Pos.stVal.Fault Fault bit 1 = Pos(00/11)
.Pos.stSeld Control selected 1 = Selected
CTRL.DCCILO2
.EnaOpn.stVal ENA_OPEN Open enabled 1 = Enabled
.EnaCls.stVal ENA_CLOSE Close enabled 1 = Enabled
CTRL.DCXSWI2
.BlkOpn.stVal BLK_OPEN Open blocked 1 = Blocked
.mcd
.BlkCls.stVal BLK_CLOSE Close blocked 1 = Blocked
.mcd
.ItlByPss.stVal ITL_BYPASS Interlock bypass 1 = Bypass
.mcd
2.3.3.7 CTRL.ESSXSWI2 Earth switch (2) mom. position
Table 101: CTRL.ESSXSWI2 Earth switch (2) mom. position
BitA RegA IEC 61850 name SA name Description Values
CTRL.ESSXSWI3 POSITION
.Pos.stVal.Close Close bit 1 = Close
.Pos.stVal.Open Open bit 1 = Open
.Pos.stVal.Fault Fault bit 1 = Pos(00/11)
58 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.8 CTRL.ESXSWI1 Controllable earth switch (1) mom. position data
Table 102: CTRL.ESXSWI1 Controllable earth switch (1) mom. position data
BitA RegA IEC 61850 name SA name Description Values
CTRL.ESXSWI1 POSITION
.Pos.stVal.Close Close bit 1 = Close
.Pos.stVal.Open Open bit 1 = Open
.Pos.stVal.Fault Fault bit 1 = Pos(00/11)
.Pos.stSeld Control selected 1 = Selected
CTRL.ESCILO1
.EnaOpn.stVal ENA_OPEN Open enabled 1 = Enabled
.EnaCls.stVal ENA_CLOSE Close enabled 1 = Enabled
CTRL.ESXSWI1
.BlkOpn.stVal BLK_OPEN Open blocked 1 = Blocked
.mcd
.BlkCls.stVal BLK_CLOSE Close blocked 1 = Blocked
.mcd
.ItlByPss.stVal ITL_BYPASS Interlock bypass 1 = Bypass
.mcd
2.3.3.9 LD0.DIAGLCCH1 Ethernet supervision (1)
Table 103: LD0.DIAGLCCH1 Ethernet supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.DIAGLCCH1
.ChLiv.stVal CHLIV Ethernet channel live 1=Live
.mcd
.RedChLiv.stVal REDCHLIV Red. Ethernet channel live 1=Live
.mcd
2.3.3.10 LD0.EFHPTOC2 Earth-fault protection high stage (2)
Table 104: LD0.EFHPTOC2 Earth-fault protection high stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.EFHPTOC2
.Str.general START General start 1 = Start
.mcd
.Op.general OPERATE General operate 1 = Operate
.mcd
REF615 59
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.11 LD0.FRPFRQ4 Frequency protection (4)
Table 105: LD0.FRPFRQ4 Frequency protection (4)
BitA RegA IEC 61850 name SA name Description Values
LD0.FRPTRC4
.Str.general START Stage 4 start 1 = Start
.mcd
LD0.FRPTOF4 Overfrequency
.Op.general OPR_OFRQ Operate 1 = Operate
.mcd
LD0.FRPTUF4
.Op.general OPR_UFRQ Underfrequency 1 = Operate
.mcd Operate
LD0.FRPFRC4
.Op.general OPR_FRG Frequency gradient 1 = Operate
.mcd Operate
2.3.3.12 LD0.HREFPDIF1 High-impedance restricted earth-fault detection (1)
Table 106: LD0.HREFPDIF1 High-impedance restricted earth-fault detection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.HREFPDIF1
.Str.general START General start 1 = Start
.mcd
.Op.general OPERATE General operate 1 = Operate
.mcd
2.3.3.13 LD0.HREFPDIF2 High-impedance restricted earth-fault detection (2)
Table 107: LD0.HREFPDIF2 High-impedance restricted earth-fault detection (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.HREFPDIF2
.Str.general START General start 1 = Start
.mcd
.Op.general OPERATE General operate 1 = Operate
.mcd
60 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.14 LD0.IL1TCTR1 3-phase CT supervision (1)
Table 108: LD0.IL1TCTR1 3-phase CT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.IL1TCTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.3.15 LD0.MAPGAPC1 Multipurpose analog protection function (1)
Table 109: LD0.MAPGAPC1 Multipurpose analog protection function (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC1
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.16 LD0.MAPGAPC2 Multipurpose analog protection function (2)
Table 110: LD0.MAPGAPC2 Multipurpose analog protection function (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC2
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.17 LD0.MAPGAPC3 Multipurpose analog protection function (3)
Table 111: LD0.MAPGAPC3 Multipurpose analog protection function (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC3
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
REF615 61
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.18 LD0.MAPGAPC4 Multipurpose analog protection function (4)
Table 112: LD0.MAPGAPC4 Multipurpose analog protection function (4)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC4
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.19 LD0.MAPGAPC5 Multipurpose analog protection function (5)
Table 113: LD0.MAPGAPC5 Multipurpose analog protection function (5)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC5
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.20 LD0.MAPGAPC6 Multipurpose analog protection function (6)
Table 114: LD0.MAPGAPC6 Multipurpose analog protection function (6)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC6
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.21 LD0.MAPGAPC7 Multipurpose analog protection function (7)
Table 115: LD0.MAPGAPC7 Multipurpose analog protection function (7)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC7
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
62 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.22 LD0.MAPGAPC8 Multipurpose analog protection function (8)
Table 116: LD0.MAPGAPC8 Multipurpose analog protection function (8)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC8
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.23 LD0.MAPGAPC9 Multipurpose analog protection function (9)
Table 117: LD0.MAPGAPC9 Multipurpose analog protection function (9)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC9
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.24 LD0.MAPGAPC10 Multipurpose analog protection function (10)
Table 118: LD0.MAPGAPC10 Multipurpose analog protection function (10)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC10
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.25 LD0.MAPGAPC11 Multipurpose analog protection function (11)
Table 119: LD0.MAPGAPC11 Multipurpose analog protection function (11)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC11
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
REF615 63
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.26 LD0.MAPGAPC12 Multipurpose analog protection function (12)
Table 120: LD0.MAPGAPC12 Multipurpose analog protection function (12)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC12
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.27 LD0.MAPGAPC13 Multipurpose analog protection function (13)
Table 121: LD0.MAPGAPC13 Multipurpose analog protection function (13)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC13
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.28 LD0.MAPGAPC14 Multipurpose analog protection function (14)
Table 122: LD0.MAPGAPC14 Multipurpose analog protection function (14)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC14
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.29 LD0.MAPGAPC15 Multipurpose analog protection function (15)
Table 123: LD0.MAPGAPC15 Multipurpose analog protection function (15)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC15
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
64 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.30 LD0.MAPGAPC16 Multipurpose analog protection function (16)
Table 124: LD0.MAPGAPC16 Multipurpose analog protection function (16)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC1
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.31 LD0.MAPGAPC17 Multipurpose analog protection function (17)
Table 125: LD0.MAPGAPC17 Multipurpose analog protection function (17)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC17
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.32 LD0.MAPGAPC18 Multipurpose analog protection function (18)
Table 126: LD0.MAPGAPC18 Multipurpose analog protection function (18)
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC18
.Str.general START Stage start 1 = Start
.mcd
.Op.general OPERATE Stage operate 1 = Operate
.mcd
2.3.3.33 LD0.MDSOPT1 Generic operation time supervision (1)
