HVAC Budget for Unimart Project
HVAC Budget for Unimart Project
SHORT DESCRIPTION
SL. NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Total Am
Imported material Local material Installation
SHORT DESCRIPTION
Price Price Price
Chiller 7,108,051.00
AHU & FCU 8,497,006.00
Pump 9,238,200.00
Cooling Tower 4,000,000.00
Central Monitoring System
Pipe & accessories 3,193,060.98
Pipe Insulation 686,212.78
Room Thermostat 1,280,027.00
Drain Pipe with insulation 96,820.00
VALVE ACCESSORIES 4,394,205.39
Ventilation Fan 2,991,080.00
Air Terminal 1,042,888.01 1005795
Ducting Work 5,148,128.52 48667.5
Electromagnetic Flow Meter: -
EXPANSION TANK (Close Type) : 328,700.00
WATER SOFTNER PLANT : 908,250.00
Dirt and Air separator : 2,175,475.00
MAKE-UP WATER TANK WITH
55,000.00
FLOAT VALVE:
Chemical Dosing System: 198,950.00
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
The motor for only secondary Chilled Water Pumps shall be suitable for use
with Variable Frequency Drive (Only for secondary pump). The motor shall be
-
screen protected drip proof (SPDP) and TEFC type. The efficiency class of
motors shall be IE 4 (Premium Efficiency) class as per IEC 60034-30 (2008).
Cooling tower shall be Induced draft counter flow type. It shall be complete with
make-up water valve, Float assembly, access door, Motor, Fan, Eliminators,
steel support, HDG ladder etc. Cooling Tower details along with accessories -
shall comply accordance with CTI/JCI Certification Standard STD-201 and
specification, the energy efficiency requirements of ASHRAE Standard 90.1.
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Supply, installation, testing & commissioning of low height and low noise
Indoor Unit with all necessary accessories and fittings, Fixing for
commissioning of the equipment including return filter , electrical terminal box -
and all other electrical & Civil works as follows technical specification, drawing
and time to time site instruction from Consultant / Owner.
-
6.1 Fan Coil Unit (Ducted type)with Drain Water Pump : -
Required Cooling Capacity 2.5 TR, ESP 50 Pa (Height less than 240mm) 90 Nos. 26,296.00 2,366,640.0 0
Required Cooling Capacity 3.0 TR, ESP 50 Pa (Height less than 240mm) 4 Nos. 26,296.00 105,184.0 0
Required Cooling Capacity 4.0 TR, ESP 50 Pa (Height less than 240mm) 3 Nos. 32,870.00 98,610.0 0
Required Cooling Capacity 5.0 TR, ESP 50 Pa (Height less than 300mm) 7 Nos. 34,600.00 242,200.0 0
Required Cooling Capacity 5.5 TR, ESP 50 Pa (Height less than 300mm) 21 Nos. 34,600.00 726,600.0 0
Required Cooling Capacity 6.0 TR, ESP 50 Pa (Height less than 300mm) 10 Nos. 34,600.00 346,000.0 0
-
6.2 Fan Coil Unit (Cassette type) : -
Required Cooling Capacity 1.5 TR 5 Nos. 17,300.00 86,500.0 0
Required Cooling Capacity 3.0 TR 4 Nos. 22,490.00 89,960.0 0
- 0
6.3 Fan Coil Unit (Wall Type) : - 0
Required Cooling Capacity 1.5 TR 2 Nos. 17,992.00 35,984.0 0
- 0
6.4 Pre Cooled Unit(Slim Type, Low height & Low Noise,E.S.P 80 Pa) - 0
600 CFM(4TR) 3 Nos. 40,000.00 120,000.0 0
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
-
6.4 Split Type (Wall Mounted Unite): -
-
9.0 Drain Pipe with Insulation: -
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Supply, installation, testing & commissioning of Ball / Butter fly valve shall be
lever-operated type, anti corrosive cast iron body. All should be comply with
-
specification Valve upto 80mm dia shall be welded socket ball type complete
with companion flanges, nut-bolt, gasket etc.
