100% found this document useful (1 vote)
159 views93 pages

Catalogo Regulador Gas Natural

Eska Valve produces gas pressure regulators, filters, and valves. It has been in business since 1968 in Turkey and exports products to over 30 countries. The document provides information about Eska Valve's ERG-H6 series gas pressure regulator. The ERG-H6 is used to reduce inlet gas pressure for distribution and can be integrated with safety accessories like a relief valve, over pressure shut-off system, and under pressure shut-off system. It has a maximum inlet pressure of 20 bar and outlet pressure range of 15-4000 mbar.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
159 views93 pages

Catalogo Regulador Gas Natural

Eska Valve produces gas pressure regulators, filters, and valves. It has been in business since 1968 in Turkey and exports products to over 30 countries. The document provides information about Eska Valve's ERG-H6 series gas pressure regulator. The ERG-H6 is used to reduce inlet gas pressure for distribution and can be integrated with safety accessories like a relief valve, over pressure shut-off system, and under pressure shut-off system. It has a maximum inlet pressure of 20 bar and outlet pressure range of 15-4000 mbar.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 93

w w w. e s k a v a l v e .

c o m

GENERAL
CATALOGUE
ESKA VALVE is gas equipment producer (Gas Pressure Regulators, Gas Filters and Valves) in Turkey since 1968. Our
certified products are being used in civic and industrial areas all around the world.

For 50 years, our product portfolio, operations and ESKA VALVE family has grown and still keep growing. Ingenuity,
reliability and hard work led us to be the market leader in Turkey and expanded our international operations in more than
30 countries in global scale. By the time you read this text , probably we will be reaching out another locations and placing
our products into grids.

By examining, following and applying 133 national and international standards from our R&D Department library, and
with our Quality Department’s deep commitment to test each and every product on over 100 inspection-test points have
made us to produce annually more than 1.000.000 accurate and reliable unit products which 52 gas distribution companies
trust worldwide .

Hope to gain your trust and see you in our ever-growing family.
ERG-H7 ERG-H6 ERG-H5
SERIES SERIES SERIES
Page 05 - 09 Page 10 - 14 Page 15 - 19

ERG-H1 ERG-SX ERG-S


SERIES SERIES SERIES
Page 20 - 24 Page 26 - 29 Page 30 - 34

ERG-SE ERG-SR E R G
SERIES SERIES SERIES
Page 35 - 49 Page 40 - 44 Page 46 - 50

ERG-E ERG-H ERG-EH


SERIES SERIES SERIES
Page 51 - 55 Page 56 - 59 Page 60 - 63

E G F EGF-H E M V
SERIES SERIES SERIES
Page 65 - 69 Page 70 - 72 Page 74 - 78

E G V E A C CABINET
SERIES SERIES SOLUTIONS
Page 80 - 84 Page 85 - 86 Page 87 - 92
DIRECT ACTING
GAS PRESSURE REGULATOR
w w w. e s k a v a l v e . c o m

ERG-H7
SERIES
ERG-H7
SERIES

ERG-H7 Series pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure.

It is mainly used in Distribution of Natural Gas and also suitable to use with non-corrosive gases. ERG-H7 is a
single stage direct acting regulator with a optional security systems such as relief valve UPSO and OPSO

FEATURES
• For medium and high pressure domestic or industrial second group gas lines.
• Max inlet pressure 0,2 to 16 bar.
• Max outlet pressure 20-4000 mbar.
• Outlet pressure tolerance is ±%5-10 (AC5 & AC10)
• Lock up pressure tolerance is max +%10 (SG30 and SG20 is possible also)
• Can be integrated with UPSO & OPSO
• Temperature class as a standard -20 to +60 Celcius Degree. Low temperature series has ability to
work under as low as -40 Celcius Degree.
• Flow direction inline type.

CONFIGURATIONS

INLINE TYPE

06
ERG-H7
SERIES

DIMENSIONS

C
K

B
A

DN
DN
E

TYPE DN A B C D E F K (Max) K (Min) L

ERG-H7 LP 50 244 428 G 1/2” 380 109 254 559 451 G 1/2”

ERG-H7 HP 50 244 428 G 1/2” 380 109 254 567 459 G 1/2”

ERG-H7 LP 80 289 421 G 1/2” 380 132 298 583 475 G 1/2”

ERG-H7 HP 80 289 421 G 1/2” 380 132 298 592 484 G 1/2”

07
ERG-H7
SERIES

OPSO - UPSO
SAFETY AND ACCESSORIES
Over Pressure Shut-Off System
OPSO system is very useful during major
breakdown situations and keeps
the customer side safe. System works
as a security valve and activates itself
when the outlet pressure passes OPSO
calibration point. OPSO system cuts the
gas off, and manual reset is needed to
activate the regulator again.

System has an independent shut-off


mechanism and orifice and it monitors
outlet pressure changes cont inuously, so
activation time is below 2 seconds.

Under Pressure Shut-Off System.


• UPSO system on ERG-H7 series regulator is
pressure based. It cuts the gas off when the
outlet pressure drops below the UPSO
calibration point.
• UPSO valve continuously monitors outlet
pressure changes. Scenarios like, pipeline
breakdown on outlet sides, or consumption is
exceeding the total capacity of regulator or
lack of inlet pressure situations etc…the
outlet pressure drops and the regulator cuts
the gas off once UPSO system is activated.

08
ERG-H7
SERIES

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Maximum inlet pressure : 16 bar
Outlet pressure range : 20 mbar to 4 bar
Fail Mode : Fail to Open
DN : 2” (50) - 3" (80)

DESIGN
The ERG-H7 Series pressure regulator body consists of :
• Valve housing
• Set up tool
• Breather consol.
• Over pressure shut off OPSO
• Under pressure shut off UPSO
• Furthermore the truly “top entry design” allows an easy periodical maintenance without removing body from
the line.
• High flow rate coefficient
• High accuracy, even at maximum flow rates
• Reduced response times,
• Periodical maintenance without disassembling the body from the pipework,

MATERIALS
• Body is ductile cast iron
• Rubber components have gas approval according to EN 549
• Head covers is die cast alluminium EN AC-AISI 12

09
w w w. e s k a v a l v e . c o m

ERG-H6
SERIES
ERG-H6
SERIES

ERG-H6 Series pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure.

It is mainly used in Distribution of Natural Gas and also suitable to use with non-corrosive gases. ERG-H6 is a
single stage direct acting regulator with a optional security systems such as relief valve UPSO and OPSO

Monitor version is also available.

FEATURES
• For medium and high pressure domestic or industrial second group gas lines.
• Max inlet pressure 0,3 to 20 bar.
• Max outlet pressure 15-4000 mbar.
• Outlet pressure tolerance is ±%5-10 (AC5 & AC10)
• Lock up pressure tolerance is max +%10 (SG30 and SG20 is possible also)
• Can be integrated with Relief valve & UPSO & OPSO
• Temperature class as a standard -20 to +60 Celcius Degree. Low temperature series has ability to
work under as low as -40 Celcius Degree.
• Flow direction inline type.

CONFIGURATIONS

INLINE TYPE

11
ERG-H6
SERIES

DIMENSIONS

K
B

L
A
DN DN

DN A B C D E F K L

50 227 345 G 1/2” 280 175 255 430 G 1/2”

12
ERG-H6
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief RELIEF
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Over Pressure Shut-Off System


OPSO - UPSO
OPSO system is very useful during major
breakdown situations and keeps the
customer side safe. System works as a
security valve and activates itself when the
outlet pressure passes OPSO calibration
point. OPSO system cuts the gas off, and
manual reset is needed to activate the
regulator again.
System has an independent shut-off
mechanism and orifice and it monitors
outlet pressure changes continuously, so
activation time is below 2 seconds.

Under Pressure Shut-Off System.


• UPSO system on ERG-H6 series regulator is pressure based. It cuts the gas off when the outlet pressure drops
below the UPSO calibration point.
• UPSO valve continuously monitors outlet pressure changes. Scenarios like, pipeline breakdown on outlet sides,
or consumption is exceeding the total capacity of regulator or lack of inlet pressure situations etc…the outlet
pressure drops and the regulator cuts the gas off once UPSO system is activated.

