HGP HT: Technical Manual

This technical manual provides information on air-water heat pump units for indoor installation including general features, specifications, performance data, dimensions, and operating limits. The units can be used for heating, cooling, and domestic hot water production for residential and commercial applications. They use refrigerant circuits, plate heat exchangers, and fans for efficient indoor heat transfer. Installation requires only electrical and hydraulic connections.

Uploaded by

CRETU NICOLAE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views28 pages

HGP HT: Technical Manual

This technical manual provides information on air-water heat pump units for indoor installation including general features, specifications, performance data, dimensions, and operating limits. The units can be used for heating, cooling, and domestic hot water production for residential and commercial applications. They use refrigerant circuits, plate heat exchangers, and fans for efficient indoor heat transfer. Installation requires only electrical and hydraulic connections.

Uploaded by

CRETU NICOLAE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

-FRIEND

O
C

L
E

Y
RE
S
A

F
G R
T IG
RA N E

HGP HT
AIR-WATER
65 .0

HEAT PUMPS
FOR INDOOR INSTALLATION

TECHNICAL MANUAL
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.

2
TABLE OF CONTENTS

GENERAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - VERY HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - HIGH TEMPERATURE plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
NOMINAL performances - STANDARD plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
NOMINAL performances - RADIANT plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
HEATING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Source side aeraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
DESUPERHEATER performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3
4
GENERAL FEATURES

Unit description

This series of air-water heat pumps satisfies the heating, coo- flow to simplify the maintenance operations, is equipped with
ling and domestic hot water production requirements of autono- two scroll compressors mounted on damper supports, brazed
mous or centralized residential plants of medium and large size. plate heat exchangers, electronic expansion valve, reverse
All the units are suitable for indoor installation. The possibiliy to cycle valve, centrifugal fans (plug fans), finned coil realized with
produce water at high temperatures makes these units particu- copper pipes and alluminium fins. The circuit is protected by high
larly suitable to be applied to radiators plants as well as to fan and low pressure switches and flow switches on the plate heat
coil plants and radiant floor plants. exchanger.
The control system allows to manage not only the refrigerant The compressors are arranged in tandem on a single refrigerant
circuit but the whole plant with the possibility to choose different circuit and allow the capacity modulation according to the plant
solutions both for the heating and cooling plant and for the do- requests in order to guarantee a high seasonal efficiency.
mestic hot water management. The possibility of solar panels or Both the compressors are equipped with vapour and liquid
other heating sources integration is also available. injection and are placed on an economized refrigerant circuit with
The heating function optimizes the flow water temperature ac- plate heat exchanger and electronic expansion valve dedicated
cording both to the ambient temperature and to the outdoor tem- to the injection.
perature through climatic curves adaptable to the building featu- The plate heat exchanger and all the hydraulic pipes are ther-
res. It’s possible to manage a storage tank and two independent mally insulated in order to avoid condensate generation and re-
circuits (a direct one and a mixed one). duce thermal losses.
The domestic hot water management allows to control the th- The plug fans with electronic control of the rotational speed gua-
ree way valve, the storage tank and the anti-legionella cycles (if rantee high efficiencies and low noise in all the operating condi-
necessary). tions and allow to install the unit indoor (with ducted air inlet and
The cooling function can be realized through “active cooling” outlet). It is moreover possible to reduce the noise level during
(refrigerant circuit inversion). When the unit is used in radiant the night.
floor plants, to avoid condensate generation, a room humidity All the units are provided with a phase sequence and correct se-
sensor can be installed. During cooling mode operation a part of quence controller device and with an outdoor temperature sensor
the heating power in excess can be recovered for the domestic in order to realize the climatic control.
hot water production (VD version). All the units are accurately built and individually tested in the
The internal programmer clock allows to define different daily factory. Only electric and hydraulic connections are required for
switching programs for heating, cooling and domestic hot water installation.
production.
The refrigerant circuit, contained in a box repaired from the air

Unit identification code

The codes that identify the units and the meaning of the letters used are described below.