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Supply, installation, testing & commissioning of Automatic vent valve with ball
valve shall be free floating type having test cock, 20 mm threaded outlets to 15 Nos. 349.8 5,247.6
accept drain line and threaded inlet connection. Vent valve shall be 20-mm size.
0
Brand: Tozen, Kitz or equivalent -
-
11.0 METERING DEVICE : -
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Supply & Installation of ceiling mounted Impulse Two speed type jet fans are
suitable for ventilation of larger buildings where space limitaiton is substantial
and duct work should be avoided. By adding momentum to the air the jet vent
thrusts air to the desired point and generates comfort velocity. Each fan shall be
complete with dual speed motor, casing made of sheet steel duly MS Powder
coated, die cast aluminium impeller, mounting arrangements, Powder coated
-
mild steel outlet deflector and zinc plated inlet guard with silencer. Fans shall be If not available in
capable of delivering 2800 cfm air against a minimum thrust of 86N at full load local market
and 2800 cfm air against a minimum thrust of 22N to successfully throw the air
in the entire region. Fan frame shall be constructed from galvanised steel with a
alluminium alloy impeller. Fans ball bearings shall be sealed for lifetime & Low
Noise type(Sound level shoud be maintain less than 60db at 1m distance)
0
Capacity : 2800 cfm 3 Nos. 92,555.00 277,665.0 0
Capacity : 2800 cfm (For Basement) 4 Nos. 92,555.00 370,220.0 0
-
15.0 Air Terminal : -
Supply & installation of Air terminal with necessary frame,fitting,gasket and
-
adjustment items.
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
-
15.1 Supply Air Grille -
Supply & installation of Aluminum Louvered ceiling Diffuser with back damper
and plenum shall be selected to confirm face for adjustable horizontal discharge
airflow. At typical flow rates, isothermal throws of 6 to 16 feet with 37 NC
level . The diffuser shall have an easily removable core with fixed blades in 1, 2,
3, or 4-way configurations. The manufacturer shall provide published (printed or
electronic) performance data for the diffuser. The diffuser shall be tested in
-
accordance to the data standards at the time of product introduction or
ANSI/ASHRAE Standard 70.
Linear slot diffuser, plenum shall be attached to the linear by means of spring
clips to allow for plenum removal without use of special tools.Selection chart
should be provided based on required CFM which are indicated in drawing to
get approval.
Brand: Systemair, TROX, Titus, Price, Ruskin, Halton or equivalent - If available in local
market &Selected
-
by Architect
Neck Size: 4975 x 200 mm 3 Nos. 8,304.00 26,942.3
Neck Size: 400 x 400 mm 20 Nos. 1,332.10 28,813.3
Neck Size: 450 x 450 mm 91 Nos. 1,660.80 163,450.1
Neck Size: 1500 x 100 mm 0 Nos. 1,427.25 -
Neck Size: 1525 x 75 mm 35 Nos. 1,159.10 43,874.8
Neck Size: 1375 x 75 mm 4 Nos. 2,032.75 8,793.7
Neck Size: 1200 x 100 mm 232 Nos. 1,081.25 271,294.3
Neck Size: 1675 x 75 mm 4 Nos. 1,297.50 5,613.0
Neck Size: 900 x 200 mm 0 Nos. 1,531.05 -
Neck Size: 900 x 100 mm 22 Nos. 899.60 21,404.2
Neck Size: 600 x 100 mm 75 Nos. 726.60 58,936.3
Neck Size : Dia 300 mm(Round Diffuser) 58 Nos. 1,055.30 66,195.8
Neck Size: 300 x 300 mm 11 Nos. 1,591.60 18,934.5
Neck Size: 1200 x 150 mm 0 Nos. 1,584.00 -
Neck Size: m² 0 m² -
15.2 Fresh Air Louver With insect screen and Washable Filter: -
Neck Size: 400 x 200 mm 3 Nos. 808.78 2,624.1
Neck Size: 600 x 350 mm 1 Nos. 1,848.00 1,998.6
Neck Size: 1200 x 450 mm 1 Nos. 4,752.00 5,139.3 If available in local
market &Selected
Neck Size: 120 x 250 mm (For Basement) 4 Nos. 264.00 1,142.1 by Architect
-
-
15.3 Exhaust Air Louver With insect screen: -
Supply, installation, testing & commissioning of extruded aluminium Exhaust
Air Louver With insect screen terminal with mat finishing of approved colour on
the air distribution duct line /coller / ceiling etc. including supply and -
installation of necessary fixing screw, gasket , necessary insulation( if required)
etc.