13
ERG-H6
SERIES

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 20 bar
Outlet pressure range : 21 mbar to 4 bar
Conforming : 2014/68/EU
Type : IS
Fail Mode : Fail to Open
DN : 1” (25) - 1”1/2 (40) - 2” (50)

DESIGN
The ERG-H6 Series pressure regulator body consists of :
• Valve housing
• Set up tool
• Breather consol.
• Over pressure shut off OPSO
• Under pressure shut off UPSO
• Furthermore the truly “top entry design” allows an easy periodical maintenance without removing body from
the line.
• High flow rate coefficient
• High accuracy, even at maximum flow rates
• Reduced response times,
• Periodical maintenance without disassembling the body from the pipework,

MATERIALS
• Body is ductile cast iron
• Rubber components have gas approval according to EN 549
• Orifice is Brass
• Head covers is die cast alluminium EN AC-AISI 12

CAPACITIES
LP Version MP Version
Norminal Diameter 25 40 50 25 40 50
CG Flow Coffivient 275 665 792 326 704 781
KG Flow Coffivient 290 695 833 343 739 820
K1 Body Shape Factor 98 98 91 101 98 100
Sizing of regulators is usually made on the basis of Cg valve and KG flow rate coeffcients. Flow rates at the fully open position and the various operating

Q = flow rate in Scm/h


Pe = Absolute Upstream Pressure in bar
Pa = Absolute Downstream Pressure in bar

When the Cg and KG values of the regulator are known, as well as Pe and Pa, the flow rate can be calculated as
follows:
1- in non-critical conditions: (Pe < 2 x Pa)

Pe - Pa
Q = 0,52 x Cg x Pe x sen (K1 x ) Q = KG x Pa x (Pe - Pa)
Pe

2- in critical conditions: (Pe ≥ 2 x Pa)

KG
Q= x Pe
2

Q = 0,52 x Cg x Pe

14
w w w. e s k a v a l v e . c o m

ERG-H5
SERIES
ERG-H5
SERIES

ERG-H5 Series pressure regulator which is used on gas line to reduce inlet pressure to desired outlet pressure.

ERG-H5 series pressure regulators are suitable for commercial usage like Gas Skids where the maximum inlet
pressure up to 20 bar and outlet pressure up to 2,5 bar.

It is mainly used in Distribution of Natural Gas and also suitable to use with non-corrosive gases. ERG-H5 is a single
stage direct acting regulator with a optional security systems such as relief valve UPSO and OPSO

FEATURES
• For medium and high pressure domestic or industrial second group gas lines.
• Max inlet pressure 1 to 20 bar.
• Max outlet pressure LPO : 15 to 100 mbar MPO : 100 to 300 mbar HPO : 300 to 2,5 bar
• Optional filter on inlet.
• Outlet pressure tolerance is ±%5-10 (AC5 & AC10)
• Lock up pressure tolerance is max +%30 (SG30,SG10 and SG20 is possible also)
• Can be integrated with Relief valve & UPSO & OPSO
• Temperature class as a standard -20 to +60 Cantigrade Degree. Low temperature series has ability to work
under as low as -40 Centigrade Degree.
• Flow direction inline

CONFIGURATIONS

INLINE TYPE

16
ERG-H5
SERIES

DIMENSIONS

MODEL A B C D E MODEL A B C D E

ERG-H5 (1” - 1”) 100 249 402 1” 1” ERG-H5 (1”-1 1/2”) 129 254 411 1” 1 1/2”

CONNECTION TYPES

Without Connection With Flanged Connection With Loose Connection


17
ERG-H5
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief
RELIEF
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

OPSO - UPSO
Over Pressure Shut-Off System
OPSO system is very useful during major
breakdown situations and keeps the
customer side safe. System works as a
security valve and activates itself when the
outlet pressure passes OPSO calibration
point. OPSO system cuts the gas off, and
manual reset is needed to activate the
regulator again.
System has an independent shut-off
mechanism and orifice and it monitors
outlet pressure changes continuously, so
activation time is below 2 seconds.

Under Pressure Shut-Off System.


• UPSO system on ERG-H5 series regulator is pressure based. It cuts the gas off when the outlet pressure drops
below the UPSO calibration point.
• UPSO valve continuously monitors outlet pressure changes. Scenarios like, pipeline breakdown on outlet sides,
or consumption is exceeding the total capacity of regulator or lack of inlet pressure situations etc…the outlet
pressure drops and the regulator cuts the gas off once UPSO system is activated.

18
ERG-H5
SERIES

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 6 bar (Optional 10 bar, 20 bar)
Outlet pressure range : 15 mbar to 2,5 bar
Conforming : 2014/68/EU
Filter : As a standard 100 micron pore diameter.

DESIGN
The ERG-H5 Series pressure regulator body consists of :
• Valve housing
• Internal thread
• Filter
• Set up tool
• Breather consol.
• Over pressure shut off OPSO
• Under pressure shut off UPSO
• Integrated bypass

MATERIALS
• Body Steel or Iron
• Rubber components have gas approval according to EN 549
• Brass materials are suitable according to EN12164 - EN12165 Standard.

MODELS / CAPACITIES

1"-1" WITH INTERNAL SENSING LINE ACTIVE 1"-1" WITH INTERNAL AND EXTERNAL SENSING LINE ACTIVE

Outlet Pressure 15-100 mbar Outlet Pressure 100-300 mbar Outlet Pressure 15-100 mbar Outlet Pressure 100-300 mbar
LP Version MP Version LP Version MP Version

Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20

Outlet 70 85 95 Outlet 100 120 130 Outlet 45 70 90 Outlet 90 130 140


Pressure+0,5bar Pressure+0,5bar Pressure+0,5bar Pressure+0,5bar
Outlet 70 115 130 Outlet 140 170 190 Outlet 70 130 140 Outlet 130 190 220
Pressure+1bar Pressure+1bar Pressure+1bar Pressure+1bar
Outlet 90 115 130 Outlet 230 280 280 Outlet 110 190 220 Outlet 180 280 280
Pressure+2,5bar Pressure+2,5bar Pressure+2,5bar Pressure+2,5bar
Outlet 80 130 150 Outlet 280 280 280 Outlet 130 230 280 Outlet 330 330 330
Pressure+5bar Pressure+5bar Pressure+5bar Pressure+5bar

1"-1 1/2" WITH INTERNAL SENSING LINE ACTIVE 1"-1 1/2" WITH INTERNAL AND EXTERNAL SENSING LINE ACTIVE

Outlet Pressure 15-100 mbar Outlet Pressure 100-300 mbar Outlet Pressure 15-100 mbar Outlet Pressure 100-300 mbar
LP Version MP Version LP Version MP Version

Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20 Inlet Pressure AC5 AC10 AC20

Outlet 70 90 100 Outlet 110 140 160 Outlet 65 100 105 Outlet 90 150 170
Pressure+0,5bar Pressure+0,5bar Pressure+0,5bar Pressure+0,5bar
Outlet 150 170 190 Outlet 160 240 270 Outlet 150 160 170 Outlet 150 230 270
Pressure+1bar Pressure+1bar Pressure+1bar Pressure+1bar
Outlet 130 190 190 Outlet 340 370 400 Outlet 280 330 330 Outlet 500 500 500
Pressure+2,5bar Pressure+2,5bar Pressure+2,5bar Pressure+2,5bar
Outlet 120 150 170 Outlet 340 400 450 Outlet 190 235 280 Outlet 500 500 500
Pressure+5bar Pressure+5bar Pressure+5bar Pressure+5bar

19
w w w. e s k a v a l v e . c o m

ERG-H1
SERIES
ERG-H1
SERIES

ERG-H1 Series pressure regulator is used on gasline to reduce inlet pressure to desired outlet pressure.
ERG-H1 series pressure regulators are suitable for commercial usage like Gas Skids where the maximum inlet pres-
sure up to 20 bar and outlet pressure up to 4bar.
It is mainly used in Distribution of Natural Gas and also suitable to use with non-corrosive gases. ERG-H1 is a single
stage regulator with an optional security systems such as relief valve, UPSO and OPSO.
The regulators are manufactured according to Ped Directive 2014/68/EU. The performance of the regulators
complies with EN 334

FEATURES
• For medium and high pressure domestic or industrial second group gas lines.
• Max inlet pressure 1 to 20 bar.
• Max outlet pressure MPO: 100 to 800 and HPO : 800 to 4 bar.
• Optional filter on inlet.
• Outlet pressure tolerance is ±%5-10 (AC5&AC10)
• Lock up pressure tolerance is max +%30 (SG30)
• Can be integrated with Relief valve & UPSO & OPSO
• Flow direction inline and angle type.