Table 127: LD0.MDSOPT1 Generic operation time supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MDSOPT1
OpTmWrn.stVal START Accum.op.time Warn. 1 = Warning
.mcd
OpTmAlm.stVal OPERATE Accum.op.time Alarm 1 = Alarm
.mcd
REF615 65
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.34 LD0.MVGAPC1 Multipurpose binary inputs, MOM-only or latch use (1)
Table 128: LD0.MVGAPC1 Multipurpose binary inputs, MOM-only or latch use (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.MVGAPC1
.Q1.stVal (Mom-only) Input 1 momentary value 1 = On
.Q1.stVal (Latch) Input 1 latched value 1 = On (latched)
.Q2.stVal (Mom-only) Input 2 momentary value 1 = On
.Q2.stVal (Latch) Input 2 latched value 1 = On (latched)
.Q3.stVal (Mom-only) Input 3 momentary value 1 = On
.Q3.stVal (Latch) Input 3 latched value 1 = On (latched)
.Q4.stVal (Mom-only) Input 4 momentary value 1 = On
.Q4.stVal (Latch) Input 4 latched value 1 = On (latched)
.Q5.stVal (Mom-only) Input 5 momentary value 1 = On
.Q5.stVal (Latch) Input 5 latched value 1 = On (latched)
.Q6.stVal (Mom-only) Input 6 momentary value 1 = On
.Q6.stVal (Latch) Input 6 latched value 1 = On (latched)
.Q7.stVal (Mom-only) Input 7 momentary value 1 = On
.Q7.stVal (Latch) Input 7 latched value 1 = On (latched)
.Q8.stVal (Mom-only) Input 8 momentary value 1 = On
.Q8.stVal (Latch) Input 8 latched value 1 = On (latched)
2.3.3.35 LD0.MVGAPC2 Multipurpose binary inputs, MOM-only or latch use (2)
Table 129: LD0.MVGAPC2 Multipurpose binary inputs, MOM-only or latch use (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.MVGAPC2
.Q1.stVal (Mom-only) Input 1 momentary value 1 = On
.Q1.stVal (Latch) Input 1 latched value 1 = On (latched)
.Q2.stVal (Mom-only) Input 2 momentary value 1 = On
.Q2.stVal (Latch) Input 2 latched value 1 = On (latched)
.Q3.stVal (Mom-only) Input 3 momentary value 1 = On
.Q3.stVal (Latch) Input 3 latched value 1 = On (latched)
.Q4.stVal (Mom-only) Input 4 momentary value 1 = On
.Q4.stVal (Latch) Input 4 latched value 1 = On (latched)
.Q5.stVal (Mom-only) Input 5 momentary value 1 = On
.Q5.stVal (Latch) Input 5 latched value 1 = On (latched)
.Q6.stVal (Mom-only) Input 6 momentary value 1 = On
.Q6.stVal (Latch) Input 6 latched value 1 = On (latched)
.Q7.stVal (Mom-only) Input 7 momentary value 1 = On
Table continues on next page
66 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
BitA RegA IEC 61850 name SA name Description Values
.Q7.stVal (Latch) Input 7 latched value 1 = On (latched)
.Q8.stVal (Mom-only) Input 8 momentary value 1 = On
.Q8.stVal (Latch) Input 8 latched value 1 = On (latched)
2.3.3.36 LD0.PHIZ1 High impedance fault detection (1)
Table 130: LD0.PHIZ1 High impedance fault detection (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHIZ1
.Str.general START General start 1 = Start
.mcd
.Op.general OPERATE General operate 1 = Operate
.mcd
2.3.3.37 LD0.PHLPTOC2 Phase overcurrent protection low stage (2)
Table 131: LD0.PHLPTOC2 Phase overcurrent protection low stage (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.PHLPTOC2
.Str.general START General start 1 = Start
.mcd
.Str.phsA phsA start 1 = Start
.mcd
.Str.phsB phsB start 1 = Start
.mcd
.Str.phsC phsC start 1 = Start
.mcd
.Op.general OPERATE General operate 1 = Operate
.mcd
.Op.phsA phsA operate 1 = Operate
.mcd
.Op.phsB phsB operate 1 = Operate
.mcd
.Op.phsC phsC operate 1 = Operate
.mcd
REF615 67
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.38 LD0.RESTCTR1 Io CT supervision (1)
Table 132: LD0.RESTCTR1 Io CT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESTCTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.3.39 LD0.RESTCTR2 Io CT supervision (2)
Table 133: LD0.RESTCTR2 Io CT supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESTCTR2
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.3.40 LD0.RESTVTR1 Uo VT supervision (1)
Table 134: LD0.RESTVTR1 Uo VT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.RESTVTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.3.41 LD0.SCERFLO1 Fault locator (1)
Table 135: LD0.SCERFLO1 Fault locator (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.SCERFLO1
.Alm.stVal ALARM Fault locator alarm 1 = Alarm
.mcd
.TrgSt.stVal TRIGG Distance calculation trig 1 = Triggered
.mcd
68 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.42 LD0.SPCGGIO1 Multipurpose binary output states (1)
Table 136: LD0.SPCGGIO1 Multipurpose binary output states (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.SPCGGIO1
.SPCSO1.stVal Ouput state 1 0/1=Off/On
.mcd
.SPCSO2.stVal Ouput state 2 0/1=Off/On
.mcd
.SPCSO3.stVal Ouput state 3 0/1=Off/On
.mcd
.SPCSO4.stVal Ouput state 4 0/1=Off/On
.mcd
.SPCSO5.stVal Ouput state 5 0/1=Off/On
.mcd
.SPCSO6.stVal Ouput state 6 0/1=Off/On
.mcd
.SPCSO7.stVal Ouput state 7 0/1=Off/On
.mcd
.SPCSO8.stVal Ouput state 8 0/1=Off/On
.mcd
.SPCSO9.stVal Ouput state 9 0/1=Off/On
.mcd
.SPCSO10.stVal Ouput state 10 0/1=Off/On
.mcd
.SPCSO11.stVal Ouput state 11 0/1=Off/On
.mcd
.SPCSO12.stVal Ouput state 12 0/1=Off/On
.mcd
.SPCSO13.stVal Ouput state 13 0/1=Off/On
.mcd
.SPCSO14.stVal Ouput state 14 0/1=Off/On
.mcd
.SPCSO15.stVal Ouput state 15 0/1=Off/On
.mcd
.SPCSO16.stVal Ouput state 16 0/1=Off/On
.mcd
REF615 69
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.43 LD0.TRPPTRC3 Protection trip conditioning (3)
Table 137: LD0.TRPPTRC3 Protection trip conditioning (3)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC3
.Op.general Op. input signal 1 = Operate
.mcd
.Tr.general Trip output signal 1 = Trip
.mcd
2.3.3.44 LD0.TRPPTRC4 Protection trip conditioning (4)
Table 138: LD0.TRPPTRC4 Protection trip conditioning (4)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC4
.Op.general Op. input signal 1 = Operate
.mcd
.Tr.general Trip output signal 1 = Trip
.mcd
2.3.3.45 LD0.TRPPTRC5 Protection trip conditioning (5)
Table 139: LD0.TRPPTRC5 Protection trip conditioning (5)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC5
.Op.general Op. input signal 1 = Operate
.mcd
.Tr.general Trip output signal 1 = Trip
.mcd
2.3.3.46 LD0.UL1TVTR1 3-phase VT supervision (1)
Table 140: LD0.UL1TVTR1 3-phase VT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.UL1TVTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
70 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.3.3.47 LD0.UL1TVTR2 3-phase VT supervision (2)
Table 141: LD0.UL1TVTR2 3-phase VT supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.UL1TVTR2
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.3.48 LD0.VMMXU2 Phase voltage limit supervision (2)
Table 142: LD0.VMMXU2 Phase voltage limit supervision (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.VMMXU2
.HiAlm.stVal HIGH_ALARM High alarm 1 = Alarm
.mcd
.HiWrn.stVal HIGH_WARN High warning 1 = Warning
.mcd
.LoWrn.stVal LOW_WARN Low warning 1 = Warning
.mcd
.LoAlm.stVal LOW_ALARM Low alarm 1 = Alarm
.mcd
2.3.3.49 LD0.XARGGIO130 Alarm/warning
Table 143: LD0.XARGGIO130 Alarm/warning
BitA RegA IEC 61850 name SA name Description Values
LD0.XARGGIO130
.Alm.stVal XARGGIO130 alarm 1 = Alarm
.mcd
.Wrn.stVal XARGGIO130 warning 1 = Warning
.mcd
REF615 71
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.3.3.50 LD0.XRGGIO130 Alarm/warning
Table 144: LD0.XRGGIO130 Alarm/warning
BitA RegA IEC 61850 name SA name Description Values
LD0.XRGGIO130
.Alm.stVal - XRGGIO130 alarm 1=Alarm
.mcd
.Wrn.stVal - XRGGIO130 warning 1=Warning
.mcd
2.4 Registers
Table 145: Explanations of columns in register tables
Column name Description
RegA Default 3X and 4X register address for the data.
Type Type of the register. The alternatives are u16, u32 (unsigned 16 and 32 bits
integer) or i16, i32 (signed 16 and 32 bit integer).
Scale Scale factor as default. Also, an adjustable offset value exists that is set to 0 by
default.
IEC 61850 Original IED data object identification. Described in the IEC 61850 format as
name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Also, if a register is writable, it is stated here.
Values The value range of the original IEC 61850 value, that is, before scaling.
