VLCC Effie Maersk - Imo 9682978 - Machinery Operating Manual
VLCC Effie Maersk - Imo 9682978 - Machinery Operating Manual
List of Contents: 2.3 Condensate and Feed Systems 2.13 Electrical Power Distribution
Issues and Update Control 2.3.1 Condensate System 2.13.1 Electrical Equipment
Mechanical Symbols and Colour Scheme 2.3.2 Drains Systems 2.13.2 Main Switchboard and Generator Operation
Introduction 2.3.3 Boiler Feed System 2.13.3 Electrical Distribution
Additional 2.3.4 Water Sampling and Treatment System 2.13.4 Shore Power
2.13.5 Main Alternators
Part 1: Operational Overview 2.4 Sea Water Systems 2.13.6 Emergency Alternator
2.4 1 Main and Auxiliary Sea Water Systems 2.13.7 Preferential Tripping and Sequential Restarting
1.1 To Bring Vessel into Live Condition 2.4.2 Sea Water General Service System 2.13.8 Uninterruptible Power Supply (UPS) and Battery Systems
2.4.3 Engine Room Ballast System 2.13.9 Cathodic Protection System
1.2 To Prepare Main Plant for Operation 2.4.4 Evaporator
2.4.5 Distilled Water Transfer and Distribution 2.14 Accommodation Systems
1.3 To Prepare Main Plant for Manoeuvring from In Port Condition 2.14.1 Domestic Fresh Water System
2.5 Fresh Water Cooling Systems 2.14.2 Domestic Refrigeration System
1.4 To Change Main Plant from Manoeuvring to Full Away 2.5.1 Main Engine Jacket Cooling Water System 2.14.3 Accommodation Air Conditioning Plant
2.5.2 Central Fresh Water Cooling System 2.14.4 Miscellaneous Air Conditioning Units
1,5 To Prepare for UMS Operation 2.14.5 Sewage Treatment
2.6 Fuel Oil and Diesel Oil Service Systems 2.14.6 Incinerator and Garbage Disposal
1.6 To Change from UMS to Manned Operation 2.6.1 Main Engine Fuel Oil Service System
2.6.2 Auxiliary Engine Fuel Oil Service System Illustrations
1.7 To Change Main Plant from Full Away to Manoeuvring Condition 2.6.3 Auxiliary Boiler Fuel Oil System
2.6.4 Incinerator Fuel Oil System 2.1.1a Main Engine
1.8 To Secure Main Plant at Finished With Engines 2.1.1b Main Engine Control - Start System
2.7 Fuel Oil and Diesel Oil Transfer Systems 2.1.2a Main Engine Manoeuvring Control - Telegraph System
1.9 To Secure Main Plant for Dry Dock 2.7.1 Fuel Oil and Diesel Oil Bunkering and Transfer System 2.1.2b Main Engine Local Control Station
2.7.2 Fuel Oil and Diesel Oil Purifying Systems 2.1.2c Main Engine Digital Governor Panel
Illustrations 2.1.3a Main Engine Safety System Panel
Propeller Jacking Up System 2.8 Lubricating Oil Systems 2.2.1a Auxiliary Boiler
Location Plan of Engine Room - Floor Plan 2.8.1 Main Engine Lubricating Oil System 2.2.2a Boiler Control Panel
Location Plan of Engine Room - 3rd Floor Plan 2.8.2 Stern Tube Lubricating Oil System 2.2.4a Medium Pressure Steam System
Location Plan of Engine Room - 2nd Floor Plan 2.8.3 Lubricating Oil Purifying System 2.2.5a Low Pressure Steam System
Location Plan of Engine Room - Elevation 2.8.4 Lubricating Oil Filling and Transfer System 2.2.6a Economiser Feedwater System
2.3.1a Condensate System
Part 2: Main Engine and Auxiliary Systems 2.9 Bilge System 2.3.2a Heating Drains / Contaminated Water System
2.9.1 Engine Room Bilge System and Bilge Separator 2.3.3a Boiler Feedwater System
2.1 Main Engine 2.9.2 Pump Room Bilge System 2.4.1a Main and Auxiliary Sea Water Cooling System
2.1.1 Main Engine Particulars 2.9.3 Bosun’s Store and Chain Locker Bilge System 2.4.2a Sea Water General Service System
2.1.2 Main Engine Manoeuvring Control 2.4.3a Engine Room Ballast System
2.1.3 Main Engine Safety System 2.10 Air Systems 2.4.4a Evaporator
2.10.1 Starting Air System 2.4.5a Distilled Water Transfer and Distribution
2.2 Boilers and Steam Systems 2.10.2 General Service Air System 2.5.1a Main Engine Jacket Cooling Water System
2.2.1 General Description 2.10.3 Control Air System 2.5.2a Central Fresh Water Cooling System
2.2.2 Boiler Control Systems 2.6a Viscosity - Temperature Graph
2.2.3 Sootblowers 2.11 Steering Gear 2.6.1a Main Engine Fuel Oil Service System
2.2.4 Medium Pressure Steam System 2.6.2a Auxiliary Engines Fuel Oil Service System
2.2.5 Low Pressure Steam System 2.12 Electrical Power Generators 2.6.3a Auxiliary Boiler Fuel Oil Service System
2.2.6 Economiser 2.12.1 Diesel Generators 2.6.4a Incinerator Fuel Oil Service System
2.12.2 Emergency Diesel Generator 2.7.1a Fuel Oil and Diesel Oil Bunkering and Transfer System
2.7.2a Fuel Oil Purifying System
Illustrations
Illustrations
3.1.1a February 2001
3.1.2a February 2001
3.1.3a February 2001
3.1.5a February 2001
3.1.6a February 2001
3.2a February 2001
Text
4.1 February 2001
4.2 February 2001
4.3 February 2001
4.4 February 2001
4.5 February 2001
Illustrations
4.1a February 2001
4.2a February 2001
4.3a February 2001
4.4a February 2001
4.5a February 2001
Text
5.1 February 2001
5.2 February 2001
5.3 February 2001
5.4 February 2001
5.5 February 2001
S Not Connected
Non Return Valve Solenoid Valve Diaphragm With Positioner Orifice LT Cooling Water
Crossing Pipes
Sea Water
Hand Operated Normally Open
Swing Check Valve Piston Valve (Locked Open) Connected Crossing Pipes N.O or N.C or
Normally Closed Hydraulic Oil
Hand Operated
Hose Valve Diaphragm Operated Valve (Locked Shut) Branch Pipe Lubricating Oil
(3-Way Control)
Fire/Deck Water
Safety Valve Stop Valve (Angle) Cylinder Piston Actuator Mud Box
Positive Displacement CO2
Pump
M Motor Driven Simplex Water Strainer
Pressure Reducing Valve Lift Check Valve (Angle) Fuel Oil
In many cases the best operating practice can only be learned by experience. The concept of this Machinery Operating Manual is to provide information to The following notices occur throughout this manual:
Where the information in this manual is found to be inadequate or incorrect, technically competent ship’s officers, unfamiliar to the vessel, in a form that is
details should be sent to the Maersk Technical Operations Office so that readily comprehensible, thus, aiding their understanding and knowledge of the WARNING
revisions may be made to manuals of other ships of the same class. specific vessel. Special attention is drawn to emergency procedures and fire Warnings are given to draw reader’s attention to operation where
fighting systems. DANGER TO LIFE OR LIMB MAY OCCUR.
The manual consists of a number of parts and sections which describe the ! CAUTION
systems and equipment fitted and their method of operation related to a Cautions are given to draw reader’s attention to operations where
schematic diagram where applicable. DAMAGE TO EQUIPMENT MAY OCCUR.
Part One details the machinery commissioning procedures required to bring (Note ! Notes are given to draw reader’s attention to points of interest or to
the vessel into varying states of readiness, from bringing the vessel to a live supply supplementary information.)
condition through to securing plant for dry dock.
SKF Connection
Nipples
Vent
SKF Pumpset
Oil Grooves
Gauging Stop Ring
SKF Pumpset
SKF Pumpset
Propeller Boss
Tail Shaft
Jacking Ring
Key
Hydraulic Oil
! CAUTION
‘E’ Class Propeller Jacking System
The propeller is a taper friction grip on the propeller shaft and the propeller is
forced onto the taper of the shaft by means of hydraulic jacks. Under normal
circumstances there is a sudden pressure increase on the jacking pump pressure
gauge when the propeller is in its final position; this is because the hydraulic
jack encounters the stopper ring which is in contact with the end of the taper
on the propeller shaft. Under such circumstances the propeller cannot be
moved any further on the taper as the hydraulic jacks are effectively forcing
against the propeller shaft.
On this ship the stopper ring, for the propeller and hydraulic jack, is of
insufficient diameter to effectively stop the jack movement in the axial
direction. This means that the jack can move past the stopper ring and
continue forcing the propeller onto the taper. In order to prevent this, and
the associated high stress which would result in the propeller boss and the
taper shaft, it is essential that the position of the propeller on the taper shaft
is accurately determined, using dial gauges and/or micrometers. When
refitting the propeller the position of the propeller on the shaft must be
measured and the actual position of the propeller on the shaft must be used
for deciding when the propeller is correctly positioned.
HFO Purifier
Supply Pump
MDO Transfer No.1 Economiser
No.1 No.1 Feedwater
Pump IG Deck Seal Sea Water Boiler
LO Transfer Feedwater No.2 Pumps
Pump Pumps No.2
No.2 Pumps Water Ballast
No.3
Pump Motor
Main LO Purifier
Supply Pump
FO Overflow Starter For
HFO Transfer Tank Ballast Pump
Oily Bilge Pump
Sludge Separator No.1 Water Ballast
Pump Pump Turbine
Bilge Fire & General Service
Oily Bilge No.2 No.1
Pumps
Pump DO Storage Tank No.2 Cooling Oil
Stripping Pump
Scrubber Cooling Sea Water Motor
Ballast Oily No.1 Pump
Water Bilge Tank LO Sump Tank Vacuum
No.1 Unit
COPT Condensate
Pumps
Emergency No.2
Cargo Oil
Escape Trunk Oily Auxiliary cooling Sea Water
Holding COPT Pump Turbine
Bilge Tank Pump
Tank Condenser
No.2 No.1 No.2 Main Engine Hyundai No.1
Main P2 - Panel
LO Pump No.1
DO Storage Tank Main COPT Condenser Cooling
Sea Water Pumps
Stern Tube Oil No.2 Cargo Oil
Circulation Pump Pump Turbine
Stern Tube No.3 No.2
LO Pump Ballast Ballast
Water Water
Fresh Water Generator
Ejector Pump
Cargo Oil
Pump Turbine
Main Engine Main Engine No.3
Sewage
Turbocharger Crosshead LGSP
Treatment
LO Pumps LO Pumps Main Engine Main Engine
Plant
Jacket Cooling HT Circuit Feeding
Main LO Main LO Feed Water Pump
Discharge Cooler & Drain Tank
Filter
Generator Engine LO
Purifier Heater
Main LO
Purifier Heater
No.1, 2
Boiler FO
No.2 HFO No.1 HFO HFO
Heater
Service Service Setting
Generator Engine MDO Tank Tank Tank
Service Pumps
Elevator
Trunk
No.1
Generator
Engine Transformers
Free Above ECR
Space
No.2
Generator
Engine
Emergency
Exit Main Engine
Hyundai
No.3
Generator
Engine
Auxiliary Air
Reservoir
No.1
Boiler Water ME Jacket Cooling ER
Soot Fresh Water Pumps
Circulation Toilet
Collection
Pumps No.2 Tank
Port Use
No.2 No.1 Fresh Water
Main Engine Pumps
Jacket
Preheater No.1 Central Cooling
No.2 No.1 Fresh Water
No.2 Pumps
Spare Cylinder
Free Cover With Exhaust Valve
Space
Spare Cylinder
Liner
Spare
Piston
Spare Exhaust
Overhead Valves
Crane
Workshop
Main Engine Exhaust Valve
Seat Grinding Machine
& Working Stand
No.2 Auxiliary Boiler
Welding
VT VT Area
LGSP
Main
Fresh Water Air Compressors
Hydrophore Unit
No.3 No.2 No.1
No.1
Hot Water
Circulation Pump Air Con. Compressor Unit
Exhaust Gas
Economiser
Calorifier No.2
Control Control
Air Reservoir Air Dryer
Main
Air Reservoir
IG Fans
IG
Scrubber
Unit
Boiler FD Fan
Upper Deck
Crane Escape
Trunk
Store
Main Auxiliary Room
Boiler
2nd Deck
Elevator
Trunk Purifier
Room
Engine Control
Room
3rd Deck
Sludge Tank
COPT Condenser
COPT's
Bilge Fire
& GS Pump
Oily Bilge Main LO Main Engine Hyundai
Separator Pump
Floor
Pump Room
Tank Top
BW
BW
Main LO Sump Tank
Bilge Holding Oily Bilge FO Over Flow
Tank Tank Tank
MDO Storage Tank
Shore power available No shore power available Prepare central FW cooling systems
2.5.2
start central CW pumps.
Establish shore supply.
Check phase sequence, 2.13.2 Check DO tank level is adequate. 2.13.4
voltage and frequency.
Start up instrumentation air system. 2.10.3
Prepare an auxiliary engine for starting. Ensure the CO2 systems are ready for use. 4.2
2.12.1
Start auxiliary engine.
Two
TwoDiesel
diesel Generators
generators in use,
Stop one steering gear motor. 2.11
remaining diesel generator on standby.
Emergency generator on standby.
Boilers and steam system in use.
Diesel generators running on HFO. Put dump steam system into operation. 2.2.4
Main engine heated and ready for use on bridge
control.
Main engine circulating with hot FO.
Both steering gear in use. Operate turbocharger blower cleaning system
Deck machinery ready for use. 2.1.1
if required.
Vessel manoeuvring on bridge control.
Operate exhaust gas economiser sootblowers. 2.2.3 When run up program completes, check that
2.1.2
pressures and temperatures stabilise.
All piping systems are tight and not temporary Engine room and steering gear compartment
repaired. watertight doors and skylights are shut.
Control is on the bridge and duty officer is
3.1
informed of commencement time of UMS.
Compressed air bottles are fully charged. 2.10 Watchkeeper control switched to duty
engineer's cabin.
Vessel is Full Away on Bridge Control Test fire the boiler in use. 2.2.1
Operate EGB sootblowers and isolate system. 2.2.6
Prepare main starting air compressors for use. Check bridge/engine room clocks and
2.10.1 2.1.2
check starting air system drains for water. communications.
Isolate starting air. Prepare plant for IGS operations if required. 2.15.1
Open indicator cocks.
Open turbo blower drains. 2.1.1
Vent main engine starting air and control air Shut down deck machinery. 1.6.2
systems. Engage turning gear. Cargo
Shut down deck machinery system. 1.6.2 Isolate sequential restart system. 2.13.5 Plant Secured for Dry Dock
Cylinder Head
Turbocharger
Air Cooler
Camshaft
Scavenger Port
Piston Rod
Crosshead Guide
Crosshead LO Shoe
and Piston Cooling Pipe
Lubricating Oil
Scavenge Air
Combustion Gas
Fresh Water
Stay Bolts
Starting Air
Remote Control
Take Over Stop
From/To To Other
High Level Cylinders
Tank 2.01 Remote Control
212HA On
Control Air
Board Supply
19HB
Oil Mist
19HA Electrical Actuator Detector
23HA
To P/T Panel
To P/S Panel
Camshaft
Overspeed and
Safety Shutdown Pick-up
Remote
Control
Emergency Control
Key
Stop Signal
Astern Signal
Ahead Signal
Hydraulic Oil
Starting Air
Remote Control
Take Over Stop
From/To To Other
High Level Cylinders
Tank 2.01 Remote Control
212HA On
Control Air
Board Supply
19HB
Oil Mist
19HA Electrical Actuator Detector
23HA
To P/T Panel
To P/S Panel
Camshaft
Overspeed and
Safety Shutdown Pick-up
Remote
Control
Emergency Control
Key
Stop Signal
Astern Signal
Ahead Signal
Hydraulic Oil
Safety control air and standby supply for air spring air on the pressure reducing The following conditions must be fulfiled before activating the slow turning b) The values read off the instruments compared with those given in
valve 23HA (6 kg/cm2) operation on air: the acceptance records, taking into account engine speed and/or
engine power, provide an excellent yardstick for the engine
Turning gear is disengaged
Air spring air supply on the pressure reducing valve 19HA (7.5 kg/cm2) performance. It should be borne in mind that instrumentation
Oil pumps are operating (bearing oil and crosshead oil) faults may cause faulty readings and action should be taken to
Control air standby supply on the pressure reducing valve 19HB (7 kg/cm2) check the instrumentation before any engine adjustment is made.
Fuel interlock not released
Where low temperatures are involved, a temperature can be
p) Set the switch at the control panel for the auxiliary blower to Reversing lever is set on REMOTE CONTROL assessed by feeling the pipe and, where it is safe to do so, suspect
AUTOMATIC. instruments can be exchanged for similar devices.