DIMENSIONS

21
ERG-H1
SERIES

CONFIGURATIONS

INLINE TYPE ANGLE TYPE

CONNECTION TYPES

Without Connection With Flanged Connection With Loose Connection


22
ERG-H1
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s RELIEF
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Over Pressure Shut-Off System


OPSO system is very useful during major OPSO - UPSO
breakdown situations and keeps the
customer side safe. System works as a
security valve and activates itself when the
outlet pressure passes OPSO calibration
point. OPSO system cuts the gas off, and
manual reset is needed to activate the
regulator again.
System has an independent shut-off
mechanism and orifice and it monitors
outlet pressure changes continuously, so
activation time is below 2 seconds.

Under Pressure Shut-Off System.


• UPSO system on ERG-H1 series regulator is pressure based. It cuts the gas off when the outlet pressure drops
below the UPSO calibration point.
• UPSO valve continuously monitors outlet pressure changes. Scenarios like, pipeline breakdown on outlet sides,
or consumption is exceeding the total capacity of regulator or lack of inlet pressure situations etc…the outlet
pressure drops and the regulator cuts the gas off once UPSO system is activated.

23
ERG-H1
SERIES

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 6 bar (Optional 10 bar, 20 bar)
Outlet pressure range : 100 mbar to 4 bar.
Conforming : 2014/68/EU
Filter : As a standard 100 micron pore diameter.

DESIGN
The ERG-H1 Series pressure regulator body consists of :
• Valve housing
• Internal thread
• Filter
• Set up tool
• Breather consol.
• Optional pressure test point.
• Over pressure shut off OPSO
• Under pressure shut off UPSO
• Integrated bypass

MATERIALS
• Body Aluminum
• Rubber components have gas approval according to EN 549
• Brass materials are suitable according to EN12164 - EN12165 Standard.

CAPACITIES

Flow Rate Pin


SCMH mbar
Methane
50 Pd + 0,3 bar

75 Pd + 0,5 bar

100 Pd + 1 bar

180 Pd + 2,5 bar

250 Pd + 3,5 bar

Pd = Outlet pressure

24
DOUBLE STAGE
GAS PRESSURE REGULATOR
w w w. e s k a v a l v e . c o m

ERG-SX
SERIES
ERG-SX
SERIES

ERG-SX Series double stage pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure.
It is suitable for both commercial and domestic usage where can be directly installed to gas meters with high operation-
al reliability and accurate outlet pressure accuracy.
Simple installation procedure.
Due to different inlet and outlet connection range, ERG-SX Series can be used along with pipe diameter from DN15 to
DN50 with different thread standards as well as BSP, BSPT, NPT, NPP.
The modular concept of ERG-SX and wide range availability of inlet and outlet connections allow to match particular
customer requirements.
The regulators are manufactured according to Ped Directive 2014/68/EU. The functional tests are performed
according to EN334.

FEATURES
• For medium pressure domestic or commercial second group gas lines.
23
• Optional metallic mesh filter for easy change and guarantees longer operation life of regulator.
• Outlet pressure tolerance is +%10 (AC10) up +- %5 (AC5)
• Lock-up pressure tolerance is +%20 (SG20) up to 100 mbar outlet pressure, more than 100 mbar
outlet pressure SG20 and SG10 possible.
• Up to 6 bar inlet pressure.
• 18 - 500 mbar outlet pressure range with interchangeable springs
Optional ;
• Incorporated Under Pressure Shut Off Valve.
• Internal Relief Valve

DIMENSIONS

27
ERG-SX
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Under Pressure Shut-Off System.


UPSO system on ERG- SX series
regulator acts under those
circumstances;
• When there is no pressure inlet side.
• When the consumption exceed regula-
tor’s maximum capacity. (%101*Q to
%150*Q)
• When the pressure drop outlet side due
to consumption.
UPSO valve continuously monitors outlet
pressure changes. Scenarios like, pipeline
breakdown on outlet sides, or consump-
tion is exceeding the total capacity of regu-
lator or lack of inlet pressure situations
etc…the outlet pressure drops and the
regulator cuts the gas off once UPSO
system is activated.

28
ERG-SX
SERIES

CONFIGURATIONS

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 5 bar
Minimum inlet pressure : Depending on customer request can start as low as 0,3 bar.
Outlet pressure range : 12 to 35 mbar.
Filter : Included

DESIGN
The ERG-SX Series pressure regulator body may consists of:
• Valve housing
• Connections
• Filter
• Ventilation console
• Outlet pressure test point
• Integrated security valves (UPSO / Relief)

MATERIALS
• Body and covers Aluminum according to EN1706 standard.
• Rubber components are Nitril Rubber comply to EN 549.
• Brass materials are suitable according to EN12164 - EN12165 Standard.
• Filter material is metallic mesh filter.
MODELS

MODEL FLOW RATE UNIT WEIGHT BOX SIZE PACKAGING CARTON SIZE CARTON TOTAL CARTON
LPO MPO HPO (kgs) (LxWxH cm) (pieces/ carton) (LxWxH cm) (weight) (weight)
18-75 75-150 150-500
mbar mbar mbar

ERG-SX 06 6 1,29 12,3x12,7x16,3 24 50x50x29 1.69kg 32.65 kg

ERG-SX 10 10 1,29 12,3x12,7x16,3 24 50x50x29 1.69kg 32.65 kg

ERG-SX 15 15 1,29 12,3x12,7x16,3 24 50x50x29 1.69kg 32.65 kg

29
w w w. e s k a v a l v e . c o m

ERG-S
SERIES
ERG-S
SERIES

ERG-S Series double stage pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure.
It is suitable for both commercial and domestic usage where can be directly installed to gas meters with high operation-
al reliability and accurate outlet pressure accuracy.
Simple installation procedure.
Due to different inlet and outlet connection range, ERG-S Series can be used along with pipe diameter from DN15 to
DN50 with different thread standards as well as BSP, BSPT, NPT, NPP.
The modular concept of ERG-S and wide range availability of inlet and outlet connections allow to match particular
customer requirements.
The regulators are manufactured according to Ped Directive 2014/68/EU. The functional tests are performed
according to EN334.

FEATURES
• For medium pressure domestic or commercial second group gas lines.
• Optional metallic mesh filter for easy change and guarantees longer operation life of regulator.
• Outlet pressure tolerance is +%10 (AC10) up +- %5 (AC5)
• Lock-up pressure tolerance is +%20 (SG20) up to 100 mbar outlet pressure, more than 100 mbar
outlet pressure SG20 and SG10 possible.
• Up to 6 bar inlet pressure.
• 18 - 500 mbar outlet pressure range with interchangeable springs
Optional ;
• Incorporated Under Pressure Shut Off Valve.
• Internal Relief Valve

DIMENSIONS

31
ERG-S
SERIES

CONNECTION TYPES

BSPP
G 1/4”
G 1/2”
G 3/4”
G 1”
G 1 1/4”
G 1 1/2”

BSPT
R 1/4”
R 1/2”
R 3/4”
R 1”
R 1 1/4”
R 1 1/2”

ANSI B 1.20.1
NPT 1/4”
NPT 1/2”
NPT 3/4”
NPT 1”
NPT 1 1/4”
NPT 1 1/2”

BSPP BSPT ANSI B 1.20.1


G 1/4” R 1/4” NPT 1/4”
G 1/2” R 1/2” NPT 1/2”
G 3/4” R 3/4” NPT 3/4”
G 1” R 1” NPT 1”
G 1 1/4” R 1 1/4” NPT 1 1/4”
G 1 1/2” R 1 1/2” NPT 1 1/2”

1/2" Tapa 1/2" CF 3/4" SC 3/4" CF 7/8" 1" FC (Female) 1'' CF 1 1/4" CF
3 3 17
3 15.5 3 16.4 16.4
3 16 12.3
INLET

7.3
G1/2"

7/8"
3/4"

G1''

1 1/4"
3/4"
1/2"

B=61.3 B=72.5 20.5


B=73.2 B=66.3
A=109.2 B=73.4 A=111.2 B=70.4 B=74
A=98 A=110 A=103 A=110.1 A=107.1 A=110.7

3/4" Tapa 1/2" CF 3/4" CF 7/8" 1'' CF 1" FC (Female) 1 1/4" CF 1 1/4" CF
18.5

19.4
C=59.1
17

C=58

C=60
C=59.9

C=60
C=46.6

C=60
19.4

C=73
19.4

32.4

19.4
6

7/8" 1"
3
OUTLET

1/2" G 1''
3/4"

1" Tapa 1/2" CF 3/4" CF 7/8" 1'' CF

D=26.8 22.4
D=44 18.5 3 19.4 3
3
1/2"

3/4"

G 1''
7/8"

0 17 3 D=45.3
D=46.2 D=49

32
ERG-S
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s RELIEF
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Under Pressure Shut-Off System.


