FKDQ8007 User Manual
FKDQ8007 User Manual
Http://www.gzdongsu.cn
E-mail:[email protected] [email protected]
Sales Tel:+86-20-84738727 84737193
Technology Consultation Tel:+86-20-84731961-206
After-Sale Service Tel:+86-20-34876392
Fax:+86-20-34735730
SAFETY INSTRUCTION
OF CONTROL SYSTEM FOR SURFACE MOUNTED BOP STACK
1
5
Operation Instructions
Read it before using the unit Read it before using the unit
1. Types and Functions and Options for Control System for Surface
Mounted BOP Stacks
1.1 T ypes
FK
equipment, which is used to control BOP, 800 L in nominal total volume of accumulators, 7 objects able to be controlled.
hydraulic chock and kill system, and 1.2 C omponents and Functions of Surface Mounted BOP Control System
A BOP control system for well drilling is generally composed of:
indispensable equipment for blowout
(a)Remote control panel
prevention during drilling or well servicing (b)Driller's panel
(c)Control cable for remote control
in petroleum and natural gas industry. Refer
(d)High pressure hose
to the relevant provisions in the Operation
1.2.1 R emote Control Panel (see Fig.1)
Instruction in order to select a suitable type of
The hydraulic control system of a remote control panel is composed of the following items: heavy skid, oil reservior,
control system correctly, and install, connect, accumulator group, electric pump (electric triplex pump), pneumatic pump, pressure controller, pressure transmitter, relief valve,
and pressure regulator, solenoid (electromagnetic) valve, proximity switch, charger, battery, multiple adapter as well as change
maintain it properly. valve, etc. The electric triplex pump group charges the accumulators with hydraulic oil so that required hydraulic pressure is stored.
When the preset value is reached, the pump group stops automatically. When the blowout preventer is to be opened or closed, the
operator may remotely control the change valve to have the hydraulic oil fed into the hydraulic chamber of thus to open or close BOP.
When the hydraulic pressure in the remote control panel lowers to a preset value, the pump group will automatically activate and
maintain the required hydraulic pressure in the accumulators so that the blowout preventer may be closed in case of an emergency.
The remote control panel is equipped with a container made of sheet steel for protection. The user may choose from different houses
available basing on the environment where BOP is used to ensure the effective function of the remote control panel.
The control cable for remote control is composed of a 54 cores multiple armored cable with 54 pins multiple explosion proof
adapters at both ends , which are used to connected he driller's panel to the remote control panel. The functions of control cable are:
to transmit electrical signals of hydraulic pressure of the remote control panel to the driller's panel so that hydraulic pressure can be
read on the driller's panel; to transmit the control signal to adjust ( increase or decrease) the annular pressure; to transmit the control
panel to control the solenoid valves and actuate the air cylinders, and finally control the BOP and hydraulic valves; to transmit the
proximity switch signals so that the BOP conditions (open or close) are indicated on the driller's panel; to display the alarm signals
on the driller's panel.
01 02
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
03 04
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
The main function of the high pressure hose is to deliver hydraulic oil from the remote control panel to the hydraulic chambers
of BOP to open or close the blowout preventer and choke or kill valves, and to deliver oil from the pressure relief chambers of BOP
Buzzer or choke and kill valves hydraulic chambers back to the oil reservior on the remote control panel. It has the performance of easy
installation and convenient transportation.
Type of Type of Effective Useful Electric Total Total air Motor Type of Size Way of
(m 3/min)
Figure shower
FKDQ YCDQ 423 105 3 2 3 1 SZD1-1-7
5900 2150 At both
2300
800-7 800-7 sides
Note: Usable liquid volume of a accumulator bank is the volume of liquid discharged from the accumulator bank when pressure of
nitrogen charge is 7MPa(1000 PSI) and accumulator pressure reduces from 21MPa(3000 PSI) to 8.4MPa(1200 PSI).
05 06
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
07 08
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
2.2.1.3 Fill Oil in the Oil Atomizers on the Remote Control Panel
Hydraulic hoses connection should be started from BOP stacks. Screw out the oil-filling plug of the atomizer. Pour in lubricator of the same type as the electric pump. Then reinstall and
On the back of the remote control panel, conspicuous marks O (open) and C (close) is made at each hydraulic liquid outlet. tighten the oil-filling plug.
When hydraulic hoses are connected, marks Annular , Pipe Ram , etc. on the nameplate of the valves as well as the marks
2.2.1.4 Check Nitrogen Pressure in Accumulators
O and C for pipe outlets should be followed to avoid accidents.
Remove the upper guard cap of the accumulator. Mount the inflator a tool supplied with the control system (the hand wheel of the
charger valve must be turned anti-clockwise to the stop)-- in the position of the upper guard cap. After tightening the inflator, turn the
2.1.3 Connection of Back-Up Hydraulic Pressure Source
hand wheel of charger valve clockwise to open the inflation check valve on the top of the accumulator bladder so that nitrogen pressure
As specified in industrial standard related, the remote control panel shall be equipped with an inlet for back-up hydraulic in the bladder is sensed and displayed by the pressure gauge of the inflator. Nitrogen pressure in the bladder should normally be 6.3~7.7
pressure source. When required conditions are present and the user requires, this inlet should be connected for use in case that the Mpa (900~1100 PSI)(the higher nitrogen pressure, the larger liquid volume available from the accumulator).
remote control panel fails to supply sufficient hydraulic pressure while BOP stacks has to be closed urgently. The inlet for back-up Detailed information about the accumulator, please read the special OPERATION INSTRUCTION FOR THE ACCUMULATOR.
pressure source is located on the back of oil reservoir , with a conspicuous mark of BACKUP PRESSURE SOURCE INLET .
