Motor Test Report by ABB Shanghai

- The document is a test report for an M2BAX200MLA2 3-phase motor rated at 30kW, 400V, 50Hz, 2959rpm. - Tests performed include insulation resistance, high voltage test, no load test, locked rotor test, thermal test at full load, partial load tests at 75%, 50%, and 25% load, and temperature rise measurements. - Key results include insulation resistance of 13600MΩ, temperature rise of 17.3°C at ambient, efficiency of 93.4% at full load, and starting current and locked rotor torque ratios.

Uploaded by

Pein Akatsuki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
113 views1 page

Motor Test Report by ABB Shanghai

- The document is a test report for an M2BAX200MLA2 3-phase motor rated at 30kW, 400V, 50Hz, 2959rpm. - Tests performed include insulation resistance, high voltage test, no load test, locked rotor test, thermal test at full load, partial load tests at 75%, 50%, and 25% load, and temperature rise measurements. - Key results include insulation resistance of 13600MΩ, temperature rise of 17.3°C at ambient, efficiency of 93.4% at full load, and starting current and locked rotor torque ratios.

Uploaded by

Pein Akatsuki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Cert. No.

0AD127-A499/19-1

Test Report
Date of Issue 12/4/2019

Customer:
Type: M2BAX200MLA2

Serial no.: 3G1C19470739079001

Customer ref.:
Order no.: 502677509019

Rating: Product Code


3~Motor
V Hz kW r/min A cos φ
Insul.cl. F 400 50 30 2959 51.7 0.9

Insulation resistance Overload test


13600 MΩ 1000 V 1.6 *Tn 15s
U1 -V1 0.10789 Ω 16 ℃ Environment humidity: 35 % Pass
U1 -W1 0.10828 Ω
V1 -W1 0.10831 Ω
High-voltage test
2400 V 60S

Test Torque Line Input Output


(Nm) U[V] f[Hz] I[A] P1 [W] P2 [W] n[r/min] cos Ø ƞ [%]

No-load test / 401 V 50 16.11 919 / / / /


Locked rotor test / 100.2 V 50 104.88 7797 / 0 / /
Thermal test(100% load) 96.9 400.0 V 50 52.14 32120 30000 2958.8 0.889 93.4
Partial load points
~75% load 72.4 399.3 V 50 40.42 24070 22500 2968.1 0.860 93.5
~50%load 48.1 399.0 V 50 29.61 16150 15000 2979.8 0.787 92.9
~25% load 24.0 400.3 V 50 20.54 8400 7500 2990.9 0.590 89.3
Temperature rise at amb.temp. 17.3 ℃ Temperature Measurement method
Pole [K] Method Pole ℃ Method 1 Resistance
Stator winding 2 52 1 Ambient 2 17.3 2 2 Thermometer
Frame 2 36 2 3 Thermocouples

Starting Current(Is/IN): 9.47


These tests have been carried out on motor no. 3G1C19470739079001 on date 12/4/2019 Locked rotor torque(TL/TN): 3.66
which is identical in design with the above.

Manufactured and tested in accordance with rules of IEC 60034-1 ans IEC60034-2-1.
On behalf of customer

On behalf of manufacturer

Tested by: ABB Shanghai Motors Co., Ltd

Motors/Shanghai