UPSO system on ERG- S series regulator
acts under those circumstances;

• When there is no pressure inlet side.


• When the consumption exceed regula- UPSO
tor’s maximum capacity. (%101*Q to
%150*Q)
• When the pressure drop outlet side due
to consumption.

UPSO valve continuously monitors outlet


pressure changes. Scenarios like, pipeline
breakdown on outlet sides, or consump-
tion is exceeding the total capacity of regu-
lator or lack of inlet pressure situations
etc…the outlet pressure drops and the
regulator cuts the gas off once UPSO
system is activated.
33
ERG-S
SERIES

CONFIGURATIONS

INLINE ANGLE Q TYPE U TYPE

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 6 bar
Minimum inlet pressure : Depending on customer request can start as low as 0,1 bar.
Outlet pressure range : 18 to 500 mbar.
Filter : Included

DESIGN
The ERG-S Series pressure regulator body may consists of:
• Valve housing
• Connections
• Filter
• Ventilation console
• Outlet pressure test point
• Integrated security valves (UPSO / Relief)

MATERIALS
• Body and covers Aluminum according to EN1706 standard.
• Rubber components are Nitril Rubber comply to EN 549.
• Brass materials are suitable according to EN12164 - EN12165 Standard.
• Filter material is metallic mesh filter.

MODELS

MODEL FLOW RATE UNIT WEIGHT BOX SIZE PACKAGING CARTON SIZE CARTON TOTAL CARTON
LPO MPO HPO (kgs) (LxWxH cm) (pieces/ carton) (LxWxH cm) (weight) (weight)
18-75 75-150 150-500
mbar mbar mbar

ERG-S 06 6 1,10 15x14.5x16 16 33x58x35 0.65kg 18.2 kg

ERG-S 10 10 1,10 15x14.5x16 16 33x58x35 0.65kg 18.2 kg

ERG-S 25 25 1,10 15x14.5x16 16 33x58x35 0.65kg 18.2 kg

ERG-S 50 50 1,10 15x14.5x16 16 33x58x35 0.65kg 18.2 kg

BESIDE STANDARD FLOW RATES ABOVE, 1,6 / 2,5 / 15 / 30 / 40 / 60 / 65 SCMH ARE AVAILABLE UPON REQUEST.
34
w w w. e s k a v a l v e . c o m

ERG-SE
SERIES
ERG-SE
SERIES

ERG-SE Series double stage pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure.
It is suitable for both commercial and domestic usage where can be directly installed to gas meters with high opera-
tional reliability and accurate outlet pressure accuracy.
Simple installation procedure.
Due to different inlet and outlet connection range, ERG-SE Series can be used along with pipe diameter from DN15 to
DN50 with different thread standards as well as BSP, BSPT, NPT, NPP.
The modular concept of ERG-SE and wide range availability of inlet and outlet connections allow to match particular
customer requirements.
The regulators are manufactured according to Ped Directive 2014/68/EU. The functional tests are performed
according to EN334.

FEATURES
• For medium pressure domestic or commercial second group gas lines.
• Optional metallic mesh filter for easy change and guarantees longer operation life of regulator.
• Outlet pressure tolerance is +%10 (AC10) up +- %5 (AC5)
• Lock-up pressure tolerance is +%20 (SG20) up to 100 mbar outlet pressure, more than 100 mbar outlet
pressure SG20 and SG10 possible.
• Up to 6 bar inlet pressure.
• 18 - 500 mbar outlet pressure range with interchangeable springs
Optional ;
• Incorporated Over Pressure Shut Off Valve.
• Incorporated Under Pressure Shut Off Valve.
• Internal Relief Valve

DIMENSIONS

36
ERG-SE
SERIES

CONNECTION TYPES

BSPP
G 1/4”
G 1/2”
G 3/4”
G 1”
G 1 1/4”
G 1 1/2”

BSPT
R 1/4”
R 1/2”
R 3/4”
R 1”
R 1 1/4”
R 1 1/2”

ANSI B 1.20.1
NPT 1/4”
NPT 1/2”
NPT 3/4”
NPT 1”
NPT 1 1/4”
NPT 1 1/2”

BSPP BSPT ANSI B 1.20.1


G 1/4” R 1/4” NPT 1/4”
G 1/2” R 1/2” NPT 1/2”
G 3/4” R 3/4” NPT 3/4”
G 1” R 1” NPT 1”
G 1 1/4” R 1 1/4” NPT 1 1/4”
G 1 1/2” R 1 1/2” NPT 1 1/2”

1/2" Tapa 1/2" CF 3/4" SC 3/4" CF 7/8" 1" FC (Female) 1'' CF 1 1/4" CF
3 3 17
3 15.5 3 16.4 16.4
3 16 12.3
INLET

7.3
G1/2"

7/8"
3/4"

G1''

1 1/4"
3/4"
1/2"

B=61.3 B=72.5 20.5


B=73.2 B=66.3
A=109.2 B=73.4 A=111.2 B=70.4 B=74
A=98 A=110 A=103 A=110.1 A=107.1 A=110.7

3/4" Tapa 1/2" CF 3/4" CF 7/8" 1'' CF 1" FC (Female) 1 1/4" CF 1 1/4" CF
18.5

19.4
C=59.1
17

C=58

C=60
C=59.9

C=60
C=46.6

C=60
19.4

C=73
19.4

32.4

19.4
6

7/8" 1"
3
OUTLET

1/2" G 1''
3/4"

1" Tapa 1/2" CF 3/4" CF 7/8" 1'' CF

D=26.8 22.4
D=44 18.5 3 19.4 3
3
1/2"

3/4"

G 1''
7/8"

0 17 3 D=45.3
D=46.2 D=49

37
ERG-SE
SERIES

SAFETY AND ACCESSORIES


Relief System RELIEF
Regulator can be produced with a relief
valve. Relief valve monitors outlet pres-
sure continuously and when it detects
pressure level higher than regulator’s
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain conditions
such as gas expansion during hot weather
seasons, Relief Valve is activated before
OPSO closes the gas lines. It prevents
random shut-off regarding pressure
increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Over Pressure Shut-Off System OPSO


OPSO system is very useful during major
breakdown situations and keeps the
customer side safe. System works as a
security valve and activates itself when the
outlet pressure passes OPSO calibration
point. OPSO system cuts the gas off, and
manual reset is needed to activate the
regulator again.
System has an independent shut-off
mechanism and orifice and it monitors
outlet pressure changes continuously, so
activation time is below 2 seconds.

Under Pressure Shut-Off System.


UPSO system on ERG- SE series regulator
acts under those circumstances;

• When there is no pressure inlet side. UPSO


• When the consumption exceed regula-
tor’s maximum capacity. (%101*Q to
%150*Q)
• When the pressure drop outlet side due
to consumption.

UPSO valve continuously monitors outlet


pressure changes. Scenarios like, pipeline
breakdown on outlet sides, or consump-
tion is exceeding the total capacity of regu-
lator or lack of inlet pressure situations
etc…the outlet pressure drops and the
regulator cuts the gas off once UPSO
system is activated.
38
ERG-SE
SERIES

CONFIGURATIONS

INLINE ANGLE Q TYPE U TYPE

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60°C (optional : -40… +60°C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 6 bar
Minimum inlet pressure : Depending on customer request can start as low as 0,1 bar.
Outlet pressure range : 18 to 500 mbar.
Filter : Included

DESIGN
The ERG-SE Series pressure regulator body may consists of:
• Valve housing
• Connections
• Filter
• Ventilation console
• Outlet pressure test point
• Integrated security valves (OPSO / UPSO / Relief)

MATERIALS
• Body and covers Aluminum according to EN1706 standard.
• Rubber components are Nitril Rubber comply to EN 549.
• Brass materials are suitable according to EN12164 - EN12165 Standard.
• Filter material is metallic mesh filter.