2.2.1.5 Check Direction of Motor Rotation
2.1.4 Control cable Connection for Remote Control The motor shall rotate in the direction indicated by the arrow mark on the chain guard, otherwise effect of splash lubrication in
The control cable with explosion proof adapters at both ends is used to transmit control and pressure signals. The control cable the crankcase is compromised, and thus the bearing bush of connecting rod will be burnt.
should be laid straight and smooth and enters the remote control panel through the dedicated hole so as not to hamper the action of
the house door. Twisting of control cable should be avoided. The multiple adapters at both ends have the same pins so it can be 2.2.1.6 Air Venting From the Pipe of Remote Control Panel
connected freely.
Air in the pipe affects normal operation of pump group. Before the accumulators are pressurized, air in oil suction pipe and the
pump must be completely vented. Air venting should be carried out as follows:
2.1.5 Electric Power Connection and Compressed air Connection 1.Open the ball valve in the oil suction pipe of the electric pump (No. 37). Open the ball valve (No.2) in the oil suction pipe of
The remote control panel requires power of 690VAC /60Hz three phase and 220VAC single phase for its operation. For the pneumatic pump;
690V/60Hz power, three-core cable of 10mm 2 or larger should be used. The cable should be connected to the explosion-proof circuit 2.Turn the 2-position 4-way valve (No.20) to "Open" position;
breaker on the inner wall face of the house. After checking of rotation direction of the motor, the cover of terminal box and the cable 3.Open the stop valve (No.22);
sleeve should be tightened so as to ensure explosion proof. For 220V power, 2-core cable of 2.5mm 2 or larger should be used and 4.Check that the stop valve (No.40) between the accumulators and the pipe are open;
connected in the same way. Earthed conductors shall not be smaller than 6mm 2. 5.Open the stop valve (No.3) of air source so as to start the pneumatic pump first;
The remote control panel needs compressed dry air for its operation. Compressed air hose should be lead in through the dedicated 6.Start the electric pump by turning main switch of magnetic starter (No.30) to "Automatic" position and run the pump in no-
hose of the house. ID 25mm air source pipe for remote control panel is required. After the hose is slid over the nipple, it should be
load condition for 3 minutes.
tightened with pipe band.
The normal operation pressure shall not be less than 0.53MPa(75 PSI).
2.2.2 Items of Trial Running
2.2 Trial Running (Fig.2) Trial running shall be carried out only after the relevant hydraulic hose and pneumatic control pipe are correctly connected and
the preparation work is finished.
2.2.1 Preparation for Trial Running (May Be Performed in Logistic Site)
2.2.1.1 Fill Hydraulic Oil in the Oil Tank 2.2.2.1 Charging Time of Accumulator Group
Hydraulic oil in the oil tank shall be clean. Depending on the ambient temperature, the following types of hydraulic oil should After the pipe venting as mentioned in 2.2.1.6, close air source stop valve (3) and stop the pneumatic pump (No.28), and close
be used: the release stop valve (No.22) so that the electric pump charges pressure to the accumulators. For charging the accumulators to
21MPa, an inflation time with an error of 7% from the value recorded in ex-work test report is still normal (because of the
tolerance in nitrogen pressure charged).
Hydraulic oil of different brands or different types of the same brand shall not be mixed.
2.2.2.2 Automatic Pump Control Test
2.2.1.2 Fill lubricatin in the Electric Pump and the Chain Box With master switch of the magnetic starter (No.30) turned to "Automatic" position, the electric pump should start
automatically when the accumulator pressure lowers to 18.9MPa, and should stop automatically when the accumulator pressure
Adequate lubricant is filled into the crankcase of the electric pump and the chain box for safe operation. However, it is
reaches 20.3~21MPa. Slowly open the stop valve (No.22), to lower the accumulator pressure to 18.9MPa. The electric pump should
necessary to change the lubricant according to the ambient environment. For ambient temperatures above 0 , 32HL hydraulic
automatically start.
oil may be recommended. For ambient temperatures below 0 , 32HV low temperature anti-wear hydraulic oil may be used.
However, higher quality hydraulic oil can be used.
The oil filling port is located in the end of the pump's crankcase. To fill oil in, just pull out the filling port cover (serving also as
vent cover) and fill in oil until the oil level reaches the mark on the dipstick (attached to the filling port cover). The chain box filling
port is on the top of the chain box. The inner hexagon plug can be screwed out with the attached tool delivered with the complete unit.
