HGP HT: Technical Manual
HGP HT: Technical Manual
O
C
L
E
Y
RE
S
A
F
G R
T IG
RA N E
HGP HT
AIR-WATER
65 .0
HEAT PUMPS
FOR INDOOR INSTALLATION
TECHNICAL MANUAL
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
2
TABLE OF CONTENTS
GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - VERY HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
NOMINAL performances - STANDARD plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
NOMINAL performances - RADIANT plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Source side aeraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
DESUPERHEATER performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3
4
GENERAL FEATURES
Unit description
This series of air-water heat pumps satisfies the heating, coo- flow to simplify the maintenance operations, is equipped with
ling and domestic hot water production requirements of autono- two scroll compressors mounted on damper supports, brazed
mous or centralized residential plants of medium and large size. plate heat exchangers, electronic expansion valve, reverse
All the units are suitable for indoor installation. The possibiliy to cycle valve, centrifugal fans (plug fans), finned coil realized with
produce water at high temperatures makes these units particu- copper pipes and alluminium fins. The circuit is protected by high
larly suitable to be applied to radiators plants as well as to fan and low pressure switches and flow switches on the plate heat
coil plants and radiant floor plants. exchanger.
The control system allows to manage not only the refrigerant The compressors are arranged in tandem on a single refrigerant
circuit but the whole plant with the possibility to choose different circuit and allow the capacity modulation according to the plant
solutions both for the heating and cooling plant and for the do- requests in order to guarantee a high seasonal efficiency.
mestic hot water management. The possibility of solar panels or Both the compressors are equipped with vapour and liquid
other heating sources integration is also available. injection and are placed on an economized refrigerant circuit with
The heating function optimizes the flow water temperature ac- plate heat exchanger and electronic expansion valve dedicated
cording both to the ambient temperature and to the outdoor tem- to the injection.
perature through climatic curves adaptable to the building featu- The plate heat exchanger and all the hydraulic pipes are ther-
res. It’s possible to manage a storage tank and two independent mally insulated in order to avoid condensate generation and re-
circuits (a direct one and a mixed one). duce thermal losses.
The domestic hot water management allows to control the th- The plug fans with electronic control of the rotational speed gua-
ree way valve, the storage tank and the anti-legionella cycles (if rantee high efficiencies and low noise in all the operating condi-
necessary). tions and allow to install the unit indoor (with ducted air inlet and
The cooling function can be realized through “active cooling” outlet). It is moreover possible to reduce the noise level during
(refrigerant circuit inversion). When the unit is used in radiant the night.
floor plants, to avoid condensate generation, a room humidity All the units are provided with a phase sequence and correct se-
sensor can be installed. During cooling mode operation a part of quence controller device and with an outdoor temperature sensor
the heating power in excess can be recovered for the domestic in order to realize the climatic control.
hot water production (VD version). All the units are accurately built and individually tested in the
The internal programmer clock allows to define different daily factory. Only electric and hydraulic connections are required for
switching programs for heating, cooling and domestic hot water installation.
production.
The refrigerant circuit, contained in a box repaired from the air
The codes that identify the units and the meaning of the letters used are described below.
HGP HT IP 80.2 VB AB 0 H 5
Power supply
H - High temperature.