MODELS

MODEL FLOW RATE UNIT WEIGHT BOX SIZE PACKAGING CARTON SIZE CARTON TOTAL CARTON
LPO MPO HPO (kgs) (LxWxH cm) (pieces/ carton) (LxWxH cm) (weight) (weight)
18-75 75-150 150-500
mbar mbar mbar

ERG-SE 06 6 1,15 15x14.5x16 16 33x58x35 0.65kg 19.5 kg

ERG-SE 10 10 1,15 15x14.5x16 16 33x58x35 0.65kg 19.5 kg

ERG-SE 25 25 1,15 15x14.5x16 16 33x58x35 0.65kg 19.5 kg

ERG-SE 50 50 1,15 15x14.5x16 16 33x58x35 0.65kg 19.5 kg

BESIDE STANDARD FLOW RATES ABOVE, 1,6 / 2,5 / 15 / 30 / 40 / 60 / 65 SCMH ARE AVAILABLE UPON REQUEST.
39
w w w. e s k a v a l v e . c o m

ERG-SR
SERIES
ERG-SR
SERIES

ERG-SR Series pressure regulator is used on gas line to reduce inlet pressure to desired outlet pressure. It is
suitable for both commercial and residential usage where can be directly installed to gas meters with high
operational reliability and accurate outlet pressure accuracy.
Simple installation procedure. Direction of the line can be inline or angle.
Due to different inlet and outlet connection range, ERG-SR Series can be used along with pipe diameter from
DN20 to DN50 with different thread standards as well as BSP, BSPT, NPT, NPP. (Also, can be added to flange
connection.)
The regulators are manufactured according to Ped Directive 2014/68/EU. The functional tests are performed
according to EN334.

FEATURES
• For medium pressure domestic or commercial second group gas lines.
• Optional metallic mesh filter for easy change and guarantees longer operation life of regulator.
• Outlet pressure tolerance is +%10 (AC10) up +- %5 (AC5)
• Lock-up pressure tolerance is +%20 (SG20) up to 100 mbar outlet pressure, more than 100 mbar outlet
pressure SG20 and SG10 possible.
• Up to 6 bar inlet pressure.
• 15 - 360 mbar outlet pressure range with interchangable springs
• OPSO pressure range 35 - 520 mbar
• UPSO pressure range 8 - 250 mbar

CONFIGURATIONS

INLINE TYPE ANGLE TYPE

41
ERG-SR
SERIES

DIMENSIONS

CONNECTION TYPES

Without Connection With Flanged Connection With Loose Connection

42
ERG-SR
SERIES

SAFETY AND ACCESSORIES


Relief System
Regulator can be produced with a relief
valve. Relief valve monitors outlet
pres sure continuously and when it detects RELIEF
pressure level higher than regulator’s
nominal outlet pressure, it activates and
discharges gas to the atmosphere.
Relief valve has limited discharge capacity.
Usually calibration point is lower than
OPSO system. Under certain
conditions such as gas expansion during
hot weather seasons, Relief Valve is
activated before OPSO closes the gas lines.
It prevents random shut-off regarding
pressure increase on outlet side.
Relief valve can be recalibrated by using
proper tools.

Over Pressure Shut-Off System


OPSO system is very useful during major
breakdown situations and keeps the OPSO - UPSO
customer side safe. System works as a
security valve and activates itself when the
outlet pressure passes OPSO set point.
OPSO system cuts the gas off, and manual
reset is needed to activate the regulator
again.
System has an independent shut-off
mechanism and orifice and it monitors
outlet pressure changes continuously, so
the activation time is below 2 seconds.

Under Pressure Shut-Off System.


UPSO system on SR series regulator is pressure based. It cuts the gas off when the outlet pressure drops below
the UPSO calibration point.
UPSO valve continuously monitors outlet pressure changes. Scenarios like, pipeline breakdown on outlet sides,
or consumption is exceeding the total capacity of regulator or lack of inlet pressure situations etc…the outlet
pressure drops and the regulator cuts the gas off once UPSO system is activated.
43
ERG-SR
SERIES

SPECIFICATIONS
Medium : Natural Gas, LPG and Non-Corrosive Gases
Operating temperature : -20… + 60 °C (optional : -40… +60 °C)
Assembly : Vertical and Horizontal Position
Maximum inlet pressure : 6 bar
Outlet pressure range : 15 to 360 mbar.
Referring : Ped 2014/68/EU
Filter : Included

DESIGN
The ERG-SR Series pressure regulator body consists of:
• Loose nut or body thread or flanged connection
• Filter
• Ventilation console
• Outlet pressure test point
• Integrated security valves

MATERIALS
• Body and covers Aluminum comply with EN1706 standard.
• Rubber components comply with EN549.
• Brass materials comply with EN12164 Standard.
• Filter material is metallic mesh filter.

MODELS

MODEL NOMINAL CAPACITY REQUIRED MINIMUM INLET PRESSURE BAR (PSI)


ERG-SR 50 50 STM3/H OUTLET PRESSURE + 0.5
ERG-SR 75 75 STM3/H OUTLET PRESSURE + 0.5
ERG-SR 100 100 STM3/H OUTLET PRESSURE + 0.5

44
SINGLE STAGE
GAS PRESSURE REGULATOR
w w w. e s k a v a l v e . c o m

E R G
SERIES
E R G
SERIES

INTRODUCTORY

ERG series gas pressure regulators are used in the gas lines in order to reduce maximum 1 bar input pressure to the
desired output pressure between 16 and 150 mbar. The range of the output pressure can be set with the choice of a
different spring.

ERG 1015 - 1020 - 1025

ERG 1032 - 1040 - 1050

47
E R G
SERIES

TECHNICAL INFORMATION

• Usage : City gas networks and gas pipelines in industrial areas


• Medium : Non‐corrosive gases such as Natural Gas (Methane), LPG, Town Gas, Air, etc…

• Pressure Class : PN0.5


• Connection or Port Size : 1/2”, 3/4”, 1”, 11/4”, 11/2”, 2” Threaded (Female)
• Inlet Pressure Range : 0.05 up to 0.5 bar
• Outlet Pressure Range : 16 mbar up to 150 mbar
• Filter : Optional
• Number of Stages : Single Stage
• Accuracy Class : AC 10 (± 10%) (On Request AC5, AC15, AC20)
• Lock Up Pressure Class : SG30 (+ 30%) (On Request SG10, SG20))
• Ambient Temperature : ‐20°C up to 60°C (On request -40 °C)
• Material Standard : Aluminum-EN 1706 / Brass-EN 12164 and EN 12165 / Rubber-EN 549
• According to Directives : 2014/68/EU

ERG SERIES CAPACITY GRAPH

ERG 1015
100 ERG 1020
ERG 1025
50 ERG 1032
ERG 1040
ERG 1050

10
P mbar

Convertion Constant
1 Methane : 1,28
LPG : 1,61

0,1
10 50 100 200 300 500 1000
Q (Air) SCMH

48
E R G
SERIES

CONFIGURATIONS
INLINE

ERG 1015 - 1020 - 1025

INLINE

ERG 1032 - 1040 - 1050

CONNECTION OUTLET PRESSURE


(21mbar)

1/2" 20 m3/h

3/4" 25 m3/h

1" 35 m3/h

11/4" 85 m3/h

11/2" 100 m3/h

2" 120 m3/h

FLOW RATE TABLE (FOR NATURAL GAS) AT INLET PRESSURE 300 mbar ACCURACY CLASS AC10
49
E R G
SERIES

DIMENSIONS

MODEL A B C D E F

ERG 1015 1/2” 122 107 141 136 145

ERG 1020 3/4” 122 107 141 136 145

ERG 1025 1” 122 107 141 136 145

MODEL A B C D E

ERG 1032 1 1/4” 160 225 237 183

ERG 1040 1 1/2” 160 225 237 183

ERG 1050 2” 162 225 259 192

50
w w w. e s k a v a l v e . c o m

ERG-E
SERIES
ERG-E
SERIES

INTRODUCTORY

ERG-E series gas pressure regulators are used in the gas lines in order to reduce maximum 1 bar input pressure to
the desired output pressure between 16 and 150 mbar. The range of the output pressure can be set with the choice of a
different spring. The regulator with safety stopping gets automatically active and stops the gas flow in case that the input
pressure gets higher or lower than the adjusted value in order to ensure the safety of the devices used in the system
thanks to the safe stopping system it includes.

