10x10 DF Reddy Buffaloes Pump

The document appears to be a bulletin from Reddy-Buffaloes Pump Inc. that advertises fire pumps. It includes performance curves and specifications for two 10x10 fire pumps rated for 1495 GPM and 1785 GPM. The bulletin provides contact information for Reddy-Buffaloes Pump Inc. and indicates the pumps are UL, FM, and NFPA approved.

Uploaded by

sinahims
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views19 pages

10x10 DF Reddy Buffaloes Pump

The document appears to be a bulletin from Reddy-Buffaloes Pump Inc. that advertises fire pumps. It includes performance curves and specifications for two 10x10 fire pumps rated for 1495 GPM and 1785 GPM. The bulletin provides contact information for Reddy-Buffaloes Pump Inc. and indicates the pumps are UL, FM, and NFPA approved.

Uploaded by

sinahims
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

8902RBull504 3/6/09 7:50 AM Page 1

BULLETIN 504
10 x 10 DF UL FM
NFPA

Fire Pumps MOTOR DRIVEN OR ENGINE DRIVEN


THE BEST YOU CAN BUY
CONTACT YOUR NEAREST DISTRIBUTOR

R-B Pump, Inc.


REDDY - BUFFALOES PUMP, INC.
1 DIXIE DRIVE • P.O. BOX 557 • BAXLEY, GA 31513 • (912) 367-6345 • (912) 367-6394
8902RBull504 3/6/09 7:50 AM Page 1

1
8902RBull504 3/6/09 7:50 AM Page 8

8
8902RBull504 3/6/09 7:50 AM Page 9

9
8902RBull504 3/6/09 7:50 AM Page 10

10
8902RBull504 3/6/09 7:50 AM Page 11

11
8902RBull504 3/6/09 7:50 AM Page 12

12
8902RBull504 3/6/09 7:50 AM Page 13

13
8902RBull504 3/6/09 7:50 AM Page 14

14
8902RBull504 3/6/09 7:50 AM Page 15

15
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


3/6/09

MEMBER OF 1495
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0110
DIA_______PATTERN NO.____________________
7:50 AM

NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS

300 UL/FM APPROVAL


Page 16

FLOW PR. RANGE


Dia. 18 3/8" (GPM) (PSI)
60%
1500 73-109
70%
250 2000 69-104
17"
80% 2500 64-98
3000 -91
16"

200
15"

16
60%
70%
150 80%
80%

85% 70%

100
85%
80%
70%

200 50

Dia. 18 3/8"
N.P.S.H.R.

15"
0 0
0 1000 2000 3000 4000 5000 6000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


MEMBER OF 1785
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
3/6/09

&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0110
DIA_______PATTERN NO.____________________
NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
2) PROPER N.P.S.H. CONDITIONS
7:50 AM

LISTED APPROVED

UL/FM APPROVAL
FLOW PR. RANGE
(GPM) (PSI)
Page 17

1500 60-158
2000 55-154
2500 55-150
3000 65-142
3500 97-112

400
Dia. 18 3/8" 60% 70%
80%

17
300
16"
80%

14" 70%
200

85%
12"

500 100
60% 70%
Dia. 16 1/2" 80%
80%
70% N.P.S.H.R.
0 0 12"
0 1000 2000 3000 4000 5000 6000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


3/6/09

MEMBER OF 2100
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0110
DIA_______PATTERN NO.____________________
NFPA
7:50 AM

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS

UL/FM APPROVAL
Page 18

FLOW PR. RANGE


(GPM) (PSI)
1500 85-225
500 2000 80-215
2500 80-208
3000 75-200
Dia. 16 1/2" 60% 3500 90-160
70%
80%
400 85%

18
15"

300 85%
13 1/2"
90%
80%

12"
200

60%
70%
80%

500 100

Dia. 16 1/2" 80%

0 0 12" N.P.S.H.R.
0 1000 2000 3000 4000 5000 6000 7000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


3/6/09

MEMBER OF 2300
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0110
DIA_______PATTERN NO.____________________
NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
7:50 AM

LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS


600 UL/FM APPROVAL
FLOW PR. RANGE
Page 19

(GPM) (PSI)
Dia. 16 1/2" 50% 60%
70% 1500 100-218
500 80% 2000 100-216
2500 100-210
85% 3000 95-203
15" 3500 113-197

400
85%

19
13 1/2" 90%
80%
300

12"

1000 200 50%


60%
70%
80%

80%
500 100
Dia. 16 1/2"

12" N.P.S.H.R.
0 0
0 1000 2000 3000 4000 5000 6000 7000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


3/6/09

MEMBER OF 3580
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0110
DIA_______PATTERN NO.____________________
7:50 AM

NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS
600 50% UL/FM APPROVAL
Page 20

Dia. 12" 60% FLOW PR. RANGE


(GPM) (PSI)
70%
1500 180-245
500 2000 175-240
11 1/2"
80% 2500 169-240
3000 -235

10 1/2"
400

20
50%
60%
300

80%

70%

1000 200

Dia. 12"
500 100
10 1/2"

N.P.S.H.R.
0 0
0 1000 2000 3000 4000 5000 6000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


MEMBER OF 1795
3/6/09

RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________


&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0146
DIA_______PATTERN NO.____________________
NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
7:50 AM

LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS


600 UL/FM APPROVAL
FLOW PR. RANGE
(GPM) (PSI)
Page 21

1500 46-130
500 2000 42-125

400

21
60% 70%
Dia. 17 1/8"
300 80%
85%

15"

85%
200 13"
80%
70%

11 1/4"

500 100
60%
70%

Dia. 17 1/8" 70%


N.P.S.H.R.
0 0
11 1/4"
0 1000 2000 3000 4000 5000
GPM
8902RBull504

REDDY-BUFFALOES PUMP INC. BAXLEY, GA 31513 PUMP CHARACTERISTIC CURVES


3/6/09

MEMBER OF 2950
RATING GPM__________FT. HD. __________RPM________CERTIFIED TEST BY____________
&
DF 10" x 10"
PUMP TYPE______SIZE________IMPELLER C-0146
DIA_______PATTERN NO.____________________
7:50 AM

NFPA

BR. H.P.
PERFORMANCE CURVES ARE BASED ON: 1) CLEAR WATER WITH A SPECIFIC GRAVITY OF 1.0
FM

N.P.S.H.FT.
HEADFT.
UL
LISTED APPROVED 2) PROPER N.P.S.H. CONDITIONS
Dia. 15"
600 60% UL/FM APPROVAL
Page 22

70% FLOW PR. RANGE


(GPM) (PSI)
14" 80% 2000 145-230
500 2500 136-215
85%
13"

12"
400
85%

22
80%
60%
300 70%
70%

200

70%

500 100

Dia. 15"

12"
0 0 N.P.S.H.R.
0 1000 2000 3000 4000 5000 6000
GPM
8902RBull504 3/6/09 7:50 AM Page 23

23
8902RBull504 3/6/09 7:50 AM Page 27

Other R-B Pump Products:


Horizontal Split Case Axial & Mixed End Suction
Centrifugal Pumps Flow Pumps ANSI Pumps
• Single & Two Stage Design • Capacities: 1000 - 250,000 GPM • High Efficiencies
• Capacities: To 50,000 GPM • Head: 5-54 Ft., per Stage • ANSI B16.1 - 1977 STD. Design
• Head up to 1,000 ft. • Custom Designed to 600,000 GPM • Capacities 25-5,000 GPM
• Head up to 400 ft.

Inline Booster Vertical Turbine Non Clog Dry


Pumps Pumps Pit Pumps
• Capacities to 1,000 GPM • Single to Multi Stage design • Capacities to 100,000 GPM
• Head up to 400 ft. • Capacities to 30,000 GPM • Head up to 100 ft.
• Head up to 400 ft.

Member of the

R-B Pump, Inc.


P.O. Box 557
Baxley, Georgia 31513
(912) 367-6345 FAX 912-367-5024
(2003-3000)