09 10
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
2.2.2.3 Automatic Control Test of Pneumatic Pump 2.3.1 To Control from The Driller's Control Panel
When the accumulator pressure rises to 20.3~21MPa, hydropneumatic switch (No.8) should close automatically, the From the Fig. 2, you can see that to operate the buttons on the driller's panel can energize or de-energize the solenoid air
pneumatic pump should stop. When the accumulator pressure lowers to 18 Mpa (2556 PSI), the hydropneumatic switch should open valves, and then proceed to actuate the air cylinder; finally, the rotary valves are operated. This operation must be done with both
automatically and the pneumatic pump should stop automatically. It has been so adjusted in the factory. If readjustment is required,
hands (this is to avoid unintended activation). Push and hold the red button marked “PUSH & AND HOLD TO OPERATE” with
use the adjusting rod ( attached tool ) to adjust the round nut on the hydropneumatic switch. When the nut is turned in the direction for
your left hand, and then push function buttons to control the BOP or hydraulic valves with your right hand.
further compressing the spring, the closing pressure rises, and vice versa. After pressure adjusting, the hold-down nut should be
Note that to adjust the annular pressure is not needed two hand operation.
tightened. The pressure to open the hydropneumatic switch depends on the characteristics of the spring in the hydropneumatic
To test BOP for its behavior, all items to be controlled shall be tested one by one to see if they are the real items
switch and is un-adjustable.
corresponding to the aims of control, their motions are as required and the hydraulic piping is not leakage. In case of
inconformity, remove the hydraulic pressure in the system, find out the cause of trouble then retest.
2.2.2.4 Adjustment of Manifold Pressure (See attached Fig.3) To protect the stripper of the annular BOP, hydraulic pressure in the control oil loop for the annular BOP may be lowered a
little or run in a drill pipe of larger diameter may be used.
The manifold pressure (the hydraulic piping for controlling ram BOP and hydraulic valve) is adjusted through a 2-position 4-
After all items to be controlled are identified as aimed, two tests of opening and closing motions should be made so as to
way valve (No.20). When this valve is open, pressure is charged from the accumulators to the manifold. When this valve is closed,
vent all air in the hydraulic control cylinder and hydraulic piping.
the outlet of the regulator (No.15) is connected with the manifold. In normal operation, the 2-position 4-way rotary valve is in closed
During tests, " delay time of control " should be taken (with 3 people working cooperatively). To do this, operate the change valve
position and the manifold pressure is set by the relief valve . When turn the handwheel of the regulator clockwise and watch the
manifold pressure gauge, you can see the manifold pressure rising and the output pressure increase from the regulator is stepwise. on the driller's control panel. When the 3-position 4-way valve is in position, record the time for the 3-position 4-way valve on
So when the manifold pressure rises to about 10.5MPa(1500 PSI), it is necessary to open the relief valve (No.22) a little then close it the remote control panel to finish direction. This time should not be longer than 0.5 second.
immediately so that the outlet pressure of the relief valve slightly lowers then increases again. The re-increased pressure is the real
outlet pressure of the relief valve. Should the pressure be too high, the hand wheel has to be turned anti-clockwise. Usually after one
or two adjusting operations, the suitable output pressure of the valve can be made. After adjustment, engage the locking handle. 2.3.2 Seal Test under Nominal Pressure
Turn the 2-position 4-way valve (No.20) on the remote control panel to "Open" position so that manifold pressure rises to
2.2.2.5 Adjustment of Annular Pressure Manifold nominal value. Make seal test on each item controlled. In case that accumulator pressure is not high enough but does not lower to the
value at which the electric pump starts charging, open the bypass valve (No.3a) of compressed air source for the pneumatic pump for
The manifold pressure of the annular BOP is set by the manual-pneumatic regulator (No.21). In the normal situation,
pressurizing. If any seal test is not successful on any item controlled, the cause should be identified and removed or the item should
pneumatic control function should be used. As the back-up, manual pressure adjustment may be used when pneumatic control
be replaced in time. After test, turn the 2-position 4-way valve to "Close" position, close the bypass valve so that the remote control
completely fails. Adjusting of output pressure of the manual regulator is performed separately on the remote control panel and the
panel is again in normal working condition.
driller's control panel:
a.To carry out adjustment on remote control panel: Set the 3-way air tap (No.19) in position of "Remote Control Panel" by
2.4 Confirmation of Normal Working of the Remote Control Panel
referencing to the arrow marked on it. Turn he hand wheel of the air pressure regulator (No.18, Fig.1) to adjust the outlet pressure of
the relief valve to 10.5MPa(1500 PSI). Lock the hand wheel by tightening the locknut on it. After tests of BOP behavior and seal under nominal pressure, lower the accumulator pressure to 21MPa(3000 PSI). When the
b. To carry out adjustment on driller's control panel: Set the 3-way air tap (No.19) in position of " Driller's control panel' by pump group stops working, unscrew the screw plugs on either sides of the oil tank. Under illumination, check all visible oil return
referencing to the arrow mark on it. Push the red " INC. Button " on the driller's control panel to increase the annular pressure, and ports in the oil tank. There should be no dripping leakage from the oil return ports (except the remaining oil drips in the oil returning
push the green " "DEC. Button " to decrease the annular pressure. Watch the intelligent meter of " Annular Pressure " and adjust the chamber of the hydraulic valves).
outlet pressure of the regulator to the same reading of 10.5MPa (1500PSI). Please note that push (click) the button and remove hand
immediately to prevent the pressure from too fast increase or decrease. 2.5 Normal Lowering of Accumulator Pressure on Remote Control Panel
After accumulator pressure reaches 21MPa (3000 PSI), gradually lowering of this pressure is a normal phenomenon if no
leakage occurs. The rate of pressure lowering is related to the charging rate of the pump group. The higher charging rate, the more
heat is generated in the nitrogen inflated in the accumulators due to compression. When the accumulators are pressurized to 21MPa,
2.2.2.6 Oil Drips Adjustment of The Oil Atomizers
(3000 PSI) the pump group stops, and the temperature of nitrogen in the accumulators will gradually lower, volume of the nitrogen
When the pneumatic pump is in operation, oil drips supplied by the oil atomizer (No.5) as visible from its upper part should be will gradually become smaller. So the accumulator pressure will lower gradually.
checked. Number of drips per minute should be 5~8. In case of the contrary, this per-minute number of drips should be adjusted by
the small needle valve on the upper part of the oil atomizer so that sufficient oil mist is supplied to the pneumatic cylinder of the 2.6 Indication Error Between Pressure Gauge and Intelligent Digital Meter
pneumatic pump and the directional mechanism for lubrication.