If available in local
Neck Size: 450 x 250 mm 3 Nos. 990.00 3,212.1 market &Selected
Neck Size: 600 x 450 mm 1 Nos. 2,768.00 2,993.6 by Architect
Neck Size: 1200 x 600 mm 1 Nos. 6,336.00 6,852.4
Neck Size: 600 x 250 mm 0 Nos. 1,320.00 -
Neck Size: 120 x 250 mm (For Basement) 4 Nos. 264.00 1,142.1
Neck Size: m² 20 m² -
-
15.4 Return Air Liner Bar Grille : -
Neck Size: 350 x 350 mm 4 Nos. 631.45 2,731.7
Neck Size: 300 x 300 mm 0 Nos. 484.40 -
Neck Size: 1200 x 500 mm 21 Nos. 986.10 22,395.8 If available in local
Neck Size: m² 0 m² - market &Selected
- by Architect
15.5 Service Door With Return Grill : -
Neck Size: 600 x 600 mm 93 Nos. 2,768.00 278,404.1
-
16.0 DUCT WORK: -
Supply, fabrication and installation of galvanized sheet steel duct work complete
with bends, Tees, reducers, branch takeoffs, air chamber etc. as per direction and
drawing. Hangers, brackets, stiffeners and isolator boxes shall be fabricated with
M.S. angle/F.I. bar or rod as per drawing and direction and shall be galvanized.
Duct shall be constructed with best-bloomed galvanized sheet steel. Before
- For center fresh air
installation of duct, inside and outside shall be cleaned from any dust. Between
flanges, for flanged end duct, approved type of gasket shall be used. Approved duct
type of sealing compound shall be used to make the duct work leak-proof. Duct
shall be hanged or supported at an interval of not more than 1.8 meter.
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Supply and installation of opposed blade type Non return damper constructed
with 18 BWG sheet steel painted with two coats of synthetic black paint. The
damper shall have adjustable locking arrangement with worm gear operable
50 sqm 9,300.00 502,897.5
from outside duct work and shall be flanged end type suitable to mount on
flanged end duct work. Non return dampers shall be as per layout drawings and
direction.
Supply of Electromagnetic flow meter for constant measuring flow of the piping
system shall be constructed from high grade steel / alloy steel with flange end,
leak proof gasket ,suitable for working pressure up to 300 psig and complete -
with SENSORPROM unit for automatically uploads calibration values and
setting ete compatible operation of BMS etc.
The price shall be included all chemical items for one year. -
The design parameter shall be fixed based on the water quality and test report. -
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
Construction material -
Shell: Carbon Steel
-
Coalescing Medium: Stainless Steel
Maximum working pressure 150 Psig -
Flow rate= 1680 US GPM -
-
25.0 MAKE-UP WATER TANK WITH FLOAT VALVE: 1 Set. 55,000.0 59,482.5
Brand:Carno or equivalent -
-
26.0 Chemical Dosing System: 1 Set. 198,950.0 198,950.0 0
Supply of include with auto feed type suitable to handle of chilled water to
control corrosion, scale and biological effect and shall be complete with dosing
- if not available in
pumps, sensor, control valves, PVC tubes and tube fittings for chemical feed, pH
analyzer and indicator etc. complete. local market
System handling capacity is 210 gpm and residual head- 20 meter after filtration. -
Performance Test / Check at Factory (or PSI) : Before shipment the main
product vendor/contractor should arrange the Performance test arrangement for
the main product at Manufacturer factory lab for Consultant and Client 1 Job -
person.There should have testing arrangement as per standard procedure at
factory test facility area .chiller test should perform as per AHRI condition.