HGP HT IP 80.2 VB AB 0 H 5

Power supply

Unit type 1 - 230V - 1 - 50 Hz


5 - 400V - 3 - 50 Hz
IP - Units suitable for hydronic plant in-
stallation operating as reversible heat
pumps Operating range

H - High temperature.
The unit is suitable to produce
water at high temperature
Unit model

Refrigerant type
N° compressors
0 - R410A

Unit version Acoustic setting up

VB - Base version AB - Base setting up


VD - Desuperheater version AS - Low noise setting up

5
GENERAL FEATURES

Description of components

External structure. Basement, supporting structure and lateral The refrigerant circuit of each unit contains moreover solid
panels are made of galvanized and painted sheet-steel to core hermetic filter dryer (5) to restrain impurity and moisture
guarantee good resistance to atmospheric agents. Accessibility residuals that could be present in the circuit, high and low
to internal parts is possible removing the frontal and lateral pressure switches in order to assure the compressor to
panels. For extraordinary manteinances also the other panels operate inside the permitted limits, 4 way reverse cycle valve
can be removed. (6) to allow operating mode change reversing the refrigerant
Refrigerant circuit. It is contained inside a compartment flow, liquid receiver (7) to compensate the different refrigerant
separated from the air flow to simplify maintenance and control charge required in heating and in cooling mode and pressure
operations. connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket
and blind nut, as required for the use of R410A refrigerant (they
allow the complete check of the refrigerant circuit: compressor
inlet pressure, compressor outlet pressure and expansion valve
upstream pressure). All the pipes of the refrigerant circuit are
properly insulated to avoid condensate generation and minimize
thermal losses
The plug fans (8) are equipped with an high efficiency
electronically commutated (EC) motor and guarantee enough
available static pressure to allow the indoor ducted installation
besides high efficiencies in all the operating conditions.
Hydraulic circuit. All the pipes are thermally insulated to avoid
condensate generation and minimize thermal losses. The circuit
can be equipped with a standard, high head or modulating
circulation pump (option). The circuit is always equipped also
with expansion vessel, safety valve and air vents.
Electrical panel. It contains all the power, control and security
components necessary to guarantee the unit to work properly.
The unit is managed by a microprocessor controller to which
all the electrical loads and the control devices are connected.
The user interface, to be placed indoor, allows to view and to
modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor,
to be installed outside, in order to realize the climatic control.
The scroll compressors (1) are mounted on damper supports
and are protected against overtemperatures and overcurrents.
Each compressor is equipped with an electrcal heater, that is
activated when the compressor turns off, to keep the compressor
crankcase oil temperature high enough to prevent migration of
the refrigerant during winter stops and to evaporate any liquid
8
present in the crankcase, in order to prevent possible liquid
rushes on starting.
3
Both the compressors are equipped with vapour and liquid
injection and are placed on an economized refrigerant circuit
with plate heat exchanger and electronic expansion valve
dedicated to the injection.
The plant side heat exchanger (2) is a brazed stainless steel
plate heat exchanger, properly insulated to avoid condensate
generation and to minimize thermal losses, and protected by a
flow switch that detects whatever water flow lack.
The source side heat exchanger (3) is a finned coil realized
with grooved copper pipes and hydrophilic aluminium fins with
waved profile to increase the heat exchange coefficient. A tray
is placed under the coil to collect the condensate generated in
heating mode.
The expansion device (4), an electronic expansion valve,
allows the unit to adjust itself to the different operating conditions 2
keeping steady the set superheating.
6
1 4
7

6
GENERAL FEATURES

Control system

The microprocessor controller is able to manage not only the


unit itself but also all that components of the plant which allow to
realize a complete system.
The main functions of the control system are :
- room temperature control according to the outdoor temperatu-
re (climatic control) 18:28
- domestic hot water production (management of 3 way valve,
storage tank, anti legionella cycles…)
20.5 C
Room temperature
- management of a heating and/or cooling mixed circuit (pump
and 3 way mixing valve)
- management of a heating direct circuit (only pump)
- management of a storage tank for heating and/or cooling
- management of electrical heaters for heating and domestic
hot water (3 steps logic)
- solar panels integration
- room humidity control for cooling with radiant systems
- internal programmer clock (for heating, cooling and domestic
hot water)
- digital input for electrical energy low tariff
- alarm memory management and diagnostic
- compressor and pump operating hour counter
- possibility to manage more units in cascade (maximum 16)

The unit controller is able to manage a lot of different plant so-


Besides the user interface of the unit to be placed indoor, wi- lutions enabling automatically the necessary control algorythms
red or wireless remote thermostats are available which allow to according to the components which have been connected. The
control all the operating parameters of the unit and to acquire management of such components is possible through additional
the temperature in the different zones in order to realize a more expansion modules which communicate with the unit by means
precise and comfortable control. of an internal bus and provide all the inputs and outputs required
to fulfil a complete system.