The deviation between ccumulator Pressure Manifold Pressure , Annular Pressure and Air Source Pressure
on the remote control panel and hydraulic contact gauges of direct liquid contact type is generally not greater than 1.5%. What the
corresponding pressure gauges on the driller's control panel indicate are pressure signals output from the pressure transmitter.
2.3 Test of BOP Control Hence an indication error of 1 is possible. In total, an accumulated error not greater than 3% resulted from the two should be
acceptable.
Before testing the closing behavior of BOP, to avoid trouble, check that no foreign matters that can hamper the closing of BOP
are present.
11 12
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
2.7 Usual Failures and Recovery During Trial Running and Test of BOP Control System 2.8 Daily Checking and Maintenance
2.7.2 During test of opening and closing 1.Dirt sticks on the exposed part of the piston 1.Check and remove the dirt.
the 3-position 4-way valve by operating rod. 2.Stop operation, turn the valve handle by hand Once a week 1.Lower the accumulator pressure on remote control panel to zero. Check if the electric pump and the
the solenoid valves on the driller's 2.The driving cylinder of the 3-position 4-way and move the piston to and fro for two times. pneumatic pump work normally.
valve has been in stillness for a long time, so 2.Check if the charging process of the accumulator group is OK.
the sealing elements give a high resistance. 3.Reduce the pressure of the manual pressure regulator and the pneumatic pressure regulator to zero, and
then readjust them to give suitable pressure.
2.7.3 a.Charging time of accumulators a.A suction valve of an accumulator group does a.Check for un-opened valve and open it.
is too short. not open. b.Discharge the hydraulic oil then inflates
b.Charging time of accumulator is too b.Nitrogen pressure is too low. accumulators with nitrogen.
long.
Once a month 1.Close the compressed air source; clean the air filter and the oil atomizer. Add lubricat in the oil
atomizer and adjust for proper dripping rate.
2.Lower the accumulator pressure to zero, check for nitrogen pressure of the accumulators. Add nitrogen
or replace rubber bladder (if damaged) as necessary.
3.Clean the screen of the high pressure filter (No.11).
2.7.4 During being released, high Some rubber bladders in accumulators Close the stop valve of the accumulator and
connect the release stop valve to the oil 4.Clean the screens of the inlet low pressure filters of the electric pump and pneumatic pump.
pressure drops quickly and low pressure are broken so nitrogen is mixed with
reservoir with the attached hose and then open 5.Check the lubricating oil level in the crankcase of the electric pump, replenish with lubricating if
falls slowly with large volume of gas the hydraulic oil.
the release stop valve to release the pressure of necessary. Replenish the chain box with lubricating .
entering oil tank and oil becoming milky the accumulator. Discharge the oil in the.
6.Pressurize the system after the procedure described in 2.2.1.6 "Air venting from the pipe of remote
white.
Check and replace the broken bladder(s) . control panel"and reset the remote control panel to normal working condition.
2.7.5 In the field, when the control 1.Leakage on the hydraulic hose connected to 1.Check along the hydraulic pipe and find out Once a year 1.Drain out all hydraulic oil from the tank. Clean the tank, the filter and replace hydraulic oil.
s y s t e m i s c o n n e c t e d t o a B O P, BOP. the leakage. Depressurize the pipe and 2.Drain out all lubricats from the crankcase of the electric pump. Clean the crankcase. Replace lubricator.
accumulator pressure lowers 2.A stop valve of the accumulator is not closed remove the leakage. 3.Follow the procedure of air venting from the piping of remote control panel (2.2.1.6) to vent the air in
continuously. completely. 2.Close the stop valve one by one the piing. Then inflate the accumulators. Turn the electric main switch to "Manual" position and test the
3.Outward or inward leakage of hydraulic (No.22a~22b). relief valve for its behavior of opening and closing. If the condition of overflowing is OK, turn the
chamber of BOP (hydraulic oil flows to the 3.Adjust the accumulator pressure and the electric main switch to "Automatic" position and reset the remote control panel to normal working
relieving chamber through the cylinder outlet pressure of the regulator to the condition.
p i s t o n a t t h e p i s t o n ) . highest normal pressure.Set the 3-position
4-way Valve in open or close
position.Remove the screw plugs on both sides of the oil tank and check the oil return ports of the valves. If so, check the corresponding valve
(see chapter 3 of these operation Instruction). If oil flows out from the return port for the 3-position 4-way valve, it is necessary to find out 2.9 To Use Back-Up Pressure Source
whether the leakage is from the inside of the hydraulic chamber of BOP. The method is to isolate the oil return pipe of the leakage rotary valve
from the remote control panel. After isolation, if the oil flow from the return port for the valve in the tank becomes smaller, leakage from BOP When power failure, failure of compressed air supply or zero accumulator pressure occurs and BOPs have to be closed
is meant. If the valve is considered leakage, it should be disassembled for check. Replace seals if damaged. If a component is damaged but can
not be repaired in the field, replace the whole valve.
emergently, back-up power source shall be used.