Speed control on minimum (Position 0)
q) Bring the safety cut-out to operating position. Indicator valves closed The essential readings are:
Shut-off valves on the starting air receivers open The load indicator position
r) Press the EMERGENCY STOP button on the control panel and
observe if the safety cut-out on the fuel injection pumps reacts, Handwheel on the automatic starting air shut-off valve 2.03 set to the Turbocharger speed
i.e. their suction valves are lifted. After this check, press the AUTOMATIC position
Charge air pressure
EMERGENCY STOP RESET button.
Air pressure for air spring correctly set
Exhaust gas temperature before and after the turbine
s) Check whether the pressure gauge on the supply unit for cylinder During slow turning, the cylinder lubrication must be switched on.
lubrication indicates 40 kg/cm2. A valuable criterion is also the daily fuel consumption. When comparing with
Slow Turning Function engine trials data, consideration must be given to the lower calorific value of
t) Take out the turning gear and secure the lever. the heavy fuel used in service compared with the diesel oil employed during
The procedure is similar to starting the engine. The following designation the acceptance trials.
u) Open the test valve 2.06 of the main automatic starting air shut- numbers refer to the Sulzer engine manual control diagram.
c) Check all shut-off valves in the cooling and lubricating system for
off valve 2.03 for a short time and listen for the valve opening correct position. The shut-offs for the cooling inlets and outlets on
(can be heard distinctly). Close the valve again. The automatic starting air shut-off valve 2.03, is opened by the control valve
2.05. When the control is moved to the start position, starting air flows to the the engine must always be fully open in service. They serve only
starting cut-off valve 212HA on the starting air distributor as well as the to cut off individual cylinders from the cooling water circuit
v) Check hydraulic system of exhaust valve drive for tightness. during overhauls.
starting air valves 2.07 located in the cylinder heads.
Check that the fuel injection nozzles are in excellent condition. This is partic- Repair all the defects detected in service (leaks, etc.). If one or more of these operating conditions prevails, residues, mainly
ularly important for prolonged operation at low load. consisting of incompletely burnt fuel and cylinder lubricating oil will
If any engine maintenance work is to be undertaken, safety precautions must accumulate at the following points:
The cylinder lubricating oil quantity is automatically adapted to the lower load. be observed and warning notices posted at all control positions, including the
The lubricating oil quantities are regulated in accordance with engine load or turning gear control. Between piston rings and piston ring grooves; this can result in
position of intermediate regulating shaft. For prolonged operation at low load, the jamming of piston rings causing breakage or blow-past.
the cylinder lubrication must be checked frequently to ensure that it is at the Fouling and Fires in the Scavenge Air Spaces
optimum level. On the piston skirts. In the scavenge ports; this can affect the
The principle cause of fouling is blow-by of combustion products, unburnt fuel performance of the scavenging process resulting in incomplete
Procedures after Shutting Down the Engine and cylinder lubricant between piston and cylinder into the scavenge air removal of combustion products from the cylinder and
spaces. The fouling will be greater if there is incomplete combustion of the fuel subsequent defective combustion.
Where the engine must remain manoeuvrable, all pumps must be kept running injected (exhaust smoke).
and temperatures maintained in the cooling systems, lubrication systems and On the bottom of the cylinder jacket (piston underside).
fuel system. Control air must be available and the air receivers maintained at Causes of Poor Combustion:
full pressure. Causes of the Fires
The fuel injectors are not working correctly; incorrect fuel
If the engine does not need to remain manoeuvrable after the engine has been atomisation. The blow-by of hot combustion gases and sparks which have bypassed the
stopped, the cooling water and lubricating oil pumps should be left running for piston rings between piston and cylinder liner running surface, enter the space
The fuel is at too low a temperature; resulting in high fuel on the piston underside. Any residues present can ignite.
at least a further 20 minutes in order to allow the temperatures to equalise. The
viscosity and poor fuel atomisation.
LO and cooling water should not be cooled down below their normal inlet tem-
peratures. As main engine cooling forms part of a central cooling system, Poorly adjusted injection pump timing; late injection results in If there is after-burning of fuel in the cylinder due to late injection or poor fuel
attention must be paid to the needs of other parts of that system, such as the after burning of fuel. atomisation, the cylinder pressure, when the scavenge ports are uncovered,
diesel generators, and no items should be shut down which will have an effect may be higher than the scavenge air pressure and hot combustion gases may
Operation with a temporary shortage of air during extreme
on the operation of the central cooling system, e.g. sea water circulating pump. enter the scavenge space.
variations in engine loading and with the charge air pressure
dependent fuel limiter in the governor set too high.
The starting air supply has to be closed as soon as possible after stopping the A defective piston rod gland may allow oil from the crankcase to enter the
engine; i.e. shut the main stop valves on the starting air receivers and open the Engine overloading; too much fuel for the available air. scavenge space. The piston rod gland drains should be checked frequently for
starting air line venting valve A23V to vent the air start supply line. Turn the signs of crankcase system oil as this indicates defective gland sealing rings.
handwheel on the shut-off valve for starting air 2.03 until the pointer is at the Insufficient supply of air due to restricted engine room
CLOSED position and drain the valve by opening vent valve 2.21. ventilation.
The safety of shipboard personnel should be paramount whenever dealing with When running continuously at reduced load, check the cylinder g) Lock the casing doors and keep away from them.
fires anywhere aboard ship. lubricating oil feed rate and readjust if necessary. Ensure that fuel
Inform the bridge of the situation atomisation and combustion is correct for the reduced load h) Prepare the fire-fighting equipment.
condition.
Reduce engine power i) Do not open the crankcase until at least 20 minutes after stopping
Cut out the fuel injection pump of the cylinder concerned The permanent drain of residue from the piston underside must the engine. Ideally leave the engine for as long as possible before
always be checked. To prevent accumulation of dirt, the drain opening the crankcase doors as this will ensure that the hot spot
Increase lubrication to the respective cylinder cock on the collector main must be opened for a short time each has cooled below the ignition temperature and so any mist which
day. persists will not ignite from this source. It is important that no
(Note ! If a serious fire occurs, shut down the engine after obtaining
naked lights exist in the vicinity of the crankcase when the doors
permission from the bridge and operate the fixed fire extinguishing system.)
Prevention of Crankcase Explosions are opened in order to prevent ignition of any residual mist from
that source.
A fire should have died down after 5 to 15 minutes. This can be verified by
The oil mist in the crankcase is inflammable over a very narrow range of
checking the exhaust gas temperatures and the temperatures of the doors to the
mixture. Weaker or richer mixtures do not ignite. There must always be an j) Stop the lubricating oil pump. Take off/open all the doors on one
piston bottoms.
extraneous cause to set off ignition, such as hot engine components. Only side of the crankcase. Cut off the starting air, and engage the
under these circumstances and the presence of a critical mixture ratio of oil turning gear.
Caution should be exercised whilst the fire is burning to ensure that it does not
mist and air can an explosion occur. A ‘hot spot’ is the common feature of all
cause a fire in the engine room. Extreme care must be taken to ensure that
crankcase explosions and this can be due to metal-to-metal contact at a wiped
leakage of oil onto the hot scavenge space sides does not happen.
bearing, rubbing guide, defective piston rod gland, damaged thrust, un-
lubricated gear wheel, etc. or even due to a prolonged scavenge fire. The ‘hot
After it has been confirmed that the fire has been extinguished the engine must
spot’ provides the heat source to evaporate oil, which condenses to form mist-
be stopped as soon as possible and the cause of the fire established. The
like droplets which will ignite readily, and ignite the mist. If the mist concen-
scavenge space must be allowed to cool completely before access doors are
tration in the crankcase reaches a critical level an explosion can occur.
opened to allow inspection.
Engines are equipped with an oil mist detector, which constantly monitors
Checks should be made on the cylinder running surfaces, piston rings, fuel
intensity of oil mist in the crankcase and triggers an alarm if the mist exceeds
injectors, valve groups in the scavenge space, piston rod gland and liner seals.
the density limit.
Tie rod tension should be checked if the fire has been severe.
Measures to be Taken When Oil Mist Has Occurred
After a careful check, or if necessary repair, the engine can be put back on load
with cut-in fuel injection pump and automatic cylinder lubrication.
a) Do not stand near crankcase doors or relief valves or in corridors
near doors to the engine room casing.
Should a stoppage of the engine not be feasible and the fire has died down, the
fuel injection pump can again be cut in, the load increased slowly and the
b) Reduce speed to slowdown level immediately, if not already
cylinder lubrication brought back again to the normal output. Avoid prolonged
carried out automatically. Explain the situation and ask the bridge
running with the considerably increased cylinder lubrication.
for permission to stop.
Main Engine Graviner Oil Mist Detector
k) Locate the hot spot. Feel over, by hand, all the sliding surfaces WARNING
(bearings, thrust bearing, piston rods, stuffing boxes, crossheads,
lubricant supply toggle lever pipes, gears, vibration dampers, Special Engine Room Dangers
moment compensators, etc.). Look for squeezed-out bearing
metal and discolouration caused by heat (blistered paint, burnt oil, Keep clear of spaces below loaded cranes.
oxidised steel). Keep possible bearing metal found at the bottom
of the oil tray for later analysing. Prevent further hot spots by The opening of cocks may cause discharge of hot liquids or gases.
preferably making a permanent repair. Ensure that the respective
sliding surfaces are in good condition. Take special care to check The dismantling of parts may cause the release of springs.
that the circulating oil supply is in order. The engine should not
be restarted until the cause of the hot spot has been located and The removal of fuel valves or other valves in the cylinder cover
rectified. may cause oil to run onto the piston crown. If the piston is hot an
explosion may blow out the valve.
l) Start the circulating oil pump and turn the engine by means of the
turning gear. Check the oil flow from all bearings, spray pipes and When testing fuel valves do not touch the spray holes as the jets
spray nozzles in the crankcase, camshaft drive gear wheel case may pierce the skin.
and thrust bearing. Check for possible leakages from pistons or
piston rods. Beware of high-pressure oil leaks when using hydraulic
equipment, wear protective clothing.
m) Start the engine. After running for about 30 minutes stop and feel
over surfaces for signs of abnormal temperature rise. Especially Arrange indicator cocks with pressure relief holes directed away
feel over the sliding surfaces which caused the overheating. There from personnel, wear goggles when using indicator equipment.
is a possibility that the oil mist is due to atomisation of the
circulating oil, caused by a jet of air/gas, e.g. by combination of Do not weld in the engine room if the crankcase is opened before
the following: Stuffing box leakages (not air tight). Blow-by fully cooled.
through a cracked piston crown or piston rod (with direct
connection to crankcase via the cooling oil outlet pipe). An oil Turning gear must be engaged before working on or inside the
mist could also develop as a result of heat from a scavenge fire engine as the wake from other ships in port or waves at sea may
being transmitted down the piston rod or via the stuffing box. Hot cause the propeller to turn. Also, isolate the starting air supply.
air jets or flames could also have passed through the stuffing box
into the crankcase. Use warning notices at the turning gear starter and other control
stations to warn personnel that people are working on the engine.
AHEAD AHEAD
kg/cm2 ASTERN ASTERN
ERGENC
EM
ALARM INDICATION
Y
SAFETY OTHER SETPOINT
STATE
FUNCTIONS ALARMS LIMITER
SHUTDOWN
NOT
MANUAL
START
REMOTE CHIEF STOP
SLOW INTERLOCK CONTROL RPM
CANCAL-
ABLE DOWN FAILURE LIMIT
Slow
A
CANCEL FUNCTIONS OTHER FUNCTIONS Half H
CANCEL
CANCEL
LAMP COMMIS.
E
CANCEL
SHUT CANCEL
SLOW SLOW VIT
DOWN
SHD DOWN
SLD LIMITATION
SPEED
LOAD
PROGRAM
TURNING LOW NOX TEST LOCK
Full
A
EL.SHAFT
CONTROL LOCATION
D NOR
SEA MANOEUV WARNING EMER CONTROL
MODE MODE GENCY ROOM
BRIDGE
ETU EMERGENCY SYSTEM CONTROL
RESET Engine Telegraph Unit
Max.
TELEGRAPH STATUS Ah.
FULL
NEW
COMMAND
WRONG
WAY
RCS
NOT
READY
A A
S H HALF
BRIDGE
ENGINE
ROOM
BRIDGE
BRIDGE BRIDGE D
WING
ROOM
CONTROL
CONTROL
WING SYSTEM R DEAD
SLOW
LAMP
TEST
SOUND
OFF
INTERNAL
FAILURE
N
CONTROL LOCATION
EMER STOP
NORMAL
GENCY
RESET
SOUND ALARM TELEGRAPH STATUS
OFF ACKN.
NEW DEAD
COMMAND
A SLOW
S
SLOW
R
T
E
REMOTE CONTROL SYSTEM HALF
STATUS WARNING SYSTEM
R
SYST.OP. POW. FAIL LAMP SOUND INTERNAL
N
FULL
I/O SIM. COMMUN. TEST OFF FAILURE
RECEIVE MEMORY
CONTROL
TRANSMIT IN./OUT.
FAILSAFE
The engine room unit has emergency telegraph pushbuttons grouped according Emergency
to AHEAD, ASTERN and STOP commands. The names on the telegraph LED indicator is illuminated to indicate that control of the main engine is from
handle and the pushbuttons are self-explanatory. the emergency operator station in the engine room. It indicates that there is a
direct communication between the bridge unit and the engine room unit.
Direct control of the main engine is achieved via the telegraph handle for Normally commands originate from the bridge unit to the operator station a) In the CONTROL LOCATION section of the sub-telegraph panel,
AHEAD, ASTERN and STOP commands. In this ETS installation, control of (control room or emergency position). Personnel at the operator station unit check that the EMERGENCY pushbutton is illuminated to
the engine is directed from the telegraph handle and each position controls the then acknowledge commands from the bridge unit. indicate the communication link, when selected by a control lever
engine in preset rpm increments, according to which LED indicator is selected, in the control room.
Maximum, Full, Half, Slow or Dead Slow. Alternatively, the telegraph handle A command given from the bridge unit causes the pushbuttons and LED
may be turned 90º and the handle can be moved by any amount thereby giving indicators on the ETS panels at the operator station units in the control room b) At the bridge unit, position the telegraph handle for the engine
greater speed control over the engine and allowing for smoother operation. and the engine room, to illuminate. These correspond with the pushbutton and command.
LED indicator illuminations on the bridge, as follows:
Bridge control is achieved when the BRIDGE indicator is illuminated. c) The LED indicator at the bridge unit and the engine room unit,
Flickering which corresponds with the new command position on the
Control room control is achieved when the CONTROL ROOM indicator is A new command has been received but has not been acknowledged. The bell telegraph, will flicker and a bell will sound in the control room.
illuminated. will also sound until the command is acknowledged.
The ETS will show three telegraph pushbuttons illuminated:
(Note ! When passing control between stations the control must be offered by Steady
the station giving up control and it must be accepted by the station taking over The command has been acknowledged. 1. The last acknowledged command LED indicator on the engine
control. Control cannot just be handed over, it must be accepted.) telegraph has a steady illumination.
Procedure for Communication from the Bridge to the Control Room Unit
The LED indicators in the control room unit and engine room unit illuminate 2. The NEW COMMAND pushbutton has a steady illumination
to correspond to the telegraph handle position in the bridge unit. A short a) In the CONTROL LOCATION section of the sub-telegraph panel, to indicate that a new command is given.
audible signal is given in the control room and engine room for each engine check that the control room pushbutton is illuminated to indicate
order change. All changes and commands are logged on the order printer. the communication link. A pushbutton in the control room selects 3. The new telegraph position LED indicator is flickering.
this.
Procedure for Direct Control from the Bridge or Control Room d) When the command has been carried out, the operator at the
b) At the bridge unit move the telegraph handle to the new engine engine room will press the flickering telegraph pushbutton to
Telephone communications between the two stations should confirm which command position. The LED indicator at the bridge unit and the acknowledge that the new command has been carried out. The
station is to have control. control room unit, which corresponds with the new command telegraph handle will have only the one LED indicator with
position from the telegraph handle of bridge unit, will flicker and steady illumination.
a) Check that the BRIDGE (or CONTROL ROOM) indicator is a bell will sound in the control room.
illuminated, when selected by the pushbutton in the control room. Sub-Telegraph System Controls and Indicators
The ETS panel now shows three illuminated telegraph pushbuttons:
b) At the telegraph handle, check that the telegraph handle is in the Control Location
STOP position and the STOP LED indicator is illuminated. 1. The last acknowledged command LED indicator on the
telegraph handle has a steady illumination. This panel section indicates the communication link between the bridge unit
c) Move the telegraph handle to the desired engine command and an operator station unit. The control location is indicated according to the
position in the AHEAD group or ASTERN group. 2. The NEW COMMAND pushbutton has a steady illumination position selected by the control lever, or other type of control, in the control
to indicate that a new command is given. room. The indicators are:
Communicating Engine Commands to Personnel
Emergency: Engine room operator station unit
3. The LED indicator for the new telegraph handle position is
The ETS may be used as a sub-system of the AutoChief - 4 installation in order flickering. Control Room: Control room operator station unit
to communicate commands between the locations. When this method is used,
Bridge: Control directly from the bridge
the ETS only communicates engine commands between its units and the c) When the command has been carried out, the operator at the
engine personnel/operator, who initiates the engine changes in the control control room will position the telegraph handle to the position
room or the engine room. corresponding to the flickering LED indicator, thereby
acknowledging that the new command has been carried out.