FS

The controller is able to manage up to two zones in heating For each zone the following parameters can be set :
(one by means of a mixed circuit and the other by means of a - set point
direct circuit) and one zone in cooling (by means of a mixed
- daily or weekly operating time table
circuit).
- climatic control curve
It’s possible to realize more complex plants connecting to the
heat pump controller further expansion modules in order to - room control sensor : it can be in common with the other
extend without limits the number of zones to be managed. zones or independent (in that case it’s necessary to install
an additional room thermostat)

7
GENERAL FEATURES

Options

Allows to recover a part of the available heating power (and otherwise not used
Version VD - Desuperheater version
during cooling operating mode) for the domestic hot water production.

Acoustic Allows to reduce the noise produced by the unit by means of the refrigerant
AS - Low noise acoustic setting up
setting up circuit vane acoustic insulation and sound jackets on the compressors.

Standard pump Allows the circulation of the water on the plant side.
Plant side
Allows the circulation of the water on the plant side and guarantees a higher
flow rate High head pump
available static head.
management
Allows the circulation of the water on the plant side keeping constant the
Modulating pump
temperature difference between inlet and outlet.
Domestic hot water Allow to divert the hot water produced by the heat pump from the heating circuit
3 way valve
production to the domestic hot water circuit.

Soft starter Reduces the compressor start current.

The controller flexibility and the big number of options available the type of plant to which the heat pump will be connected, both
allow to get, for each model, a lot of different configurations that for what concerning the heating and cooling circuits, and for
integrate inside the heat pump many components of the plant what concerning the domestic hot water management.
and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define

Reversible heat pump (IP) without options Opzione "Version" : "Desuperheater version (VD)"

Option “Plant side flow rate management”


Pump (standard or high head or modulating)

8
GENERAL FEATURES

Option “Domestic hot water production”


3 way valve
In this configuration the heat pump can
be coupled to a domestic hot water
tank equipped with a coil designed for
a maximum water temperature between
55°C and 60°C.
The anti legionella cycles have to be
performed by means of electrical heaters
placed on the heat pump outlet (see
option “Integrative electrical heaters”) or
directly inside the tank.

9
GENERAL FEATURES

Accessories

Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor
Rubber vibration dampers
and by the fans in their normal operating mode.

Coil protection grilles Protect the external surface of the finned coil.

3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
for domestic hot water
Remote thermostat Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order
(wired or wireless) to realize a climatic control.
Remote control Replicates all the control and visualization functionalities of the controller installed on the unit. The on board
(wired or wireless) temperature sensor can be used in order to realize a climatic control.
Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor
Wireless transmitter
temperature sensor.

Wireless repeater Extends wireless operating range.

Wireless adaptor for


Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.
outdoor temperature sensor

Condensate sensor In cooling mode it allows the minimum flow temperature control when condensate generation occurs.

Room hygrostat In cooling mode it allows the minimum flow temperature control according to the room humidity.

Room humidity sensor In cooling mode it allows the minimum flow temperature control according to the room dew point, calculated from
(with or without display) the measured room humidity.
Transformer
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
230V / 24V - 3VA

10
TECHNICAL DATA AND PERFORMANCES

Technical data

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Refrigerant
Type R410A -
Compressor
Type scroll with vapour injection (EVI) -
Quantity 2 n°
Oil charge 3,4 3,4 3,4 3,4 3,4 kg
Refrigerant circuit
Number of circuits 1 1 1 1 1 -
Power steps 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 0 - 50 - 100 %
Plant side heat exchanger
Type stainless steel brazed plates -
Quantity 1 n°
Water volume 8,0 9,0 10,0 12,0 14,0 l
Source side heat exchanger
Type finned coil -
Quantity 1 n°
Frontal surface 1,71 2,56 2,56 3,42 3,42 m2
Fans
Type plug fan with high efficiency EC motor -
Quantity 2 3 4 n°
Diameter 560 560 560 560 560 mm
Maximum rotational speed 1560 1560 1560 1560 1560 rpm
Total installed power 6,20 9,30 9,30 12,4 12,4 kW
Plant side hydraulic circuit
Safety valve set point 6 6 6 6 6 bar
Expansion vessel volume 12 12 12 12 12 l
Plant side pump - standard and modulating (option)
centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump -

Quantity 1 1 1 1 1 n°
Installed power 1,5 1,5 1,5 1,5 1,5 kW
Plant side pump - high head (option)
centrifugal centrifugal centrifugal centrifugal centrifugal
Type pump pump pump pump pump -

Quantity 1 1 1 1 1 n°
Installed power 3,0 3,0 3,0 3,0 3,0 kW

11
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - VERY HIGH TEMPERATURE plants

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Heating A7W65 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 60,5 71,2 79,5 89,8 105 kW
Power input 23,8 27,9 31,3 35,3 41,3 kW
COP 2,54 2,55 2,54 2,54 2,54 -
Water flow rate plant side 5293 6229 6955 7856 9160 l/h
Pressure drops plant side 7 8 8 7 7 kPa
Heating A2W65 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 51,8 61,0 68,2 77,0 89,7 kW
Power input 23,8 28,0 31,4 35,3 41,3 kW
IP
COP 2,18 2,18 2,17 2,18 2,17 -
Water flow rate plant side 4532 5337 5967 6736 7847 l/h
Pressure drops plant side 5 6 6 5 5 kPa
Heating A-7W65 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 55°C out 65°C )
Heating capacity 45,3 53,3 59,6 67,3 78,4 kW
Power input 23,9 28,1 31,5 35,4 41,4 kW
COP 1,90 1,90 1,89 1,90 1,89 -
Water flow rate plant side 3963 4663 5214 5888 6859 l/h
Pressure drops plant side 4 4 4 4 4 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

12
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - HIGH TEMPERATURE plants

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Heating A7W55 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 59,2 69,7 77,8 87,8 102 kW
Power input 19,1 22,5 25,1 28,3 33,1 kW
COP 3,10 3,10 3,10 3,10 3,08 -
Water flow rate plant side 6440 7584 8466 9556 11147 l/h
Pressure drops plant side 10 11 11 10 10 kPa
Heating A2W55 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 50,3 59,3 66,3 74,9 87,3 kW
Power input 19,1 22,4 25,2 28,4 33,2 kW
IP
COP 2,63 2,65 2,63 2,64 2,63 -
Water flow rate plant side 5481 6462 7213 8150 9502 l/h
Pressure drops plant side 7 8 8 7 7 kPa
Heating A-7W55 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 47°C out 55°C )
Heating capacity 43,6 51,4 57,4 64,8 75,5 kW
Power input 19,2 22,5 25,2 28,4 33,2 kW
COP 2,27 2,28 2,28 2,28 2,27 -
Water flow rate plant side 4751 5601 6255 7061 8227 l/h
Pressure drops plant side 6 6 6 6 6 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

13
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - STANDARD plants

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 58,2 68,6 76,6 86,4 101 kW
Power input 15,6 18,4 20,5 23,1 27,0 kW
COP 3,73 3,73 3,74 3,74 3,74 -
Water flow rate plant side 10080 11870 13260 14963 17449 l/h
Pressure drops plant side 22 24 25 22 22 kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 49,3 58,2 64,9 73,3 85,4 kW
Power input 15,5 18,3 20,5 23,1 27,0 kW
COP 3,18 3,18 3,17 3,17 3,16 -
Water flow rate plant side 8551 10080 11244 12704 14807 l/h
Pressure drops plant side 17 18 18 16 16 kPa
IP
Heating A-7W45 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 42,4 49,9 55,7 62,9 73,3 kW
Power input 15,6 18,3 20,5 23,1 27,0 kW
COP 2,72 2,73 2,72 2,72 2,71 -
Water flow rate plant side 7351 8655 9663 10914 12722 l/h
Pressure drops plant side 13 14 14 12 12 kPa
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 44,6 52,6 58,7 66,2 77,2 kW
Power input 14,1 16,6 18,6 20,9 24,5 kW
EER 3,16 3,17 3,16 3,17 3,15 -
Water flow rate plant side 7671 9044 10091 11378 13283 l/h
Pressure drops plant side 14 15 15 14 14 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