Such back-up power air source may be a pressurized accumulator group or a group of cylinders filled with high pressure
nitrogen. Before the stop valve (No.40Y) for the back pressure source is opened, the stop valve (No.40) for the accumulator group
on the remote control panel must be closed first lest the accumulators absorb the backup pressure energy.
13 14
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
3.1.2 The pump group inflates the accumulators and store energy in them
Turn the main switch of the magnetic starter to " Automatic " position, when the accumulator pressure is below 18.9MPa(2684
PSI), one of electric pumps starts. Oil is sucked in through low pressure ball valve and low pressure filter, and is fed to the
accumulators via check valve and the high pressure ball valves. The oil with the pressures higher than the nitrogen compresses the
nitrogen-inflated bladders and so the oil can be stored in the accumulators. When oil pressure rises to 21MPa(3000 PSI), the
electronic pressure controller makes the magnetic starter de-energize and the motor stop working. When accumulator pressure
lowers to 18.9MPa(2684 PSI), the pressure controller makes the magnetic starter energize and the motor starts, and charges pressure
to the accumulators. A relief valve (No.26) is installed in the output pipe of the electric pump. When the pressure controller fails, the
relief valve will open and release excessive pressure to protect the electric pump.
With the remote control panel in normal working condition, the pump group is in oil pressure charging condition or stand-by
condition to maintain required hydraulic pressure on the remote control panel.
15 16
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
After flowing through stop valves (No.40a~No.40d), stop valve (No.40) and high-pressure filter (No.11), pressurized
hydraulic oil from the accumulators is distributed in 3 passages:
Oil in the first passage: after pressure reducing (normal value is 10.5 MPa)(15000 PSI) by manual regulator (No.15), enters the
manifold via the 2-position 4-way valve (No.20), then is distributed to the 3-position 4-way valves (No.10b~10g) for controlling
ram BOP and hydraulic valves.
Oil in the second passage: flows to the 2-position 4-way valve (No.20), and if necessary, is fed to the manifold after diverted by
the valve.
Oil in the third passage: flows to manual-pneumatic regulator (No.21), then to 3-position 4-way valve (No.40a) for controlling
the annular BOP after reducing pressure by the same valve.
17 18
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
3.2.1.1 20pcs 11gal accumulator is used for FKDQ800-7 BOP control system. Its type and 26.Valve cap
technical specifications is as follows: 24.Gasket
As may be seen from the construction drawing, the accumulator is composed of rubber bladder, body, charge valve, suction
valve, etc. The rubber bladder is charged with nitrogen through the upper charge valve. Thus the rubber bladder is expanded, presses
against the body. Finally the bladder is elongated and the suction valve is pressed down thus the bladder is protected and prevented
from expanding out of the body. Hydraulic oil of higher pressure than that of the nitrogen enters the accumulator from the bottom of
the accumulator and pushes the suction valve open. Oil pressure inside the body increases with the quantity of oil charged in the
accumulator. So the bladder is compressed and becomes smaller. The more oil is charged in the accumulator, the higher pressure in
the accumulator and smaller nitrogen volume will be, until the upper pressure limit is reached. In this way, energy is stored in the
accumulator. When the hydraulic oil is discharged via the oil discharging port in the bottom, pressure in the accumulator lowers
accordingly, and the nitrogen expands and forces out more oil from the accumulator. When the pressure lowers to the pre-charged
nitrogen pressure, all hydraulic oil charged in will be discharged.
Details on accumulator please read the special Operation Manual for Bladder Accumulator.
16.Valve
15.Spring 12.Supporting ring
2.Gasket
19 20
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
YB-160L-4
3.2.2.4 Features
Because elastic material like rubber and graphite PTFE packing is used on the pump for sealing, filtering fineness
requirements of the pump is low. Wear of plunger and packing can be compensated by adjusting the compression ring, so discharge
pressure and oil volume discharged will not be affected by small wear. Replacing of rubber packing is also very easy and may be
done on-site.
01
21 22
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
Type: QYB35-175L
move down and compresses the directional spring, the spring seat touches the shoulder of the tension bar and the piston forces 18
shuttle valve (21) down. Steel ball (16) is forced back. When the shuttle valve moves down to the middle between the two arc 19
grooves, compressed air is vented to the atmosphere, the shuttle valve stops moving and the shuttle valve is pushed down in-position 20
by the compressed directional spring. The steel ball is then forced by the side spring to enter the arc shape groove in the upper part of 21
1 6
the shuttle valve and the shuttle valve changes from downward movement to upwards movement. Compressed air flows through the
inner bore of shuttle valve and air pipe (19) to enter the lower chamber of the cylinder. The piston is forced upwards and passes
through the position where piston sheath (9) compresses directional spring (10). When the piston continues to go up and reaches the
limiting point, it forces the shuttle valve to go up. The steel ball retreats and fixes the shuttle valve in the upper position. To this
point, a stroke is completed. Then another stroke begins, compressed air flow reverses and the same process repeats. Such cycle
repeats continuously and the piston makes reciprocal movement continuously.