The telegraph handle will have only one LED indication with
steady illumination.
REMOTE CONTROL
10
START A
H 9
E
A 8
0
RUN D
2 1
7 AUX BLOWERS SAFETY SYSTEM
Fuel Rack
3
No 1 No 2 No 3
4
6 Regulating Rod
5
RUN AFT FWD SHUT
OVER
SLOW
6
DOWN DOWN
RUNNING RUNNING SPEED
7
REMOTE ACTIVE ACTIVE
5
8
CONTROL
9
10
4 PRE PRE
SHUT EMERG RESET
Load Indicator SELECT SELECT
DOWN
CANCEL
STOP SAFETY
-LED ACTIVE SYSTEM
3
RUN A
S 2 SHUT EMERG LAMP
T OFF OFF DOWN
CANCEL STOP TEST
E
R 1
START N
0
STOP
REMOTE
CONTROL
ETU EMERGENCY SYSTEM NOR
Connecting Rod Engine Telegraph Unit CONTROL
EMERGENCY REMOTE
SUBTELEGRAPH MODE CONTROL
Detail of Plate TELEGRAPH
STAND
FWE FAOP FULL
BY
A
H HALF
E
A SLOW
D DEAD
SLOW
NOR
ETU EMERGENCY SYSTEM CONTROL
Engine Telegraph Unit
CONTROL LOCATION
FULL STOP
EMER CONTROL
TELEGRAPH STATUS
Stop / Run
Lever (5.07)
NOR
CONTROL
NEW DEAD
COMMAND
A SLOW
S
SLOW
T
E
HALF
SYSTEM
R
LAMP SOUND INTERNAL
N
FULL
TEST OFF FAILURE
The load dependant, variable controlled injection, influences the control of the c) Press the BRIDGE CONTROL pushbutton/LED on the control
valves in the fuel pumps. The maximum firing pressure is kept constant in the room panel. The buzzer will be released on the bridge panel.
upper load range, which provides for reduced fuel consumption.
d) Press the BRIDGE CONTROL pushbutton/LED on the bridge
AutoChief - 4 Control Transfer System panel. The bridge control pushbutton/LED stays lit on the bridge
and the control room panel. Control is transferred to the bridge.
Although control will normally take place from the bridge, there are times
when it is necessary to transfer control from the bridge to the control room or From Control Room to Bridge, Requested by the Control Room
to the local control station.
a) Press the BRIDGE CONTROL pushbutton/LED on the control
From Bridge or Control Room to Local room panel. The bridge pushbutton/LED starts to flash on the
bridge and control room panels and a buzzer sounds on the bridge
This enables the engineers to take control of the engine directly. The actual panel.
action available and the steps to be taken depend upon whether the electronic
governor is still functioning. For details of the procedures see section 5.2. b) Press the BRIDGE CONTROL pushbutton/LED at the bridge
panel. The bridge control pushbutton/LED changes to steady light
From Local to Control Room on the bridge and control room panels. The buzzer is silenced on
the bridge panel. Control is transferred to the bridge.
At the local control station:
From Bridge to Control Room, Direct Take-Over
a) Set the fuel lever (3.12) to the REMOTE position.
a) Press pushbutton/LED ENGINE ROOM CONTROL on the
b) Set local manoeuvring lever (5.03) to the REMOTE CONTROL control room panel. The pushbutton/LED ENGINE ROOM
position. CONTROL is illuminated and control transfers to the control
room. The pushbutton/LED on the bridge starts to flash and a
c) Set the stop lever (5.07) to the RUN position. buzzer sounds.
d) Push the REMOTE CONTROL pushbutton on the local control b) Press pushbutton/LED ENGINE ROOM CONTROL on the
panel. The REMOTE CONTROL pushbutton lamp starts to flash bridge panel. The pushbutton/LED ENGINE ROOM CONTROL
on the local control panel. The ENGINE ROOM CONTROL changes to steady light on the bridge panel. The buzzer is silenced
pushbutton/LED starts to flash in the AutoChief - 4 panel on the on the bridge panel.
engine control room.
1
2
MODE SELECT
RPM COMMAND (RPM)
REGULATOR 1
2
MODE SELECT
FUEL COMMAND (LI pos.)
ACTUATOR
3 RPM MEASURED (RPM) 3 FUEL OUTPUT (LI pos.) CHANGE
4 (GENERAL INFORMATION) 4 SERVO DEVIATION OUTP (LI pos.) LOCK
5 SCAV. AIR PRESSURE (BAR) 5 SERVO DEADBAND (LI pos.)
6 MAN. RPM LIMIT (RPM) 6 (GENERAL INFORMATION) O
7 MAN. FUEL LIMIT (LI pos.) 7 FEEDBACK FAIL P
8 RPM DEADBAND (RPM) 8 IN-DATA ERROR
E
9 OTHER STATUS
N
9 OTHER STATUS
10 OTHER ALARM 10 OTHER ALARM
LAMP LAMP
TEST DOWN UP SAVE DOWN UP TEST DOWN UP SAVE DOWN UP
RESET RESET
1
2
MODE SELECT
RPM COMMAND (RPM)
REGULATOR 1
2
MODE SELECT
FUEL COMMAND (LI pos.)
ACTUATOR
3 RPM MEASURED (RPM) 3 FUEL OUTPUT (LI pos.) CHANGE
4 (GENERAL INFORMATION) 4 SERVO DEVIATION OUTP (LI pos.) LOCK
5 SCAV. AIR PRESSURE (BAR) 5 SERVO DEADBAND (LI pos.)
6 MAN. RPM LIMIT (RPM) 6 (GENERAL INFORMATION) O
7 MAN. FUEL LIMIT (LI pos.) 7 FEEDBACK FAIL P
8 RPM DEADBAND (RPM) 8 IN-DATA ERROR
E
9 OTHER STATUS
N
9 OTHER STATUS
10 OTHER ALARM 10 OTHER ALARM
LAMP LAMP
TEST DOWN UP SAVE DOWN UP TEST DOWN UP SAVE DOWN UP
RESET RESET
07 THRUST BEARING OIL 14 PISTON COOL OIL OUTLET 21 THRUST BEARING LUB. OIL
OUTLET HIGH TEMP HIGH TEMP OUTLET HIGH TEMP
CANCEL CANCELLABLE CANCEL REDUCE RPM CANCEL REDUCE RPM RPM DETECTOR SYSTEMS
FAIL 1 FAIL 2
RESET COMMIS
SHUT DOWN VALVES/ 36 41 42 43 40 41 42 43
35 EM STOP VALVE ACTIVATED ROUGH ROUGH SEA MODE
SOUND ALARM SLOW COMMIS SYSTEM AUTO SYSTEM
SEA OFF ACMM DOWN OFCODE NO.1 NO.2
MODE
CHANGE
STATUS WARNING OP.CODE PARAMETER VALUE LOCK
O
SYSTEM OPERATION INT POWER FAIL
P
I/O SIMULATE COMMUNICATION E
RECEIVE MEMORY N
TRANSMIT INPUT/ OUTPUT
FAILSAFE
HYUNDAI
DOWN UP DOWN UP LOWER RAISE ENTER TEST
CONTROL
SAFETY SYSTEM UNIT
07 THRUST BEARING OIL 14 PISTON COOL OIL OUTLET 21 THRUST BEARING LUB. OIL
OUTLET HIGH TEMP HIGH TEMP OUTLET HIGH TEMP
CANCEL CANCELLABLE CANCEL REDUCE RPM CANCEL REDUCE RPM RPM DETECTOR SYSTEMS
FAIL 1 FAIL 2
RESET COMMIS
SHUT DOWN VALVES/ 36 41 42 43 40 41 42 43
35 EM STOP VALVE ACTIVATED ROUGH ROUGH SEA MODE
SOUND ALARM SLOW COMMIS SYSTEM AUTO SYSTEM
SEA OFF ACMM DOWN OFCODE NO.1 NO.2
MODE
CHANGE
STATUS WARNING OP.CODE PARAMETER VALUE LOCK
O
SYSTEM OPERATION INT POWER FAIL
P
I/O SIMULATE COMMUNICATION E
RECEIVE MEMORY N
TRANSMIT INPUT/ OUTPUT
FAILSAFE
HYUNDAI
DOWN UP DOWN UP LOWER RAISE ENTER TEST
CONTROL
SAFETY SYSTEM UNIT
07 THRUST BEARING OIL 14 PISTON COOL OIL OUTLET 21 THRUST BEARING LUB. OIL
OUTLET HIGH TEMP HIGH TEMP OUTLET HIGH TEMP
CANCEL CANCELLABLE CANCEL REDUCE RPM CANCEL REDUCE RPM RPM DETECTOR SYSTEMS
FAIL 1 FAIL 2
RESET COMMIS
SHUT DOWN VALVES/ 36 41 42 43 40 41 42 43
35 EM STOP VALVE ACTIVATED ROUGH ROUGH SEA MODE
SOUND ALARM SLOW COMMIS SYSTEM AUTO SYSTEM
SEA OFF ACMM DOWN OFCODE NO.1 NO.2
MODE
CHANGE
STATUS WARNING OP.CODE PARAMETER VALUE LOCK
O
SYSTEM OPERATION INT POWER FAIL
P
I/O SIMULATE COMMUNICATION E
RECEIVE MEMORY N
TRANSMIT INPUT/ OUTPUT
FAILSAFE
HYUNDAI
DOWN UP DOWN UP LOWER RAISE ENTER TEST
CONTROL
SAFETY SYSTEM UNIT
Cancellable Slowdown
A cancellable slowdown slows the engine within a specified time of the alarm
condition being detected by the slowdown sensor(s). The usual time delay is 6
seconds but the interval may be adjusted within the range 0 to 255 seconds.
When a cancellable slowdown alarm is detected the following happens.
The alarm LED indicator for the actual alarm starts to flicker
indicating that a slowdown sensor has been activated. Pressing the
cancel button in the specified time delay period will cancel the
slowdown. The horn sounds.
It is possible to cancel the slowdown from the bridge when in the SSU is in
bridge control mode.
Steam Gas
Outlet Outlet
Burner
Manhole
Air
(Front)
Inlet
N.W.L.
Soot Blower Rear (Front)
Roof Header
Roof Wall
Tube
Downcomer
Screen Wall
Tube
Rear Bank Observation Hole
Tube (Side)
Partition
Plate Observation Hole
(Front)
Sootblower
Access Door
(Front)
Gas Outlet
Side Wall Tube Rear (Front)
Wall Tube
Access Door
(Front)
Rear (Front)
Bottom Header
Water Washing
Blow Pipe
Combustion Control Volcano Co. Ltd The boiler structure is rigid enough to withstand rolling, pitching and shock The feedwater pipe enters the steam drum at the rear of the boiler and is
Electronic/Air Operated loading of the ship operating in a seaway. The boiler is supported at the water attached to an internal perforated feed pipe which extends to the front of the
drum and the water wall lower headers, and there are no rigid connections at steam drum. This ensures that there is complete mixing of incoming feed with
Feedwater Regulator ABB Industry KK any other points in order to allow for thermal expansion. the existing boiler water and an equalising of temperatures. The chemical
Electronic/Air Operated feedwater treatment pipe attaches to the internal feedwater pipe and this also
Furnace ensures that there is complete mixing of the chemicals before the water reaches
Remote Water Level Gauge Yamatake the downcomers. The open ended surface blow off internal pipe extends to the
Closely spaced water wall tubes of 76.2mm outside diameter, form the surface of the steam drum to ensure that only floating solids on the water
Drum Level Safety System Yamatake membrane walls at the side, roof, except for burner opening, rear, and front of surface are discharged through this scum blowdown line. The boiler blowdown
Electronic the furnace. This construction is in order to increase the radiant heat absorption connection is fitted to the lower part of the water drum.
in the furnace and to make it strong enough to withstand vibration. The furnace
Oil Burner Volcano Co. Ltd is made completely gas-tight by the welded water wall construction.
Steam Jet Oil Burner
! CAUTION d) Do not blow down the boiler unless the tube failure is so severe Maintaining Boiler in Warm Condition
Do not attempt to cool down the boiler by blowing down or by filling with that personnel could be endangered. When the boiler has cooled,
cold water. the blowdown may be used to empty the boiler. At sea, with one boiler being circulated through the waste heat economiser, the
standby boiler should be maintained in a warm condition by supplying steam
Emergency Operation e) When the boiler has cooled enough, an inspection should be to the heating element in the bottom drum. This is done by closing the heating
carried out to assess the situation and carry out necessary repairs. coil drain valve and opening the inlet and outlet valves. The boiler pressure
Low Water Level should be maintained at 0.5 kg/cm2 or above. When the heating element is not
f) If tube failure is not serious and the water level can readily be in use, the inlet/outlet valves are closed and the drain left open.
A low water level, 140mm or more below the normal working level, will maintained, the boiler can be shut down in the normal manner.
activate the visual and audible alarms (illumination of the alarm lamp on the The forced draft air supply should be maintained to carry away In port with the economiser shut down, the standby boiler is maintained at
control panel and sounding of the alarm buzzer). Should the water level fall to vapours generated by the leaking water and the water level 2kg/cm2 or above by switching the burner on and off. Do not use the bottom
250mm or more below the normal working level, the fuel oil emergency trip maintained during the cooling down period. When boiler pressure drum heater.
valve will close, shutting off fuel from the boiler. The feedwater valve and has fallen to 2 kg/cm2, the steam drum vent valve boiler may be
steam stop valve should be fully closed, the burner shut down completely and opened and the boiler blown down. Dry Lay-up
the forced draught fan stopped after purging the furnace. Never attempt to
supply feedwater to the boiler until the boiler has cooled sufficiently, as there Putting the Boiler Out of Service This should only be undertaken if a wet lay-up cannot be performed.
is a danger of bringing comparatively cold feed into contact with hot surfaces.
When the boiler water level has been restored the boiler may be flashed up When putting a boiler out of service, the wet lay-up method is preferable, as it a) Whilst the boiler remains warm, drain it of all water and ensure
using the normal procedure. requires less preparation and it can be quickly returned to service. These steps that all headers are dry.
are taken if the ship is to be taken out of service for some time and are not part
Flame Failure of normal operational routine. b) Remove the end piece of the waterwall lower header to check that
no water remains.
In case of flame failure, close the oil inlet valve and reduce air pressure to Wet Lay-up
prevent over cooling the furnace. c) Provide some dry heat, electric heaters preferably, in the furnace
When the boiler is in the cooling down process following shutdown, to promote internal drying.
Purge the furnace thoroughly before relighting the burner. Always use the pilot appropriate quantities of boiler chemicals should be injected into the drum
burner for ignition, never attempt to relight the burner from the hot furnace using the boiler chemical injection device. To ensure adequate protection of the d) When the boiler is completely dry, put some quick lime or
refractory. boiler, follow the guidelines given by the chemical supplier. The quantity of calcium chloride in a shallow dish for placement in the drum and
the chemicals required will depend upon the condition of the boiler water and header then close the end plate and manhole doors. Check the
Evaporating Tube Failure a water test should be carried out prior to shutting down. After dosing the moisture absorbent chemicals every week initially and replenish
boiler water should register pH of 12, (alkalinity 300 to 400 ppm) phosphoric as required.
Serious tube failure where water level cannot be maintained. acid about 50 ppm, and sodium sulphite 80 to 100 ppm. The high alkalinity
will ensure adequate protection of the boiler. When returning the boiler to e) Cover the funnel outlet and close the air inlet to the furnace.
a) Shut off the oil supply to the boiler and if the tube failure results service the chemical concentrations should be returned to normal levels and
from low boiler water level, shut off the feed supply, close the this means blowing down the boiler and filling with untreated make-up feed.
feedwater valve and steam stop valve.
a) When the pressure is approaching atmospheric pressure, open the
b) If the tube failure results from a cause other than low water level, steam drum air vent valve.
the fuel supply should be shut off but the feedwater supply should
be maintained in order to assist in the cooling down process. b) When the pressure is off the boiler, supply distilled water until it
When the boiler has cooled sufficiently, close the feed valve and issues from the vent valve, then close the vent valve.
steam stop valve and open the steam drum vent.
c) Put a hydrostatic pressure of 3.5 to 5kg/cm2 on the boiler. Hold
this pressure until the boiler has cooled to ambient temperature.
