Device: 7SJ82 Overcurrent protection
Product code
Short: P1J39905
Long: 7SJ82JAAAAA00WWWW0AK041112111BBAA000000AB0HB1BD4JA0
Technical Data:
Firmware: Without FW, latest CPU
Binary inputs: 23
Binary outputs: 16 Relays (16 Standard, 0 Fast, 0 High-Speed, 0 Power)
Current transformers: 4 for protection
Voltage transformers: 4 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
0 (temperature)
Housing width: 1/3 x 19''
Housing type: Flush mounting
Modules in 19" row 1: IO102, PS101, IO110
LEDs/Push-buttons: 16 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Small display
Front Design: Standard
Power Supply: DC 110 V-250 V, AC 100 V-230 V
________________________________________________________________________________________________
1/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BB-2FO: 2x optical Ethernet 100 Mbit/s, 1300 nm, duplex LC
connector
, 2 km over 50/125 um or 62.5/125 um multimode optical fiber
Communication Protocols: applicable for DIGSI 5, IEC 61850-8-1
MMS and
GOOSE, IEC 60870-5-104, DNP3 TCP, Modbus TCP,
Synchrophasor (IEEE
C37.118 - IP), Profinet IO, SUP, DHCP, SNTP, SNMP, etc.
Redundancy protocols: Line Mode, RSTP, HSR, PRP
Plug-in module position F: Port is available but not assembled
Functions:
Function points class: Base + 150 function points
Note on function-points class
The function-points class results from the sum of the function points of the selected functions. You can
apply these functions as selected. The device allows also each other selection of functions as long as the
sum of the required function points is within the selected function-points class. With the maximum
function-points class of 1400 it is possible to activate all the functions in the device. The function-points
exceeding 1400 are free of charge. In the engineering phase DIGSI 5 checks that the selected
configuration is suitable (capable of running in the device) before loading it to the device.
Miscellaneous:
Warranty: 10 years
Special Approvals: Without
Firmware: Without FW, latest CPU
________________________________________________________________________________________________
2/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
7SJ82 Overcurrent-Time Protection - Overview Function points calculation
(P1J39905)
Included Functions
ANSI Function Abbr. Included
Protection functions for 3-pole tripping 3-pole
37 Undercurrent I<
38 Temperature supervision θ>
46 Negative-sequence overcurrent protection I2>
46 Unbalanced-load protection (thermal) I2² t>
49 Thermal overload protection θ, I²t
49 Thermal overload protection, user-defined characteristic θ, I²t
Instantaneous tripping at switch onto fault SOTF
50HS Instantaneous high-current tripping I>>>
50/51 TD Overcurrent protection with positive-sequence current I1 I1> 20 X
(from V7.9)
50N/ 51N Overcurrent protection, ground IN>
TD
50N/ 51N Overcurrent protection, 1-phase IN>
TD
50Ns/ 51Ns Sensitive ground-current detection for systems with INs>
resonant or isolated neutral systems incl. a) 3I0>, b)
admittance Y0>, c) 3I0-harm> (from V7.8)
74TC Trip-circuit supervision TCS
74CC Closed-circuit supervision (from V7.9) CCS
86 Lockout
AFD Arc-protection (only with plug-in module ARC-CD-3FO) 5X
Measured values - standard
Switching statistic counters
PQ-Basic measured values: THD (Total Harmonic
Distortion) and harmonics (from V8.01) THD voltage
aggregation values (from V8.40)
________________________________________________________________________________________________
3/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
CFC (Standard, control)
Switching sequences function 20 X
Inrush current detection
External trip initiation
Control
Fault recording of analog and binary signals
Monitoring and supervision
Protection interface, serial
Frequency-tracking groups (from V7.8) 6X
Temperature acquisition via communication protocol
Optional Functions
ANSI Function Abbr. Included Quantity Value Points
24 Overexcitation protection V/f 0 25 0
25 Synchrocheck, synchronization Sync 1 50 50
function
25 Synchrocheck, synchronization Sync 0 80 0
function with balancing