The oil pump's connecting rod attached to the lower end of the piston rod makes vertical reciprocal movement. A suction port is
equipped in the lower end of cylinder (3). Steel ball (1) is the core of the suction valve. The lower end of connecting rod serves as the
3.2.4 3-Position 4-Way Valve
body of the check valve, steel ball (4) in the inner chamber serves as the core of the check valve. When the connecting rod moves up,
the check valve is closed by steel ball (4), the suction valve opens and oil is sucked in, while the oil in the annular space between 3.2.4.1 Technical Specifications
connecting rod (7) and liquid cylinder (3 is forced out of the pump. When the connecting rod moves down, the suction valve is closed
and the check valve is opened. Oil in the liquid cylinder is forced out of the pump via the check valve and the annular space in the Type: 34ZS21- 25
upper part of the liquid cylinder. Quantity of oil discharged is equal to 50% of the oil sucked in, and the rest of the oil stored in the W orking pressure: 21M Pa
annular space will be discharged during the next upward movement. That is, the oil sucked in is discharged in two halves.
Flow rat e: 280L/m in
Because the area ratio of the pneumatic cylinder to liquid cylinder is 50:1and direct link mode is used, the pump is very good at Connect ing t hreads: NPT1 "
under-load starting. Especially, it can be started under extra-high hydraulic load (higher than 32MPa)(4550 PSI).
Operat ing m ode: M anual and pneum at ic
3.2.3.5 Role Played in the Control System
Rot at ing t orque: 25N m
This is an independent pump group on the remote control panel. It is powered by compressed air and is indispensable for the
Lengt h x w idt h x height : 300 x 136 x 230m m
control system. This pump is particularly important when it is necessary to use a pressure higher than 21MPa (3000 PSI) to control
BOPs (for example shearing ram).
3.2.4.2 Construction as Shown in Fig.6
23 24
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
(1)When the valve handle is in the middle position, as shown in Fig.6-1 (b), the 4 oil ports of the valve core are offset by 45 to
the 4 oil ports of the body. So the 4 ports i.e. P, O, A and B in the body are blocked and not through to each other. Pressure oil cannot
flow through port P. No returning oil flows out from port O. Oil can neither be sucked in nor be returned from ports A and B that are
Function Symbol linked to the both ends of the oil cylinder so the oil cylinder is blocked in the previous open or closed position. The piston inside the
oil cylinder cannot be moved by external force like vibration (except that the pipe is leakage). Therefore, such functional structure
of the valve is called "O" type.
(2)When the valve handle is in left position, as shown in Fig.6-1 (a), the two passages in the valve core link port P with B, and A
as well as port O. Pressure oil flows from port P to B via the passage in the valve core, and enters BOP-opening chamber, forcing the
piston to move down and open BOP. At the same time, pressureless oil in BOP-closing chamber is forced out by the piston and
returns to the oil reservior via a pipe, port A, the other passage of the valve core and port O.
(3) When the valve handle is in right position, as shown in Fig.6-1 (c), the passages in the valve core link port P with port A, B
and O. Pressure oil flows from port P to port A via the passage in the valve core, enters BOP-closing chamber via a pipe and forces
4 5 6 7 8 9 10 11 12 13 14
the piston to go upwards to close BOP. At the same time, the pressureless oil in BOP-opening chamber is forced out by the piston and
returns to the oil reservior via pipe, port B, the other passage of the valve core and port O.
4-Z1"
118 P P P
16 15
A B A B A B
182
Component O O O
No. Code Note
1 3.4HXF-00-01 Spindle
a b c
2 3.4HXF-00-02 Spindle sleeve
25 26
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
Weight: 20kg
20
3.2.5a.2 Construction As shown in Fig.7. 21
4
602.5(Hghest point)
take-in slide bush up to close the oil inlet of the plunger, so pressure in the inner chamber does not rise. Now the space in the oil take-
in slide bush is open to the oil inlet and is separate with the valve inner chamber. Under the pressure difference, the oil take-in slide 10 Z1/2"
bush is pressed tightly against the sealing face of the oil take-in plunger and an improvement in sealing is created. In this condition, 3
11 27
when the discharge port is open, there will be no oil flowing out. Therefore such mode is called "0" (zero) mode. Z1"
b)Pressure adjusting-stabilizing mode 28
12
In "0" mode, if the hand wheel is turned so that the rectangular springs are compressed, and the valve stem is forced downward. Z1"
When the spring load is greater than the friction between the oil take-in slide bush and oil take-in plunger as well as between the oil
relieving slide bush and the plunger, the valve plate slides down and opens the oil inlet. With oil entering, pressure in the valve inner
chamber rises, and the valve plate goes up accordingly. When the pressure in the inner chamber rises to the extent that is balanced 13
with the spring load, the valve plate moves the oil take-in slide bush up to the position where the oil inlet will be closed, and the 14
valve inner chamber pressure is also stabilized at a certain value. When the oil discharge port opens, pressure in the valve inner 15
chamber drops, the rectangular springs forces the valve plate to slide down and open the oil inlet port. Oil then flows in to replenish
16
until the hydraulic chamber of BOP is full, pressure rises again to the preset value and the oil inlet is closed by the oil take-in slide
102 17 102
bush again. Therefore this mode of working is called "pressure adjusting and stabilizing mode". The working mode of the valve
determines that pressure adjusting is by valves, with stepwise pressure rising. The step of rising depends on valve design and 132 178
manufacture.
