Siquench: Arc Quenching Device For Medium-Voltage Switchgear "Protection Beyond The Standards"
Siquench: Arc Quenching Device For Medium-Voltage Switchgear "Protection Beyond The Standards"
siemens.com/siquench
SIQuench
The occurrence of an internal arc fault in a well-designed, type-tested, correctly installed and operated switchgear
is improbable – but not impossible – mostly linked to human-related errors or environmental causes. The safety
risk is only one aspect of arc faults. The damage to equipment causing power supply and process disturbance may
lead to substantial costs, in the order of millions of euros per incident. In the case of occupational incidents, the
total costs may be even higher due to medical and legal expenses. Said catastrophic effects could be mitigated
through acting on the arc itself by limiting its duration.
Fig. 1
Powerbox with primary switching units
Benefits
2
The value received =
reliability + capability + functionality + availability + maintainability
The system works in conjunction with an arc protection SIQuench is reusable up to its permissible switching duties:
relay to rapidly and reliably detect the ignition of an • Capable of switching 5 times at the full rated short-time
internal arc via continuous monitoring of light and withstand current (with peak withstand current)
overcurrent – the standard characteristics of an arc that • Capable of switching 30 times without load for testing /
make it detectable. Upon detection of an internal arc, commissioning purposes
the arc protection relay simultaneously sends a trip signal
to the main circuit-breaker and a trigger signal to the SIQuench is maintenance-free for 20 years and capable
controller of the SIQuench. of serving for 30 years with maintenance at the end of the
given maintenance-free period.
The enhanced arc effects mitigation functionality provided
by SIQuench is achieved by consciously and rapidly closing
the main current path of the switchgear to earth via
dedicated phase-wise primary switching devices – creating Energy (I²t - kA²s)
a lower-impedance current path to the fault current – Cable catches fire
and transforming the open arc into a controlled 3-phase
Copper catches fire
metallic short circuit. Continuous self-supervision
maximizes the reliability of the system. Steel catches fire
The damage to the switchgear is limited to an insignificant Fig. 2 Damage caused by incident arc energy
level and wholly avoided for the direct surroundings. This
leads to an extreme reduction of repair costs along with
absolute elimination of switchgear room and surroundings Pressure (kPa)
cleaning costs. The switchgear can be restored back to 160
operation within minimum maintenance time, meaning 140
an incredible boost in system and process availability. 120
The system needs no replacement after an arc fault.
100
0 10 20 30 40 50 60 70 80
Time (ms)
ttrip < 5ms (starting from ignition of the arc)
Fig. 4 Condition of a 12 kV NXAIR cable compartment after an internal arcing test with a fault current
of 80 kA (peak) / 31.5 kA (r.m.s.), with arc ignition inside the cable compartment
CB
Trip 1
Busbar
compart-
ment
Switching –
device
compartment
Cable
compartment
4
SIQuench is available as a complete solution integrated into type-tested, internal arc classified, medium-voltage
switchgear type NXAIR, rated up to 17.5 kV, 50 kA, 4000 A.
** F
unctional units having busbar components
(e.g. VTs, busbar earthing switch, ventilation box...)
are out of this scope
5
Published by
Siemens AG 2019
Energy Management
Medium Voltage & Systems
Mozartstraße 31 C
91052 Erlangen, Germany
For further information, please contact
our Customer Support Center:
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
E-mail: [email protected]
siemens.com/siquench
Article No. EMMS-B10128-00-7600
Printed in Germany
Dispo 30400
PU 184/004613 0219 0.6
Subject to changes and errors. The information given in this document
only contains general descriptions and/or performance features which
may not always specifically reflect those described, or which may
undergo modification in the course of further development of the
products. The requested performance features are binding only when
they are expressly agreed upon in the concluded contract.