ERG-E 1015 - 1020 - 1025

ERG-E 1032 - 1040 - 1050

52
ERG-E
SERIES

TECHNICAL INFORMATION

• Usage : City gas networks and gas pipelines in industrial areas


• Medium : Non‐corrosive gases such as Natural Gas (Methane), LPG, Town Gas, Air, etc…

• Pressure Class : PN0.5


• Connection or Port Size : 1/2”, 3/4”, 1”, 11/4”, 11/2”, 2” Threaded (Female)
• Inlet Pressure Range : 0.05 up to 0.5 bar
• Outlet Pressure Range : 16 mbar up to 150 mbar
• Filter : Optional
• Number of Stages : Single Stage
• Accuracy Class : AC 10 (± 10%) (On Request AC5, AC15, AC20)
• Lock Up Pressure Class : SG30 (+ 30%) (On Request SG10, SG20))
• Ambient Temperature : ‐20°C up to 60°C (On request -40 °C)
• OPSO Pressure Range : 30 mbar up to 200 mbar
• OPSO Pressure Tolerance : 20%
• UPSO Pressure Range : 12 mbar up to 40 mbar
• UPSO Pressure Tolerance : 20%
• Shut Off Time : Less than 1 second
• Structural Additional Features : With Shutoff
• Material Standard : Aluminum-EN 1706 / Brass-EN 12164 and EN 12165 / Rubber-EN 549
• According to Directives : 2014/68/EU

ERG-E SERIES CAPACITY GRAPH

ERG-E 1015
100 ERG-E 1020
ERG-E 1025
50 ERG-E 1032
ERG-E 1040
ERG-E 1050

10
P mbar

Convertion Constant
Methane : 1,28
1
LPG : 1,61

0,1
10 50 100 200 300 500 1000
Q (Air) SCMH

53
ERG-E
SERIES

CONFIGURATIONS AND CONNECTION TYPES


INLINE

ERG-E 1015 - 1020 - 1025

INLINE

ERG-E 1032 - 1040 - 1050

CONNECTION OUTLET PRESSURE


(21mbar)

1/2" 20 m3/h

3/4" 25 m3/h

1" 35 m3/h

11/4" 85 m3/h

11/2" 100 m3/h

2" 120 m3/h

FLOW RATE TABLE (FOR NATURAL GAS) AT INLET PRESSURE 300 mbar ACCURACY CLASS AC10

54
ERG-E
SERIES

DIMENSIONS

MODEL A B C D E F

ERG-E 1015 1/2” 122 106 198 136 146

ERG-E 1020 3/4” 122 106 198 136 146

ERG-E 1025 1” 122 106 198 136 146

MODEL A B C D E

ERG-E 1032 1 1/4” 160 225 311 183

ERG-E 1040 1 1/2” 160 225 311 183

ERG-E 1050 2” 162 225 333 192

55
w w w. e s k a v a l v e . c o m

ERG-H
SERIES
ERG-H
SERIES

INTRODUCTORY

ESKA ERG-H series gas pressure regulators are used in the gas lines in order to reduce maximum 5 bar input pressure to the
desired output pressure between 16 and 500 mbar. The range of the output pressure can be set with the choice of different
springs.

The regulators are manufactured according to Ped Directive 2014/68/EU. The functional tests are performed according to
EN334.

ERG-H 1015 - 1020 - 1025 ERG-H 1032 - 1040 - 1050

CONFIGURATIONS

ERG-H 1015 - 1020 - 1025 ERG-H 1032 - 1040 - 1050

57
ERG-H
SERIES

TECHNICAL INFORMATION

• Usage : City gas networks and gas pipelines in industrial areas


• Medium : Non‐corrosive gases such as Natural Gas (Methane), LPG, Town Gas, Air, etc…
• Pressure Class : PN5
• Connection or Port Size : 1/2”, 3/4”, 1”, 11/4”, 11/2”, 2” Threaded and (Flanged)
• Inlet Pressure Range : 0.5 up to 5 bar
• Outlet Pressure Range : 16 mbar up to 500 mbar
• Filter : Optional
• Number of Stages : Single Stage
• Accuracy Class : AC 10 (± 10%) (On Request AC5, AC15, AC20)
• Ambient Temperature : ‐20°C up to 60°C (On request -40 °C)
• Shut Off Time : Less than 1 second

• Material Standard : Aluminum-EN 1706 / Brass-EN 12164 and EN 12165 / Rubber-EN 549
• According to Directives : 2014/68/EU
• Capacity : Up to 1000m3/h

58
ERG-H
SERIES

DIMENSIONS

MODEL A B C D E

ERG-H 1015 1/2” 136 156 215 110

ERG-H 1020 3/4” 136 156 215 110

ERG-H 1025 1” 136 156 215 110

MODEL A B C D E

ERG-H 1032 1 1/4” 160 225 238 183

ERG-H 1040 1 1/2” 160 225 238 183

ERG-H 1050 2” 162 225 238 192


59
w w w. e s k a v a l v e . c o m

ERG-EH
SERIES
ERG-EH
SERIES

INTRODUCTORY

ERG-EH series gas pressure regulators are used in the gas lines in order to reduce maximum 5 bar input pressure to
the desired output pressure between 16 and 500 mbar. The range of the output pressure can be set with the choice of a
different spring. The regulator with safety stopping gets automatically active and stops the gas flow in case that the input
pressure gets higher or lower than the adjusted value in order to ensure the safety of the devices used in the system
thanks to the safe stopping system it includes.

ERG-EH 1015 - 1020 - 1025 ERG-EH 1032 - 1040 - 1050

CONFIGURATIONS
INLINE

INLINE

ERG-EH 1015 - 1020 - 1025 ERG-EH 1032 - 1040 - 1050

61
ERG-EH
SERIES

TECHNICAL INFORMATION

• Usage : City gas networks and gas pipelines in industrial areas


• Medium : Non‐corrosive gases such as Natural Gas (Methane), LPG, Town Gas, Air, etc…
• Pressure Class : PN5
• Connection or Port Size : 3/4”, 1”, 11/4”, 11/2”, 2” Threaded and (Flanged)
• Inlet Pressure Range : 0.5 up to 5 bar
• Outlet Pressure Range : 16 mbar up to 500 mbar
• Filter : Optional
• Number of Stages : Single Stage
• Accuracy Class : AC 10 (± 10%) (On Request AC5, AC15, AC20)
• Lock Up Pressure Class : SG30 (+ 30%) (On Request SG10, SG20))
• Ambient Temperature : ‐20°C up to 60°C (On request -40 °C)
• OPSO Pressure Range : 30 mbar up to 200 mbar
• OPSO Pressure Tolerance : 20%
• UPSO Pressure Range : 12 mbar up to 150 mbar
• UPSO Pressure Tolerance : 20%
• Shut Off Time : Less than 1 second
• Structural Additional Features : With Shutoff
• Material Standard : Aluminum-EN 1706 / Brass-EN 12164 and EN 12165 / Rubber-EN 549
• According to Directives : 2014/68/EU
• Capacity : Up to 1000m3/h

62
ERG-EH
SERIES

DIMENSIONS

MODEL A B C D E

ERG-EH 1015 1/2” 136 156 215 110

ERG-EH 1020 3/4” 136 156 215 110

ERG-EH 1025 1” 136 156 215 110

MODEL A B C D E

ERG-EH 1032 1 1/4” 160 225 332 183

ERG-EH 1040 1 1/2” 160 225 332 183

ERG-EH 1050 2” 160 225 332 183


63
G A S
FILTER
w w w. e s k a v a l v e . c o m

E G F
SERIES
E G F
SERIES

INTRODUCTORY

EGF model gas filters are the elements that seperates the dust particles carried by the gas or very small particles
spread within the gas (for example: dust and rust), holds these and protects the burner, gas counter and adjustment
devices which may possibly be damaged. Dust, woodchips, smut and other physical substances and dirt in the gas are held
by the fiber. When the dust tank capacity is exceeded or a very high pressure difference effected, the filter loses its filter
protection function. The filters are resistant against the mechanical and thermal stress that occur under operational
conditions.The device must be kept away from rain and water as much as possible.