14
TECHNICAL DATA AND PERFORMANCES

NOMINAL performances - RADIANT plants

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 57,5 67,8 75,7 85,4 99,5 kW
Power input 12,2 14,4 16,1 18,1 21,1 kW
COP 4,71 4,71 4,70 4,72 4,72 -
Water flow rate plant side 9923 11689 13058 14737 17179 l/h
Pressure drops plant side 22 24 24 22 21 kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 48,5 57,3 63,9 72,1 84,0 kW
Power input 12,2 14,4 16,1 18,1 21,1 kW
COP 3,98 3,98 3,97 3,98 3,98 -
Water flow rate plant side 8382 9888 11031 12451 14512 l/h
Pressure drops plant side 16 18 18 16 16 kPa
IP
Heating A-7W35 ( source : air in -7°C d.b. -8°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 41,4 48,8 54,5 61,5 71,6 kW
Power input 12,3 14,4 16,1 18,1 21,2 kW
COP 3,37 3,39 3,39 3,40 3,38 -
Water flow rate plant side 7152 8434 9421 10633 12382 l/h
Pressure drops plant side 12 13 13 12 12 kPa
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 58,7 69,1 77,3 87,1 102 kW
Power input 15,3 18,1 20,2 22,7 26,6 kW
EER 3,84 3,82 3,83 3,84 3,83 -
Water flow rate plant side 10156 11966 13380 15070 17587 l/h
Pressure drops plant side 23 25 25 22 22 kPa

Data declared according to EN 14511. The values are referred to units without options or accessories.

15
TECHNICAL DATA AND PERFORMANCES

HEATING performances

Heating capacity

1.6 The graphs allow to get the corrective factors to


be applied to the nominal performances in order
to obtain the real performances in the selected
1.4
operating conditions.
A
The reference nominal condition is :
1.2
B A7W35
source : air in 7°C d.b. 6°C w.b.
C plant : water in 30°C out 35°C
1.0
D Outlet temperature
plant side :
0.8 E A = 65°C
B = 55°C
C = 45°C
0.6 D = 35°C
E = 25°C

0.4
-20 -15 -10 -5 0 5 10 15 20 25 30

Inlet air temperature w.b. [°C]

Power input COP

2.2 2.2

2.0 2.0
E
1.8 1.8
D
1.6 1.6

C
1.4 1.4

1.2 1.2 B

1.0 1.0 A
0.8 0.8

0.6 0.6

0.4 A B C D E 0.4

0.2 0.2
-20 -15 -10 -5 0 5 10 15 20 25 30 -20 -15 -10 -5 0 5 10 15 20 25 30

Inlet air temperature w.b. [°C] Inlet air temperature w.b. [°C]

16
TECHNICAL DATA AND PERFORMANCES

COOLING performances

Cooling capacity

2.2 The graphs allow to get the corrective factors to


be applied to the nominal performances in order
2.0 to obtain the real performances in the selected
operating conditions.
1.8
The reference nominal condition is :
1.6 A35W7
source : air in 35°C d.b.
1.4 plant : water in 12°C out 7°C

1.2 Outlet temperature


plant side :
1.0 A = 24°C
B = 18°C
0.8 C = 12°C
A B C D
D = 7°C
0.6

0.4
0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C]

Power input EER

2.2 2.2

2.0 2.0 A

1.8 1.8 B

1.6 1.6 C

1.4 1.4 D
B
1.2 1.2

A
1.0 1.0

0.8 D 0.8

0.6 C 0.6

0.4 0.4
0 5 10 15 20 25 30 35 40 45 50 0 5 10 15 20 25 30 35 40 45 50

Inlet air temperature d.b. [°C] Inlet air temperature d.b. [°C]

17
TECHNICAL DATA AND PERFORMANCES

Plant side hydraulic performances

Pressure drops - unit without options

60

100.2
50
90.2

80.2
40
Pressure drops [ kPa ]

70.2

30 60.2

20

10

0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]

Pressure drops to be added - unit with option "Domestic hot water production" : “3 way valve”

60

50

40
Pressure drops [ kPa ]

30

20

10

0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

18
TECHNICAL DATA AND PERFORMANCES

Available static head - unit with option “Plant side flow rate management” : “Standard pump” and “Modulating pump”