commands (from V7.82)
27 Undervoltage protection: V< 1 5 5
"3-phase" or
"positive-sequence system V1"
or "universal Vx"
27R, 59R Rate-of-voltage-change dV/dt 0 5 0
protection (from V8.30)
Undervoltage-controlled Q>/V< 0 15 0
reactive power protection
32, 37 Power protection P<>, Q<> 0 10 0
active/reactive power
32R Reverse-power protection - P< 0 5 0
46 Negative-sequence I2>, ∠(V2,I2) 0 10 0
overcurrent protection with
direction
________________________________________________________________________________________________
4/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
47 Overvoltage protection: V2>; V2/V1> 0 5 0
"negative-sequence V2" or
"negativ-sequence
V2/positiv-sequence V1"
49 Thermal overload protection θ, I²t 0 10 0
for RLC filter elements of a
capacitor bank
50/51 Overcurrent protection, phases I> 2X 2 30 0
TD
Ground-fault detection via IN-pulse 0 15 0
pulse pattern detection; Note:
this stage additionally requires
the function 50Ns/51Ns or
67Ns "Sensitive ground-fault
detection for systems with
resonant or isolated neutral"
Intermittent ground-fault Iie> 0 20 0
protection
50/51 Overcurrent protection for RLC I> 0 10 0
TD filter elements of a capacitor
bank
50BF Circuit-breaker failure CBFP 1 5 5
protection, 3-pole
50RS Circuit-breaker restrike CBRS 0 20 0
protection
51V Overcurrent protection, t=f(I,V) 0 10 0
voltage dependent
59, 59N Overvoltage protection: V> 1 5 5
"3-phase" or "zero-sequence
system V0" or "universal Vx"
59C Peak overvoltage protection, V> cap. 0 30 0
3-phase, for capacitors
59NU Neutral-point UNU> 0 30 0
Voltage-Unbalance Protection
(from V8.6)
60C Current-unbalance protection Iunbal> 0 50 0
for capacitor banks
60 Voltage-comparison ΔU> 0 5 0
supervision
67 Directional overcurrent I>, ∠(V,I) 1 15 15
protection, phases
67N Directional overcurrent IN>, ∠(V,I) 1 15 15
protection, ground
________________________________________________________________________________________________
5/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
67Ns Dir. sensitive ground-fault 0 30 0
detection for systems with
resonant or isolated neutral
incl. a) 3I0>, b) V0>, c)
Cos-/SinPhi, d) Transient
ground-fault fct., e) Phi(V,I), f)
admittance
Directional stage with a ∠(V0h,I0h) 0 10 0
harmonic; Note: this stage
additionally requires the
function "67Ns Dir. sensitive
ground-fault detection for
systems with resonant or
isolated neutral"
Directional intermittent Iie dir> 0 20 0
ground-fault protection
79 Automatic reclosing, 3-pole AR 1 35 35
81 Frequency protection: "f>" or f<>; df/dt<> 0 5 0
"f<" or "df/dt"
81U Underfrequency load-shedding f<(UFLS) 0 15 0
Vector-jump protection Δφ> 0 20 0
87N Restricted ground-fault ΔIN 0 15 0
protection
87C Differential protection, ΔI 0 95 0
capacitor bank
90V Automatic voltage controller 0 150 0
for two-winding transformer
90V Automatic voltage controller 0 180 0
for two-winding transformer
with parallel operation
Number of two-winding 2 5 0
transformers with parallel
operation (Note: only together 2X
with the function "Automatic
voltage controller for
two-winding transformer with
parallel operation")
FL Fault locator, single-sided FL-one 0 25 0
FL Fault locator plus (from V7.9) FL plus 0 45 0
PMU Synchrophasor measurement PMU 0 40 0
Measured values - extended: 0 3 0
Min, Max, Avg
PQ-Basic measured values: 0 20 0
Voltage unbalance (from
V8.40)
________________________________________________________________________________________________
6/7
SIPROTEC 5 - Configuration 17.02.2022 , 05:37:32 PM
________________________________________________________________________________________________
PQ-Basic measured values: 0 30 0
Voltage variations - voltage
dips, swells and interruptions
(from V8.40)
PQ-Basic measured values: 0 10 0
TDD - Total Demand Distortion
(from V8.40)
CFC arithmetic 0 40 0
Circuit-breaker wear ΣIx, I²t, 2P 0 10 0
monitoring
Circuit-breaker 4X 4 3 0
Disconnector/Grounding 4X 4 3 0
switch
Cyber Security: Role-Based 0 25 0
Access Control (from V7.8)
Cyber Security: IEEE 802.1x 0 10 0
based network authentication
(from V8.3)
Total: 130