FO PRESS FO PRESS NO.2 FO FAN RUN NO.2 FO P/P RUN NO.1 FO P/P RUN NO.1 FO FAN RUN IGS MODE FO PRESS FO PRESS
FDF TRIP DRAFT PRESS LOW ATM STM PRESS LOW BLR STM PRESS LOW BLR STM PRESS HIGH BLR STM PRESS HIGH BLR STM PRESS LOW ATM STM PRESS LOW DRAFT PRESS LOW FDF TRIP
LOW-LOW LOW LOW-LOW LOW
WATER LEVEL WATER LEVEL IGS UPTAKE IGS UPTAKE WATER LEVEL WATER LEVEL
WATER LEVEL HIGH WATER LEVEL LOW AC 220V SOURCE AC 220V SOURCE WATER LEVEL LOW WATER LEVEL HIGH
HIGHEST LOWEST V/V OPEN V/V OPEN LOWEST HIGHEST
NO.2 F.O FAN NO.2 F.O PUMP NO.1 F.O PUMP NO.1 F.O FAN
BLR. ON FDF RUN BLR. ON FDF RUN
200 300 30 40 50 30 40 50 200 300
FO TEMP 100 60
0
20 10
0
20 10 100 60 FO TEMP
INTERLOCK INTERLOCK 0
09
00 01
0
01
0
0
09
00 INTERLOCK INTERLOCK
15
15
0
0
START NORMAL ABNORMAL START NORMAL ABNORMAL
PV A A A A PV
SEQUENCE SEQUENCE
FURNACE ATOM. STM. FURNACE ATOM. STM.
PURGE ON V/V OPEN SP SP PURGE ON V/V OPEN
RDY RDY
IGNITION IGNITION EV1 EV2 OT SP1 RDY EV1 EV2 OT SP1 RDY
IGNITION IGNITION
FLAME ON PARA PARA
FLAME ON
YAMATAKE SDC10 YAMATAKE SDC10
OIL V/V BNR. FIRING SPACE SPACE SPACE SPACE OIL V/V BNR. FIRING
OPEN HEATER ON HEATER ON HEATER ON HEATER ON OPEN
EV1 EV2 OT1 OT1 OT1 EV1 EV2 OT1 OT1 OT1
SDC40
YAMATAKE
1.0 1.0
RESET MASTER/ PARA ODE RESET
0.9 1.1 SLAVE 0.9 1.1
GS
7K ODE
MODE
2 3 2 3
1 4 1 4
RINGLEMANN RINGLEMANN
5
5
0
0
SMOKE DENSITY METER SMOKE DENSITY METER
ON ON ON ON BL STOP
SMOKE DENSITY METER SMOKE DENSITY METER
ZERO ADJUST ALARM POINT SOURCE ZERO ADJUST ALARM POINT SOURCE
OFF OFF OFF OFF TEST
BELL LAMP
2 3 ON 2 3 ON
1 4 1 4
OFF OFF
6 5 6 5
ZERO FULL ZERO FULL
In the event of a serious abnormality occurring, which would make it unsafe Burner Control System e) Check that all alarm lamps are out.
for the boiler to continue in operation, the boiler automatic control system The boiler control panel (BCP) operates in a number of functions associated
shuts down the boiler in an emergency mode, by immediately shutting down with the boiler including the boiler management system (BMS), automatic Operating Method
the fuel oil supply to the boiler. combustion control (ACC), and feedwater control (FWC). There are two
boilers and they are controlled on a master/slave basis with one of the boilers There are three burner operating modes, AUTO (Automatic), MAN (Manual)
Control Panels being designated the master by the control system and the other the slave. and HARD MAN (Hard Manual) mode. The burner is usually operated in the
Under normal circumstances the master boiler would operate to supply the AUTO mode and the MAN modes are only used in an emergency when the
ECR Console Remote Indication Panel ship’s steam requirements but if it cannot meet demand the slave boiler is AUTO mode cannot function. The HARD MAN mode allows for reposition-
This indication panel is installed in the engine control room and it mimics the started and comes under the control of the boiler control system. The boilers ing of the burner switches and the MAN mode is for operating on manual.
monitoring systems and main controls found at the boiler and boiler side may also operate in conjunction with the economiser; usually this means that
control panel. the economiser is operating at sea and one of the boilers is selected to act as Selection of Operating Modes
the water supplier and the steam collector for the economiser. The boiler
The ECR console has the following items: would operate if the economiser could not maintain steam pressure for any HARD MAN Mode
reason. When operating in this mode, the operator must always be at the boiler and
Drum level indicator
able to monitor the situation and provide manual intervention at the control.
Steam drum pressure indicator The boiler control system controls the remote, manual and automatic
operations of one single-throat burner which is provided in the roof of the The following interlocks are effective:
Smoke indicator boiler. This unit contains a programmable sequence control, which operates the
furnace purge, pilot burner and the automatic operation of the burner piston Drum water level low-low
Emergency stop switch
valve. This is done by linking up with the boiler protective system and the Flame monitor (pilot burner and main burner)
Burner run lamp ACC. In addition, it transmits the automatic adjustment commands of
Lamp test switch combustion air quantity and fuel oil quantity to the ACC for the start/stop of Operating Procedure
the burner. Combustion control is at the heart of boiler operation because if
Boiler Side Boiler Control Panel anything goes wrong with the boiler, its water supply or the combustion a) Check that the boiler and burner are in operating condition.
This control panel is installed at the boiler side. It contains the system power system, fuel must be shut-off and that will prevent any problem becoming
supply unit, the sequence control for operation of the burner, the automatic more severe. b) Start the fuel oil pump and the forced draught fan in the MAN
boiler controller and various necessary relay units. mode.
There are three boiler operating modes, one is the 18k mode (steam supply at
The following alarms are mounted on the control panel : 18kg/cm2), the second is the 7k mode (steam supply at 7kg/cm2) and the third c) Turn the burner switch from the OFF position to the HARD MAN
is the IGS mode (inert gas system in operation). position.
Electrical AC power source failure
Burner start sequencer inactive In port during cargo discharge the 18k mode would be selected but, at sea only d) Set the fuel pressure controller and the air controller to the MAN
the 7k mode would normally be required with the oil fired boiler installation mode.
Manual trip
providing support for the waste heat economiser. In some cases, intermittent
FD fan trip oil firing on the boiler may be needed to maintain steam pressure and the boiler e) Purge the furnace. To do this the air controller should be manually
control panel would organise that. Selection of 18k mode or 7k mode is operated and the forced draught fan inlet vane should be fully
Pilot pump abnormal opened. The furnace must be purged for at least 3 minutes.
executed by the changeover switch and selection of a particular mode auto-
Drum level low-low matically changes the set point on the pressure indicator control (PIC).
f) Check that the fuel temperature is within the required range.
FO PRESS FO PRESS NO.2 FO FAN RUN NO.2 FO P/P RUN NO.1 FO P/P RUN NO.1 FO FAN RUN IGS MODE FO PRESS FO PRESS
FDF TRIP DRAFT PRESS LOW ATM STM PRESS LOW BLR STM PRESS LOW BLR STM PRESS HIGH BLR STM PRESS HIGH BLR STM PRESS LOW ATM STM PRESS LOW DRAFT PRESS LOW FDF TRIP
LOW-LOW LOW LOW-LOW LOW
WATER LEVEL WATER LEVEL IGS UPTAKE IGS UPTAKE WATER LEVEL WATER LEVEL
WATER LEVEL HIGH WATER LEVEL LOW AC 220V SOURCE AC 220V SOURCE WATER LEVEL LOW WATER LEVEL HIGH
HIGHEST LOWEST V/V OPEN V/V OPEN LOWEST HIGHEST
NO.2 F.O FAN NO.2 F.O PUMP NO.1 F.O PUMP NO.1 F.O FAN
BLR. ON FDF RUN BLR. ON FDF RUN
200 300 30 40 50 30 40 50 200 300
FO TEMP 100 60
0
20 10
0
20 10 100 60 FO TEMP
INTERLOCK INTERLOCK 0
09
00 01
0
01
0
0
09
00 INTERLOCK INTERLOCK
15
15
0
0
START NORMAL ABNORMAL START NORMAL ABNORMAL
PV A A A A PV
SEQUENCE SEQUENCE
FURNACE ATOM. STM. FURNACE ATOM. STM.
PURGE ON V/V OPEN SP SP PURGE ON V/V OPEN
RDY RDY
IGNITION IGNITION EV1 EV2 OT SP1 RDY EV1 EV2 OT SP1 RDY
IGNITION IGNITION
FLAME ON PARA PARA
FLAME ON
YAMATAKE SDC10 YAMATAKE SDC10
OIL V/V BNR. FIRING SPACE SPACE SPACE SPACE OIL V/V BNR. FIRING
OPEN HEATER ON HEATER ON HEATER ON HEATER ON OPEN
EV1 EV2 OT1 OT1 OT1 EV1 EV2 OT1 OT1 OT1
SDC40
YAMATAKE
1.0 1.0
RESET MASTER/ PARA ODE RESET
0.9 1.1 SLAVE 0.9 1.1
GS
7K ODE
MODE
2 3 2 3
1 4 1 4
RINGLEMANN RINGLEMANN
5
5
0
0
SMOKE DENSITY METER SMOKE DENSITY METER
ON ON ON ON BL STOP
SMOKE DENSITY METER SMOKE DENSITY METER
ZERO ADJUST ALARM POINT SOURCE ZERO ADJUST ALARM POINT SOURCE
OFF OFF OFF OFF TEST
BELL LAMP
2 3 ON 2 3 ON
1 4 1 4
OFF OFF
6 5 6 5
ZERO FULL ZERO FULL
h) Open the sub-door for the HARD MAN operating switches. Set d) The purge timer (2P) commences when the burner switch is Automatic Combustion Control
the pilot burner switch to the MANU ON position and ignite the moved to the AUTO position and the time set on this timer is 60 This system automatically regulates the fuel and air supply to the furnace in
pilot burner. If the pilot burner has not ignited after 15 seconds the seconds. After the 60 seconds has elapsed, the forced draught fan order to maintain a preset steam pressure in the boiler. Regulation of the fuel
pilot burner switch should be reset to AUTO and the process inlet vane starts closing gradually to the ignition position. At this supply is accomplished by means of the air operated fuel control valve whilst
started over again from item e) above, ‘Purge the furnace’. point the furnace will have been effectively purged. the air supply is controlled by means of the inlet vane of the forced draught fan.
Fuel supply is automatically cut off in the event of forced draught fan failure
i) With the pilot burner burning correctly the main burner is ignited. e) The pilot burner is ignited 35 seconds after item ‘d’. or due to high or low water level in the boiler drum. The ACC system is
The fuel oil valve switch is set to MANU ON and the main burner electro-pneumatically operated.
should ignite. If the main burner does not ignite after a period of f) When the flame of the pilot burner is detected by the flame eyes,
10 seconds the fuel oil valve switch should be reset to AUTO and the electrical igniter stops sparking. The automatic combustion control (ACC) system employed is of
the procedure started over again from item ‘e’, above ‘Purge the a fuel oil pressure/air pressure measuring type.
furnace’. g) The main fuel oil valve opens 5 seconds after the pilot burner is
ignited. The ACC is held at predetermined ignition position until the
j) With the main burner operating correctly the pilot burner switch burner is ignited.
is reset to AUTO. h) The pilot burner is extinguished 15 seconds after it has been
ignited (item ‘e’). After the burner is ignited the combustion rate is fixed at the
(Note ! When extinguishing the main burner the fuel oil valve switch must be ignition position until the boiler pressure reaches the predeter-
returned to AUTO.) i) The program timer stops at the lock-in position (graduation 85) mined pressure of 5 kg.cm2. This period is called ‘steaming’.
5 seconds after the pilot burner is extinguished.
When burner purging is required, the burner purging switch must be used and When the steaming period is completed, the ACC system goes to
this must be set to MANU ON. j) If there is an ignition failure or a flame failure the burner control AUTO RUNNING and the combustion rate can be adjusted by the
goes into an extinction sequence. system.
Fuel Oil Temperature Bypass
k) The extinction sequence commences when the burner CUT During the steaming period the combustion rate can be changed
The fuel oil temperature by-pass switch is inside the sub-door. In this bypass INTERLOCKS have actuated (following item ‘j’ above) or if the by operating the fuel oil pressure controller in the MANU mode.
mode the starting interlock for fuel oil temperature low alarm is bypassed. It is burner switch is turned from the AUTO to the OFF position.
used when starting the boiler in the cold condition when steam is unavailable The air/fuel ratio can be changed by up to ± 20% by altering the
for heating. When using ‘A’ grade heavy oil, the switch is set to BYPASS. l) The program timer starts from the lock-in position. air ratio dial. This dial would normally be set at the position 1.
AUTO Mode m) The pilot burner is ignited 2 seconds after item l) above. MAN Mode
This is the mode which will normally be used. All operations, including the This mode is selected to allow for manual starting of the boiler in order to see
commands for ignition and extinction, are operated automatically. that all stages are completed correctly. It is used when the boiler would
n) The burner purge valve opens and the burner is purged for about normally be operated automatically as a means of checking the start-up
6 seconds. The burner is purged when the interlock is normal and procedure. The procedure is the same as for HARD MAN start but no switches
a) Set the fuel oil pumps, the forced draught fan and the controllers the pilot burner lights up. behind the HARD MAN sub-door are changed.
to the AUTO mode.
Feedwater Control
o) The post purge period commences and the forced draught fan inlet
b) Turn the burner switch from the OFF to the AUTO position. This controller is of the two element type; both have proportional and integral
vane starts to open to its fully open position when the burner
When stopping this switch must be returned to the OFF position. (P+I) control. It measures the steam flow rate and also the water level in the
completes it purge cycle.
boiler and adjusts the feedwater supply in line with changes in these values.
The following sequence of events must be accomplished for main burner The P+I operation is performed when comparing signals from two separate
p) After the set time (60 seconds) on the post-purge timer is
ignition. systems. One of the signals is generated by the difference between the water
completed, the forced draught fan inlet vane starts closing to the
level set and that detected in the steam drum of the boiler. The other is from
ignition position which takes about 30 seconds.
a) When the burner switch is moved to the AUTO position the comparison between the detected steam flow rate from a steam flow
program timer starts. transmitter and the operating signal to the feedwater control valve. In ECON
q) The forced draught fan stops after 30 minutes.
(economiser) mode the water level change due to the ship’s rolling and
b) After a delay of 5 seconds the forced draught fan starts and the pitching is accounted for by consideration of the moving average level in the
atomising steam valve opens. steam drum.
e) The pressure in the slave boiler needs to exceed 11 kg/cm2 in Inert Gas Topping-up Mode
order for the master/slave configuration to operate. The inert gas system (IGS) topping-up mode is used in order to allow the boiler
to operate on a minimum load so that the IGS may function correctly. A
f) In addition to the master/slave operation it is possible to select the minimum boiler load of 25% is required so that the flue gases will contain no
PARA mode where both boilers can be turned off independently. more than 5% oxygen; the flue gas flow at minimum rate will be 10,300m3/h
In this case the boilers would be operating together each under its at a temperature of 5ºC. The following items will be interlocked, and hence not
own independent control and not as a master/slave pair. operable, in this mode.
Safety and Control System Boiler minimum load is limited to 30% or greater if dumping of steam
Incorporated in the safety and control system are operating functions, or sub- is operating.
systems, which react automatically to a change in condition outside of the pre- The IGS running lamp is illuminated
set range. Failure of most sub-systems produces a visual alarm on the main
control panel and may also produce an audible alarm. In the majority of cases, Bypass of the FO burner auto stop
failure of a sub-system requires manual resetting of the cut-out before the sub- Steam supply valve to soot blowers is interlocked to FULL CLOSE
system can be restarted. This provides protection for personnel on the ship and
for the boiler installation, as the reason for a sub-system failure can involve
more than that particular sub-system.
Steam Header
Drains
Sootblowing has to be carried out at regular intervals to ensure that the heat e) Operate the top sootblower first, followed by the bottom one. The
transfer surfaces are kept clear of deposits, as these retard heat transfer and can top blower should be operated again. The system is then shut
constitute a fire hazard. down and the drain valve opened.
Two sootblowers are fitted to each boiler and should be operated daily when WARNING
boilers are in use, bearing in mind the position of the vessel and any local Do not operate the auxiliary boiler sootblowers during inert gas operations.
legislation concerning pollution and clean air. They should be operated when
leaving port prior to shutting down the boiler. The sootblowers are fitted with Economiser Sootblowers
an air purge connection, the air being supplied from the discharge of the forced
draught fan. This purge or sealing air keeps the nozzles clear during boiler No. of sets : Two (Manual type)
operation and provides a seal at the air sealed wall boxes to prevent the escape Maker : KangRim Industries Ltd
of boiler exhaust gas into the machinery space. Non-return valves prevent Model : KR18
steam from entering the air lines.