The unit is suitable to produce
water at high temperature
Unit model
Refrigerant type
N° compressors
0 - R410A
5
GENERAL FEATURES
Description of components
External structure. Basement, supporting structure and lateral The refrigerant circuit of each unit contains moreover solid
panels are made of galvanized and painted sheet-steel to core hermetic filter dryer (5) to restrain impurity and moisture
guarantee good resistance to atmospheric agents. Accessibility residuals that could be present in the circuit, high and low
to internal parts is possible removing the frontal and lateral pressure switches in order to assure the compressor to
panels. For extraordinary manteinances also the other panels operate inside the permitted limits, 4 way reverse cycle valve
can be removed. (6) to allow operating mode change reversing the refrigerant
Refrigerant circuit. It is contained inside a compartment flow, liquid receiver (7) to compensate the different refrigerant
separated from the air flow to simplify maintenance and control charge required in heating and in cooling mode and pressure
operations. connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket
and blind nut, as required for the use of R410A refrigerant (they
allow the complete check of the refrigerant circuit: compressor
inlet pressure, compressor outlet pressure and expansion valve
upstream pressure). All the pipes of the refrigerant circuit are
properly insulated to avoid condensate generation and minimize
thermal losses
The plug fans (8) are equipped with an high efficiency
electronically commutated (EC) motor and guarantee enough
available static pressure to allow the indoor ducted installation
besides high efficiencies in all the operating conditions.
Hydraulic circuit. All the pipes are thermally insulated to avoid
condensate generation and minimize thermal losses. The circuit
can be equipped with a standard, high head or modulating
circulation pump (option). The circuit is always equipped also
with expansion vessel, safety valve and air vents.
Electrical panel. It contains all the power, control and security
components necessary to guarantee the unit to work properly.
The unit is managed by a microprocessor controller to which
all the electrical loads and the control devices are connected.
The user interface, to be placed indoor, allows to view and to
modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor,
to be installed outside, in order to realize the climatic control.
The scroll compressors (1) are mounted on damper supports
and are protected against overtemperatures and overcurrents.
Each compressor is equipped with an electrcal heater, that is
activated when the compressor turns off, to keep the compressor
crankcase oil temperature high enough to prevent migration of
the refrigerant during winter stops and to evaporate any liquid
8
present in the crankcase, in order to prevent possible liquid
rushes on starting.
3
Both the compressors are equipped with vapour and liquid
injection and are placed on an economized refrigerant circuit
with plate heat exchanger and electronic expansion valve
dedicated to the injection.
The plant side heat exchanger (2) is a brazed stainless steel
plate heat exchanger, properly insulated to avoid condensate
generation and to minimize thermal losses, and protected by a
flow switch that detects whatever water flow lack.
The source side heat exchanger (3) is a finned coil realized
with grooved copper pipes and hydrophilic aluminium fins with
waved profile to increase the heat exchange coefficient. A tray
is placed under the coil to collect the condensate generated in
heating mode.
The expansion device (4), an electronic expansion valve,
allows the unit to adjust itself to the different operating conditions 2
keeping steady the set superheating.
6
1 4
7
6
GENERAL FEATURES
Control system
FS
The controller is able to manage up to two zones in heating For each zone the following parameters can be set :
(one by means of a mixed circuit and the other by means of a - set point
direct circuit) and one zone in cooling (by means of a mixed
- daily or weekly operating time table
circuit).
- climatic control curve
It’s possible to realize more complex plants connecting to the
heat pump controller further expansion modules in order to - room control sensor : it can be in common with the other
extend without limits the number of zones to be managed. zones or independent (in that case it’s necessary to install
an additional room thermostat)
7
GENERAL FEATURES
Options
Allows to recover a part of the available heating power (and otherwise not used
Version VD - Desuperheater version
during cooling operating mode) for the domestic hot water production.
Acoustic Allows to reduce the noise produced by the unit by means of the refrigerant
AS - Low noise acoustic setting up
setting up circuit vane acoustic insulation and sound jackets on the compressors.
Standard pump Allows the circulation of the water on the plant side.
Plant side
Allows the circulation of the water on the plant side and guarantees a higher
flow rate High head pump
available static head.
management
Allows the circulation of the water on the plant side keeping constant the
Modulating pump
temperature difference between inlet and outlet.
Domestic hot water Allow to divert the hot water produced by the heat pump from the heating circuit
3 way valve
production to the domestic hot water circuit.
