Circulating Current Test:: DIE 4B 115/13.8kV SS

1. The document reports on a circulating current test for a 115/13.8kV substation with transformers T1 and T2 run in parallel. 2. The test measured circulating current values with T1 and T2 at varying phase angles and voltage compensation settings to validate a compensation formula. 3. Results showed circulating current values from ±2.3A to ±328A with corresponding voltage compensation percentages ranging from 94.93% to 105.13%, validating the compensation formula.

Uploaded by

Vinod Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views1 page

Circulating Current Test:: DIE 4B 115/13.8kV SS

1. The document reports on a circulating current test for a 115/13.8kV substation with transformers T1 and T2 run in parallel. 2. The test measured circulating current values with T1 and T2 at varying phase angles and voltage compensation settings to validate a compensation formula. 3. Results showed circulating current values from ±2.3A to ±328A with corresponding voltage compensation percentages ranging from 94.93% to 105.13%, validating the compensation formula.

Uploaded by

Vinod Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

Contract No: 4400005948 Contractor: NCC

AVR (ZIV) FAINAL SETTING TEST REPORT (T/T2 Parallel) Client: National Grid SA

DIE 4B 115/13.8kV SS Sheet : Page 1 of 1


Panel No :RTCC.1 / RTCC.2 CONTROL ROOM

Circulating Current Test:

VComp (%) = VCON (%) + KR (%). (Icirc-sec / 0.1 In)

Circulating Current for the case T1 and T2 in parallel condition:

Kr=4.4% CTR:2803/1 VTR:120


Voltage Input: VRY Current Input: IY Correction angle:210
BW=2.0
I circulating =I1Sinⱷ1-I2sinⱷ2
=1*sin(246.5-240)-1*sin(240-240)
=0.113=2803*0.113= +141.8A(T1)
= -141.8A(T2)
T2 P
Sl. T1 L T2-Vcomp
PARALLE T1-Icir T2- Icir T1-Vcomp (%)
No LOCAL (%)
L

1 1 242.9º 1 240º 140 -141 102.19 97.79

2 1 240º 1 240º 6.7 -7.3 100.09 99.70

3 1 240º 1 242.9º -145.0 143.1 97.75 102.27

4 1 242.9º 1 242.9º 2.3 -3.3 100.05 99.75

5 1 242.9º 1 62.9º 326.1 -322.9 105.11 94.93

6 1 62.9º 1 242.9º -328.0 327.1 94.85 105.13

Test Equipment:
1-Freja 300
S.NO:1302708
CAL.EXPIRY:26.9.2017
2-Multimeter FLUKE
S.NO:30850238
CAL.EXPIRY:17.11.2017

TESTING ENGINEER CSD- Engineer


Signature: ________________ Signature: ________________
Name : VINODE KUMAR(XER-062) Name : ZULQARNAIN MUSHTAQ