2.4.1 Premapped registers
2.4.1.1 User definable registers [Alt.1], visible on 3x and 4x
Table 146: User definable registers [Alt.1], visible on 3x and 4x
RegA Type Scale IEC 61850 name SA name Description Values
(0) Reg < not mappable- not visible >
1 Reg User Register 1
2 Reg User Register 2
3 : :
: : :
: : :
127 Reg User Register 127
72 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.2 User definable bits [Alt.2], visible on 0x,1x,3x and 4x
Table 147: User definable bits [Alt.2], visible on 0x,1x,3x and 4x
BitA Type Scale IEC 61850 name SA name Description Values
(0) Bit < not mappable - not visible >
1 Bit Usr Reg 1.Bit 01
2 Bit Usr Reg 1.Bit 02
3 Bit Usr Reg 1.Bit 03
: : :
: : :
15 Bit Usr Reg 1.Bit 15
16 Bit Usr Reg 2.Bit 00
17 Bit Usr Reg 2.Bit 01
: : :
: : :
2046 Bit Usr Reg 127.Bit 14
2047 Bit Usr Reg 127.Bit 15
2.4.1.3 SSR1 System status register (1) device health
Table 148: SSR1 System status register (1) device health
RegA Type Scale IEC 61850 name SA name Description Values
128.00 Bit Device global error 1=Error
128.01 Bit Device global warning 1=Warning
128.02 Bit < reserved > 0
128.03 Bit < reserved > 0
128.04 Bit < reserved > 0
128.05 Bit < reserved > 0
128.06 Bit < reserved > 0
128.07 Bit < reserved > 0
128.08 Bit < reserved > 0
128.09 Bit < reserved > 0
128.10 Bit < reserved > 0
128.11 Bit < reserved > 0
128.12 Bit < reserved > 0
128.13 Bit < reserved > 0
128.14 Bit < reserved > 0
128.15 Bit < reserved > 0
REF615 73
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.4 SSR2 System status register (2) IED mode and state
Table 149: SSR2 System status register (2) IED mode and state
RegA Type Scale IEC 61850 name SA name Description Values
129.00 Bit Device test mode 1=Test mode
129.01 Bit < reserved > 0
129.02 Bit Remote/Local state 0/1=Rem/Loc
Active setting group SG=1..6
129.03 Bit - bit 0
129.04 Bit - bit 1
129.05 Bit - bit 2
129.06 Bit IED timesynch failure 1=Failure
129.07 Bit < reserved > 0
129.08 Bit Last reset cause a 1=Cold start
129.09 Bit Last reset cause b 1=Watchdog
129.10 Bit Last reset cause c 1=Warm start
129.11 Bit < reserved > 0
129.12 Bit < reserved > 0
129.13 Bit < reserved > 0
129.14 Bit < reserved > 0
129.15 Bit < reserved > 0
2.4.1.5 SSR3 System status register (3) data available 1 (client-dependent)
Table 150: SSR3 System status register (3) data available 1 (client-dependent)
RegA Type Scale IEC 61850 name SA name Description Values
130.00 Bit Unread event records available 1=Available
130.01 Bit Unread fault records available 1=Available
130.02 Bit < reserved > 0
130.03 Bit < reserved > 0
130.04 Bit Any momentary bit updated 1=Updated
130.05 Bit Any mcd bit set 1=Set
130.06 Bit Device restart bit 1=IED restart
130.07 Bit < reserved > 0
130.08 Bit Event record selected 1=Selected
130.09 Bit Fault record selected 1=Selected
130.10 Bit < reserved > 0
130.11 Bit < reserved > 0
130.12 Bit < reserved > 0
Table continues on next page
74 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
130.13 Bit < reserved > 0
130.14 Bit < reserved > 0
130.15 Bit < reserved > 0
2.4.1.6 SSR4 System status register (4) data available 2 (client-dependent -
user-definable)
Table 151: SSR4 System status register (4) data available 2 (client-dependent - user-definable)
RegA Type Scale IEC 61850 name SA name Description Values
131.00 Bit Data category 1 has changed 1=Changed
131.01 Bit Data category 2 has changed 1=Changed
131.02 Bit Data category 3 has changed 1=Changed
131.03 Bit Data category 4 has changed 1=Changed
131.04 Bit Data category 5 has changed 1=Changed
131.05 Bit Data category 6 has changed 1=Changed
131.06 Bit Data category 7 has changed 1=Changed
131.07 Bit Data category 8 has changed 1=Changed
131.08 Bit Data category 9 has changed 1=Changed
131.09 Bit Data category 10 has changed 1=Changed
131.10 Bit Data category 11 has changed 1=Changed
131.11 Bit Data category 12 has changed 1=Changed
131.12 Bit Data category 13 has changed 1=Changed
131.13 Bit Data category 14 has changed 1=Changed
131.14 Bit Data category 15 has changed 1=Changed
131.15 Bit Data category 16 has changed 1=Changed
2.4.1.7 SSR5 System status register (5) device alive register
Table 152: SSR5 System status register (5) device alive register
RegA Type Scale IEC 61850 name SA name Description Values
132 u16 1 Device alive counter 0..65535
REF615 75
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.8 SSR6 System status register (6) control command status (client-
dependent)
Table 153: SSR6 System status register (6) control command status (client-dependent)
RegA Type Scale IEC 61850 name SA name Description Values
Last cmd result code See doc.
133.00 Bit - bit 0
133.01 Bit - bit 1
133.02 Bit - bit 2
133.03 Bit - bit 3
133.04 Bit - bit 4
133.05 Bit - bit 5
133.06 Bit - bit 6
133.07 Bit - bit 7
Response Type See doc.
133.08 Bit - bit 0
133.09 Bit - bit 1
Command state See doc.
133.10 Bit - bit 0
133.11 Bit - bit 1
Cmd sequence number 0..15
133.12 Bit - bit 0
133.13 Bit - bit 1
133.14 Bit - bit 2
133.15 Bit - bit 3
2.4.1.9 LD0.DARREC1 Autorecloser values (1)
Table 154: LD0.DARREC1 Autorecloser values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.DARREC1
-2..4 (see
135 i16 1 .AutoRecSt.stVal STATUS AR state doc)
136 u16 1 .ShotPntr.stVal SHOT_PTR AR shot pointer value 0..6
137 u16 1 .OpCntRs.stVal COUNTER AR operation counter 0..65535
76 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.10 LD0.CMMXU1 Phase current measurements (1)
Table 155: LD0.CMMXU1 Phase current measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMMXU1 Phase current (1)
0.00..40.0
138 u16 1000 .A.phsA.instCVal.mag I_INST_A - phsA amplitude [xIn]
0.00..40.0
139 u16 1000 .A.phsB.instCVal.mag I_INST_B - phsB amplitude [xIn]
0.00..40.0
140 u16 1000 .A.phsC.instCVal.mag I_INST_C - phsC amplitude [xIn]
2.4.1.11 LD0.RESCMMXU1 Residual current measurement (1)
Table 156: LD0.RESCMMXU1 Residual current measurement (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.RESCMMXU1 Residual current (1)
0.00..40.0
141 u16 1000 .A.res.instCVal.mag I0_INST - amplitude [xIn]
2.4.1.12 LD0.RESVMMXU1 Residual voltage measurement (1)
Table 157: LD0.RESVMMXU1 Residual voltage measurement (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.RESVMMXU1 Residual voltage (1)
0.00..4.00
142 u16 1000 .A.res.instCVal.mag U0_INST - amplitude [xUn]
2.4.1.13 LD0.CMSQI1 Sequence of current measurements (1)
Table 158: LD0.CMSQI1 Sequence of current measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMSQI1 Sequence of currents
0.00..40.0
143 u16 1000 .SeqA.c1.instCVal.mag I1_INST - positive amplitude [xIn]
0.00..40.0
144 u16 1000 .SeqA.c2.instCVal.mag I2_INST - negative amplitude [xIn]
0.00..40.0
145 u16 1000 .SeqA.c2.instCVal.mag I3_INST - zero amplitude [xIn]
REF615 77
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.14 LD0.T1PTTR1 Thermal protection values (1)
Table 159: LD0.T1PTTR1 Thermal protection values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.T1PTTR1
-100.0…
146 i16 1 .Tmp.mag TEMP Object temperature 9999.9 [C]
0.00…99.99
147 u16 1 .TmpRl.mag TEMP_RL Relative temperature [C]
-99…999.99
148 i16 1 .TmpUsed.mag TEMP_AMB Ambient temperature [C]
0…600,000
149 u16 .001 .TmmsOp.stVal THERMLEV_ST Est. time to operate [ms]
0…600,000
150 u16 .001 .TmmsRecEna.stVal THERMLEV_END Est. time to deactivate block [ms]
2.4.1.15 LD0.HAEFMHAI1 Current harmonics (1)
Table 160: LD0.HAEFMHAI1 Current harmonics (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.HAEFMHAI1
151 u16 10 .HRmsA.res.cVal.mag I_HARM_RES Current harmonics 0..250.0 [A]
2.4.1.16 LD0.VMMXU1 Voltage measurements (1)
Table 161: LD0.VMMXU1 Voltage measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMMXU1 Phase-ground voltage (1)
0.00..4.00
152 u16 1000 .phV.phsA.cVal.mag U_DB_A - phsA amplitude [xUn]
0.00..4.00
153 u16 1000 .phV.phsB.cVal.mag U_DB_B - phsB amplitude [xUn]
0.00..4.00
154 u16 1000 .phV.phsC.cVal.mag U_DB_C - phsC amplitude [xUn]
LD0.VMMXU1 Phase-phase voltage (1)
0.00..4.00
155 u16 1000 .PPV.phsAB.cVal.mag U_DB_AB - phsAB amplitude [xUn]
0.00..4.00
156 u16 1000 .PPV.phsBC.cVal.mag U_DB_BC - phsBC amplitude [xUn]
0.00..4.00
157 u16 1000 .PPV.phsCA.cVal.mag U_DB_CA - phsCA amplitude [xUn]