Procedure for the Operation of the Economiser Sootblowers
The sootblowers are only to be operated when the available steam pressure
exceeds 8 kg/cm2. An isolating valve, located in the steam line between the Both sets are fitted at the same height within the economiser and are manually
sootblower steam supply valve (T25V) and the sootblower distribution line, operated. The frequency of operation will depend upon the degree of fouling
will only be opened by its associated pressure switch if the steam pressure of the economiser and that depends upon the nature of main engine
exceeds 8 kg/cm2. combustion. If the main engine operates for prolonged periods at reduced
speed there will be increased fouling. Regular inspection of the heating
Before operation, request permission from the bridge and notify the bridge on surfaces through the manholes and inspection doors will give an indication of
completion. the degree of fouling.
Procedure for the Operation of the Auxiliary Boiler Sootblowers a) The air supply for sealing purposes comes from the main engine
scavenge system and so will always be available when the main
a) The boiler should be on a minimum of 50% of full load and the engine operates. Air should always be supplied to the sootblower
forced draught fan operating at a high rate during the sootblowing in order to prevent the escape of main engine exhaust gas, but a
period. The steam pressure must exceed 8 kg/cm2. check should be made to ensure that air is reaching the
sootblower. The sealing air supply should be at a pressure of
b) With the drain open slightly (No.1 boiler valve T29V and No.2 100mmWG above the pressure in the economiser gas ways.
boiler valve T28V), open the steam stop valve (T25V) to the
sootblower header. b) Open the drain on the steam supply line to the sootblowers and
then open the steam valve slightly. When the line is hot, close the
c) When the pipeline is warmed sufficiently, shut the drain valve and drain and open the steam valve fully.
open the stop valve fully.
c) Operate No.1 sootblower by rotating the handle a complete
revolution; this should take about 20 to 25 seconds.
T379V
Drain
PC PI To IG Deck Seal Separator
From Boiler 342V
and Slop Tank Heating T341V 317V
Main Steam Line
T394V 319V
T301V T302V T303V
T345V 318V
18/10kg/cm2
T395V
Air W.B.P.T.
T304V
T391V
PC PI To 7kg/cm2 Steam
Service System
T378V
T305V T306V T307V To Feed Filter Tank
18/7kg/cm2 Heating System
317V 340V
T339V
T308V
324V
To Auxiliary Boiler T332V
Atomising Steam 322V
T331V
No.1
C.O.P.T.
T348V
T392V
T346V T347V T377V
Air
T337V 324V 338V
326V
S
PC 325V
No. 2
C.O.P.T.
Steam Dump Valve
Control
To Steam T350V T349V
PS
Drain System Economiser Steam
Dumping Valve T310V T311V T312V CI
PS
PC Air
T407V
S C.O.P.T.
Condenser 327V 336V
T335V
T397V 329V
TI CI PS
T320V 328V
Key T52V T51V T90V
TI LS LS T398V
No. 3
Steam Atmospheric
C.O.P.T.
T75V Condenser LAH LAH
Exhaust Steam Line
T376V
Control Air
Instrumentation
Electrical Supply
General Description Position Description Valve The procedure described assumes that the economiser unit is initially working.
Closed Steam supply master valve T331V
Saturated steam is led from both auxiliary boilers into a common steam main, a) Ensure that two generator engines are running.
the normal pressure of the steam being 18 kg/cm2. Steam is branched off the Closed Steam supply warming through valve T332V
main line through reducing valves to supply the low pressure service systems b) Slowly open cargo pump steam inlet line warming through valve
Open Main line drain trap inlet T347V
at pressures of 10 kg/cm2 and 7 kg/cm2. One reducing valve unit, complete T332V; this allows steam into the cargo pump lines at a low rate.
with bypass valve, supplies steam to the 10 kg/cm2 and another reducing valve Open Main line drain trap outlet to cascade tank T346V
unit supplies the 7 kg/cm2 system. c) Start a main COPT CSW pump (a pump should already be
Open Cargo pump line drain trap inlet T397V
running to provide cooling sea water to the central cooling system
The main steam line of the medium pressure steam system supplies the three Open Cargo pump line drain trap outlet T398V coolers) and switch it to MANUAL.
cargo oil pump turbines, No.1 water ballast pump turbine and the inert gas
pressure control valve (dump valve). The Inert Gas System (IGS) control valve Closed Cargo pump line drain trap bypass T320V d) Start one of the boiler feedwater pumps and bring the auxiliary
dumps steam to the vacuum condenser to allow the boiler to remain on a Open No.3 cargo pump line drain trap inlet T327V boilers into operation in 7 bar mode.
minimum of 30% load to give an acceptably low oxygen reading in the flue
gas. Excess steam pressure at other times is taken care of by dumping steam to Open No.3 cargo pump line drain trap outlet T328V e) When the auxiliary boiler is providing steam at full demand rate,
the atmospheric condenser. The medium pressure system also supplies the Closed No.3 cargo pump line drain trap bypass T329V stop the economiser feed pump.
sootblowers for the exhaust gas economiser, auxiliary boiler atomising steam
and auxiliary boiler sootblowers. Closed No.3 cargo pump line drain to bilge T336V f) Switch the selected standby boiler feed pump to standby mode.
Open No.2 cargo pump line drain trap inlet T324V
Preparation for Supplying Steam to the Cargo Pump System g) Close the 7 bar steam dump valve T52V to the atmospheric
Open No.2 cargo pump line drain trap outlet T325V condenser.
(Note ! Prior to operating the cargo pump or ballast pump turbines the level of Closed No.2 cargo pump line drain trap bypass T326V
oil in the sumps must be checked and replenished if necessary.) h) Check that the overboard discharge valve S69V and the outlet
Closed No.2 cargo pump line drain to bilge T338V valve S58V from the vacuum condenser are open.
The boilers are on automatic control supplying steam directly at a pressure of Open No.1 cargo pump line drain trap inlet T321V
18 kg/cm2 and, via reducing valves, to the 10 - 7 kg/cm2 steam systems. i) Check that the sea water inlet valve S57V to the vacuum
Open No.1 cargo pump line drain trap outlet T322V condenser is open and that the outlet valve from the central cooler
Closed No.1 cargo pump line drain trap bypass T323V to the main condenser S62V is closed.
T304V Closed No.1 cargo pump line drain to bilge T340V j) Start another main COPT CSW pump (No.2 or No.3 if No.1 is
Closed No.3 cargo pump steam valve T335V already running) and open the crossover valve S26V and close the
crossover valve S28V. This is in order that two main COPT CSW
Closed No.3 cargo pump turbine warming through valve pumps are running, with the pump just started dedicated to the
T302V
Closed No.2 cargo pump steam valve T337V vacuum condenser and the pump which was originally running
T308V
dedicated to the main cooling sea water system. Depending upon
T301V Closed No.2 cargo pump turbine warming through valve conditions, it may be necessary to start the third main COPT CSW
Closed No.1 cargo pump steam valve T339V pump so that there are two pumps supplying the vacuum condenser.
T307V T303V
T305V Closed No.1 cargo pump turbine warming through valve k) Bleed the vacuum condenser of air and ensure that there is a full
Closed No.1 cargo pump exhaust valve T378V sea water flow.
T306V
Closed No.2 cargo pump exhaust valve T377V l) Check that all turbine steam inlet stop valves are closed and open
the exhaust valves from the three COPT turbines and the ballast
Closed No.3 cargo pump exhaust valve T376V
pump turbine.
Open No.1 cargo pump turbine drains
m) Check the oil level in the turbine sumps and then start the turbine
Open No.2 cargo pump turbine drains
LO priming pumps; if all trips have been set the trip cylinder will
18/7 and 18/10kg/cm2 Reducing Valves Open No.3 cargo pump turbine drains now move out.
T379V
Drain
PC PI To IG Deck Seal Separator
From Boiler 342V
and Slop Tank Heating T341V 317V
Main Steam Line
T394V 319V
T301V T302V T303V
T345V 318V
18/10kg/cm2
T395V
Air W.B.P.T.
T304V
T391V
PC PI To 7kg/cm2 Steam
Service System
T378V
T305V T306V T307V To Feed Filter Tank
18/7kg/cm2 Heating System
317V 340V
T339V
T308V
324V
To Auxiliary Boiler T332V
Atomising Steam 322V
T331V
No.1
C.O.P.T.
T348V
T392V
T346V T347V T377V
Air
T337V 324V 338V
326V
S
PC 325V
No. 2
C.O.P.T.
Steam Dump Valve
Control
To Steam T350V T349V
PS
Drain System Economiser Steam
Dumping Valve T310V T311V T312V CI
PS
PC Air
T407V
S C.O.P.T.
Condenser 327V 336V
T335V
T397V 329V
TI CI PS
T320V 328V
Key T52V T51V T90V
TI LS LS T398V
No. 3
Steam Atmospheric
C.O.P.T.
T75V Condenser LAH LAH
Exhaust Steam Line
T376V
Control Air
Instrumentation
Electrical Supply
p) Close warming through valve T332V. ff) To start the turbine, the main stop valve should be opened slowly Inert Gas Steam Control Valve
until the governor takes over at approximately 600 rpm.
q) Open the gland steam valve and check that the pressure is 0.3 to Steam is led directly from the boilers to the inert gas control valve. This valve
0.5 bar. gg) Inform the cargo control room that the cargo/ballast pump is used to dump steam to the vacuum condenser whenever the boiler is
turbines are ready for operation. supplying inert gas to the cargo tanks when there is a low steam demand on the
(Note ! The boiler is still operating in 7 bar mode so the pressure needs to be boiler. Dumping steam increases the steam demand on the boiler, increasing
regulated when changing to 18 bar mode.) hh) If two boilers are required, a second feed pump must be started the boiler load and thereby causing the oxygen reading in the exhaust gas to be
and the switch turned to manual. reduced to an acceptable level. The use of this valve would not normally be
r) Close all turbine and governor drain valves. required in port when cargo pumps are running.
ii) The standby boiler must be started at around 50% on the master
s) Check the level of water in the vacuum pump tank and replenish controller output signal. ! CAUTION
if necessary. Start both vacuum pumps and note the rise in the jj) The master boiler will reach a maximum when the pressure is Whenever warming through steam lines great care must be taken in order
vacuum. approximately 17 bar and the master controller output signal is to avoid damage due to water hammer. It is essential that the drain valve
68%. be open and the drain trap working so that all condensate is drained from
t) Open the IGS dump valve and set the regulator to 19 bar. the system. All lines must be warmed through before the steam inlet valve
kk) The standby boiler will normally be run on manual at the fuel is opened fully.
u) Select the master/slave mode on the boiler control unit and set the controller in order that it can take the steam peak demand.
master boiler to MAN operation with an output signal of 11-12%.
v) Switch the boilers over to 18 bar mode and the boiler pressure will
rise gradually until 18.5 bar is reached when it will cycle off and
T407V
recycle at 15.5 bar. Adjust the gland steam pressure so as to
maintain 0.3 to 0.5 bar.
x) Start one main condenser pump and set the other to standby. Regulating Valve
T311V
y) Crack open the main steam stop valves for the turbines to let them
warm through. T331V
bb) Switch the boiler mode to PARA and set the master controller to
AUTO.
cc) The IGS dump valve will dump steam until there is load on the
turbines. Main Steam Stop to COPT
Steam Dump Regulating Valve with Warming Through Valve
Incinerator Waste Oil Incinerator Waste Oil Generator Engine Main L.O. Accommodation
Service Tank Settling Tank L.O. Setting Tank Setting Tank Fresh Water Heater
F.O. Auto
TC TC TC Heater
TI TI TI TI 137V
Main Engine F.O.
Safety Filter
No. 2 H.F.O. No.1 H.F.O. H.F.O. Sludge No. 2 F.O. No.1 F.O. F.O. Service Line Generator Engine No. 2 Main No.1 Main No. 3 H.F.O. No. 2 H.F.O. No.1 H.F.O. No. 2 Boiler No.1 Boiler
Service Tank Service Tank Setting Tank Tank Heater Heater Steam Tracing L.O. Purifier L.O. Purifier L.O. Purifier Purifier Purifier Purifier F.O. Heater F.O. Heater
Heater Heater Heater Heater Heater Heater
T431V
T178V T208V T278V T300V T173V T432V T200V T144V
T439V T430V
T284V
T165V T277V T145V T183V T187V
T447V T179V T179V T280V T146V
T181V T138V T210V T174V T433V T197V
To Low
T276V T275V T274V T273V T272V
Sea Chest
T428V T175V (Steam Blow)
TI TI TI TI T411V T412V T413V T414V TI T415V T416V T417V T418V T419V T420V
T263V Main Engi
Main Engine Main Engine Jacket
Scavenge Space F.O. Line TC TC TC TC TC Preheater
Fire Steam T198V
Extinguishing Tracing TI TI TI TI TI
To High
Sea Chest
Oily Bilge Oily Bilge Residue Main L.O. Outer H.F.O. Inner H.F.O. H.F.O. Outer H.F.O. Aft H.F.O. Fore H.F.O. T262V
Tank (Dirty) Tank (Clean) Tank Sump Tank Bunker Tank (P) Bunker Tank (P) Overflow Bunker Tank (S) Bunker Tank (S) Bunker Tank (S)
Tank
Auxiliary engine LO settling tank Open 10 kg/cm2 reducing valve inlet valve T301V
Incinerator waste oil service and settling tanks Open 10 kg/cm2 reducing valve outlet valve T303V
Calorifier Closed 10 kg/cm2 reducing valve bypass valve T304V
FW generator Closed Master valve for slop tank heating
18/7 and 18/10kg/cm2 Reducing Valves
Main engine residue tank Closed Master valve for slop tank heating
Auxiliary boiler burner cleaning
Accommodation services
Inert gas uptake valve cleaning
Sea chest clearing
From Air
Service Line
A14V A37V
TI PI PI
W24V W23V
To Central Cooling
Fresh Water T95V T94V
CI CI
System
No. 2 Boiler Water No. 1 DPS Main Engine Exhaust Gas
Circulating Pump
CI 16m3/h CI
T31V T32V
W17V W18V
Key
Feedwater
LT Cooling
Steam Dump
Control Line
407V W.B.P.T. No. 1
C.O.P.T.
No. 1
Vacuum PS
Pump Unit
(80m3/h)
376V
377V
CI
PS PS
No. 2
Cooling LAH
LS No. 2 No. 3
C.O.P.T.
Fresh Water C.O.P.T. C.O.P.T.
Condenser
In/Out LAH
LS
Sealing Water
Cooler
LC TI
Electrical Signal
Illustration 2.3.2a Heating Drains / Contaminated Water System Incinerator Waste Oil Incinerator Waste Oil Generator Engine L.O. Main L.O. Accommodation
Service Tank Service Tank Setting Tank Setting Tank Fresh Water Heater
From Economiser
Sootblowing Steam Drain
From Deck Seal and Calorifier
Slop Tank Heating
To Observation Tank TI TI TI TI
From T60V
T59V
Accommodation
T102V Air Condition
Room
Atmospheric To Observation Tank T258V T256V T254V T252V T260V T182V
Condenser Key
T259V T257V T255V T253V T261V T191V
Condensate
T106V T108V T142V T111V T116V T184V
To Observation
Tank Steam
Generator Engine No. 2 Main No. 1 Main No. 3 H.F.O. No. 2 H.F.O. No. 1 H.F.O.
No. 2 H.F.O. TI No. 1 H.F.O. TI H.F.O. TI Sludge No. 2 F.O. No. 1 F.O. L.O. Purifier L.O. Purifier L.O. Purifier Purifier Purifier Purifier No. 2 Boiler No. 1 Boiler
Service Tank Service Tank Setting Tank Tank Heater Heater Heater Heater Heater Heater Heater Heater F.O. Heater F.O. Heater
F.O
M/E F.O Purifying
Service Steam Steam Trace
Trace Line M/E F.O M/E F.O Line
TI Auto Filter Safety Filter
From
Steam
line T201V T202V T218V T217V
Drain T195V T250V T211V T296V
T426V T209V T212V T241V T244V T243V T249V T248V T247V
T425V T139V T251V T265V T264V T299V T213V T242V T267V T266V T246V T245V T214V
T199V
T140V
T427V T196V T126V T132V T103V T136V T134V T233V T144V T153V T236V T162V T159V
T190V
TI TI TI TI TI TI TI TI TI TI
T237V T238V T239V T240V T438V T437V T269V T270V T149V T156V
T219V T258V T448V T281V T285V T288V T434V
T290V
T220V T271V T450V T283V T129V T292V T297V T298V T263V
T287V T289V T429V
T168V T172V T148V T186V T188V
T421V T176V T449V T282V
T286V T150V T92VT
T167V T171V T147V T185V T189V
T198V T262V
Steam supplied for heating purposes to a heater element or trace heating line Main engine scavenge space fire extinguishing system
gives up maximum heat when it condenses back to water and the aim of any Procedure for Preparing the Drains System for Operation
heating system of this type is to ensure that only condensed steam, condensate,
returns to the atmospheric condenser which, therefore, acts as a drain cooler. a) Ensure that pressure gauges and instrumentation valves are open
All drains outlets from heating lines are fitted with a drain trap which only lets and that the instruments are working correctly.
water pass and so keeps the steam in the heating line until it has condensed.