240

100.2

200 90.2

80.2
Available static head [ kPa ]

160
70.2

60.2
120

80

40

0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]

Available static head - unit with option “Plant side flow rate management” : “High head pump”

240

200
Available static head [ kPa ]

160

100.2
120
90.2

80.2
80
70.2

40 60.2

0
0 5000 10000 15000 20000 25000 30000
Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

19
TECHNICAL DATA AND PERFORMANCES

Source side aeraulic performances

Available static head

240

200
Available static head [ Pa ]

160
90.2

120
70.2
100.2

80
80.2

40 60.2

0
0 4000 8000 12000 16000 20000 24000 28000 32000 36000 40000

Flow rate [ m /h ]
3

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Maximum static head


available for ducted installation
150 150 150 150 150 U.M.

In case of ducted installation the total pressure drops in the inlet and outlet ducts can not exceed the maximum available static head.
The minimum duct section must guarantee that the medium air velocity does not exceed 2,5 m/s in order to avoid noise problems and to keep
the pressure drops as lower as possible.
The rotational speed of the fans can be increased compared to the factory setting in order to increase the available static head up to the
maximum available value reported in the table.

The graphs are referred to units operating with air at the temperature of 15°C (density 1,2 kg/m3).

20
TECHNICAL DATA AND PERFORMANCES

Performances DESUPERHEATER

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Power supply 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz

Cooling A35W7-W45
( source : air in 35°C d.b. / plant : water in 12°C out 7°C / heat recovery : water in 40°C out 45°C )
Cooling capacity 46,4 54,7 61,0 68,8 80,3 kW

Power input 13,7 16,1 18,2 20,4 23,8 kW

EER 3,39 3,40 3,35 3,37 3,37 -

IP Water flow rate plant side 7980 9404 10503 11841 13815 l/h

Pressure drops plant side 15 16 16 15 15 kPa

Heating capacity (desuperheater) 13,7 16,2 18,1 20,4 23,8 kW

EER with heat recovery 4,39 4,40 4,35 4,37 4,37 -

Water flow rate desuperheater side 2381 2815 3146 3545 4136 l/h

Pressure drops desuperheater side 1,2 1,6 1,3 1,7 2,3 kPa

Data declared according to EN 14511. The values are referred to units with the only option "VD - Desuperheater version".

Pressure drops desuperheater - unit "VD - Desuperheater version"

30

25 100.2

90.2
20
Pressure drops [ kPa ]

80.2

70.2
15
60.2

10

0
0 1000 2000 3000 4000 5000 6000
Flow rate [ l/h ]

The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).

21
TECHNICAL DATA AND PERFORMANCES

Operating limits

The graphs reported below show the operating area inside which the correct working of the unit is guaranteed.

HEATING

75

70
DT = 10 °C
65

60
Outlet temperature - plant side [°C]

55

50

45

40

35

30

25

20

15

10

5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

Inlet air temperature d.b. [°C]

COOLING

45

40
Outlet temperature - plant side [°C]

35

30

25

20

15

10

-5
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

Inlet air temperature d.b. [°C]

Temperature difference between unit inlet and outlet Plant side


DT max Maximum value 11 °C

DT min Minimum value 3 °C

22
TECHNICAL DATA AND PERFORMANCES

Electrical data

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Unit
Power supply 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 V-ph-Hz

F.L.A. Maximum total current input 49,1 57,7 62,7 73,5 82,5 A

F.L.I. Maximum total power input 30,6 35,8 39,0 45,6 51,4 kW

Maximum total start current 187 204 219 248 286 A


M.I.C. Maximum total start current
121 135 147 170 194 A
with soft starter (option)

Plant side pump - standard (option)


Power supply 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 V-ph-Hz

F.L.A. Maximum total current input 2,5 2,5 2,5 2,5 2,5 A

F.L.I. Maximum total power input 1,5 1,5 1,5 1,5 1,5 kW

Plant side pump - high head (option)


Power supply 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 V-ph-Hz

F.L.A. Maximum total current input 5,1 5,1 5,1 5,1 5,1 A

F.L.I. Maximum total power input 3,0 3,0 3,0 3,0 3,0 kW

Plant side pump - modulating (option)