78 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.17 LD0.VMSQI1 Sequence of voltage measurements (1)
Table 162: LD0.VMSQI1 Sequence of voltage measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMSQI1 Sequence of voltages
0.00..4.00
158 u16 1000 .SeqA.c1.instCVal.mag U1_INST - positive amplitude [xUn]
0.00..4.00
159 u16 1000 .SeqA.c2.instCVal.mag U2_INST - negative amplitude [xUn]
0.00..4.00
160 u16 1000 .SeqA.c2.instCVal.mag U3_INST - zero amplitude [xUn]
2.4.1.18 LD0.PEMMXU1 Three-phase power measurements (1)
Table 163: LD0.PEMMXU1 Three-phase power measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.PEMMXU1
161 i32 1 .TotW.instMag P_INST Total active power P (high) -/+ 999,999
162 .TotW.instMag (low word)
163 i32 1 .TotVAr.instMag Q_INST Total reactive power Q (high) -/+ 999,999
164 .TotVAr.instMag (low word)
165 i32 1 .TotVA.instMag S_INST Total apparent power S (high) -/+ 999,999
166 .TotVA.instMag (low word)
167 i16 1000 .TotPF.instMag PF_INST Average power factor -1..1
2.4.1.19 LD0.FMMXU1 Frequency measurement (1)
Table 164: LD0.FMMXU1 Frequency measurement (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.FMMXU1
35.00..75.00
168 u16 100 .Hz.mag F_DB Frequency [Hz]
2.4.1.20 LD0.SECRSYN1 Synchrocheck (1)
Table 165: LD0.SECRSYN1 Synchrocheck (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.SECRSYN1
169 u16 1 .EnSt.stVal ENERG_STATE Energ. state of line and bus 0..4 (see doc)
REF615 79
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.21 Indication bits mirrored in registers
Table 166: Indication bits mirrored in registers
RegA Type Scale IEC 61850 name SA name Description Values
170.00 Bit Indication bit 2720 (0x1700)
170.01 Bit Indication bit 2721 (0x1701)
: : :
170.14 Bit Indication bit 2734 (0x170E)
170.15 Bit Indication bit 2735 (0x170F)
171.00 Bit Indication bit 2736 (0x1710)
2.4.1.22 LD0.PEMSTA1 Power measurement demand values (1)
Table 167: LD0.PEMSTA1 Power measurement demand values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.PEMSTA1 Demand
1939 i32 1 .AvW.mag - Active power P (high) -/+ 999,999
1940 - (low word)
1941 i32 1 .AvVAr.mag - Reactive power Q (high) -/+ 999,999
1942 - (low word)
1943 i32 1 .AvVA.mag - Apparent power S (high) -/+ 999,999
1944 - (low word)
1945 i16 1000 .AvPF.mag - Power factor -1..1
1946 < reserved > 0
Max values:
1947 i32 1 .MaxW.mag - Active power P (high) -/+ 999,999
1948 - (low word)
1949 i32 1 .MaxVAr.mag - Reactive power Q (high) -/+ 999,999
1950 - (low word)
1951 i32 1 .MaxVA.mag - Apparent power S (high) -/+ 999,999
1952 - (low word)
1953 < reserved > 0
2.4.1.23 LD0.VMSTA1 Voltage demand values (1)
Table 168: LD0.VMSTA1 Voltage demand values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMSTA1 Demand phase-to-ground
1954 u16 1000 .AvVPhsA.mag U_DMD_A - phsA amplitude 0..4.0 [xUn]
1955 u16 1000 .AvVPhsB.mag U_DMD_B - phsB amplitude 0..4.0 [xUn]
Table continues on next page
80 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
1956 u16 1000 .AvVPhsC.mag U_DMD_C - phsC amplitude 0..4.0 [xUn]
Demand phase-to-phase
1957 u16 1000 .AvVPhsAB.mag U_DMD_AB - phsAB amplitude 0..4.0 [xUn]
1958 u16 1000 .AvVPhsBC.mag U_DMD_BC - phsBC amplitude 0..4.0 [xUn]
1959 u16 1000 .AvVPhsCA.mag U_DMD_CA - phsCA amplitude 0..4.0 [xUn]
Update time stamp See doc.
1960 u16 - - Year - month
1961 u16 - - Day - hour
1962 u16 - - Minute - second
1963 u16 - - Milliseconds
1964 u16 - - Time quality
2.4.1.24 LD0.RESVMSTA1 Residual voltage demand value (1)
Table 169: LD0.RESVMSTA1 Residual voltage demand value (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.RESVMSTA1 Demand value
0.00..4.0
1977 u16 1000 .AvVolts.mag U_DMD_RES - residual amplitude [xUn]
Update time stamp See doc.
1978 u16 - - Year - month
1979 u16 - - Day - hour
1980 u16 - - Minute - second
1981 u16 - - Milliseconds
1982 u16 - - Time quality
0.00..4.0
1983 u16 1000 .MaxVolts.mag Max demand Uo - Max Uo demand [xUn]
Update time stamp See doc.
1984 u16 - - Year - month
1985 u16 - - Day - hour
1986 u16 - - Minute - second
1987 u16 - - Milliseconds
1988 u16 - - Time quality
REF615 81
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.25 LD0.RESCMSTA1 Residual current demand value (1)
Table 170: LD0.RESCMSTA1 Residual current demand value (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.RESCMSTA1 Demand value
0.00..40.0
1989 u16 1000 .AvAmps.mag I_DMD_RES - residual amplitude [xIn]
Update time stamp See doc.
1990 u16 - - Year - month
1991 u16 - - Day - hour
1992 u16 - - Minute - second
1993 u16 - - Milliseconds
1994 u16 - - Time quality
0.00..40.0
1995 u16 1000 .MaxAmps.mag Max demand Io - Max Io demand [xIn]
Update time stamp See doc.
1996 u16 - - Year - month
1997 u16 - - Day - hour
1998 u16 - - Minute - second
1999 u16 - - Milliseconds
2000 u16 - - Time quality
2.4.1.26 LD0.CMSTA1 Phase current demand values (1)
Table 171: LD0.CMSTA1 Phase current demand values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMSTA1 Demand value
0.00..40.0
2001 u16 1000 .AvAmpsA.mag I_DMD_A - phsA amplitude [xIn]
0.00..40.0
2002 u16 1000 .AvAmpsB.mag I_DMD_B - phsB amplitude [xIn]
0.00..40.0
2003 u16 1000 .AvAmpsC.mag I_DMD_C - phsC amplitude [xIn]
Update time stamp See doc.
2004 u16 - - Year - month
2005 u16 - - Day - hour
2006 u16 - - Minute - second
2007 u16 - - Milliseconds
2008 u16 - - Time quality
0.00..40.0
2009 u16 1000 .MaxAmpsA.mag Max demand IL1 - Max phsA demand [xIn]
Table continues on next page
82 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
Update time stamp See doc.
2010 u16 - - Year - month
2011 u16 - - Day - hour
2012 u16 - - Minute - second
2013 u16 - - Milliseconds
2014 u16 - - Time quality
0.00..40.0
2015 u16 1000 .MaxAmpsB.mag Max demand IL2 - Max phsB demand [xIn]
Update time stamp See doc.
2016 u16 - - Year - month
2017 u16 - - Day - hour
2018 u16 - - Minute - second
2019 u16 - - Milliseconds
2020 u16 - - Time quality
0.00..40.0
2021 u16 1000 .MaxAmpsC.mag Max demand IL3 - Max phsC demand [xIn]
Update time stamp see doc.
2022 u16 - - Year - month
2023 u16 - - Day - hour
2024 u16 - - Minute - second
2025 u16 - - Milliseconds
2026 u16 - - Time quality
2.4.1.27 CTRL.CBCSWI1 Circuit breaker operation counter (1)
Table 172: CTRL.CBCSWI1 Circuit breaker operation counter (1)
RegA Type Scale IEC 61850 name SA name Description Values
CTRL.CBCSWI1
2027 u16 1 .OpCntRs.stVal Operation counter Operation counter 0…65535
2.4.1.28 LD0.ARCSARCx1 Fault arc counters
Table 173: LD0.ARCSARCx1 Fault arc counters
RegA Type Scale IEC 61850 name SA name Description Values
LD0.ARCSARC11
2028 u16 1 .FACntRs.stVal Fault arc 1 counter 0…65535
LD0.ARCSARC21
Table continues on next page
REF615 83
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
2029 u16 1 .FACntRs.stVal Fault arc 2 counter 0…65535
LD0.ARCSARC31
2030 u16 1 .FACntRs.stVal Fault arc 3 counter 0…65535
2.4.1.29 LD0.DARREC1 Autorecloser counters (1)
Table 174: LD0.DARREC1 Autorecloser counters (1)
RegA Typw Scale IEC 61850 name SA name Description Values
LD0.DARREC1
2031 u16 1 .OpCnt1.stVal CNT_SHOT1 AR 1st shot counter 0…65535
2032 u16 1 .OpCnt2.stVal CNT_SHOT2 AR 1st shot counter 0…65535
2033 u16 1 .OpCnt3.stVal CNT_SHOT3 AR 1st shot counter 0…65535
2034 u16 1 .OpCnt4.stVal CNT_SHOT4 AR 1st shot counter 0…65535
2035 u16 1 .OpCnt5.stVal CNT_SHOT5 AR 1st shot counter 0…65535
2036 u16 1 .FrqOpCnt.stVal FRQ_OPR_CNT AP freq.op. counter 0…65535
2.4.1.30 LD0.PEMMTR1 Three-phase energy measurements (1)
Table 175: LD0.PEMMTR1 Three-phase energy measurements (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.PEMMTR1
0..1E10
2037 u32 1 .SupWh.actVal Reverse active energy (high) [kWh]
2038 .SupWh.actVal (low word)
0..1E10
2039 u32 1 .SupVArh.actVal Reverse reactive energy (high) [kVAr]
2040 .SupVArh.actVal (low word)
0..1E10
2041 u32 1 .DemWh.actVal Forward active energy (high) [kWh]
2042 .DemWh.actVal (low word)
0..1E10
2043 u32 1 .DemVArh.actVal Forward reactive energy (high) [kVAr]
2044 .DemVArh.actVal (low word)
84 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.31 System diagnostic values
Table 176: System diagnostic values
RegA Type Scale IEC 61850 name SA name Description Values
LD0.LPHD1
2050 u16 1 .PhyHealth1.stVal Warning Last warning code see doc.