The drain traps are provided with inlet and outlet valves and also with a bypass b) Set up the valves as in the following table.
valve to allow the heater to remain in operation even if the drain trap becomes
defective. A defective drain trap is indicated by steam returning to the Drains System
atmospheric condenser and the defective drain trap can be traced by the fact
that its return line will be abnormally hot as it will contain steam. If a drain trap Position Description Valve
has to be bypassed, the bypass valve should be throttled so as to restrict the
passage of steam. Closed Atmospheric condenser bypass valve T60V
Open Atmospheric condenser inlet valve T59V
The following services return to the cascade tank through the drains cooler:
Open Cooling water inlet valve S19V
HFO storage, service and settling tanks
Open Cooling water outlet valve S71V
Calorifier
Accommodation fresh water heater c) The various services can now be put into operation as required, by
opening the associated drain trap outlet valve.
Steam tracing
LO sump tank Excessive temperature at the drains cooler would indicate a defective drain
trap. Services should be isolated in turn until the defective trap is located.
Accommodation services
Main engine and auxiliary engine LO settling tanks
Boiler FO heaters
Cargo slop tank heating
Incinerator waste oil tank heating
HFO and LO purifier heaters
Waste oil tank
HFO overflow tank
HFO auto and safety filters
Bilge tanks
T64V T63V
D42V Boiler Water T16V
Sampling
T15V T10V
T66V T65V
PI
Boiler Economiser
Feed Water Feed Water
T1V
Pumps Pumps
LAL LAH
(63m3/h) (4m3/h)
MC MC
T2V Inspection PS PS PS PS PS
Tank LS LS PI PI
PI PI PI
(0.57m3)
T3V 3 2 1 2 1
From Distilled T76V T27V T26V T82V 81V
CI CI CI CI CI
Water Tank T88V T41V
T89V
Feed Filter T78V T7V T6V T9V T8V
TI Tank SAH
TC (14.04m3) SX
MC
From Steam
System T5V
T74V
Key
To Bilge
Holding Tank
T4V Feedwater
Air
Fresh Water Filling Valve Fresh Water Cooling Fresh Water Cooling
Inlet Valve D42V Outlet Valve T10V
a) Check that the cooling water lines from the domestic fresh water d) Open the chemical injection valve on the boiler.
system to the sample coolers are open, inlet valve D42V and
outlet valve T10V. e) Open the pump suction and discharge valves and start the pump.
Once running, adjust the stroke of the pump as necessary to allow
b) Open the sample cooler inlet valve, T15V and outlet valve T16V. the chemicals to enter the boiler over a period of time.
Allow several minutes to pass until the line is drained of any
standing water which may be present from previous use. The f) On completion switch off the pump, close all the valves and drain
sample cooler is a large distance from the boiler and sufficient the tank.
time must be allowed for the old water in the line to clear in order
to ensure that a water sample is taken of the water presently in the
system.
S71V S16V
S17V
3rd Deck
S61V PI TI
S21V S62V
S58V
COPT Fresh Water
Condenser Generator
PI PI (36 Tons/Day)
S69V
TI
B20V
To IG Scrubber TI
S33V
PAL PX
To Deck Seal MC
S26V
S56V S54V From Distilled
B16V B15V
Deck Seal S30V Pump Discharg
Sea Water S10V
1 2 B22V
Pumps 9m3/h S37V
To Fire To Fire S29V S28V S36V S35V
Main Main B23V
S27V Chemical
S55V S53V
S52V S24V S12V S11V Dosing Unit
S32V
PI PI PI
PI PI
Auxiliary Cooling Main COPT Fresh Water
2nd Deck 1 Bilge, Fire 2 Scrubber Water Sea Water 1 Cooling Sea 2 3 Generator Supply
& GS Pumps Pump 310m3/h Pump 400m3/h Water Pumps Pump 75 m3/h
CI CI CI CI
650/1,010m3/h CI
TI
T5V Steam MC 2nd Deck
Blow
TX
B2V B1V S51V S7V S23V S59V S8V S31V
Steam
Blow
Sea Chest T6V
(High) S2V S4V S3V
To Oily Bilge B6V Sea Chest
Pump Emergency (Low)
S72V Bilge Suction S1V
Scrubber Circulating Sea Water Pump The FW generator is supplied by its own dedicated ejector pump which takes Open No.1 central FW cooler outlet valve S16V
No. of sets: 1 suction from the SW suction main. Should the FW generator feed pump fail, a Closed No.2 central FW cooler inlet valve S13V
Capacity: 310m3/h x 5.5 kg/cm2 SW supply can be maintained via a crossover from the Bilge, Fire and GS
Services: IG scrubber system, by means of valve S35V. Closed No.2 central FW cooler outlet valve S15V
Open Central FW cooler manifold outlet valve S62V
Introduction Operation
Closed Auxiliary cooling SW pump crossover valve S26V
Main System Preparation for the operation of the cooling sea water system Closed Auxiliary cooling SW pump crossover valve to IG scrubber S30V
Sea water is circulated through the central cooling system, atmospheric a) Ensure that the suction strainers are clear. Closed Vacuum condenser inlet valve S57V
condenser and the vacuum condenser by one of three main cooling pumps. Closed Vacuum condenser outlet valve S58V
One of the pumps will be selected as the operating pump and another will be b) Ensure that all pressure gauge and instrumentation valves are
set up as the standby pump and will cut in automatically should the operating open and that instruments are functioning correctly. Closed Vacuum condenser overboard discharge valve S69V
pump fail. In port when the cooling requirement is low, the auxiliary cooling Closed Atmospheric condenser inlet valve S19V
SW pump may be used to circulate sea water through the system. Individual c) Set up the valves as shown in the tables below. In this case the low
pumps can be isolated from the system by means of isolating valves and a suction is in use with No.1 central cooler operating. Closed Atmospheric condenser inlet valve S71V
system of cross connections allows the inert gas scrubber SW pump to supply Open Atmospheric condenser bypass valve S17V
the vacuum condenser.
Open Atmospheric condenser overboard discharge valve S21V
S71V S16V
S17V
3rd Deck
S61V PI TI
S21V S62V
S58V
COPT Fresh Water
Condenser Generator
PI PI (36 Tons/Day)
S69V
TI
B20V
To IG Scrubber TI
S33V
PAL PX
To Deck Seal MC
S26V
S56V S54V From Distilled
B16V B15V
Deck Seal S30V Pump Discharg
Sea Water S10V
1 2 B22V
Pumps 9m3/h S37V
To Fire To Fire S29V S28V S36V S35V
Main Main B23V
S27V Chemical
S55V S53V
S52V S24V S12V S11V Dosing Unit
S32V
PI PI PI
PI PI
Auxiliary Cooling Main COPT Fresh Water
2nd Deck 1 Bilge, Fire 2 Scrubber Water Sea Water 1 Cooling Sea 2 3 Generator Supply
& GS Pumps Pump 310m3/h Pump 400m3/h Water Pumps Pump 75 m3/h
CI CI CI CI
650/1,010m3/h CI
TI
T5V Steam MC 2nd Deck
Blow
TX
B2V B1V S51V S7V S23V S59V S8V S31V
Steam
Blow
Sea Chest T6V
(High) S2V S4V S3V
To Oily Bilge B6V Sea Chest
Pump Emergency (Low)
S72V Bilge Suction S1V
a) Ensure that there is flow in the main SW circulating system. a) Vent the atmospheric condenser.
b) Ensure that all pressure gauge and instrumentation valves are Procedure for the Operation of the FW Generator Pumps
open and that instruments are reading correctly.
a) Set up valves as shown in the tables below.
c) Set up the valves as shown in the tables below.
b) Start the FW generator, see section 2.4.3 for operational
d) Set up the cooling water flow to the vacuum pump unit sealing procedure.
water cooler.
Position Description Valve
e) Check the water level in the sealing water tank and top up as
Open FW generator pump suction valve S31V
necessary from the FW hydrant system via valve D309V.
Open FW generator pump discharge valve 32V
f) Start the vacuum pumps.
Closed FW generator SW supply from bilge, fire and GS pump S35V
g) Check that a vacuum is established in the vacuum condenser. Open FW generator inlet valve
Open FW generator outlet valve
Position Description Valve
Open Overboard discharge valve S33V
Vacuum Condenser System
Open Vacuum condenser inlet valve S57V
Open Vacuum condenser outlet valve S58V
Open Vacuum pump overboard discharge valve S69V
To Deck Fire
Wash Main
B73V
B22V B22V
No.1 No.2 PI
PI Bilge/Fire/GS PI Bilge/Fire/GS PI No.3 Main COPT
Pump Pump Cooling Sea
1 2
(350/290 m3/h) (350/290 m3/h) Water Pump
CI CI CI (650/1,010 m3/h)
B23V
B82V B83V 6V
LS LS
B3V
B4V B5V To Sewage To Cooling
B72V S8V
Plant Sea Water
B2V B1V B71V
B77V
To/From Aft Peak Emergency
Tank Bilge
From Stern Suction
Tube Cooling 47V
Tank
7V
Bilge Direct
Suction
8V
Forward Bilge
Forward S2V S4V S3V S1V Well
Bilge Well (Starboard)
(Port)
9V LAH
LS
MC
High
Sea Chest Low
(P) Aft Bilge
Sea Chest
Well
(S)
(Port)
Key
Bilges
Sea Water
Hydraulic Oil
The auxiliary sea water services are supplied by the following pumps:
Maker: Shinko
No. of sets: 2
Model: RVP 200-2MS MVDC self-priming
Capacity: 350/290 m3/h at 30/110 mth
Both Bilge, Fire and GS pumps are permanently set up for foam and fire main
service, with the discharge and suction valves open. In an emergency the
pumps can pump bilges directly overboard from either the bilge main or a
common direct suction in the port bilge well. Both bilge suction valves on each
pump are normally closed. The pump(s) suction and discharge valves are
hydraulically interlocked, so that the suction from the bilges cannot be open at
the same time as the pump(s) discharge to the fire main is open.
Both pumps can provide a back-up for the inert gas scrubber system. The aft
peak tank is filled/emptied via the bilge, fire and GS pumps.
Pump No.1 has a direct bilge suction from the port aft well.
To Deck Fire
Wash Main
B20V B73V
B22V
S11V
LS LS
B84V B85V
No.1 No.2 PI
PI Bilge / Fire / G.S PI Bilge / Fire / G.S PI Cooling Sea
1 Pump 2 Pump Water
(350/290 m3/h) (350/290 m3/h) Pump
CI CI CI (650/1,010 m3/h)
B23V
B82V B83V 6V
Steering Gear
LS LS
Compartment
B3V
To Sewage To Cooling S8V
Plant Sea Water
B2V B72V B4VB B5V S1VS B71V
Bilge Direct Emergency
Suction Bilge
Aft Peak Suction
Tank
7V
Forward
Bilge Well
(P) 8V
B70V
Forward Bilge
S2V S4V Sea Water Cross Connection Main S3V S1V Well
(S)
LAH
9V LS
MC
47V
Stern Tube Key
Cooling Water Tank High Aft Bilge
Sea Chest Well Low
Bilges
(P) (P) Sea Chest
(S)
Sea Water
Hydraulic Oil
The engine room ballast system consists of the after peak tank which is to be a) Start the selected bilge, fire and GS pump. a) Start the selected bilge fire and GS pump.
full during ballast condition.
b) Open the discharge valve B73V slowly until discharge piping is b) Open the discharge valve(s) No.1 pump B16V, or No.2 pump
This tank is used in conjunction with the main ballast system to trim the vessel. pressurised. B15V slowly until discharge piping is pressurised.
It can also be used during certain loaded conditions to provide optimum trim
for efficient operation of the main engine. c) Fill the tank to the required level. c) Empty the aft peak tank, taking care that the pump is not run dry.
The after peak tank is serviced by the two bilge, fire and GS pumps, which can d) Shut the line discharge valve B73V and stop the pump. d) Shut the pump discharge valve and stop the pump.
fill and empty the tank as required.
e) Close all valves. e) Close all valves.
The after peak tank has a filling/suction valve, B70V, which is used during
ballast operations. Deballasting
Procedure for Ballasting/Deballasting the Engine Room Tanks a) All the valves are initially closed.
Ballasting b) Ensure that the transmitters for the remote reading gauges are in
operation.
a) Ensure that all the valves are initially closed.
c) Set up the valves as shown below.
b) Ensure that the transmitters for the remote reading gauges are in
operation. Position Description Valve
c) Set up the valves as shown below. Open Aft peak ballast tank filling/suction valve B70V
Closed No.1 bilge, fire and GS pump sea suction valve B2V
Position Description Valve
or
Open Aft peak ballast tank filling/suction valve B70V
Closed No.2 bilge, fire and GS pump sea suction valve B1V
Open No.1 bilge, fire and GS pump sea suction valve D2V
Open No.1 bilge, fire and GS suction valve B72V
or
or
Open No.2 bilge, fire and GS pump sea suction valve B1V
Open No.2 bilge, fire and GS suction valve B71V
Closed No.1 bilge, fire and GS pump bilge suction valve B4V
Open Overboard discharge B20V
or
Closed Discharge valve to ballast tank B73V
Closed No.2 bilge, fire and GS pump bilge suction valve B3V
Closed No.1 pump discharge valve to OB discharge line B16V
Closed Overboard discharge B20V
or
Open No.1 bilge, fire and GS pump discharge valve B16V
Closed No.2 pump discharge valve to OB discharge line B15V
or
Open No.2 bilge, fire and GS pump discharge valve B15V
Closed Discharge valve to aft peak tank B73V
Fresh Water
Evaporator
Salinity Jacket HT PI 36 ton/day
Panel Cooling Supply
W78V TI
TI
PI SA
FI
W77V
S Distillate Pump
2.1m3/h
W79V
High Salinity PI
Return to Evaporator
Eductor Extraction
Steriliser S32V
(1,500 l/h)
PI
PI S33V
Fresh Water
D13V Generator CI Chemical
Ejector/Feed Dosing Tank
Pump
Mineraliser 73m3/h S31V
(1,500 l/h)
S
Key
Fresh Water
Sea Water Crossover Main Pipeline
Sea Water
HT Cooling
Having reached boiling temperature, which is lower than at atmospheric Condenser Section b) Set the valves as follows:
pressure, the feedwater undergoes a partial evaporation and the mixture of
generated vapour and brine enters the separator vessel, where the brine is Just like the evaporator section, the condenser section consists of a plate heat Position Description Valve
separated from the vapour and is extracted by the combined brine/air ejector. exchanger enclosed in the separator vessel.
Open Ejector pump suction valve S31V
After passing through a demister, the vapour enters every second plate channel Combined Brine/Air Ejector Open Ejector pump discharge valve S32V
in the condenser section.
Closed Crossover valve from bilge, fire and GS pump S35V
The ejector extracts brine and non-condensable gases from the separator
The sea water supplied by the combined cooling/ejector water pump vessel, thus creating and maintaining a vacuum within the evaporator unit. Open Overboard discharge valve S33V
distributes itself into the remaining channels, thus absorbing the heat being
Open Jacket cooling water inlet valve to evaporator W78V
transferred from the condensing vapour. Ejector Pump
Open Jacket cooling water outlet valve from evaporator W79V
The fresh water or distillate produced is extracted by the freshwater or distillate The ejector pump is a single-stage centrifugal pump which supplies the
pump and led to the freshwater tank. The quality of the distillate produced is condenser with sea water and the brine/air eject with jet water as well as Closed Evaporator jacket cooling water bypass valve W77V
continuously monitored by the salinometer and if the salinity rises above a set feedwater for evaporation.
Fresh Water
Evaporator
Salinity Jacket HT PI 36 ton/day
Panel Cooling Supply
W78V TI
TI
PI SA
FI
W77V
S Distillate Pump
2.1m3/h
W79V
High Salinity PI
Return to Evaporator
Eductor Extraction
Steriliser S32V
(1,500 l/h)
PI
PI S33V
Fresh Water
D13V Generator CI Chemical
Ejector/Feed Dosing Tank
Pump
Mineraliser 73m3/h S31V
(1,500 l/h)
S
Key
Fresh Water
Sea Water Crossover Main Pipeline
Sea Water
HT Cooling
e) Start the ejector pump and create a vacuum of at least 90%; this
should be developed in less than 10 minutes.
a) Stop the hot water supply to the unit by closing the evaporator
jacket cooling water inlet and outlet valves and opening the
bypass valve.
