R-MA6
MODULE WITH 6 ANALOG INPUTS + 6 ANALOG OUTPUTS
Main features
• Installation on R-BUSxx backplane
• 6 optically isolated analog inputs at 16 bit
• Configuration of inputs via software
Main applications • On board power supply for transducers
• Plastic machines • 6 optically isolated analog outputs at
• Packing and packaging 16 bit ±10V 20mA
machines • Electronic protection of the outputs
• Auxiliary machines • Diagnostic LEDs
• Automation systems • In Conformity with UL508
PROFILE TECHNICAL DATA Over-voltage on inputs for 1 ms maxi-
The R-MA6 is a mixed module with 6 - 6 analog inputs with 16 bit A/D mum: max. 1kV
analog inputs and 6 analog outputs. conversion
- Sample time for all channels: 200µs Outputs
It controls 6 analog inputs configura- - Power supply output; 24VDC ±25%
- Selectable digital filter
ble for potentiometer, voltage, current 500mA max
- Power supply via backplane
(channels 3,4,5,6 only) and strain- - Management of 6 analog outputs
R-BUS (x) 3.3V
gauge, satisfying the applicative with conversion D/A to 16bit
needs of common transducers used - Settling time 100µs max.
Inputs
in industrial applications. - Voltage outputs ±10V, max. 20mA for
- Potentiometer min. 2kΩ
The conversion system is sequential channel
- Differential 0...100mV, 0...30mV for
on the 6 channels. - Electronic protection against short
strain gauge
circuit and overload for each group
Analog-digital conversion is at 16 bits. - Linear 0...10V, 0...2V
of 3 channels: 100mA max.
The board can be software program- - Linear 0...20mA, 4...20mA
- Linearity better than 0.5%
med to run intercepts and launch - Output isolation: > 2,0KV
interrupts to the Gateway node. Input impedance for:
- Over-voltage on inputs for 1 ms:
It also controls 6 analog outputs in - Potentiometer > 1MΩ
maximum 1kV
- Linear 0...10V, 0...2V > 1MΩ
bipolar voltage ± 10V with maximum
- Strain gauge: > 1MΩ Diagnostics
current of 20mA per output.
- Linear 0/4...20mA = 100Ω - Yellow LED presence external 24V
The outputs have 16 bit resolution.
power supplies
They are protected against short cir- Accuracy of inputs better than 0,5% - Yellow LED presence power supply
cuit and overload by an electronic for transducers
system. Power supply for Inputs - Green RUN LED with double
The module has output diagnostics to 24VDC ±25% 500mA max external function:
check correct function. (fed to terminals): • slow flash for standard configuration
• 10V for strain-gauge max 150mA • fast flash for user configuration
• 24V for amplified sensors max - Red LED Interrupt on
500mA - Red Fail LED module error
Input isolation: > 2,0kV
MECHANICAL DATA AMBIENT CONDITIONS
Dimensions: 92x90x25,4mm Working temperature: 0...50°C
Weight: 130g. Storage temperature: -20...70°C
Attachment: snaps onto R-BUS(x) Humidity: max. 90% Rh not
Protection level IP20 condensing
36 pin front panel connector with
spring-mounted lock
CONFIGURABILITY OF INPUTS
Potentiometer Voltage Current Amplified sensor Strain-gauge
10V power supply 0...10V 0/4...20mA 24V power supply 10V power supply
on board on board on board
CH1 X X X X
CH2 X X X X
CH3 X X X X
CH4 X X X X
CH5 X X X X
CH6 X X X X
INSTALLATION AND CONNECTIONS
The front connections of the module have:
Power supplies 24Vdc ±15% 500mA max., use unipolar cable 0,75mm max., do not attach lug
• Transducer inputs:
potentiometer, use 3 pin shielded cable with 0.5 mm max. cross-section. Do not attach lug. Connect shiel-
ding directly to the grounded plate and as close as possible to the module.
amplified sensor, use 2 or 3 pin shielded cable with 0.5 mm max. cross-section. Do not attach lug. Con-
nect shielding directly to the grounded plate and as close as possible to the module.
strain-gauge, use 4 or 6 pin shielded cable with 0.5 mm max. cross-section. Do not attach lug. Connect
shielding directly to the grounded plate and as close as possible to the module. To calibrate the transducer,
use calibration cables outside the module.
• Linear inputs:
voltage, use 2 pin shielded cable with 0,5mm max. cross-section. Do not attach lug. Connect shielding
directly to the grounded plate and as close as possible to the module.
current, use 2 pin shielded cable with 0,5mm max. cross-section. Do not attach lug. Connect shielding
directly to the grounded plate and as close as possible to the module.
Bipolar analog outputs ±10V or 0/20mA, use shielded cable with 0,5mm max. cross-section, do not attach lug,
connect shielding directly to the grounded plate and as close as possible to the module.
NOTE:
The shield for the analog inputs/outputs must be fixed near the module and directly on the grounded
plate.
INSTALLATION AND CONNECTIONS
+24Vin
Yellow led POWER 1
VS / VP 1 2
Yellow led POWER 2 1 2
+V24in GNDin
3 4
3 3 4
VS1 VS2
5 6
4 5 6
VP1 VP2
7 8
5 7 8
-IN1 -IN2
1 9 10
6 9 0
+IN1 +IN2
1 1 11 12
7 1 2
GNDR1 GNDR2
1 1 13 14
8 3 4
GND1 GND2
1 1 15 16
9 +24Vout1 +24Vout2
5 6
1 1 17 18
10 7 8
VP3 VP4
1 2 19 20
11 9 0
+IN3 +IN4
2 2 21 22
12 1 2
GNDR3 GNDR4
2 2 23 24
13 VP5 VP6
3 4
2 2 25 26
14 +IN5 +IN6
5 6
2 2 27 28
GNDR5 GNDR6
6 AI 16 Bit + 6 AO 16 Bit ± 10V
15 7 8
2 3 29 30
16 GNDout1 GNDout2
9 0
3 3 31 32
17 OUT1 OUT2
1 2
3 3 33 34
Red led INT 18 OUT3 OUT4
3 4
3 3 35 36
Green led RUN 19 OUT5 OUT6
5 6
Red led FAIL 20
1 2
4 3 R-MA6
INSTALLATION AND CONNECTIONS
1
24Vdc ± 25%
500mA max
2
strain-gauge amplified probe
3 unipolar
5 potentiometer voltage
9 Channel 1
13
11
strain-gauge amplified probe
4 unipolar
6 potentiometer voltage
10 Channel 2
14
12
amplified probe unipolar
potentiometer voltage current
17
19 Channel 3
13
21
amplified probe unipolar
potentiometer voltage current
18
20 Channel 4
14
22
amplified probe
unipolar
23 potentiometer voltage current
25 Channel 5
27
amplified probe unipolar
potentiometer voltage current
24
26 Channel 6
28
29 30
OUT 1 31 Ω 32 Ω
OUT 3 33 Ω 34 Ω
OUT 5 35 Ω 36 Ω
ORDER CODE
module code R-MA6 F032132 Code
GEFRAN spa reserves the right to make aesthetic or functional changes at any time and without notice
Conformity UL508 File no. E198546
The device conforms to European Union Directives 2004/108/CE and LVD 2006/95/CE with reference to generic standards: CEI-EN
61000-6-2 (immunity in industrial environment) – EN 61000-6-3 (emissions in residential environments) – EN 61010-1 (safety) – EN
61161-2 (product standard)