2051 u16 1 .PhyHealth2.stVal Internal fault Last internal fault code see doc.
DR.RDRE1
2052 u16 1 .FltNum.stVal Num.of DR recordings 0..N
2053 u16 1 .MemUsed.stVal DR memory used 0..100 [%]
LD0.LPHD1
2054 u16 1 .NumPwrUp.stVal Num of cold starts 0..65535
2055 u16 1 .WrmStr.stVal Num of warm starts 0..65535
2056 u16 1 .WacTrg.stVal Num of watchdog resets 0..65535
2057 u16 1 .NumCmpChg.stVal Num of conf. changes 0..65535
2.4.1.32 LD0.SSCBR1 Circuit-breaker condition monitoring values (1)
Table 177: LD0.SSCBR1 Circuit-breaker condition monitoring values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.SSCBR1
2060 u16 1 .InaTmdCnt.stVal INA_DAYS CB inactive days 0..65535
2061 u16 1 .TmmsOpn.mag T_TRV_OP Open travel time 0..60000 [ms]
2062 u16 1 .TmmsCls.mag T_TRV_CL Close travel time 0..60000 [ms]
0.00…99.99
2063 u16 100 .TmsSprCha.mag T_SPR_CHR Spring charge time [s]
2064 i16 1 .RmnLifPhA.stVal CB_LIFE_A Remain.life phsA -/+ 9999
2065 i16 1 .RmnLifPhB.stVal CB_LIFE_B Remain.life phsB -/+ 9999
2066 i16 1 .RmnLifPhC.stVal CB_LIFE_C Remain.life phsC -/+ 9999
2067 u16 1 .AccAPwrPhA.mag IPOW_A Iyt phsA 0..1E6
2068 u16 1 .AccAPwrPhB.mag IPOW_B Iyt phsB 0..1E6
2069 u16 1 .AccAPwrPhC.mag IPOW_C Iyt phsC 0..1E6
2.4.1.33 LD0.PH1QVVR1 Short duration voltage variations (1)
Table 178: LD0.PH1QVVR1 Short duration voltage variations (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.PH1QVVR1 Voltage swell:
2100 u32 1 .SwlInstCnt.stVal INSTSWELLCNT - Inst counter (high) 0…
2101 - (low word) 2147483647
2102 u32 1 .SwlMomCnt.stVal MOMSWELLCNT - Mom counter (high) 0…
Table continues on next page
REF615 85
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
2103 - (low word) 2147483647
2104 u32 1 .SwlTmpCnt.stVal TEMPSWELLCNT - Temp counter (high) 0…
2105 - (low word) 2147483647
MAXDURSWELLC
2106 u32 1 .SwlMaxCnt.stVal NT - Max duration.counter (high) 0…
2107 - (low word) 2147483647
Voltage dip:
2108 u32 1 .DipInstCnt.stVal INSTDIPCNT - Inst counter (high) 0…
2109 - (low word) 2147483647
2110 u32 1 .DipMomCnt.stVal MOMDIPCNT - Mom counter (high) 0…
2111 - (low word) 2147483647
2112 u32 1 .DipTmpCnt.stVal TEMPDIPCNT - Temp counter (high) 0…
2113 - (low word) 2147483647
2114 u32 1 .DipMaxCnt.stVal MAXDURDIPCNT - Max duration.counter (high) 0…
2115 - (low word) 2147483647
Voltage interrupts:
2116 u32 1 .IntrMomCnt.stVal MOMINTCNT - Mom counter (high) 0…
2117 - (low word) 2147483647
2118 u32 1 .IntrTmpCnt.stVal TEMPINTCNT - Temp counter (high) 0…
2119 - (low word) 2147483647
2120 u32 1 .IntrSstCnt.stVal SUSTINTCNT - Sustain counter (high) 0…
2121 - (low word) 2147483647
2122 u32 1 .IntrMaxCnt.stVal MAXDURINTCNT - Max duration.counter (high) 0…
2.4.1.34 LD0.CMHAI1 Current total demand distortion (1)
Table 179: LD0.CMHAI1 Current total demand distortion (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMHAI1 3 2nd mean value:
2150 u16 100 .TddA.phsA.cVal.mag 3SMHTDD_A - phsA 0..500.00 [%]
2151 u16 100 .TddA.phsB.cVal.mag 3SMHTDD_B - phsB 0..500.00 [%]
2152 u16 100 .TddA.phsC.cVal.mag 3SMHTDD_C - phsC 0..500.00 [%]
Demand value:
.DmdTddA.phsA.cVal.m
2153 u16 100 ag DMD_TDD_A - phsA 0..500.00 [%]
.DmdTddA.phsB.cVal.m
2154 u16 100 ag DMD_TDD_B - phsB 0..500.00 [%]
.DmdTddA.phsC.cVal.m
2155 u16 100 ag DMD_TDD_C - phsC 0..500.00 [%]
Max demand value:
Table continues on next page
86 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
.MaxDmdTddA.phsA.cV
2156 u16 100 al.mag - - phsA 0..500.00 [%]
.MaxDmdTddA.phsB.cV
2157 u16 100 al.mag - - phsB 0..500.00 [%]
.MaxDmdTddA.phsB.cV
2158 u16 100 al.mag - - phsC 0..500.00 [%]
2.4.1.35 LD0.VMHAI1 Voltage total demand distortion (1)
Table 180: LD0.VMHAI1 Voltage total demand distortion (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMHAI1 3 2nd mean value:
2170 u16 100 .ThdPhV.phsA.cVal.mag 3SMHTHD_A - phsA 0..500.00 [%]
2171 u16 100 .ThdPhV.phsB.cVal.mag 3SMHTDD_B - phsB 0..500.00 [%]
2172 u16 100 .ThdPhV.phsC.cVal.mag 3SMHTDD_C - phsC 0..500.00 [%]
Demand value:
.DmdThdPhV.phsA.cVal.
2173 u16 100 mag DMD_TDD_A - phsA 0..500.00 [%]
.DmdThdPhV.phsB.cVal.
2174 u16 100 mag DMD_TDD_B - phsB 0..500.00 [%]
.DmdThdPhV.phsC.cVal.
2175 u16 100 mag DMD_TDD_C - phsC 0..500.00 [%]
Max demand value:
.MaxDmdThdV.phsA.cV
2176 u16 100 al.mag - - phsA 0..500.00 [%]
.MaxDmdThdV.phsB.cV
2177 u16 100 al.mag - - phsB 0..500.00 [%]
.MaxDmdThdV.phsC.cV
2178 u16 100 al.mag - - phsC 0..500.00 [%]
2.4.1.36 Active parameter setting group - read and write
Table 181: Active parameter setting group - read and write
RegA Type Scale IEC 61850 name SA name Description Values
2301 u16 1 Active setting group 1..6
REF615 87
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.37 Control structure 1
Table 182: Control structure 1
RegA Type Scale IEC 61850 name SA name Description Values
8001 Execute register 1
8002 Password reg 1 acc to setting
8003 Password reg 2 acc to setting
8004 Control register < single bit >
8005 Confirm register < single bit >
2.4.1.38 Control structure 2
Table 183: Control structure 2
RegA Type Scale IEC 61850 name SA name Description Values
8006 Execute register 1
8007 Password reg 1 acc to setting
8008 Password reg 2 acc to setting
8009 Control register < single bit >
8010 Confirm register < single bit >
2.4.1.39 Control structure 3
Table 184: Control structure 3
RegA Type Scale IEC 61850 name SA name Description Values
8011 Execute register 1
8012 Password reg 1 acc to setting
8013 Password reg 2 acc to setting
8014 Control register < single bit >
8015 Confirm register < single bit >
2.4.1.40 Control structure 4
Table 185: Control structure 4
RegA Type Scale IEC 61850 name SA name Description Values
8016 Execute register 1
8017 Password reg 1 acc to setting
8018 Password reg 2 acc to setting
8019 Control register < single bit >
8020 Confirm register < single bit >
88 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.41 Control structure 5
Table 186: Control structure 5
RegA Type Scale IEC 61850 name SA name Description Values
8021 Execute register 1
8022 Password reg 1 acc to setting
8023 Password reg 2 acc to setting
8024 Control register < single bit >
8025 Confirm register < single bit >
2.4.1.42 Control structure 6
Table 187: Control structure 6
RegA Type Scale IEC 61850 name SA name Description Values
8026 Execute register 1
8027 Password reg 1 acc to setting
8028 Password reg 2 acc to setting
8029 Control register < single bit >
8030 Confirm register < single bit >
2.4.1.43 Control structure 7
Table 188: Control structure 7
RegA Type Scale IEC 61850 name SA name Description Values
8031 Execute register 1
8032 Password reg 1 acc to setting
8033 Password reg 2 acc to setting
8034 Control register < single bit >
8035 Confirm register < single bit >
2.4.1.44 Control structure 8
Table 189: Control structure 8
RegA Type Scale IEC 61850 name SA name Description Values
8036 Execute register 1
8037 Password reg 1 acc to setting
8038 Password reg 2 acc to setting
8039 Control register < single bit >
8040 Confirm register < single bit >
REF615 89
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.1.45 Device ID string
Table 190: Device ID string
RegA Type Scale IEC 61850 name SA name Description Values
9000 u16 ASCII coded string see doc.
