Data sheet for SINAMICS Power module PM230
Article No. : 6SL3210-1NE26-0UL0
Client order no. : Item no. : Figure similar
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Rated data Ambient conditions
Input Cooling Internal air cooling
Number of phases 3 AC Cooling air requirement 0.080 m³/s (2.825 ft³/s)
Line voltage 380 ... 480 V ±10 % Installation altitude 1,000 m (3,280.84 ft)
Line frequency 47 ... 63 Hz Ambient temperature
Rated current (LO) 56.00 A Operation LO 0 ... 40 °C (32 ... 104 °F)
Rated current (HO) 42.00 A Operation HO 0 ... 50 °C (32 ... 122 °F)
Output Transport -25 ... 55 °C (-13 ... 131 °F)
Number of phases 3 AC Storage -25 ... 55 °C (-13 ... 131 °F)
Rated voltage 400V IEC 480V NEC 1) Relative humidity
Rated power (LO) 30.00 kW 40.00 hp Max. operation 95 % RH, condensation not permitted
Rated power (HO) 22.00 kW 30.00 hp
Connections
Rated current (LO) 60.00 A
Line side
Rated current (HO) 45.00 A
Version M6 bolt
Max. output current 67.00 A
16.00 ... 35.00 mm²
Conductor cross-section
Pulse frequency 4 kHz (AWG 6 ... AWG 2)
Output frequency for vector control 0 ... 200 Hz Motor end
Output frequency for V/f control 0 ... 550 Hz Version M6 bolt
Overload capability 16.00 ... 35.00 mm²
Conductor cross-section
(AWG 6 ... AWG 2)
Low Overload (LO)
Max. motor cable length
1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of
300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time Shielded 25 m (82.02 ft)
of 300 s
Unshielded 100 m (328.08 ft)
High Overload (HO)
1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of Mechanical data
300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time Degree of protection IP20 / UL open type
of 300 s
Frame size FSD
General tech. specifications
Net weight 11.00 kg (24.25 lb)
Power factor λ 0.90
Dimensions
Offset factor cos φ 0.95
Width 275 mm (10.83 in)
Efficiency η 0.97
Height 419 mm (16.50 in)
Sound pressure level (1m) 60 dB
Depth 204 mm (8.03 in)
Power loss 0.68 kW
Filter class (integrated) -
Standards
Compliance with standards CE
CE marking Low-voltage directive 2006/95/EC
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Sat Mar 26 19:03:33 CET 2022
Data sheet for SINAMICS Power module PM230
Article No. : 6SL3210-1NE26-0UL0
Converter losses to IEC61800-9-2*
Efficiency class IE2
Comparison with the reference
41.10 %
converter (90% / 100%)
I 656.0 W (1.60 %) 728.0 W (1.80 %) 818.0 W (2.00 %)
100%
408.0 W (1.00 %) 439.0 W (1.10 %) 475.0 W (1.10 %)
50%
321.0 W (0.80 %) 336.0 W (0.80 %)
25%
50% 90% f
The percentage values show the losses in relation to the rated apparent power of
the converter.
The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator
frequency(f). The values are valid for the basic version of the converter without
options/components.
*converted values
1) The output current and HP ratings are valid for the voltage range 440V-480V
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Sat Mar 26 19:03:33 CET 2022