EGF 1015 - 1020 - 1025 EGF 1032 - 1040 - 1050

EGF 1065 -1080 - 1100

66
E G F
SERIES

TECHNICAL INFORMATION
• Filter : Pore dimensions as standard 50
• Usage : City gas networks and gas
micron (10-20 microns on
pipelines in industrial areas
request)
• Fluid Type : Non‐corrosive gases such as
• Ambient
Natural Gas (Methane), LPG, Temperature Range : ‐20°C up to 60°C
Town Gas, Air, etc… • Pressure
• Pressure Class : PN1 Test Connection : 1/4” Threaded (Female)
• Connection or • Material Standard : Aluminum EN 1706,
Port Size : 1/2”, 3/4, 1”, 11/4”, 11/2”, 2” Rubbers EN 549
Threaded (Female) and DN65,
DN80, DN100 Flanged

CONFIGURATION
INLINE

INLINE

EGF 1015 - 1020 - 1025 EGF 1032 - 1040 - 1050

INLINE
INLINE

EGF 1065 -1080 - 1100

EGF SERIES CAPACITY GRAPH


200
EGF 1015
100 EGF 1020
EGF 1025
50
EGF 1032
EGF 1040
EGF 1050
10 EGF 1065
P (mbar)

EGF 1080
5 EGF 1100

Convertion Constant
1 Methane : 1,28
LPG : 1,61

0.1
10 50 100 200 300 500 1000

Q (m3/hAir)
67
E G F
SERIES

DIMENSIONS

MODEL DN A B C D E F

EGF 1015 15 1/2” 136 32 54,5 93 AA43

EGF 1020 20 3/4“ 136 32 54,5 93 AA43

EGF 1025 25 1” 136 32 54,5 93 AA43

MODEL DN A B C D E

EGF 1032 32 1 1/4” 160 53,5 91 140

EGF 1040 40 1 1/2” 160 53,5 91 140

EGF 1050 50 2” 160 68,5 114 140

68
E G F
SERIES

DIMENSIONS

MODEL DN A B C D E K Numbers of holes

EGF 1065 65 70 290 93 195 218 145 4

EGF 1080 80 85 310 104 204 218 160 8

EGF 1100 100 100 355 108 211 254 180 8

69
w w w. e s k a v a l v e . c o m

EGF-H
SERIES
EGF-H
SERIES

INTRODUCTORY AND TECHNICAL INFORMATION


EGF-H model gas filters are the elements that seperates the dust particles carried by the gas or very small particles
spread within the gas (for example: dust and rust), holds these and protects the burner, gas counter and adjustment
devices which may possibly be damaged. Dust, woodchips, smut and other physical substances and dirt in the gas are held
by the fiber. When the dust tank capacity is exceeded or a very high pressure difference effected, the filter loses its filter
protection function. The filters are resistant against the mechanical and thermal stress that occur under operational
conditions.The device must be kept away from rain and water as much as possible.

• Usage : City gas networks and gas • Filter : Pore dimensions as standard
pipelines in industrial areas 50 micron (5-10-20 microns
• Fluid Type : Non‐corrosive gases such as on request)
Natural Gas (Methane), LPG, • Ambient
Temperature Range : ‐20°C up to 60°C
Town Gas, Air, etc…
• Pressure
• Pressure Class : PN6
Test Connection : 1/4” Threaded (Female)
• Connection or
• Material Standard : Aluminum EN 1706,
Port Size : 1/2”, 3/4, 1”, 11/4”, 11/2”, 2”
Threaded (Female) Rubbers EN 549

EGF-H 1015 - 1020 - 1025 EGF-H 1032 - 1040 - 1050

EGF-H SERIES CAPACITY GRAPH


200
EGF-H 1015
100 EGF-H 1020
EGF-H 1025
50 EGF-H 1032
EGF-H 1040
EGF-H 1050

10
P (mbar)

Convertion Constant
5 Methane : 1,28
LPG : 1,61

0.1
*> 10 50 100 200 300 500 1000
Q (m3/hAir)

71
EGF-H
SERIES

CONFIGURATIONS

INLINE INLINE

EGF-H 1015 - 1020 - 1025 EGF-H 1032 - 1040 - 1050

DIMENSIONS

MODEL DN A B C D E

EGF-H 1015 15 1/2” 120 61,5 108,5 120

EGF-H 1020 20 3/4” 120 61,5 108,5 120

EGF-H 1025 25 1” 120 61,5 108,5 120

MODEL DN A B C D E

EGF-H 1032 32 1 1/4” 160 53,5 91 140

EGF-H 1040 40 1 1/2” 160 53,5 91 140


EGF-H 1050 50 2” 160 68,5 114 140

72
MECHANICAL
ACTUATED
SEISMIC VALVE SERIES
w w w. e s k a v a l v e . c o m

E M V
SERIES
E M V
SERIES

MECHANICAL ACTUATED SEISMIC VALVE


EMV Series Earthquake Valve is a shut off valve which is activated during seismic oscillation. Activation and non-acti-
vation waves are defined in TS 12884 Turkish Standard. This Turkish standard is created based on ANSI Z11 standard in
United States. Once mechanical actuation system sense the seismic oscilation, valve will shut the gas off and you should
rearm manually in order to reactivated gas flow. This valve basicaly is a manual reset, normally open gas valve. Main aim
to decrease the risk of fire related to gas leakage, in case of earthquake occurs. In countries that this safety system is
avaliable, main regulation is done by fire safety department.

TECHNICAL INFORMATION
• Usage : City gas networks and gas • Maximum Working
pipelines in industrial areas Pressure : 0,5 bar
• Ambient
• Medium : Non‐corrosive gases such as
Temperature Range : ‐23°C up to 51,5°C
Natural Gas (Methane), LPG,
• Reset : Manually
Town Gas, Air, etc…
• Material Standard : Aluminum-EN 1706 /
• Montage Position : Vertical
Brass-EN12164 and
• Position : Normally Open
EN12165 / Rubber-EN549
• Connection or Port Size: 1”, 11/4”, 11/2”, 2” Threaded
(Female) DN65, DN80, DN100
Flanged

EMV 1025
EMV 1032 - 1040 - 1050

EMV 1065 - 1080 - 1100


75
E M V
SERIES

CONFIGURATION INLINE
INLINE

EMV 1025 EMV 1032 - 1040 - 1050

INLINE INLINE

EMV 1065 - 1080 - 1100

EMV SERIES CAPACITY GRAPH

100

DN 25-EMV 1025
10 DN 32-EMV 1032
DN 32-EMV 1032M
P (mbar)

5 DN 40-EMV 1040M
DN 40-EMV 1040
DN 50-EMV 1050
DN 65-EMV 1065
1
DN 80-EMV 1080
DN 100-EMV 1100
0.3
0.2

0.1
1 5 10 50 100 1000 10000

Q m3/hAir (Methane)

76
E M V
SERIES

DIMENSIONS

MODEL DN A B C D E F G

EMV 1025 25 1” 141 110 21,5 140 AA 43 82

MODEL DN A B C D E F G

EMV 1032 32 1 1/4” 141 110 30 160 AA 60 133

EMV 1040 40 1 1/2” 158 144 30 165 AA 60 133

EMV 1050 50 2” 158 144 35 172 AA 70 133

77
E M V
SERIES

DIMENSIONS

MODEL DN A B C D E K Number of holes

EMV 1065 65 70 290 316 185 216 145 4

EMV 1080 80 85 310 324 203 216 160 8

EMV 1100 100 100 350 325 211 254 180 8

78
MANUAL RESET
VALVE SERIES
w w w. e s k a v a l v e . c o m

E G V
SERIES
E G V
SERIES

INTRODUCTORY
These are the manually adjusted gas valves used with the safety purposes in the gas lines to automatically stop the gas
flow by the effect of the signals given by the third party equipments such as gas alarm detectors, ventilation equipments
etc.

EGV 1015 - 1020 - 1025

EGV 1032 - 1040 - 1050

EGV 1065 - 1080 - 1100


81
E G V
SERIES

TECHNICAL INFORMATION

• Usage : City gas networks and gas • Ambient


pipelines in industrial areas Temperature Range : ‐20°C up to 60°C
• Medium : Natural Gas (Methane), LPG, • Protection Class : IP54
Town Gas, Air, etc… • Voltage Tolerance : ± %10
• Position : Normally Open • Response Time : Less than 1 second
• Connection or • Reset : Manually
Port Size : 1/2”, 3/4, 1”, 11/4”, 11/2”, 2” • Material Standard : Aluminum-EN 1706 /
Threaded (Female), DN65, DN80 Rubber-EN 549
DN100 Flanged
• Maximum Working
Pressure : 0,5 bar
• Working Voltage Range : 12V, 220V AC or DC (On request
other voltages)

PRESSURE DROP GRAPH

EGV 1100
EGV 1080
100
EGV 1065
50 EGV 1015
EGV 1020
EGV 1032
EGV 1025
10 EGV 1040
P (mbar)

5 EGV 1050

Convertion Constant
1
Methane : 1,28
LPG : 1,61

0,1
*= 10 50 100 200 300 500 1000

Q (m3/hAir)

82
E G V
SERIES

DIMENSIONS

MODEL DN A B C D E F

EGV 1015 15 1/2” 85,5 102 21,5 55 AA 43

EGV 1020 20 3/4” 85,5 102 21,5 55 AA 43

EGV 1025 25 1” 85,5 102 21,5 55 AA 43

MODEL DN A B C D E F

EGV 1032 32 1 1/4” 110 112 30 72 AA 60

EGV 1040 40 1 1/2” 144 125 30 133 AA 60

EGV 1050 50 2” 144 123 35 133 AA 70

83
E G V
SERIES

DIMENSIONS

MODEL DN A B C D E K Number of holes

EGV 1065 65 70 290 312 185 216 145 4

EGV 1080 80 85 310 320 203 216 160 8

EGV 1100 100 100 352 317 211 254 180 8

84
w w w. e s k a v a l v e . c o m

E A C
SERIES
E A C
SERIES

INTRODUCTORY AND TECHNICAL INFORMATION


EAC model gas alarm device is an A type device, which complies with the EN 50194-1 standard, designed to be used at
homes, offices and similar places to detect the explosive gases (natural gas and LPG). It is an electrical alarm device
constantly working, set on a stable place and which creates an output signal that activates the stopper and/or auxiliary device
with a visual and audial warning. It works with 230V AC 50/60 Hz network voltage. It makes the devices like horn, siren, gas
stopping valve in case of an alarm thanks to its output contact.