...
9120 u16
2.4.1.46 IED Real-time clock (in local time mode) - read and write (synchronize)
Table 191: IED Real-time clock (in local time mode) - read and write (synchronize)
RegA Type Scale IEC 61850 name SA name Description Values
0..2 (see
9201 Control register doc.)
9202 Year 2000..2999
9203 Month 1..12
9204 Day 1..31
9205 Hour 0..23
9206 Minute 0..59
9207 Second 0..59
9208 Millisecond 0…999
2.4.1.47 IED real-time clock (in UTC time mode) - read and write (synchronize)
Table 192: IED real-time clock (in UTC time mode) - read and write (synchronize)
RegA Type Scale IEC 61850 name SA name Description Values
0..2 (see
9211 Control register doc.)
9212 Year 2000..2999
9213 Month 1..12
9214 Day 1..31
9215 Hour 0..23
9216 Minute 0..59
9217 Second 0..59
9218 Millisecond 0…999
90 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.4.1.48 Time and reason for latest IED reset
Table 193: Time and reason for latest IED reset
RegA Type Scale IEC 61850 name SA name Description Values
9221 u16 1 Year 2000..2999
9222 u16 1 Month 1..12
9223 u16 1 Day 1..31
9224 u16 1 Hour 0..23
9225 u16 1 Minute 0..59
9226 u16 1 Second 0..59
9227 u16 1 Millisecond 0…999
9228 u16 1 Reset reason
9228.0 Bit - bit 0 1=Cold start
9228.1 Bit - bit 1 1=Watchdog
9228.2 Bit - bit 2 1=Warm start
2.4.1.49 Event record structure
Table 194: Event record structure
RegA Type Scale IEC 61850 name SA name Description Values
Selection write:
9250 u16 1 - Num of multiple records 1..10
9251 i16 1 - Read selection -499…3
Record 1 data to read:
9252 u16 1 - Record sequence num 1..9999
9253 u16 1 - Unread records left 0..499
Timestamp of record
9254 u16 1 - Year, Month Year/Month
9255 u16 1 - Day, Hour Day/Hour
9256 u16 1 - Minute, Second Min/Sec
9257 u16 1 - Millisecond Millisecond
9258 u16 1 Event identification see doc.
9259 u16 1 Data object ID1 see doc.
9260 u16 1 Data object ID2 see doc.
9261 u16 1 Event data value 1 see doc.
9262 u16 1 Event data value 2 see doc.
Record 2 data to read: If selected
9263 u16 1 - Record sequence num 1..9999
Table continues on next page
REF615 91
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
9264 u16 1 - Unread records left 0..499
Timestamp of record
9265 u16 1 - Year, Month Year/Month
9266 u16 1 - Day, Hour Day/Hour
9267 u16 1 - Minute, Second Min/Sec
9268 u16 1 - Millisecond Millisecond
9269 u16 1 Event identification see doc.
9270 u16 1 Data object ID1 see doc.
9271 u16 1 Data object ID2 see doc.
9272 u16 1 Event data value 1 see doc.
9273 u16 1 Event data value 2 see doc.
Record 3 data to read: If selected
9274 u16 1 - Record sequence num 1..9999
9275 u16 1 - Unread records left 0..499
Timestamp of record
9276 u16 1 - Year, Month Year/Month
9277 u16 1 - Day, Hour Day/Hour
9278 u16 1 - Minute, Second Min/Sec
9279 u16 1 - Millisecond Millisecond
9280 u16 1 Event identification see doc.
9281 u16 1 Data object ID1 see doc.
9282 u16 1 Data object ID2 see doc.
9283 u16 1 Event data value 1 see doc.
9284 u16 1 Event data value 2 see doc.
Record 4 data to read: If selected
9285 u16 1 - Record sequence num 1..9999
9286 u16 1 - Unread records left 0..499
Timestamp of record
9287 u16 1 - Year, Month Year/Month
9288 u16 1 - Day, Hour Day/Hour
9289 u16 1 - Minute, Second Min/Sec
9290 u16 1 - Millisecond Millisecond
9291 u16 1 Event identification see doc.
9292 u16 1 Data object ID1 see doc.
9293 u16 1 Data object ID2 see doc.
9294 u16 1 Event data value 1 see doc.
9295 u16 1 Event data value 2 see doc.
Table continues on next page
92 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
Record 5 data to read: If selected
9296 u16 1 - Record sequence num 1..9999
9297 u16 1 - Unread records left 0..499
Timestamp of record
9298 u16 1 - Year, Month Year/Month
9299 u16 1 - Day, Hour Day/Hour
9300 u16 1 - Minute, Second Min/Sec
9301 u16 1 - Millisecond Millisecond
9302 u16 1 Event identification see doc.
9303 u16 1 Data object ID1 see doc.
9304 u16 1 Data object ID2 see doc.
9305 u16 1 Event data value 1 see doc.
9306 u16 1 Event data value 2 see doc.
Record 6 data to read: If selected
9307 u16 1 - Record sequence num 1..9999
9308 u16 1 - Unread records left 0..499
Timestamp of record
9309 u16 1 - Year, Month Year/Month
9310 u16 1 - Day, Hour Day/Hour
9311 u16 1 - Minute, Second Min/Sec
9312 u16 1 - Millisecond Millisecond
9313 u16 1 Event identification see doc.
9314 u16 1 Data object ID1 see doc.
9315 u16 1 Data object ID2 see doc.
9316 u16 1 Event data value 1 see doc.
9317 u16 1 Event data value 2 see doc.
Record 7 data to read: If selected
9318 u16 1 - Record sequence num 1..9999
9319 u16 1 - Unread records left 0..499
Timestamp of record
9320 u16 1 - Year, Month Year/Month
9321 u16 1 - Day, Hour Day/Hour
9322 u16 1 - Minute, Second Min/Sec
9323 u16 1 - Millisecond Millisecond
9324 u16 1 Event identification see doc.
9325 u16 1 Data object ID1 see doc.
Table continues on next page
REF615 93
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
9326 u16 1 Data object ID2 see doc.
9327 u16 1 Event data value 1 see doc.
9328 u16 1 Event data value 2 see doc.
Record 8 data to read: If selected
9329 u16 1 - Record sequence num 1..9999
9330 u16 1 - Unread records left 0..499
Timestamp of record
9331 u16 1 - Year, Month Year/Month
9332 u16 1 - Day, Hour Day/Hour
9333 u16 1 - Minute, Second Min/Sec
9334 u16 1 - Millisecond Millisecond
9335 u16 1 Event identification see doc.
9336 u16 1 Data object ID1 see doc.
9337 u16 1 Data object ID2 see doc.
9338 u16 1 Event data value 1 see doc.
9339 u16 1 Event data value 2 see doc.
Record 9 data to read: If selected
9340 u16 1 - Record sequence num 1..9999
9341 u16 1 - Unread records left 0..499
Timestamp of record
9342 u16 1 - Year, Month Year/Month
9343 u16 1 - Day, Hour Day/Hour
9344 u16 1 - Minute, Second Min/Sec
9345 u16 1 - Millisecond Millisecond
9346 u16 1 Event identification see doc.
9347 u16 1 Data object ID1 see doc.
9348 u16 1 Data object ID2 see doc.
9349 u16 1 Event data value 1 see doc.
9350 u16 1 Event data value 2 see doc.
Record 10 data to read: If selected
9351 u16 1 - Record sequence num 1..9999
9352 u16 1 - Unread records left 0..499
Timestamp of record
9353 u16 1 - Year, Month Year/Month
9354 u16 1 - Day, Hour Day/Hour
Table continues on next page
94 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
9355 u16 1 - Minute, Second Min/Sec
9356 u16 1 - Millisecond Millisecond
9357 u16 1 Event identification see doc.
9358 u16 1 Data object ID1 see doc.
9359 u16 1 Data object ID2 see doc.
9360 u16 1 Event data value 1 see doc.
9361 u16 1 Event data value 2 see doc.
2.4.1.50 Fault record structure header
Table 195: Fault record structure header
RegA Type Scale IEC 61850 name SA name Description Values
Selection write:
9401 i16 1 - Read selection -99…3
Record data header:
9402 u16 1 - Record sequence num 0..65535
9403 u16 1 - Unread records left 0..99
Timestamp of record
9404 u16 1 - Year, month Year/Month
9405 u16 1 - Day, hour Day/Hour
9406 u16 1 - Minute, second Min/Sec
9407 u16 1 - Millisecond Millisecond
9408 u16 1 - Timestamp quality see doc.