-
29.0 Cladding of Pipe: 200 sqm - #REF!
AS PER
UNIT RATE Imported TOTAL Local TOTAL
SL. NO. SHORT DESCRIPTION DWG. UNIT REMARKS
(BDT) AMOUNT (BDT) AMOUNT (BDT)
QTY
-
33.0 Chilled Water Balancing: 1 Job -
Chilled water balancing shall apply a disciplined procedure of adjustment to
water flow rates throughout the chilled water system to meet the particular
requirement of the design drawing. Following but not limited to should be -
followed during balancing
All testing and commissioning works must be documented room wise/zone wise
in approved formats. All of these document's must be jointly witnessed and -
signed by the Client and Contractor's authorized Engineer.
-
35.0 Engineering Team : Start from Mobilization 1 Job -
Senior engineer with design knowledge to prepare modification , reporting and
-
perform meeting( Should be conversant in English)
Site Supervisor Engineer, construction management team , drafting and drawing
-
preparation team.
Team also be capable of prepare shop drawing, and as built drawing, time to
-
time approval from consultant or project authorized person from client
-
36.0 DOCUMENTATION : 1 Job -
Detail layout and fabrication drawing shall be prepared as per guide line layout
drawing and shall be submitted for approval. Modification drawing shall be
prepared as per site condition. Layout drawings shall be coordinated with other
services. Required section and detail shall be prepared. Construction work shall
-
be done as per approved working drawings. Compilation of all the document
such as built drawing, testing, commissioning & balancing report, operation and
maintenance manuals etc. shall be done as per direction. Drawings shall be
prepared on Auto Cad.
-
37.0 OPERATION AND MAINTENANCE: Year -
The motor for only secondary Chilled Water Pumps shall be suitable for use
with Variable Frequency Drive (Only for secondary pump). The motor shall be
-
screen protected drip proof (SPDP) and TEFC type. The efficiency class of
motors shall be IE 4 (Premium Efficiency) class as per IEC 60034-30 (2008).
Cooling tower shall be Induced draft counter flow type. It shall be complete with
make-up water valve, Float assembly, access door, Motor, Fan, Eliminators,
steel support, HDG ladder etc. Cooling Tower details along with accessories -
shall comply accordance with CTI/JCI Certification Standard STD-201 and
specification, the energy efficiency requirements of ASHRAE Standard 90.1.
Supply, installation, testing & commissioning of low height and low noise
Indoor Unit with all necessary accessories and fittings, Fixing for
commissioning of the equipment including return filter , electrical terminal box -
and all other electrical & Civil works as follows technical specification, drawing
and time to time site instruction from Consultant / Owner.
Selected unit shall maintain Noise Criteria not more than 42 and low height units -
-
6.1 Fan Coil Unit (Ducted type)with Drain Water Pump : -
Required Cooling Capacity 2.5 TR, ESP 50 Pa (Height less than 240mm) 88 Nos. 2,000.00 176,000.0
Required Cooling Capacity 3.0 TR, ESP 50 Pa (Height less than 240mm) 4 Nos. 2,500.00 10,000.0
Required Cooling Capacity 4.0 TR, ESP 50 Pa (Height less than 240mm) 3 Nos. 3,000.00 9,000.0
Required Cooling Capacity 5.0 TR, ESP 50 Pa (Height less than 300mm) 7 Nos. 3,500.00 24,500.0
Required Cooling Capacity 5.5 TR, ESP 50 Pa (Height less than 300mm) 21 Nos. 4,000.00 84,000.0
Required Cooling Capacity 6.0 TR, ESP 50 Pa (Height less than 300mm) 10 Nos. 5,000.00 50,000.0
-
6.2 Fan Coil Unit (Cassette type) : -
Required Cooling Capacity 1.5 TR 6 Nos. 1,500.00 9,000.0
Required Cooling Capacity 3.0 TR 4 Nos. 2,500.00 10,000.0
-
6.3 Fan Coil Unit (Wall Type) : -
Required Cooling Capacity 1.5 TR 2 Nos. 1,500.00 3,000.0
-
6.4 Pre Cooled Unit(Slim Type, Low height & Low Noise,E.S.P 80 Pa) -
600 CFM(4TR) 3 Nos. 1,200.00 3,600.0
-
6.4 Split Type (Wall Mounted Unite): -
Supply, installation, testing & commissioning of split type Air-cooler
comprising condensing and evaporating units having following cooling
capacity based on indoor temperature 18ºC-24ºC DB and outdoor -
temperature 35º-40ºC DB at high fan speed condition suitable for
installation & operation in tropicalized country like Bangladesh.
