CONDUIT INSTALLATION MANHOURS PER LINEAR METER
Sizes RSC PVC Pipes EMT / IMC
Concealed Exposed Concealed Exposed Installation Concealed
Installation Installation Installation Installation
1-Feb 0.217 0.188 0.195 0.169 0.182
3-Apr 0.266 0.23 0.239 0.207 0.218
1 0.272 0.236 0.245 0.212 0.231
l-1/4 0.273 0.2371 0.246 0.213 0.232
1/1/2002 0.326 0.282 0.261 0.225 0.238
2 0.435 0.376 0.326 0.282 0.296
2·1/2 0.607 0.526 0.547 0.473 0.358
3 0.802 0.695 0.602 0.521 0.474
3·1/2 0.851 0.737 0.638 0.553 0.476
4 1.155 1 0.866 0.75 0.647
5 1.579 1.367 1.184 1.025
6 2.041 1.766 1.53 1.324
MC Flexible Steel Conduit
Exposed Installation Concealed Installation Exposed
Installation
0.158 0.11 0.155
0.188 0.142 0.177
0.2 0.184 0.23
0.201 0.188 0.236
0.206 0.231 0.289
0.256 0.288 0.36
0.31 0.435 0.544
0.41 0.608 0.759
0.412 0.895 1.119
0.559
WIRE INSTALLATION MANHOURS PER LINEAR METER
AWG Metric Size Number of Core/Conducter per Cable
Size
2 3 4
16 1.0 mm2 0.039 0.052 0.072
14 2 mm2 0.043 0.056 0.079
12 3.5 mm2 0.049 0.066 0.089
10 5.5 mm2 0.072 0.089 0.105
8 8 mm2 0.085 0.102 0.118
6 14 mm2 0.095 0.108 0.131
4 22 mm2 0.115 0.131 0.157
2 30 mm2 0.121 0.141 0.167
1 38 mm2 0.138 0.157 0.164
1/0 50 mm2 0.174 0.2 0.239
2/0 60 mm2 0.203 0.233 0.282
3/0 80 mm2 0.236 0.272 0.325
4/0 100 mm2 0.276 0.318 0.38
250 MCM 125 mm2 0.295 0.341 0.407
300 MCM 150 mm2 0.312 0.358 0.43
350 MCM 175 mm2 0.328 0.377 0.453
400 MCM 200 mm2 0.361 0.417 0.499
500 MCM 250 mm2 0.384 0.443 0.528
750 MCM 400 mm2 0.518 0.597 0.715
1000 MCM 500 mm2 0.623 0.718 0.859
6
0.102
0.108
0.125
0.141
0.161
0.171
0.207
0.216
0.246
0.312
0.364
0.423
0.495
0.528
0.558
0.587
0.646
0.689
0.928
1.118