LD0.FLTMSTA1 Fault record data
9409 u32 1 .OpCnt.stVal - Fault record number (high) 0..999999
9410 - (low word)
9411 i16 1 .ProFnc.stVal - Protection function -32768..3276
7
9412 u16 100 .StrDur.mag - Start duration 0..100.00 [%]
9413 u32 1000 .OpTm.mag - Operate time [ms] (high) 0..999999.99
9
9414 - (low word)
9415 u16 1 .ActSG.stVal - Active setting group 1..6
9416 u16 1 .ShotPntr.stVal - AR shot pointer value 0..7
9417 u32 100 .FltZ.cVal.mag -Fault resistance 0.00…
1000000.00
ohms
9418 u32 100 .FltZ.cVal.mag -Fault resistance 0.00…
1000000.00
ohms
Table continues on next page
REF615 95
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
9419 u32 100 .FltDiskm.mag -Fault distance 0.00…
9999.99 pu
9420 u32 100 .FltDiskm.mag -Fault distance 0.00…
9999.99 pu
9421 u16 < reserved > 0
2.4.1.51 Fault record data
Table 196: Fault record data
RegA Type Scale IEC 61850 name SA name Description Values
LD0.FLTMSTA1
9422 u16 1000 .MaxAmpsA.mag Max phsA current 0..50.0 [xIn]
9423 u16 1000 .MaxAmpsB.mag Max phsB current 0..50.0 [xIn]
9424 u16 1000 .MaxAmpsC.mag Max phsC current 0..50.0 [xIn]
9425 u16 1000 .MaxAmpsN.mag Max residual current 0..50.0 [xIn]
9426 u16 1000 .AmpsA.mag PhsA current 0..50.0 [xIn]
9427 u16 1000 .AmpsB.mag PhsB current 0..50.0 [xIn]
9428 u16 1000 .AmpsC.mag PhsC current 0..50.0 [xIn]
9429 u16 1000 .AmpsN.mag Residual current 0..50.0 [xIn]
9430 u16 1000 .AmpsNClc.mag Residual current (calc) 0..50.0 [xIn]
9431 u16 1000 .AmpsPsSeq.mag Positive seq. current 0..50.0 [xIn]
9432 u16 1000 .AmpsNgSeq.mag Negative seq. current 0..50.0 [xIn]
9433 u16 1000 .VoltsA.mag PhsA voltage 0..4.00 [xUn]
9434 u16 1000 .VoltsB.mag PhsB voltage 0..4.00 [xUn]
9435 u16 1000 .VoltsC.mag PhsC voltage 0..4.00 [xUn]
9436 u16 1000 .VoltsAB.mag PhsAB voltage 0..4.00 [xUn]
9437 u16 1000 .VoltsBC.mag PhsBC voltage 0..4.00 [xUn]
9438 u16 1000 .VoltsCA.mag PhsCA voltage 0..4.00 [xUn]
9439 u16 1000 .VoltsN.mag Residual voltage 0..4.00 [xUn]
9440 u16 1000 .VZroSeq.mag Zero seq. voltage 0..4.00 [xUn]
9441 u16 1000 .VPsSeq.mag Positive seq. voltage 0..4.00 [xUn]
9442 u16 1000 .VNgSeq.mag Negative seq. voltage 0..4.00 [xUn]
9443 u16 1000 .VoltsAb.mag PhsAb voltage 0..4.00 [xUn]
9444 u16 1000 .VoltsABb.mag PhsABb voltage 0..4.00 [xUn]
9445 i16 10 .DifNAngN.mag Uo-Io angle -/+ 180.0
[Deg]
9446 i16 10 .DifAAngBC.mag PhsB-C angle -/+ 180.0
[Deg]
9447 i16 10 .DifBAngCA.mag PhsC-A angle -/+ 180.0
[Deg]
9448 i16 10 .DifCAngAB.mag PhsA-B angle -/+ 180.0
[Deg]
Table continues on next page
96 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
9449 u16 100 .Hz.mag Frequency 30..80.00 [Hz]
9450 i16 100 .HzS.mag Frequency gradient -/+10.00 [Hz/
s]
9451 u16 100 .PDNS1MxRat.mag PDNSPTOC1 ratio I2/I1 0..999.99 [%]
9452 u16 100 .MaxTmpRl.mag Relative temperature 0..99.99
9453 i16 10 .DifCAngABb.mag PhsA-Bb angle -/+ 180.0
[Deg]
9454 u16 1000 .CBClrTm.mag Breaker clear time 0.00…3.000
[s]
2.4.2 Unmapped registers
Unmapped registers are register data that have no initial Modbus mapping
locations, but can be added to the user-definable Modbus area using the
Communication Management tool in PCM600. The initial register type settings of
these objects have little meaning, since it is always possible to redefine the settings
completely for the user-definable register.
2.4.2.1 LD0.MDSOPT1 Generic operation time supervision (1)
Table 197: LD0.MDSOPT1 Generic operation time supervision (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.MDSOPT1
u16 1 .OpTmh.stVal OPR_TIME Total operation hours 0…299999
2.4.2.2 LD0.MVI4GAPC1 Multipurpose analog values (1)
Table 198: LD0.MVI4GAPC1 Multipurpose analog values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.MVI4GAPC1
-/+
i32 1 .ISCS01.stVal OUT1 - Integer value 1 (high) 2147483647
- Low word
-/+
i32 1 .ISCS02.stVal OUT2 - Integer value 2 (high) 2147483647
- Low word
-/+
i32 1 .ISCS03.stVal OUT3 - Integer value 3 (high) 2147483647
- Low word
-/+
i32 1 .ISCS04.stVal OUT4 - Integer value 4 (high) 2147483647
- Low word
REF615 97
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.4.2.3 LD0.SCA4GAPC1 Multipurpose analog values (1)
Table 199: LD0.SCA4GAPC1 Multipurpose analog values (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.SCA4GAPC1
i16 1000 .AnOut1.mag AO1_VALUE Analog value 1 -/+ 10000.00
i16 1000 .AnOut2.mag AO2_VALUE Analog value 2 -/+ 10000.00
i16 1000 .AnOut3.mag AO3_VALUE Analog value 3 -/+ 10000.00
i16 1000 .AnOut4.mag AO4_VALUE Analog value 4 -/+ 10000.00
2.4.2.4 LD0.SCERFLO1 Fault locator (1)
Table 200: LD0.SCERFLO1 Fault locator (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.SCERFLO1
0…
3000.0000
u16 1 .FltDiskm.mag FLT_DISTANCE Fault distance in pu [pu]
0…7 (see
u16 1 .FltLoop.stVal FAULT_LOOP Fault impedance loop doc)
0.0...1000000
u16 1 .FltPtR.mag RF Fault point resistance .0 [ohm]
0.0...1000000
u16 1 .FltR.mag RFLOOP Fault loop resistance .0 [ohm]
0.0...1000000
u16 1 .FltX.mag XFLOOP Fault loop reactance .0 [ohm]
0.0...1000000
u16 1 .PhReact.mag XFPHASE Fault phase reactance .0 [ohm]
u16 1 .RatFltALod.mag IFLT_PER_ILD Fault to load current ratio 0...60000.00
u16 1 .EqDisLod.mag S_CALC Est. load distance 0.00...1.00
0.0...1000000
u16 1 .PhGndCapac.mag XC0F_CALC Est. PhE capacitive reactance .0 [ohm]
u16 1 .FltDisQ.stVal FLT_DIST_Q Fault distance quality 0…511
2.4.2.5 LD0.VMMXU2 Voltage measurements (2)
Table 201: LD0.VMMXU2 Voltage measurements (2)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMMXU2 Phase-ground voltage (2)
u16 1000 .phV.phsA.cVal.mag U_DB_A - phsA amplitude 0.00..4.00
[xUn]
u16 1000 .phV.phsB.cVal.mag U_DB_B - phsB amplitude 0.00..4.00
[xUn]
u16 1000 .phV.phsC.cVal.mag U_DB_C - phsC amplitude 0.00..4.00
[xUn]
Table continues on next page
98 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
RegA Type Scale IEC 61850 name SA name Description Values
LD0.VMMXU2 Phase-phase voltage (2)
u16 1000 .PPV.phsAB.cVal.mag U_DB_AB - phsAB amplitude 0.00..4.00
[xUn]
u16 1000 .PPV.phsBC.cVal.mag U_DB_BC - phsAB amplitude 0.00..4.00
[xUn]
u16 1000 .PPV.phsCA.cVal.mag U_DB_CA - phsAB amplitude 0.00..4.00
[xUn]
2.4.2.6 LD0.XARGGIO130 RTD input values
Table 202: LD0.XARGGIO130 RTD input values
RegA Type Scale IEC 61850 name SA name Description Values
LD0.XARGGIO130
i16 1 .AnIn1.mag AI_VAL1 RTD input 1 in ohms -/+ 10000.00
i16 1 .AnIn2.mag AI_VAL2 RTD input 2 in ohms -/+ 10000.00
i16 1 .AnIn3.mag AI_VAL3 RTD input 3 in ohms -/+ 10000.00
i16 1 .AnIn4.mag AI_VAL4 RTD input 4 in ohms -/+ 10000.00
2.5 Controls
Table 203: Explanations of the controls table columns
Column name Description
0xA Coil (0X) address for control value.
CS Control structure and bit within the structure for control value.
IEC 61850 Original IED data object identification. Described in the IEC 61850 format as
name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Value Meaning of the written value.