-
9.0 Drain Pipe with XLPE Insulation: -
Supply, installation, testing & commissioning of Ball / Butter fly valve shall be
lever-operated type, anti corrosive cast iron body. All should be comply with
-
specification Valve upto 80mm dia shall be welded socket ball type complete
with companion flanges, nut-bolt, gasket etc.
Supply, installation, testing & commissioning of Automatic vent valve with ball
valve shall be free floating type having test cock, 20 mm threaded outlets to 15 Nos. 650.0 9,750.0
accept drain line and threaded inlet connection. Vent valve shall be 20-mm size.
Brand: Tozen, Kitz or equivalent -
-
11.0 METERING DEVICE : -
12000 CFM, Fresh Air Fan , ESP 150 Pa.( for.Stair case) 1 Nos. 5,000.00 5,000.0
-
14.6 Jet Fan with silencer: -
Supply & Installation of ceiling mounted Impulse Two speed type jet fans are
suitable for ventilation of larger buildings where space limitaiton is substantial
and duct work should be avoided. By adding momentum to the air the jet vent
thrusts air to the desired point and generates comfort velocity. Each fan shall be
complete with dual speed motor, casing made of sheet steel duly MS Powder
coated, die cast aluminium impeller, mounting arrangements, Powder coated
-
mild steel outlet deflector and zinc plated inlet guard with silencer. Fans shall be
capable of delivering 2800 cfm air against a minimum thrust of 86N at full load
and 2800 cfm air against a minimum thrust of 22N to successfully throw the air
in the entire region. Fan frame shall be constructed from galvanised steel with a
alluminium alloy impeller. Fans ball bearings shall be sealed for lifetime & Low
Noise type(Sound level shoud be maintain less than 60db at 1m distance)
Supply & installation of Aluminum Louvered ceiling Diffuser with back damper
and plenum shall be selected to confirm face for adjustable horizontal discharge
airflow. At typical flow rates, isothermal throws of 6 to 16 feet with 37 NC
level . The diffuser shall have an easily removable core with fixed blades in 1, 2,
3, or 4-way configurations. The manufacturer shall provide published (printed or
electronic) performance data for the diffuser. The diffuser shall be tested in
-
accordance to the data standards at the time of product introduction or
ANSI/ASHRAE Standard 70.
Linear slot diffuser, plenum shall be attached to the linear by means of spring
clips to allow for plenum removal without use of special tools.Selection chart
should be provided based on required CFM which are indicated in drawing to
get approval.
Supply, fabrication and installation of galvanized sheet steel duct work complete
with bends, Tees, reducers, branch takeoffs, air chamber etc. as per direction and
drawing. Hangers, brackets, stiffeners and isolator boxes shall be fabricated with
M.S. angle/F.I. bar or rod as per drawing and direction and shall be galvanized.
Duct shall be constructed with best-bloomed galvanized sheet steel. Before
-
installation of duct, inside and outside shall be cleaned from any dust. Between
flanges, for flanged end duct, approved type of gasket shall be used. Approved
type of sealing compound shall be used to make the duct work leak-proof. Duct
shall be hanged or supported at an interval of not more than 1.8 meter.
Supply and installation of opposed blade type Non return damper constructed
with 18 BWG sheet steel painted with two coats of synthetic black paint. The
damper shall have adjustable locking arrangement with worm gear operable
50 sqm 3,228.00 161,400.0
from outside duct work and shall be flanged end type suitable to mount on
flanged end duct work. Non return dampers shall be as per layout drawings and
direction.
Supply of Electromagnetic flow meter for constant measuring flow of the piping
system shall be constructed from high grade steel / alloy steel with flange end,
leak proof gasket ,suitable for working pressure up to 300 psig and complete -
with SENSORPROM unit for automatically uploads calibration values and
setting ete compatible operation of BMS etc.