The controller flexibility and the big number of options available the type of plant to which the heat pump will be connected, both
allow to get, for each model, a lot of different configurations that for what concerning the heating and cooling circuits, and for
integrate inside the heat pump many components of the plant what concerning the domestic hot water management.
and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define
Reversible heat pump (IP) without options Opzione "Version" : "Desuperheater version (VD)"
8
GENERAL FEATURES
9
GENERAL FEATURES
Accessories
Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor
Rubber vibration dampers
and by the fans in their normal operating mode.
Coil protection grilles Protect the external surface of the finned coil.
3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
for domestic hot water
Remote thermostat Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order
(wired or wireless) to realize a climatic control.
Remote control Replicates all the control and visualization functionalities of the controller installed on the unit. The on board
(wired or wireless) temperature sensor can be used in order to realize a climatic control.
Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor
Wireless transmitter
temperature sensor.
Condensate sensor In cooling mode it allows the minimum flow temperature control when condensate generation occurs.
Room hygrostat In cooling mode it allows the minimum flow temperature control according to the room humidity.
Room humidity sensor In cooling mode it allows the minimum flow temperature control according to the room dew point, calculated from
(with or without display) the measured room humidity.
Transformer
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
230V / 24V - 3VA
10
TECHNICAL DATA AND PERFORMANCES
Technical data
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Refrigerant
Type R410A -
Compressor
Type scroll with vapour injection (EVI) -
Quantity 2 n°
Oil charge 3,4 3,4 3,4 3,4 3,4 kg
Refrigerant circuit
Number of circuits 1 1 1 1 1 -
Power steps 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 %
Plant side heat exchanger
Type stainless steel brazed plates -
Quantity 1 n°
Water volume 8,0 9,0 10,0 12,0 14,0 l
Source side heat exchanger
Type finned coil -
Quantity 1 n°
Frontal surface 1,71 2,56 2,56 3,42 3,42 m2
Fans
Type plug fan with high efficiency EC motor -
Quantity 2 3 4 n°
Diameter 560 560 560 560 560 mm
Maximum rotational speed 1560 1560 1560 1560 1560 rpm
Total installed power 6,20 9,30 9,30 12,4 12,4 kW
Plant side hydraulic circuit
Safety valve set point 6 6 6 6 6 bar
Expansion vessel volume 12 12 12 12 12 l
Plant side pump - standard and modulating (option)
centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump -
Quantity 1 1 1 1 1 n°
Installed power 1,5 1,5 1,5 1,5 1,5 kW
Plant side pump - high head (option)
centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump -
Quantity 1 1 1 1 1 n°
Installed power 3,0 3,0 3,0 3,0 3,0 kW
11
TECHNICAL DATA AND PERFORMANCES
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Heating A7W65 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 60,5 71,2 79,5 89,8 105 kW
Power input 23,8 27,9 31,3 35,3 41,3 kW
COP 2,54 2,55 2,54 2,54 2,54 -
Water flow rate plant side 5293 6229 6955 7856 9160 l/h
Pressure drops plant side 7 8 8 7 7 kPa
Heating A2W65 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 51,8 61,0 68,2 77,0 89,7 kW
Power input 23,8 28,0 31,4 35,3 41,3 kW
IP
COP 2,18 2,18 2,17 2,18 2,17 -
Water flow rate plant side 4532 5337 5967 6736 7847 l/h
Pressure drops plant side 5 6 6 5 5 kPa
Heating A-7W65 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 45,3 53,3 59,6 67,3 78,4 kW
Power input 23,9 28,1 31,5 35,4 41,4 kW
COP 1,90 1,90 1,89 1,90 1,89 -
Water flow rate plant side 3963 4663 5214 5888 6859 l/h
Pressure drops plant side 4 4 4 4 4 kPa
Data declared according to EN 14511. The values are referred to units without options or accessories.