c)Pressure reducing-relieving mode
In pressure adjusting mode, if the hand wheel is turned so that the rectangular springs are loosened to an extent that the valve No. Code Component No. Code Component
inner chamber pressure becomes greater than the spring load, the valve plate slides up until the oil discharge port is open to the valve Hand wheel
1 SDTYF-00-01 15 SDTYF-00-17 Valve plate
inner chamber. With the releasing of some oil from the valve inner chamber, the valve plate slides down until the oil relieving slide
2 SDTYF-00-02 Locking Handle 16 SDTYF-00-18 Valve body
bush just closes the oil discharge port. With the oil take-in slide bush sealing the oil inlet port, pressure in the valve inner chamber
will reduce to a value, which is equal to the spring load. When the load of the rectangular springs is adjusted to zero, the pressure in 3 SDTYF-00-10 Oil outlet flange 17 SDTYF-00-19 Lower plug
the valve inner chamber also drops to zero. This mode is called pressure reducing-relieving mode. 4 SDTYF-01-00 Spring sleeve 18 SDTYF-00-20 Screw rod
d)Mode of pressure relieving-stabilizing in the overflow Inner spring Spring cover
5 SDTYF-00-03 19 SDTYF-00-21
In pressure adjusting mode, when oil pressure at oil discharge port is higher than the preset level, if it is necessary to trip out
6 SDTYF-00-05 Outer spring GB301-64 Thrust ball bearing 8202
the drill pipe after the annular BOP is closed, the sealing pressure becomes higher when the joint of the drill pipe passes through 20
7 SDTYF-00-06 Guide ring SDTYF-00-23 Pressing seat for spring
BOP because the sealing parameter of the stripper is expanded. This high pressure reaches the valve inner chamber through the pipe 21
so the pneumatic pressure in the valve inner chamber over-balances the load of the rectangular springs; the valve plate slides up until 8 SDTYF-00-07 Upper plug 22 GB1235-76 O-ring,50 x 3.1
the oil discharge port is open. When some oil pressure is relieved, the valve plate slides down again until the oil relieving slide bush SDTYF-00-09 Blind flange for oil relieving port Corrugated spring (corrugated washer)
9 23 SDTYF-00-24
just closes the oil discharge port and the valve inner chamber pressure is stabilized at the preset level. Thus, pressure in the system is
10 SDTYF-00-11 Seat for oil relieving slide bush 24 GB1235-76 O-ring,54 x 3.5
stabilized at the preset level and not influenced by external or internal factor. This mode of working is called mode of pressure
relieving-stabilizing in the overflow. 11 GB1235-76 O-ring,32x3.1 25 SDTYF-00-25 Oil relieving plunger
13 SDTYF-00-15 Oil inlet port spring SDTYF-00-27 Flange of oil in-take port
27
14 SDTYF-00-16 Oil in-take slide bush
27 28
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
3.2.5a.4 Features
Fig.9a Manual-pneumatic Regulator JYSQ21-25
(1)The valve is of the shearing type. It would not be blocked by dirty oil, so its performance would not be compromised. Function Symbol
(2)The plunger and the slide bushes are ground and nitride, high in surface smoothness and hardness, wear resistant and long in 25
service life.
36
(3)Rational construction, with pre-sealing realized by wave spring and auxiliary sealing realized by oil pressure.
35
26
733
5
6
18
7 19
8 20
9 21
22
NPT NPT 10 Z1/2"
1 11 23
Z1"
24
12
Z1"
29 30
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
Function Symbol
A T
P1 P2
4 5 6 7 8 9 10 11 12 13 14
4-Z1"
3
3.2.6.4 Role Played In The Remote Control System
Port 2 of the valve is connected to the outlet of the manual regulator of the manifold. When the valve handle is turned right, the 2
port is open to the manifold. Port P1 is connected to the accumulators directly. When the valve handle is turned left, accumulator
1
pressure is supplied to the manifold. (This valve replaces the traditional 2-position 2-way valve. To follow the traditional custom of
118
manipulation, the same traditional pattern is used for the indication plate.)
16 15
182
1 3.4HXF-00-01 Spindle
3 3.4HXF-01-00 Handle
4 3.4HXF-00-03 Bush
5 GB1235-76 O-ring,28x3.5
6 3.4HXF-00-04 Bonnet
7 3.4HXF-00-05 Nameplate
9 GB1235-76 O-ring,110x3.1
10 GB1235-76 O-ring,25x2.4
15 3.4HXF-00-10 Spring
31 32
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
3.2.7.4 Features
56x50x193
Simple in construction and small in size. No leakage in normal condition, adjustable opening pressure and overflow oscillation.
08 W eight : 7kg
19 3
The thrust exerted on the plunger area by the hydraulic pressure is balanced by the adjustable spring load. When the hydraulic
Z 1 " ( or Z 1 / 2 " )
thrust is greater than the preset spring load, the spring is compressed. So the sealing gasket on the other end of the plunger rod is
pressed against the sealing face of the outlet, compressed air source is cut off. When the thrust is smaller than the preset spring load,
the spring moves the plunger rod up, the sealing gasket gets away from the sealing face, and compressed air supply is reconnected.