The limit of the concentration level of the gases in the environment at which explosion or sparkling is called Lower Explo-
sion Limit (LEL).the LEL level of the natural gas is 5% and the LEL of the LPG is 2%; the gas alarm device starts audial and
lightened (visual) warning before the gas leak reaches one-fifth of this value. Visual and audible alarm is received between
the 3% LEL volume rate and 20% LEL volume rate of the gas.
The alarm adjustment level of the device for natural gas is %0,5 (five in a thousand) or 5.000 ppm (five thousand in a million) (5%).

The alarm adjustment level of the device for LPG is % 0,2 (two in a thousand) or 2.000 ppm (two thousand in a million) (5%).
The device can’t detect the gases with hazardous effects such as carbon monoxide.
The visual and audible alarms of the gas detection device works within 30 seconds at most after the device is exposed to the
gas volume it needs to detect..
The operation and feeding voltage of the product is 230VAC. The product can perform all its functions with 10% of the operation
voltage.

The device must be kept away from the rain and water.

• Usage : Home, Office etc. • Response Time : 30 seconds


• Detects Gases : Methane (natural gas), LPG • Sound Intensity : 85Db
(liquefied petroleum gas) • Body Material : ABS
• Device Type : Type A (visual alarm, audible • Ambient
alarm and output signal) Temperature Range : ‐10°C up to 50°C
• Operating Voltage : 230V AC 50‐60 Hz ; ± %10 • Operating Humidity : 10% – 90%
• Power Consumption : 3VA • Visual Warning : Green-System Enabled Error
• Protection Class : IPX2D Yellow, Red-Alarm
• According to
• Output Signal
Directives : 2006/95/EC, 89/336/EC
(relay contact) : 230V AC / 7A (normally open)
• According to
• Sensor Type : Semiconductor
Standards : EN 50194‐1, EN 50270,
• Calibration Time : 1 minute EN 60335‐1

DIMENSIONS

86
CABINET
S O L U T I O N S
S 3 0 0
CABINET

S300 Wall Type Cabinets


Usage : Gas networks, industrial and domestic users
Dimensions : 210 x 535 x 1122
Flow Range: up to 500 m3/h
Regulator : ERG-H5 ( link)
Inlet Pressure Range: up to 6 bar
Outlet pressure Range: 15 mbar to 2,5 bar
Inlet Connection: CAL25 (suitable for PE connection)
Outlet Connection: 2"
Security Options: OPS0-UPSO
Set Includes : B12 filter , gas pressure regulator,
inlet and outlet manometer,
S300 NonFlammable composite cabinet,
cal 25 valve, inlet and outlet relief valves, 2"outlet pipe

DIMENSIONS
210

3
2 4
T SE

1 5
528

0 6
bar

300
200 400
T SE

100 500

0 600
mbar
1122
574

535

LEGEND
4 7 8 9 10

S300 CABINET SET


No Name Description Pcs
2
3
4
1 Inlet Valve PN5, CAL25 1
T SE

3
1

0 6
5
2 S300 Cabinet Standard 1
bar

3 B12 Extension Nipple Brass 1


300
4 B12 Cartridge Filter Aluminum Alloy , Thread, PN6 90 degree 1
200 400

5 Inlet Manometer 1/4” Threaded, 63 Diameter, 0-6 bar, KL 2,5 1


T SE

100 500

12
0 600

6 Inlet Ball Valve 1/4”, Threaded, with Blind Tap , EN331 1


mbar

2 7 Regulator Inlet Fitting Brass 1


1 5 6 11
8 Gas Pressure Regulator ERG-H5 , 1” x 1 ½” Threaded, Q: 200m3/h, Pd: 300 mbar with Security Shut-Off 1
9 Regulator Outlet Fitting Carbon Steel 1
10 Outlet Pipe 2”, Zinc Coated 1
11 Outlet Manometer 1/4”, Threaded, 63 Diameter, 0-600 mbar, KL 1,6 1
12 Outlet Ball Valve 1/4”, Threaded, with Blind Tap, EN331 1

88
S2300
CABINET

S2300 Wall Type Cabinets


Usage : Gas networks, industrial and domestic users Inlet Connection: CAL15 or CAL25
Dimensions : 380 x 215 x 500 (suitable for PE connection)
Flow Range: 2,5-250 m3/h Outlet Connection: Suitable NG plexsy for meter
Regulator : ERG-S, ERG-SE, ERG-SR, ERG-H1 ( link) Security Options: OPS0-UPSO
Inlet Pressure Range: 0,5-6 bar (for 21mbar outlet Set Includes : gas pressure regulator,
pressure ), 1,5-6 bar (for 500mbar outlet pressure) S2300 NonFlammable composite cabinet,
Outlet pressure Range: 18 mbar to 4 bar CAL15/CAL 25 valve

DIMENSIONS
500

500

30 30
360 185 360 185

89
CES200
CABINET

CES200 Underground Type Cabinets


Usage : Gas networks, industrial and domestic users Outlet Pressure Range : 21-500 mbar
Dimensions : 330 x 520 x 249 Inlet Connection : CAL15 (suitable for PE connection)
Flow Range : 2,5-60 m3/h Outlet Connection : 11/4"
Regulator : ERG-S, ERG-SE Security Options : OPS0-UPSO
inlet pressure range: 0,5-4 bar (for 21mbar outlet pressure ), Set includes : gas pressure regulator,
1,5-6 bar (for 500mbar outlet pressure) CES200 Non Flammable composite cabinet,
CAL15 valve

DIMENSIONS
100

100
30

30

CES 203 3cm Lifting Platform CES 210 10cm Lifting Platform CES 203 3cm Lifting Platform CES 210 10cm Lifting Platform
50

50

CES 205 5cm Lifting Platform CES 205 5cm Lifting Platform
GAZ

GAZ
520

520

249 330 249 330

90
S 7 0 0
CABINET

S700 Wall Type Cabinets


Usage : Gas networks, industrial and domestic users Inlet Connection : CAL15 or CAL25
Dimensions : 305 x 155-230 x 660 (suitable for PE connection)
Flow Range : 2,5-250 m3/h Outlet Connection : 11/4" or 2"
Regulator : ERG-S, ERG-SE, ERG-SR, ERG-H1 Security Options : OPS0-UPSO
Inlet Pressure Range : 0,5-4 bar (for 21mbar outlet pressure), Set includes : Gas pressure regulator,
1,5-6 bar (for 300mbar outlet pressure) S700 NonFlammable composite cabinet,
Outlet Pressure Range : 21 mbar, to 4 bar CAL15/cal 25 valve)

DIMENSIONS

230 230 230 230


210 210 210 210
660

660

660

660

305 155 305 155 305 155 305 155

91
S2200
CABINET

S2200 Underground Type Cabinets


Usage : Gas networks, industrial and domestic users Outlet Pressure Range : 21-500 mbar
Dimensions : 244 x 330 x 173 Inlet Connection : CAL15 (suitable for PE connection)
Flow Range : 2,5-60 m3/h Outlet Connection : 11/4"
Regulator : ERG-S, ERG-SE Security Options : OPS0-UPSO
ınlet pressure range: 0,5-4 bar (for 21mbar outlet pressure), Set Includes : gas pressure regulator,
1,5-6 bar (for 300mbar outlet pressure) S2200 NonFlammable composite cabinet, CAL15 valve

DIMENSIONS
380

380

244 173 244 173

92
ESKA VALVE A.Ş.
Sakarya 1. Organize Sanayi Böl. T. +90 (264) 502 54 34-35 [email protected]
11. Cad. No: 6-8 Arifiye / Sakarya F. +90 (264) 502 54 84 www.eskavalve.com