12
TECHNICAL DATA AND PERFORMANCES
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Heating A7W55 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 59,2 69,7 77,8 87,8 102 kW
Power input 19,1 22,5 25,1 28,3 33,1 kW
COP 3,10 3,10 3,10 3,10 3,08 -
Water flow rate plant side 6440 7584 8466 9556 11147 l/h
Pressure drops plant side 10 11 11 10 10 kPa
Heating A2W55 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 50,3 59,3 66,3 74,9 87,3 kW
Power input 19,1 22,4 25,2 28,4 33,2 kW
IP
COP 2,63 2,65 2,63 2,64 2,63 -
Water flow rate plant side 5481 6462 7213 8150 9502 l/h
Pressure drops plant side 7 8 8 7 7 kPa
Heating A-7W55 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 43,6 51,4 57,4 64,8 75,5 kW
Power input 19,2 22,5 25,2 28,4 33,2 kW
COP 2,27 2,28 2,28 2,28 2,27 -
Water flow rate plant side 4751 5601 6255 7061 8227 l/h
Pressure drops plant side 6 6 6 6 6 kPa
Data declared according to EN 14511. The values are referred to units without options or accessories.
13
TECHNICAL DATA AND PERFORMANCES
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 58,2 68,6 76,6 86,4 101 kW
Power input 15,6 18,4 20,5 23,1 27,0 kW
COP 3,73 3,73 3,74 3,74 3,74 -
Water flow rate plant side 10080 11870 13260 14963 17449 l/h
Pressure drops plant side 22 24 25 22 22 kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 49,3 58,2 64,9 73,3 85,4 kW
Power input 15,5 18,3 20,5 23,1 27,0 kW
COP 3,18 3,18 3,17 3,17 3,16 -
Water flow rate plant side 8551 10080 11244 12704 14807 l/h
Pressure drops plant side 17 18 18 16 16 kPa
IP
Heating A-7W45 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 42,4 49,9 55,7 62,9 73,3 kW
Power input 15,6 18,3 20,5 23,1 27,0 kW
COP 2,72 2,73 2,72 2,72 2,71 -
Water flow rate plant side 7351 8655 9663 10914 12722 l/h
Pressure drops plant side 13 14 14 12 12 kPa
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 44,6 52,6 58,7 66,2 77,2 kW
Power input 14,1 16,6 18,6 20,9 24,5 kW
EER 3,16 3,17 3,16 3,17 3,15 -
Water flow rate plant side 7671 9044 10091 11378 13283 l/h
Pressure drops plant side 14 15 15 14 14 kPa
Data declared according to EN 14511. The values are referred to units without options or accessories.
14
TECHNICAL DATA AND PERFORMANCES
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 57,5 67,8 75,7 85,4 99,5 kW
Power input 12,2 14,4 16,1 18,1 21,1 kW
COP 4,71 4,71 4,70 4,72 4,72 -
Water flow rate plant side 9923 11689 13058 14737 17179 l/h
Pressure drops plant side 22 24 24 22 21 kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 48,5 57,3 63,9 72,1 84,0 kW
Power input 12,2 14,4 16,1 18,1 21,1 kW
COP 3,98 3,98 3,97 3,98 3,98 -
Water flow rate plant side 8382 9888 11031 12451 14512 l/h
Pressure drops plant side 16 18 18 16 16 kPa
IP
Heating A-7W35 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 41,4 48,8 54,5 61,5 71,6 kW
Power input 12,3 14,4 16,1 18,1 21,2 kW
COP 3,37 3,39 3,39 3,40 3,38 -
Water flow rate plant side 7152 8434 9421 10633 12382 l/h
Pressure drops plant side 12 13 13 12 12 kPa
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 58,7 69,1 77,3 87,1 102 kW
Power input 15,3 18,1 20,2 22,7 26,6 kW
EER 3,84 3,82 3,83 3,84 3,83 -
Water flow rate plant side 10156 11966 13380 15070 17587 l/h
Pressure drops plant side 23 25 25 22 22 kPa
Data declared according to EN 14511. The values are referred to units without options or accessories.