2.5.1 CTRL.CBCSWI1 Circuit breaker (1) control
Table 204: CTRL.CBCSWI1 Circuit breaker (1) control
0xA CS IEC 61850 name SA name Description Values
CTRL.CBCSWI1
2048 1.00 .Pos.Oper.ctlVal Select open 1=Select
2049 1.01 .Pos.Oper.ctlVal Select close 1=Select
2050 1.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel
Table continues on next page
REF615 99
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
0xA CS IEC 61850 name SA name Description Values
2051 1.03 .Pos.Oper.ctlVal Execute selection 1=Execute
2052 1.04 .Pos.Oper.ctlVal Direct open 1=Open
2053 1.05 .Pos.Oper.ctlVal Direct close 1=Close
2.5.2 Reset, acknowledge and trigger points (A)
Table 205: Reset, acknowledge and trigger points (A)
0xA CS IEC 61850 name SA name Description Values
LD0.LLN0
2060 2.00 .LEDRs1.Oper.ctlVal Reset indications and LEDs 1=Reset
2061 2.01 .LEDRs2.Oper.ctlVal Reset Alarm LEDs 1=Reset
LD0.PEMSTA1
2062 2.02 .RecRs.Oper.ctlVal Reset Power max demands 1=Reset
LD0.DARREC1
2063 2.03 .RsRec.Oper.ctlVal Reset reclosing 1=Reset
2064 2.04 .RsCnt.ctlVal Reset reclosing counters 1=Reset
LD0.SSCBR1
2065 2.05 .RsAccAPwr.Oper.ctlVal Reset CB accum. energy 1=Reset
2066 2.06 .RsCBWear.Oper.ctlVal Reset CB wear data 1=Reset
DR.RDRE1
2067 2.07 .RcdTrg.Oper.ctlVal Trig DR recording 1=Trig
2068 2.08 .MemClr.Oper.ctlVal Clear DR memory 1=Clear
LD0.CMSTA1
2069 2.09 .RecRs.Oper.ctlVal Reset Max current1 demands 1=Reset
LD0.PEMMXU1
2070 2.10 .SupDmdRs.Oper.ctlVal Reset energy values 1=Reset
LD0.SCCBR1
2071 2.11 .RsTrvTm.Oper.ctlVal Reset CB travel time 1=Reset
2072 2.12 .RsSprChaTm.Oper.ctlV Reset CB spring charge time 1=Reset
al
LD0.RESCMSTA1
2073 2.13 .RecRs.Oper.ctlVal Reset Io (1) max demands 1=Reset
LD0.RESVMSTA1
2074 2.14 .RecRs.Oper.ctlVal Reset Uo (1) max demands 1=Reset
100 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
2.5.3 LD0.LPHD1 IED warm reset (1)
Table 206: LD0.LPHD1 IED warm reset (1)
0xA CS IEC 61850 name SA name Description Values
LD0.LPHD1
2080 3.00 .RsDev.Oper.ctlVal Warm reboot of IED 1=Reboot
2.5.4 LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops
Table 207: LD0.SRGAPC1 Reset SRGAPC1 generic flip-flops
0xA CS IEC 61850 name SA name Description Values
LD0.SRGAPC1
2096 4.00 .Rs1.Oper.ctlVal Reset flip-flop 1 1=Reset
2097 4.01 .Rs2.Oper.ctlVal Reset flip-flop 2 1=Reset
2098 4.02 .Rs3.Oper.ctlVal Reset flip-flop 3 1=Reset
2099 4.03 .Rs4.Oper.ctlVal Reset flip-flop 4 1=Reset
2100 4.04 .Rs5.Oper.ctlVal Reset flip-flop 5 1=Reset
2101 4.05 .Rs6.Oper.ctlVal Reset flip-flop 6 1=Reset
2102 4.06 .Rs7.Oper.ctlVal Reset flip-flop 7 1=Reset
2103 4.07 .Rs8.Oper.ctlVal Reset flip-flop 8 1=Reset
2.5.5 LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
Table 208: LD0.SRGAPC2 Reset SRGAPC2 generic flip-flops
0xA CS IEC 61850 name SA name Description Values
LD0.SRGAPC2
2104 4.08 .Rs1.Oper.ctlVal Reset flip-flop 1 1=Reset
2105 4.09 .Rs2.Oper.ctlVal Reset flip-flop 2 1=Reset
2106 4.10 .Rs3.Oper.ctlVal Reset flip-flop 3 1=Reset
2107 4.11 .Rs4.Oper.ctlVal Reset flip-flop 4 1=Reset
2108 4.12 .Rs5.Oper.ctlVal Reset flip-flop 5 1=Reset
2109 4.13 .Rs6.Oper.ctlVal Reset flip-flop 6 1=Reset
2110 4.14 .Rs7.Oper.ctlVal Reset flip-flop 7 1=Reset
2111 4.15 .Rs8.Oper.ctlVal Reset flip-flop 8 1=Reset
2.5.6 LD0.SPCGGIO1 Multipurpose binary outputs (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
REF615 101
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 209: LD0.SPCGGIO1 Multipurpose binary outputs (1)
0xA CS IEC 61850 name SA name Description Values
LD0.SPCGGIO1
2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2114 5.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2115 5.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2116 5.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
2117 5.05 .SPCS06.ctlVal Output 6 control 0/1=Off/On
2118 5.06 .SPCS07.ctlVal Output 7 control 0/1=Off/On
2119 5.07 .SPCS08.ctlVal Output 8 control 0/1=Off/On
2120 5.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On
2121 5.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On
2122 5.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On
2123 5.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On
2124 5.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On
2125 5.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On
2126 5.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On
2127 5.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On
2.5.7 LD0.SPCGGIO2 Multipurpose binary outputs (2)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 210: LD0.SPCGGIO2 Multipurpose binary outputs (2)
0xA CS IEC 61850 name SA name Description Values
LD0.SPCGGIO2
2128 6.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2129 6.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2130 6.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2131 6.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2132 6.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
2133 6.05 .SPCS06.ctlVal Output 6 control 0/1=Off/On
2134 6.06 .SPCS07.ctlVal Output 7 control 0/1=Off/On
2135 6.07 .SPCS08.ctlVal Output 8 control 0/1=Off/On
2136 6.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On
Table continues on next page
102 REF615
Point List Manual
1MRS756581 G Section 2
Modbus data mappings
0xA CS IEC 61850 name SA name Description Values
2137 6.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On
2138 6.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On
2139 6.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On
2140 6.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On
2141 6.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On
2142 6.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On
2143 6.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On
2.5.8 CTRL.DCCSWI1 Disconnector (1) control
Table 211: CTRL.DCCSWI1 Disconnector (1) control
0xA CS IEC 61850 name SA name Description Values
CTRL.DCCSWI1
2144 7.00 .Pos.Oper.ctlVal Select open 1=Select
2145 7.01 .Pos.Oper.ctlVal Select close 1=Select
2146 7.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2147 7.03 .Pos.Oper.ctlVal Execute selection 1=Execute
2148 7.04 .Pos.Oper.ctlVal Direct open 1=Open
2149 7.05 .Pos.Oper.ctlVal Direct close 1=Close
2.5.9 CTRL.DCCSWI2 Disconnector (2) control
Table 212: CTRL.DCCSWI2 Disconnector (2) control
0xA CS IEC 61850 name SA name Description Values
CTRL.DCCSWI2
2150 7.06 .Pos.Oper.ctlVal Select open 1=Select
2151 7.07 .Pos.Oper.ctlVal Select close 1=Select
2152 7.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2153 7.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2154 7.10 .Pos.Oper.ctlVal Direct open 1=Open
2155 7.11 .Pos.Oper.ctlVal Direct close 1=Close
REF615 103
Point List Manual
Section 2 1MRS756581 G
Modbus data mappings
2.5.10 CTRL.ESCSWI1 Earth switch (1) control
Table 213: CTRL.ESCSWI1 Earth switch (1) control
0xA CS IEC 61850 name SA name Description Values
CTRL.ESCXSWI1
2054 1.06 .Pos.Oper.ctlVal Select open 1=Select
2055 1.07 .Pos.Oper.ctlVal Select close 1=Select
2056 1.08 .Pos.Oper.ctlVal Cancel selection 1=Cancel
2057 1.09 .Pos.Oper.ctlVal Execute selection 1=Execute
2058 1.10 .Pos.Oper.ctlVal Direct open 1=Open
2059 1.11 .Pos.Oper.ctlVal Direct close 1=Close
104 REF615
Point List Manual
1MRS756581 G Section 3
Glossary
Section 3 Glossary
BIO Binary input and output
EMC Electromagnetic compatibility
Ethernet A standard for connecting a family of frame-based computer
networking technologies into a LAN
GOOSE Generic Object-Oriented Substation Event
HSO High-speed output
IEC International Electrotechnical Commission
IEC 61850 International standard for substation communication and
modeling
IED Intelligent electronic device
LHMI Local human-machine interface
Modbus A serial communication protocol developed by the Modicon
company in 1979. Originally used for communication in PLCs
and RTU devices.
PCM600 Protection and Control IED Manager
RTD Resistance temperature detector
REF615 105
Point List Manual
106
107
Contact us
1MRS756581 G © Copyright 2014 ABB. All rights reserved.
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
Fax +358 10 22 41094
ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone +91 265 2604032
Fax +91 265 2638922
www.abb.com/substationautomation