56V
PI
Steriliser 13V
(1,500 l/h) To Fresh
Water
Mineraliser Pump
(1,500 l/h)
S
TI Fresh Water
Salinity Evaporator
Panel PI 36 ton/day
From Sea Water
Line
PI SA
FI
From
Distillate Distillate
S Pump Pump
Discharge
High Salinity
Return to Evaporator
Eductor Extraction PI
S33V
Stern Tube
Cooling Key
WaterTank Chemical
(82.79 m3) Fresh Water Dosing Tank
Sea Water
D7V
Fire/Deck Water
The fresh water generator distillate pump discharges through a salinometer and e) Switch on the salinometer. When salinity is satisfactory, the
a flow meter. Positioned before the flow meter is a solenoid valve. This opens discharge will change over to fill the tank.
when the salinometer detects too high a salinity level, diverting the distillate
pump output back to the FW generator. Filling the Fresh Water Tanks
The discharge from the FW generator discharge valve goes to the distilled The same steps as for filling the distilled water tank, except for item ‘b’ which
water tank though inlet valve D73V; this tank has a capacity of 110.48m3. The should be replaced by the following:
distilled water tank supplies water to the boiler feedwater tank via valve D74V
and the tank can be drained to the bilge through valve D80V. The discharge Open the filling valve to the port or starboard fresh water tank, or both tanks.
line from the FW generator also supplies water to the fresh water tanks (port
253.26m3 and starboard 142.78m3), this water flows through a mineraliser unit Open valves to mineraliser unit having ensured that the unit is correctly
and a steriliser unit before entering the tank(s). The tanks are interconnected at charged with chemicals. Ensure that the steriliser bypass valve, D13V, is closed
their outlets and the common outlet pipe supplies fresh water to the stern tube and that the inlet and outlet valves to the steriliser are open. The electrical
cooling water tank. The fresh water tanks also supply water to the domestic power supply to the steriliser must be switched on. Water flow rate through the
fresh water system for the ship, via pumps and a pressurised hydrophore tank. unit is adjusted by means of the flow setting valve and the current flowing to
There is also a connection to the fresh water fire fighting spray system, via the the silver electrodes must be checked to ensure that the release of silver ions is
FW spray pump. Fresh water tanks can also be filled from a shore supply if at the correct level.
necessary. All tanks have level indicating equipment and low level alarms.
LS
LS PI
From Generator Engine
JFW Air Vent Main LAH
W16V Engine PI
W21V MC
Jacket
Cooling PI
Buffer
Auto Float To Central Cooling
Vent Valve LAL
Fresh Water Pump's
W20V MC
W19V
TX PX PS W12V TI
Fresh Water
Generator
W79V
(36 Tons/Day)
W77V TI
W83V W84V
W78V
TI TI
Main
Engine
PI PI
Jacket
Preheater
Main Engine PI No.1 PI
Jacket
Water Cooler TI TI
To Bilge Holding W74V W72V
PS W75V W66V From FW
Tank Hydrophore
Key Main Engine C.F.W Unit
To Cooling W88V D87V
Pump's 262m3/h x 30mth
Feedwater
Drain Tank W76V
HT Cooling Water
PI No.2 PI
PI CI Main Engine Jacket LAL
PI
Fresh Water Cooling Feedwater MC
W73V W71V W90V and Drain Tank
W91V
Electrical Signal S Main Engine HT
Circuit Feed 89V
Instrumentation Pump 0.5m3/h x 75mth
Chemical
Dosing
Air Unit
2.5.1 Main Engine Jacket Cooling Fresh Water System; the High d) Ensure that all main engine individual cylinder inlet and outlet c) Check that the auto float vent valve is operation correctly.
Temperature (HT) Cooling System valves are open.
d) Ensure that the buffer unit is maintaining the correct system
The system has two cooling water pumps rated at 262m3/h with a pressure of e) Ensure that all main engine individual cylinder vent and drain pressure.
30mth. These pumps supply cooling water to the main engine jackets, cylinder valves are closed.
heads and exhaust valves and circulate hot water through the FW generator. e) Supply steam to the preheater via the control valve.
f) Set the valves as shown in the tables below.
The system operates on a closed circuit principle. The pumps discharge f) Slowly bring the jacket temperature up to operating temperature.
through the jacket cooling water preheater, a valve bypassing the preheater is Position Description Valve Observe the engine builder’s instructions regarding the rate of
throttled to ensure a flow through the preheater at all times. The preheater temperature rise. Check the system for leaks as the temperature
Open No.1 JCW pump suction valve W72V
maintains the main engine jacket cooling water temperature when the main rises.
engine is at idle, on low load or when the engine is being warmed through prior Open No.1 JCW pump discharge valve W74V
to starting. g) Supply fresh water cooling to the jacket cooling water cooler
Open No.2 JCW pump suction valve W71V
from the low temperature central cooling system via valves
The FW generator can be bypassed when the main engine is on low load or Open No.2 JCW pump discharge valve W73V W85V and W86V, see section 2.5.2.
idle, but the FW generator extracts heat from the circulating jacket cooling
Open Preheater inlet valve W66V
water thus reducing the load on the coolers. After flowing through the FW h) Test the system for chemical concentration and add chemicals as
generator the jacket water passes through the jacket cooling water cooler, Open Preheater outlet valve W75V required using the chemical dosing unit.
which is in turn cooled by the low temperature (LT) fresh water central cooling
Throttled Preheater bypass valve W76V i) Switch the other jacket cooling water pump to standby.
system. A three-way control valve, actuated by the automatic temperature
controller, regulates the flow through, or bypasses, the jacket cooler depending Open Drain valve to drain tank W88V
on the engine jacket water outlet temperature. j) When the engine is at full power, check the automatic operation
Open FW generator bypass valve W77V of the cooling system and, when satisfied, the steam supply to the
The system is fitted with a buffer tank which provides a positive head to Closed FW generator inlet valve W78V preheater can be isolated and the FW generator brought into
maintain pressure and allow for thermal expansion of the water. The buffer unit operation if required.
Closed FW generator outlet valve W79V
is pressurised by compressed air from the 8kg/cm2 system, a reducing valve
supplying the buffer tanks at a pressure of 4 kg/cm2. Water is supplied to the Open JCW cooler inlet valve W84V The temperature drop in the jacket cooling water across the FW generator
HT cooling fresh water system by a HT circuit feed pump which takes suction depends upon the amount by which the evaporator bypass valve is open.
from the main engine jacket cooling feed water and drain tank. This pump Open JCW cooler outlet valve W83V
operates to maintain the correct quantity of water in the system. An auto float Operational Cooler bypass 3-way valve W12V
vent valve vents air from the system.
Open Buffer unit inlet valve from feed pump W21V
From the engine cooling water manifold branches supply cooling water to each Open Buffer unit outlet valve W20V
cylinder. Isolating valves are fitted to the inlet and outlet mains for each
cylinder to allow units to be individually isolated for maintenance purposes. Closed Buffer unit drain valve W19V
Open Buffer unit outlet valve W20V
The HT cooling system can be drained to a drain tank and can be replenished
using the fresh water transfer pump. Closed System drain valve to bilge holding tank W10V
Closed System drain valve to feed and drain tank W9V
Preparation for the Operation of the Jacket Cooling Water System
Open Air supply valve to buffer unit A93V
a) Operate the main engine HT circuit feed pump to replenish the
system from the drain tank. The drain tank can be replenished Operation
from the hydrophore unit via valve W87V.
a) Check the system level and replenish if required using the ME HT
b) Ensure that all pressure gauge and instrumentation valves are circuit feed pump.
open and that the instruments are reading correctly.
Open No.2 auxiliary engine air and LO cooler outlet valve W175V l) When the engine is at full power, check the automatic operation
Open No.2 auxiliary engine alternator cooler inlet valve W162V of the cooling system and, when satisfied, the steam supply to the
preheater can be isolated and the FW generator brought into
Open No.2 auxiliary engine alternator cooler outlet valve W165V operation if required.
Open No.3 auxiliary engine jacket cooler inlet valve W110V
The temperature drop in the jacket cooling water across the FW generator
Open No.3 auxiliary engine jacket cooler outlet valve W118V depends upon the amount by which the evaporator bypass valve is open.
Open No.3 auxiliary engine air and LO cooler inlet valve W107V
Open No.3 auxiliary engine air and LO cooler outlet valve W176V
Open No.3 auxiliary engine alternator cooler inlet valve W161V
Open No.3 auxiliary engine alternator cooler outlet valve W164V
Open No.1 preheater pump inlet valve
Open No.1 preheater pump outlet valve
Open No.2 preheater pump inlet valve
Open No.2 preheater pump outlet valve
Open Preheater outlet valve
Open No.1 auxiliary engine inlet valve from preheater W123V
Open No.1 auxiliary engine outlet valve to preheater W126V
Open No.2 auxiliary engine inlet valve from preheater W122V
Open No.2 auxiliary engine outlet valve to preheater W125V
Bu
nke
10,000 r Fu 10,000 10,000
elO
il
5,000 5,000 5,000
50 50 50
IF
-3
4 4 0 4
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 1 of 17
F199V
No. 2 No. 1
TI HFO Service HFO Service
F162V Tank Tank
To Topping-Up
Mixing Unit MDO 131.1m3 142.4m3
F210V IG Generator
(85 litre) Service
Tank
To Auxiliary Boiler
F108V
To Generator
PAL MDO Service Pump
PX
MC
F194V
F103V F102V F101V
To FO
Overflow
F120V Tank
Safety DPAH
PI CI
Filter MC
PI PI No.1 F107V
F119V
PI
To HFO F112V
Overflow Tank FI PS F114V
F164V FO Feed Pumps
(7.8m3/h)
F118V FO Auto PI CI
Back Flushing
F163V No.2 F106V
Filter
PC F111V
F113V
To Auxiliary Engine To Oily Bilge Tank
FO Service System TAHL
F211V F165V
MC
PS VC F129V
TX
PI
TI
DPX
TI
No. 1 PI PI
FO Heater
Viscorator F122V
TI
F131V F124V No. 1
PS
F130V FO Booster Pumps
(15.2m3/h)
F127V PI PI
Key
F132V F128V
PI TI
Fuel Oil F121V
F123V No. 2
No. 2
Marine Diesel Oil FO Heater
Steam Tracing TI
Air F126V
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 2 of 17
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 3 of 17
F199V
No. 2 No. 1
TI HFO Service HFO Service
F162V Tank Tank
To Topping-Up
Mixing Unit MDO 131.1m3 142.4m3
F210V IG Generator
(85 litre) Service
Tank
To Auxiliary Boiler
F108V
To Generator
PAL MDO Service Pump
PX
MC
F194V
F103V F102V F101V
To FO
Overflow
F120V Tank
Safety DPAH
PI CI
Filter MC
PI PI No.1 F107V
F119V
PI
To HFO F112V
Overflow Tank FI PS F114V
F164V FO Feed Pumps
(7.8m3/h)
F118V FO Auto PI CI
Back Flushing
F163V No.2 F106V
Filter
PC F111V
F113V
To Auxiliary Engine To Oily Bilge Tank
FO Service System TAHL
F211V F165V
MC
PS VC F129V
TX
PI
TI
DPX
TI
No. 1 PI PI
FO Heater
Viscorator F122V
TI
F131V F124V No. 1
PS
F130V FO Booster Pumps
(15.2m3/h)
F127V PI PI
Key
F132V F128V
PI TI
Fuel Oil F121V
F123V No. 2
No. 2
Marine Diesel Oil FO Heater
Steam Tracing TI
Air F126V
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 4 of 17
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 5 of 17
F199V
No. 2 No. 1
TI HFO Service HFO Service
F162V Tank Tank
To Topping-Up
Mixing Unit MDO 131.1m3 142.4m3
F210V IG Generator
(85 litre) Service
Tank
To Auxiliary Boiler
F108V
To Generator
PAL MDO Service Pump
PX
MC
F194V
F103V F102V F101V
To FO
Overflow
F120V Tank
Safety DPAH
PI CI
Filter MC
PI PI No.1 F107V
F119V
PI
To HFO F112V
Overflow Tank FI PS F114V
F164V FO Feed Pumps
(7.8m3/h)
F118V FO Auto PI CI
Back Flushing
F163V No.2 F106V
Filter
PC F111V
F113V
To Auxiliary Engine To Oily Bilge Tank
FO Service System TAHL
F211V F165V
MC
PS VC F129V
TX
PI
TI
DPX
TI
No. 1 PI PI
FO Heater
Viscorator F122V
TI
F131V F124V No. 1
PS
F130V FO Booster Pumps
(15.2m3/h)
F127V PI PI
Key
F132V F128V
PI TI
Fuel Oil F121V
F123V No. 2
No. 2
Marine Diesel Oil FO Heater
Steam Tracing TI
Air F126V
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 6 of 17
Regarding temperature levels before changeover, see ‘Changeover from HFO h) When the system is at the correct temperature put the FO heater
to DO During Running’. on automatic control.
e) Open the inlet valve to the service tank F104V (for tank No.1).
f) Open the main return valve to the HFO tanks F135V so that the
FO is pumped to the FO service tank. Ensure that there is
sufficient ullage in the service tank.
g) When the heavy fuel oil is replaced by diesel oil, close the above
return valves.
The engine can operate at all times on HFO and it may be stopped with HFO
in the fuel system. During a relatively short duration in port, the fuel system
may remain heated with the fuel circulating. However, under certain circum-
stances, the fuel feed and booster pumps may have been stopped and the fuel
system may have cooled. The fuel system must be brought back to operating
temperature before starting the engine.
a) Ensure that the fuel in the HFO settling tank is at the correct
temperature.
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 7 of 17
F161V F209V
F205V 198V
Generator Engine MDO A
Flushing Pumps PI CI 199V No. 2 No. 1
(1.3m3/h) HFO Service HFO Service
MDO Tank Tank
TI To Topping-Up Service
Compressed 131.1m3 142.4m3
IG Generator Tank
Air Mixing Unit
PI CI
No.1 (85 litre)
To Auxiliary Boiler
PS
F155V F108V
F157V
PI CI
No.2
194V
F156V F154V F103V F102V F101V
FGenerator Engine MDO
Service Pumps
(1.5m3/h) F120V To FO
DPAH Overflow PI CI
MC Tank No.1
PI PI F107V
F119V
PI F112V
LAH
F182V TI LS F176V F114V
FI PS
FO Feed Pumps
(7.8m3/h)
F118V FO Auto PI CI
F179V PIAL F173V Back Flushing No.2
MC PX
Filter F106V
From F111V
No.1 Generator Safety Filter F113V
To Oily Bilge Tank
LAH
F181V TI LS F175V
PI PI
PS VC No.1
F201V F129V
PI F122V
TI
PIAL FI F202V DPX F124V
F178V PX F172V TI
MC PS FO Booster Pumps
No.1
F200V FO Heater (15.2m3/h)
No.2 Generator
Viscorator PI PI
TI No.2
TAHL
F131V
MC F121V
LAH To
LS TX 130V F123V
F180V TI F174V Main Engine
F127V
F132V F128V
Key
PI TI
F177V PIAL F171V
MC PX
Fuel Oil
PC No.2
No.3 Generator FO Heater
F159V Marine Diesel Oil
TI
F211V F165V
Steam Tracing
F126V
Air
To Oily Bilge
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 8 of 17
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 9 of 17
F161V F209V
F205V 198V
Generator Engine MDO A
Flushing Pumps PI CI 199V No. 2 No. 1
(1.3m3/h) HFO Service HFO Service
MDO Tank Tank
TI To Topping-Up Service
Compressed 131.1m3 142.4m3
IG Generator Tank
Air Mixing Unit
PI CI
No.1 (85 litre)
To Auxiliary Boiler
PS
F155V F108V
F157V
PI CI
No.2
194V
F156V F154V F103V F102V F101V
FGenerator Engine MDO
Service Pumps
(1.5m3/h) F120V To FO
DPAH Overflow PI CI
MC Tank No.1
PI PI F107V
F119V
PI F112V
LAH
F182V TI LS F176V F114V
FI PS
FO Feed Pumps
(7.8m3/h)
F118V FO Auto PI CI
F179V PIAL F173V Back Flushing No.2
MC PX
Filter F106V
From F111V
No.1 Generator Safety Filter F113V
To Oily Bilge Tank
LAH
F181V TI LS F175V
PI PI
PS VC No.1
F201V F129V
PI F122V
TI
PIAL FI F202V DPX F124V
F178V PX F172V TI
MC PS FO Booster Pumps
No.1
F200V FO Heater (15.2m3/h)
No.2 Generator
Viscorator PI PI
TI No.2
TAHL
F131V
MC F121V
LAH To
LS TX 130V F123V
F180V TI F174V Main Engine
F127V
F132V F128V
Key
PI TI
F177V PIAL F171V
MC PX
Fuel Oil
PC No.2
No.3 Generator FO Heater
F159V Marine Diesel Oil
TI
F211V F165V
Steam Tracing
F126V
Air
To Oily Bilge
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 10 of 17
j) Continue to raise the temperature manually. If the auxiliary engines are going to operate on DO the procedure must be As already described, the auxiliary engines can be changed over to operate on
modified from step f) and replaced by the following: diesel oil via the separate generator engine MDO service pumps. Although the
k) When the set point is reached on the viscosity controller, change auxiliary engines function well on HFO it is important that all parts of the DO
the operation of the steam control valve to auto and close the ff) Open the auxiliary engine DO inlet valves F176V, F175V and system are maintained in an effective working order so that they will function
bypass valve F132V. F174V. correctly if an emergency arises. The procedure for emergency changeover to
DO from operation on HFO is exactly the same as for changing to DO
l) Open the heater steam inlet valve fully. gg) Close the auxiliary engine HFO inlet valves F173V, F172V and operation under normal circumstances. However, the nature of the emergency
F171V. may dictate that a rapid changeover is needed and the procedure may take
HFO is now circulating through the system. place without the opportunity for flushing through the system. As with all
hh) Open the inlet valves F155V and F154V and outlet valves emergency situations there will be no time to check the procedure in an
m) Close the flushing valve F208V and service tank valve F104V. F157V and F156V on the generator engine MDO service pumps operating manual and so the engineer should learn the required procedure.
and start one of the pumps, putting the other pump on standby.
n) Close the flow meter bypass valves. An air operated generator engine DO flushing pump is provided and this can
ii) When the heavy fuel oil is replaced by diesel oil, open the DO be used for flushing through a generator engine fuel system with DO if
outlet valves from the auxiliary engines, F182V, F181V and required. However, the pump is primarily intended to be used when starting a
F180V and close the HFO outlet valves from the auxiliary generator engine from cold with no electrical power to operate the other
engines, F179V, F178V and F177V. pumps.