The price shall be included all chemical items for one year. -
The design parameter shall be fixed based on the water quality and test report. -
Capacity :50 gpm -
Operating pressure - 3.5 + 0.5 Kg/cm2 -
Testing pressure - 10 Kg/cm2 -
Input water hardness - 100 ppm or design as per parameter -
Outlet water hardness - Not exceeding 20 ppm or design as per parameter -
Regeneration Cycle - 24 hours -
Brand: -
Country of Manufacture: -
Country of Origin: -
-
24.0 Dirt and Air separator : 2 Nos. 3,500.0 7,000.0
Supply, installation, testing and commissioning of dirt and air separator with
proper sized shutoff valve at both end in a combination of air & sediment
separator that utilizes a coalescing medium to remove impurities from HVAC
systems. It features a stainless steel coalescing medium with 58% open area,
removable end cover for coalescing medium -
access, and connections for an air vent, blow down valve, and skim valve. The
product is designed, constructed, inspected and
stamped per ASME Section VIII, Division 1
Construction material -
Shell: Carbon Steel
Coalescing Medium: Stainless Steel -
Maximum working pressure 150 Psig -
Flow rate= 1680 US GPM -
-
25.0 MAKE-UP WATER TANK WITH FLOAT VALVE: 1 Set. 5,000.0 5,000.0
Supply, installation, testing & commissioning of high quality PVC/Plastic make-
up water Tank along with adequately rated make-up water pump, for make-up of
water for cooling towers. The tank shall have connection for, feed water line, -
overflow line, drain line etc. complete in all respect. Cooling Tower Capacity
1680 GPM
Brand:Carno or equivalent -
-
26.0 Chemical Dosing System: 1 Set. 7,500.0 7,500.0
Supply of include with auto feed type suitable to handle of chilled water to
control corrosion, scale and biological effect and shall be complete with dosing
-
pumps, sensor, control valves, PVC tubes and tube fittings for chemical feed, pH
analyzer and indicator etc. complete.
Brand: Microdos/ Nalco/ X-Pot or equivalent -
-
27.0 Side Stream Filter System: 1 Set. 12,500.0
Supply, installation, testing & commissioning of side stream filter system
include with Pump and accessories to ensure continuously filter a portion of
cooling water to remove debris and particles. Side stream filtration requires a
minimum supply pressure to account for the inherent differential pressure drop
-
across the filter typically ranges from 20 to 30 psi. All side stream filters have a
maximum working pressure; sand filters have a threshold of 80 psi. Systems
require cleaning of filters or holding chambers to remove debris and particles
that are trapped in filters.
System handling capacity is 100 gpm and residual head- 20 meter after filtration. -
-
33.0 Chilled Water Balancing: 1 Job 70,000.0
Chilled water balancing shall apply a disciplined procedure of adjustment to
water flow rates throughout the chilled water system to meet the particular
requirement of the design drawing. Following but not limited to should be -
followed during balancing
All testing and commissioning works must be documented room wise/zone wise
in approved formats. All of these document's must be jointly witnessed and -
signed by the Client and Contractor's authorized Engineer.
-
35.0 Engineering Team : Start from Mobilization 1 Job -
Senior engineer with design knowledge to prepare modification , reporting and
-
perform meeting( Should be conversant in English)
Site Supervisor Engineer, construction management team , drafting and drawing
-
preparation team.
Team also be capable of prepare shop drawing, and as built drawing, time to
-
time approval from consultant or project authorized person from client
-
36.0 DOCUMENTATION : 1 Job -
Detail layout and fabrication drawing shall be prepared as per guide line layout
drawing and shall be submitted for approval. Modification drawing shall be
prepared as per site condition. Layout drawings shall be coordinated with other
services. Required section and detail shall be prepared. Construction work shall
-
be done as per approved working drawings. Compilation of all the document
such as built drawing, testing, commissioning & balancing report, operation and
maintenance manuals etc. shall be done as per direction. Drawings shall be
prepared on Auto Cad.
-
37.0 OPERATION AND MAINTENANCE: 2 Year -