09
10 YLF-10 Adaptor
11 YLF-11 Nameplate
33 34
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
1. Install the pressure control to control system as figure1 as above, and make sure that a visual
Control import supply voltage pressure gauge is installed on the control system.
Control low pressure import voltage 2. Put the selector switch to terminal set1 with electricity on.
Control supply loss current 3. adjust the system pressure to upper limit value, and then push the setting button “uup”, the
Export control voltage indicating light blinks for three times, upper limit setting is finished.
Export control electric current 4. adjust the system pressure to lower limit value, and then push the setting button “low”, the
Pressure transmitter power source indicating light blinks for three times, low limit setting is finished.
Pressure transmitter import 5. Put the selector switch to the terminal set0. Now all the work is finished.
Input voltage resolution
Pressure controller wiring as figure 1 IN OUT connectors are used to connect AC contactor 0 110V
220V 380V 460V connectors are control supply input JP4 connects to pressure transmitter (4 20mA)
35 36
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
37 38
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
FOREWORD It is used for indicating or alarming low accumulator pressure, low air pressure, low oil level and
pump running at two positions.
This OPERATION INSTRUCTION on alarm function, is specially compiled in
accordance with technical agreement. 1.2 Structure and working principle
1.2.1 Structure
TABLE OF CONTENTS It consists of as following:
Pressure relays (hydraulic or pneumatic), middle relay, liquid level switch, alarm box, audible and
1. Alarm and display function 1 visual alarm, indicating lights and multipolar plugs and connection cable for remote control panel.
1.1 Usage 1 1.2.2 Working principle (see electrical diagram)
Structure and working principle Put the power supply switch of driller's panel at ON position.
1.2 1
a. When accumulator pressure reaches the minimum rate, pressure relay (KP1) is energized, the
1.2.1 Alarm data 1 middle relay (1K) in alarm box joints and it makes the indicator lights (H17, H18) work and the
1.2.2 Mounting and connecting 2 audible and visual alarm device (BZ1, BZ2) work, When accumulator pressure rises to 15MPa, the
1.2.3 Notices 2 pressure relay (KP1) cuts off and middle relay (1K) de-energized, alarm stops, indicator lights
(XH17, H18) are off, alarm stops.
1.2.4 Fault control 2
b. The pressure relay (KP2) joints when air resource pressure reaches the minimum rate, the middle
1.3 Maintenance 2 relay (2K) in alarm box joints then, it makes the indicator lights (H19, H20) work timely and it
1.4 Alarm Pressure Controller 3 makes the alarm device (BZ1, BZ2) work, When air source pressure reaches 0.65MPa, pressure relay
(KP2) disconnects and middle relay (2K) is de-energized, alarm stops.
c. The middle relay (3K) is energized and level switch (XK) joints when oil level reaches the limited
level; it makes the indictor (H21, H22) the audible and visual alarm device (BZ1, BZ2). The middle
relay (3K) is de-energized, when the oil level reaches over limited line and level switch (XK) is cut
off, alarm stops.
d. When electric motor starting running, the relays in the magnetic starter (1KM, 2KM) joints, the
low accumulator pressure alarm stops (if alarm exists), the indicator light (H16) shines.
e. Press the button (SB20 or SB21) to stop audible alarm if needed. At this time, middle relay (4K) in
the alarm is energized, the power of audible and visual alarm (BZ1, BZ2) is de-energized and stop
working, and the audible alarm stops and its indicating lights (H23,H24) start working until the
alarm situation is removed.
Alarm and display devices have been assembled on both the remote control panel and the driller's
panel. It is only required to connect the remote control panel with driller's panel with electric control
cable.
1.5 Notices
a. Immediately after alarming, the alarming light and the alarm device must be released to
avoid them to work long time.
b. The electric motor running indicator light will work less than twelve minutes. If it is on for a long
time, and the accumulator pressure does not rise, it means that the charging pressure is invalid, it is
needed to check the remote panel and shoot the trouble.
39 40
Operation Instructions Operation Instructions
Read it before using the unit Read it before using the unit
No power in alarm device 1 fuse is welded out in the box. 1 replace the fuse. 5A welding
control box 2 power ling is in trouble. 2 c h e e k t h e p o w e r cores
supply and repair.
The other indicating light The resistance on the abnormal Change the damaged 55W30K
t h a t s h o u l d n o t w o r k circuit loop is invalid resistance for a new one
works when one light after power off
works.
1.7 Maintenance
a. When the cable plugs are removed from multipolar plugs, they must be protected by caps in which
it is clear.
b. The explosion proof multipolar plugs with their lips, sealing gasket must be complete and
effective.
c. When the transfer cable is not in use, or in the process of transportation, they must be collected
carefully, their insulating cover muse not be damaged by sharp things.
YKX-00a alarm pressure controller (see instruction Fig 1 Item 68) on its right side is low
accumulator pressure alarm pressure relay. Screw out the nut on the up right of the box before
calibration, Calibrating the pressure by putting the hexagon wrench into the hexagon hole on the
pressure relay and relating it , clockwise rotation, pressure will be high , anticlockwise rotation ,
pressure will be low , low pressure alarming device is on the left side of the pressure control box ,
screw out the nut on the top of the pressure relay, Calibrating the pressure by putting the hexagon
wrench into the hexagon hole and rotating it , clockwise rotation , pressure will be high ,
anticlockwise rotation , pressure will be low.
41 42