Power supply 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 V-ph-Hz

F.L.A. Maximum total current input 2,5 2,5 2,5 2,5 2,5 A

F.L.I. Maximum total power input 1,5 1,5 1,5 1,5 1,5 kW

23
TECHNICAL DATA AND PERFORMANCES

Noise levels

Option "Acoustic setting up" : "AB - Base setting up"

Sound pressure level


Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
60.2 89,3 83,6 78,5 77,4 75,5 72,6 66,8 61,8 91 80 63 54 49
70.2 89,9 84,2 79,1 78,0 76,1 73,2 67,4 62,4 92 81 64 54 49
80.2 90,3 84,6 79,5 78,4 76,5 73,6 67,8 62,8 92 81 64 55 50
90.2 90,9 85,2 80,1 79,0 77,1 74,2 68,4 63,4 93 82 64 55 50
100.2 91,3 85,6 80,5 79,4 77,5 74,6 68,8 63,8 93 82 64 56 51

Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

Option "Acoustic setting up" : "AS - Low noise setting up"

Sound pressure level


Sound power levels [dB] Sound power
Model by octave bands [Hz] level at 1 metre at 5 metres at 10 metres

63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
60.2 83,9 79,5 74,2 73,9 71,6 70,5 66,7 63,5 86 77 60 51 46
70.2 84,6 80,2 74,9 74,6 72,3 71,2 67,4 64,2 87 78 61 51 46
80.2 84,9 80,5 75,2 74,9 72,6 71,5 67,7 64,5 87 78 61 52 47
90.2 85,6 81,2 75,9 75,6 73,3 72,2 68,4 65,2 88 79 61 52 47
100.2 85,9 81,5 76,2 75,9 73,6 72,5 68,7 65,5 88 79 61 53 48

Reference conditions
Performances referred to units operating in heating mode at nominal conditions A7W35.
Unit placed in free field on reflecting surface (directional factor equal to 2).
The sound power level is measured according to ISO 3744 standard.
The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.

24
TECHNICAL DATA AND PERFORMANCES

Weights

Frame 1 2 3
Model 60.2 70.2 80.2 90.2 100.2 U.M.

Components weights
Unit without options 770 925 935 1086 1101 kg
Desuperheater
Version 15 18 21 24 24 kg
version (VD)
Acoustic Low noise
65 75 75 85 85 kg
setting up setting up (AS)
Options

Standard pump 25 26 26 29 29 kg
Plant side
flow rate High head pump 31 32 32 35 35 kg
management
High efficiency pump 35 36 36 39 39 kg
Domestic hot water production :
21 22 22 25 25 kg
3 way valve

Transport weights
Unit without options 781 937 947 1099 1114 1114
Desuperheater
Version 15 18 21 24 24 24
version (VD)
Acoustic Low noise
65 75 75 85 85 85
setting up setting up (AS)
Options

Standard pump 25 26 26 29 29 29
Plant side
flow rate High head pump 31 32 32 35 35 35
management
High efficiency pump 35 36 36 39 39 39
Domestic hot water production :
21 22 22 25 25 25
3 way valve

Operating weights

Unit without options 784 940 952 1106 1125 kg


Desuperheater
Version 19 23 27 31 31 kg
version (VD)
Acoustic Low noise
65 75 75 85 85 kg
setting up setting up (AS)
Options

Standard pump 35 37 37 42 42 kg
Plant side
flow rate High head pump 41 43 43 48 48 kg
management
High efficiency pump 45 47 47 52 52 kg
Domestic hot water production :
27 29 29 34 34 kg
3 way valve

25
TECHNICAL DATA AND PERFORMANCES

Overall dimensions

5 5
4 4
3 3
2 2
1 1

A B

1 Plant return 2" M Frame 1 Frame 2 Frame 3


2 Plant flow 2" M A 1130 mm 1130 mm 1130 mm
3 Domestic hot water flow 2" M B 1710 mm 2430 mm 3130 mm
4 Desuperheater inlet 1" 1/4 M H 1810 mm 1810 mm 1810 mm
5 Desuperheater outlet 1" 1/4 M

Minimum operating area

Respect the free area around the unit as shown in


figure in order to guarantee a good accessibility and
facilitate maintenance and control operations.

C 1200 mm
D 1000 mm
E 1000 mm

E D

26


The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The reserves the right to modify the products contents in this catalogue without previous notice.

27