15
TECHNICAL DATA AND PERFORMANCES
HEATING performances
Heating capacity
0.4
-20 -15 -10 -5 0 5 10 15 20 25 30
2.2 2.2
2.0 2.0
E
1.8 1.8
D
1.6 1.6
C
1.4 1.4
1.2 1.2 B
1.0 1.0 A
0.8 0.8
0.6 0.6
0.4 A B C D E 0.4
0.2 0.2
-20 -15 -10 -5 0 5 10 15 20 25 30 -20 -15 -10 -5 0 5 10 15 20 25 30
Inlet air temperature w.b. [°C] Inlet air temperature w.b. [°C]
16
TECHNICAL DATA AND PERFORMANCES
COOLING performances
Cooling capacity
0.4
0 5 10 15 20 25 30 35 40 45 50
2.2 2.2
2.0 2.0 A
1.8 1.8 B
1.6 1.6 C
1.4 1.4 D
B
1.2 1.2
A
1.0 1.0
0.8 D 0.8
0.6 C 0.6
0.4 0.4
0 5 10 15 20 25 30 35 40 45 50 0 5 10 15 20 25 30 35 40 45 50
Inlet air temperature d.b. [°C] Inlet air temperature d.b. [°C]
17
TECHNICAL DATA AND PERFORMANCES
60
100.2
50
90.2
80.2
40
Pressure drops [ kPa ]
70.2
30 60.2
20
10
0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]
Pressure drops to be added - unit with option "Domestic hot water production" : “3 way valve”
60
50
40
Pressure drops [ kPa ]
30
20
10
0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
18
TECHNICAL DATA AND PERFORMANCES
Available static head - unit with option “Plant side flow rate management” : “Standard pump” and “Modulating pump”
240
100.2
200 90.2
80.2
Available static head [ kPa ]
160
70.2
60.2
120
80
40
0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]
Available static head - unit with option “Plant side flow rate management” : “High head pump”
240
200
Available static head [ kPa ]
160
100.2
120
90.2
80.2
80
70.2
40 60.2
0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
19
TECHNICAL DATA AND PERFORMANCES
240
200
Available static head [ Pa ]
160
90.2
120
70.2
100.2
80
80.2
40 60.2
0
0 4000 8000 12000 16000 20000 24000 28000 32000 36000 40000
Flow rate [ m /h ]
3
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
In case of ducted installation the total pressure drops in the inlet and outlet ducts can not exceed the maximum available static head.
The minimum duct section must guarantee that the medium air velocity does not exceed 2,5 m/s in order to avoid noise problems and to keep
the pressure drops as lower as possible.
The rotational speed of the fans can be increased compared to the factory setting in order to increase the available static head up to the
maximum available value reported in the table.
The graphs are referred to units operating with air at the temperature of 15°C (density 1,2 kg/m3).
20
TECHNICAL DATA AND PERFORMANCES
Performances DESUPERHEATER
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Cooling A35W7-W45
( source : air in 35°C d.b. / plant : water in 12°C out 7°C / heat recovery : water in 40°C out 45°C )
Cooling capacity 46,4 54,7 61,0 68,8 80,3 kW
IP Water flow rate plant side 7980 9404 10503 11841 13815 l/h
Water flow rate desuperheater side 2381 2815 3146 3545 4136 l/h
Pressure drops desuperheater side 1,2 1,6 1,3 1,7 2,3 kPa
Data declared according to EN 14511. The values are referred to units with the only option "VD - Desuperheater version".
30
25 100.2
90.2
20
Pressure drops [ kPa ]
80.2
70.2
15
60.2
10
0
0 1000 2000 3000 4000 5000 6000
Flow rate [ l/h ]
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
21
TECHNICAL DATA AND PERFORMANCES
Operating limits
The graphs reported below show the operating area inside which the correct working of the unit is guaranteed.
HEATING
75
70
DT = 10 °C
65
60
Outlet temperature - plant side [°C]
55
50
45
40
35
30
25
20
15
10
5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55
COOLING
45
40
Outlet temperature - plant side [°C]
35
30
25
20
15
10
-5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55
22
TECHNICAL DATA AND PERFORMANCES
Electrical data
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Unit
Power supply 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 V-ph-Hz
F.L.A. Maximum total current input 49,1 57,7 62,7 73,5 82,5 A
F.L.I. Maximum total power input 30,6 35,8 39,0 45,6 51,4 kW
F.L.A. Maximum total current input 2,5 2,5 2,5 2,5 2,5 A
F.L.I. Maximum total power input 1,5 1,5 1,5 1,5 1,5 kW
F.L.A. Maximum total current input 5,1 5,1 5,1 5,1 5,1 A
F.L.I. Maximum total power input 3,0 3,0 3,0 3,0 3,0 kW
F.L.A. Maximum total current input 2,5 2,5 2,5 2,5 2,5 A
F.L.I. Maximum total power input 1,5 1,5 1,5 1,5 1,5 kW
23
TECHNICAL DATA AND PERFORMANCES
Noise levels
63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
60.2 89,3 83,6 78,5 77,4 75,5 72,6 66,8 61,8 91 80 63 54 49
70.2 89,9 84,2 79,1 78,0 76,1 73,2 67,4 62,4 92 81 64 54 49
80.2 90,3 84,6 79,5 78,4 76,5 73,6 67,8 62,8 92 81 64 55 50
90.2 90,9 85,2 80,1 79,0 77,1 74,2 68,4 63,4 93 82 64 55 50
100.2 91,3 85,6 80,5 79,4 77,5 74,6 68,8 63,8 93 82 64 56 51
Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
60.2 83,9 79,5 74,2 73,9 71,6 70,5 66,7 63,5 86 77 60 51 46
70.2 84,6 80,2 74,9 74,6 72,3 71,2 67,4 64,2 87 78 61 51 46
80.2 84,9 80,5 75,2 74,9 72,6 71,5 67,7 64,5 87 78 61 52 47
90.2 85,6 81,2 75,9 75,6 73,3 72,2 68,4 65,2 88 79 61 52 47
100.2 85,9 81,5 76,2 75,9 73,6 72,5 68,7 65,5 88 79 61 53 48
Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
24
TECHNICAL DATA AND PERFORMANCES
Weights
Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.
Components weights
Unit without options 770 925 935 1086 1101 kg
Desuperheater
Version 15 18 21 24 24 kg
version (VD)
Acoustic Low noise
65 75 75 85 85 kg
setting up setting up (AS)
Options
Standard pump 25 26 26 29 29 kg
Plant side
flow rate High head pump 31 32 32 35 35 kg
management
High efficiency pump 35 36 36 39 39 kg
Domestic hot water production :
21 22 22 25 25 kg
3 way valve
Transport weights
Unit without options 781 937 947 1099 1114 1114
Desuperheater
Version 15 18 21 24 24 24
version (VD)
Acoustic Low noise
65 75 75 85 85 85
setting up setting up (AS)
Options
Standard pump 25 26 26 29 29 29
Plant side
flow rate High head pump 31 32 32 35 35 35
management
High efficiency pump 35 36 36 39 39 39
Domestic hot water production :
21 22 22 25 25 25
3 way valve
Operating weights
Standard pump 35 37 37 42 42 kg
Plant side
flow rate High head pump 41 43 43 48 48 kg
management
High efficiency pump 45 47 47 52 52 kg
Domestic hot water production :
27 29 29 34 34 kg
3 way valve
25
TECHNICAL DATA AND PERFORMANCES
Overall dimensions
5 5
4 4
3 3
2 2
1 1
A B
C 1200 mm
D 1000 mm
E 1000 mm
E D
26
The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The reserves the right to modify the products contents in this catalogue without previous notice.
27
28