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 11 of 17
TX PS TI TX PX S S PX PI
LS LS
F108V F305V F304V F306V
No.1 Boiler
To Incinerator Burner
F263V
PI
F307V PS S
S Pilot
Burner
LS
S
MS
F251V F252V
F264V F278V Viscorator
TI
F280V
No.1 Boiler
VC Atomising Air
FO Heater
PS Atomising Steam S S
TI PI
F268V F279V PS
PC 310V
S
F303V TC
TX PS TI TX PX S S PX PI
PI LS LS
F267V
F265V
TI No.2 Boiler
F269V Burner
F275V No.2 Boiler PI
PI PI FO Heater PS S
S Pilot
FI F277V Burner
F289V TI LS
PI
F276V F290V No. 1 S
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 12 of 17
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 13 of 17
TX PS TI TX PX S S PX PI
LS LS
F108V F305V F304V F306V
No.1 Boiler
To Incinerator Burner
F263V
PI
F307V PS S
S Pilot
Burner
LS
S
MS
F251V F252V
F264V F278V Viscorator
TI
F280V
No.1 Boiler
VC Atomising Air
FO Heater
PS Atomising Steam S S
TI PI
F268V F279V PS
PC 310V
S
F303V TC
TX PS TI TX PX S S PX PI
PI LS LS
F267V
F265V
TI No.2 Boiler
F269V Burner
F275V No.2 Boiler PI
PI PI FO Heater PS S
S Pilot
FI F277V Burner
F289V TI LS
PI
F276V F290V No. 1 S
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 14 of 17
! CAUTION
Trace heating should not be applied to sections of pipeline isolated by
closed valves on the HFO side as damage, such as blown flange joints,
could occur due the expansion of the contents.
! CAUTION
If flame failure occurs, observe the precautions mentioned in 2.2.1.
DO in the fuel lines will be expelled through the boiler burner, at the same time
being replaced by HFO from the settling tank.
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 15 of 17
Incinerator
From Waste Oil
Marine Diesel Settling Tank
Oil Transfer (1.5 m3)
Pump
296V
291V
295V TS TS
Incinerator
Waste Oil LS
Service Tank
Incinerator (1 m3)
Marine Diesel LS 33V
Oil Tank
(0.4 m3)
298V 297V
293V
281V
Flue Gas Fan To Main Boiler 292V
Pilot Burner PI
270V
Pump Supply CI
In an Emergency Mixing
Sludge Pump
Pump
272V 3 75V (30 m3/h)
PI (26 m /h)
273V CI
S S
294V
To 271V
Marine Diesel
Oil Service PI
Tank
Overflow
32V 31V
S
WO
Combustion Burner
Chamber S
From Air
Line
77V
59V
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 16 of 17
The LO transfer pump can discharge to the incinerator waste oil tank. j) Open the incinerator waste oil settling tank run down valve,
B291V and fill the incinerator waste oil service tank.
Procedure for Transferring Waste Oil to the Incinerator Waste Oil Tank
k) Supply steam heating to the incinerator waste oil service tank and
a) Ensure that all valves are closed. trace heating to the waste oil supply lines to the incinerator ready
for incinerator operation.
b) Open the steam supply to the heating coils of the tanks to be
transferred and also the corresponding steam tracing lines. (Note ! The LO transfer pump can be used for pumping oil from the main
engine, generator engine, stern tube, main engine turbocharger, cargo oil pump
c) Set up the following valves as required for the particular tank turbine and water ballast pump turbine sumps to the incinerator waste oil tank.
concerned: the oily bilge tank low suction would be used when Discharge valve L33V and line valve B40V must be open.)
complete draining of the tank was required.
The oily bilge pump may also be used for pumping the contents of bilge wells
Position Description Valve and the bilge holding tank to the incinerator waste oil tank should that be
required. Discharge valve B37V must be open.
Open Sludge tank high suction valve F59V
Open Oily bilge tank high suction valve B80V
Closed Oily bilge tank low suction valve B79V
Issue: 1 2.6 Fuel Oil and Diesel Oil Service Systems Page 17 of 17
MDO Filling
HFO Filling
LAH LI
MC LS LX MC
LI
LI LI
MC LX
TX TIAH
MC MC LX
TX TIAH
MC
LI Outer HFO Inner HFO LI Fore HFO Aft HFO Outer HFO
Bunker Tank (P) Bunker Tank (P) LS LAH
MC Bunker Tank (S) Bunker Tank (S) Bunker Tank (S) LS LAH
MC
TIAH (1855.5m3) (1683.3m3) TIAH (1258.4m3) (1004.3m3) (1855.5m3)
MC TX LI MC TX LI
LX MC LX MC
LAH
MC LS
LI LI
TIAH
F2V F17V F85V MC TX F16V F1V
Key
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 1 of 12
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 2 of 12
MDO Filling
HFO Filling
LAH LI
MC LS LX MC
LI
LI LI
MC LX
TX TIAH
MC MC LX
TX TIAH
MC
LI Outer HFO Inner HFO LI Fore HFO Aft HFO Outer HFO
Bunker Tank (P) Bunker Tank (P) LS LAH
MC Bunker Tank (S) Bunker Tank (S) Bunker Tank (S) LS LAH
MC
TIAH (1855.5m3) (1683.3m3) TIAH (1258.4m3) (1004.3m3) (1855.5m3)
MC TX LI MC TX LI
LX MC LX MC
LAH
MC LS
LI LI
TIAH
F2V F17V F85V MC TX F16V F1V
Key
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 3 of 12
b) Ensure that the blanks on the other bunkering connections are m) Close the valve at the bunkering connection. i) Close all valves at the end of the operation.
secure and that the valves are closed, with drain and sampling
valves closed, also that the drip tray is empty and drain closed. n) Open the vent at the bunkering connection and allow the hose to Under normal operation the transfer pump will remain lined up to the settling
drain back to the supplier. tank and it will start and stop automatically, controlled by the settling tank
c) Open the filling valve(s) on the fuel oil bunker tanks to be filled. level switches.
o) Disconnect the hose connection and replace the blank.
Description Valve To Transfer FO Using the DO Transfer Pump
p) Close the tank filling valves.
Outer HFO bunker tank (port) FO08C a) Open the DO transfer pump suction crossover valve, F13V
q) Collect and label samples and send ashore for laboratory testing. (normally locked shut), and HFO suction valve F4V.
Inner HFO bunker tank (port) FO05C
Fore HFO bunker tank (starboard) FO06C b) Open the DO transfer pump discharge crossover valve F14V
To Transfer FO Using the FO Transfer Pump
(normally locked shut) and HFO discharge valve F5V. Close the
Aft HFO bunker tank (starboard) FO07C
a) At the tank to be transferred from, open the self-closing test cock DO transfer pump discharge valve to the DO service tank, F11V.
Outer HFO bunker tank (starboard) FO09C
to test for the presence of water and close it again when all water
has been drained. c) Open the selected bunker tank suction valve.
d) Open the valve at the selected bunkering connection at the cargo
manifold. d) Open the HFO settling tank inlet valve F7V.
b) Open the suction valve from the bunker tank to be transferred.
Description Valve e) Ensure all DO inlet valves are closed.
Description Valve
Manifold port forward FO01C
HFO overflow tank F3V f) Start the DO transfer pump and follow the previous procedures.
Manifold port aft FO03C
Outer HFO bunker tank (port) F2V
Manifold starboard forward FO02C (Note ! The DO transfer pump will not be started and stopped by the settling
Inner HFO bunker tank (port) F17V tank level switches.)
Manifold starboard aft FO04C
Fore HFO bunker tank (starboard) F85V
e) Establish effective communication between the control room and
Aft HFO bunker tank (starboard) F16V
the bunkering shore station.
Outer HFO bunker tank (starboard) F1V
f) Signal to the shore station to commence bunkering fuel oil at an
agreed slow rate. c) Open the required line valves of the tank to be filled.
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 4 of 12
MDO Filling
HFO Filling
LAH LI
MC LS LX MC
LI
LI LI
MC LX
TX TIAH
MC MC LX
TX TIAH
MC
LI Outer HFO Inner HFO LI Fore HFO Aft HFO Outer HFO
Bunker Tank (P) Bunker Tank (P) LS LAH
MC Bunker Tank (S) Bunker Tank (S) Bunker Tank (S) LS LAH
MC
TIAH (1855.5m3) (1683.3m3) TIAH (1258.4m3) (1004.3m3) (1855.5m3)
MC TX LI MC TX LI
LX MC LX MC
LAH
MC LS
LI LI
TIAH
F2V F17V F85V MC TX F16V F1V
Key
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 5 of 12
d) Establish effective communication between the control room and d) Open the DO transfer pump suction valve, F10V.
The DO service tank overflows to the DO storage tank.
the bunkering barge/shore station.
Diesel Oil System Tanks e) Open the DO transfer pump discharge valve, F11V.
e) Signal to the barge/shore station to commence bunkering diesel
Diesel Oil Tanks oil at an agreed slow rate. f) Start the DO transfer pump.
Compartment Capacities (S.G. 0.85) f) Check the ship to barge/shore connection and pipeline for leaks. g) Check that DO is being correctly transferred, i.e. that it is being
Volume 100% (m3) Weight 98% (Tons) transferred from the required storage tank to the designated
MDO storage tank (port) 147.92 125.73 g) Check that diesel oil is flowing into the required diesel oil storage destination.
MDO storage tank (starboard) 185.44 157.62 tank(s), and not to any other tank.
MDO service tank 54.40 46.24 The transfer pump will stop automatically when the service tank reaches the
Emergency generator MDO tank 1.80 1.53 h) Speed up bunkering to the agreed maximum rate. required level.
Total: 389.56 331.12
i) As the level in the diesel oil storage tank approaches 95%, close h) Alternatively, stop the pump when the required amount of oil has
Outlet valves from all diesel tanks are remotely operated quick-closing valves in the filling valve to top up the tank slowly. been transferred.
with a collapsible bridge which are pneumatically operated from the fire
control station located in the ship’s control centre. After being tripped from the j) Signal to the barge/shore to further reduce the flow rate until the i) Close all valves.
fire control station the valves must be reset locally. The service tank is fitted tank is full and then signal to stop.
with a self-closing test cock to test for the presence of water and to drain any
water present. Tundishes under the self-closing test cock drain any liquid to the k) Close the valve at the bunkering connection.
waste oil tank. All tanks are provided with indication, plus remote level
indication in the control room. The storage tanks also have an overfill alarm set l) Open the vent at the bunkering connection and allow the hose to
at 98 % capacity. drain back to the supplier.
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 6 of 12
MDO Filling
HFO Filling
LAH LI
MC LS LX MC
LI
LI LI
MC LX
TX TIAH
MC MC LX
TX TIAH
MC
LI Outer HFO Inner HFO LI Fore HFO Aft HFO Outer HFO
Bunker Tank (P) Bunker Tank (P) LS LAH
MC Bunker Tank (S) Bunker Tank (S) Bunker Tank (S) LS LAH
MC
TIAH (1855.5m3) (1683.3m3) TIAH (1258.4m3) (1004.3m3) (1855.5m3)
MC TX LI MC TX LI
LX MC LX MC
LAH
MC LS
LI LI
TIAH
F2V F17V F85V MC TX F16V F1V
Key
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 7 of 12
! CAUTION
Ensure that all FO is flushed out of the FO transfer pump prior to using FO Transfer PumpTo
FO Transfer Pump FO Transfer Pump Discharge
it on DO service. This can be achieved by opening the DO suction and Discharge Valve F5V Line to Settling Tank Discharge To Bunker Line
pumping for a few moments with a discharge to the FO tanks open. Before Valve F95V
starting the pump to transfer DO, make absolutely sure that all discharges
to the FO system are securely closed.
DO Transfer
PumpTo Discharge
To Bunker Line
Valve F14V
Crossover
Valve F14V
FO Transfer
Pump
DO Transfer
Pump
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 8 of 12
F35V From
To Incinerator MDO Tank DO
Transfer
F38V Pump
F60V F37V F36V
TC TC TC
F92V
TI PI TI PI TI PI
F90V S S
S
F63V F56V F55V
F53V TI TI
TI
TAHL TAHL
TAHL TX TX
TX F52V F45V
F51V
F66V FI F67V FI FI
PI PI PI
F65V F49V F43V
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 9 of 12
a) Transfer oil to the settling tank using the HFO transfer pump. Closed No.3 purifier bypass valve to settling tank F67V When the HFO has reached the correct temperature and the purifier is at
Closed No.3 purifier bypass valve to DO line F53V operating speed, the automatic control system will change the position of the
b) Check and record the level of oil in all fuel tanks. 3-way recirculating control valve and will allow oil to flow to the purifier.
Closed No.3 heater outlet bypass valve F90V
c) Open the self-closing test cock on the HFO settling tank, closing Open No.1 purifier inlet valve F43V Flow can be regulated by using the purifier inlet valve.
it again when any water has drained.
Open No.1 purifier outlet valve to service tank o) Check the purifier is operating correctly with adequate
d) All valves in the purifier system are to be initially closed. throughput.
Open Filling valve on No.1 HFO settling tank F18V
e) Open the valves, as indicated in the table below, to take suction Closed Filling valve on No.2 HFO settling tank F19V p) Ensure there is no abnormal discharge from the water outlet or
from the HFO settling tank and, using No.1 pump and No.1 sludge discharge.
purifier, discharge to No.1 HFO service tank. If another pump and
purifier are to be used, the relevant valves for that purifier are to The purifier will now operate on a timer, discharging sludge at preset intervals
be opened. or when water is detected in the oil outlet flow.
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 10 of 12
F35V From
To Incinerator MDO Tank DO
Transfer
F38V Pump
F60V F37V F36V
TC TC TC
F92V
TI PI TI PI TI PI
F90V S S
S
F63V F56V F55V
F53V TI TI
TI
TAHL TAHL
TAHL TX TX
TX F52V F45V
F51V
F66V FI F67V FI FI
PI PI PI
F65V F49V F43V
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 11 of 12
d) Apply the brake during the run down period. Closed No.3 purifier bypass valve to HFO line F67V
Open No.3 purifier inlet valve F65A
e) Stop the supply pump.
Open No.3 purifier outlet valve
f) Shut off the water supplies. Open No.3 purifier discharge valve to DO tank filling line F51V
g) Shut all valves. Closed No.3 purifier discharge valve to HFO line F66V
Open DO service tank filling valve F15V
Diesel Oil Purifying System
Diesel oil is pumped by the DO transfer pump from the storage tanks to the DO
service tank and the emergency diesel generator DO tank. Using No.3 purifier,
and No.3 purifier supply pump, the DO can be purified, the oil being taken
from the DO service tank and returned to that tank.
e) Set the valves, as indicated in the table below, to take suction from
the DO service tank and, using No.3 purifier supply pump and
No.3 purifier, return the oil to the DO service tank.
Issue: 1 2.7 Fuel Oil and Diesel Oil Transfer Systems Page 12 of 12
L151V
TI PI
L153V
Main Engine L109V
L152V To Oil Mist Crosshead L107V W96V
Main
Manifold Lubricating Oil Pump
To Oily 1 L.O Cooler
(70 m3/h)
Bilge
Tank W97V
L106V
2 PI TI
L108V
Set
45oC
TC
DPAH
PI MC PI
TAH PAL ESLD
Stuffing Box Drain MC MC DPS
L105V
To Oily Bilge
Tank TAH ESD
MC TX PX PS L113V L112V
Piston Under
Side Drain
To Oily
L145V TX TS Bilge
Tank
PS TX PX PI
Residue Tank L114V
L115V
(1.22m3) ESD TAHI PALI
146V MC MC
Electric Signal
The main engine has four separate lubricating oil systems: The two turbochargers are supplied with lubricating oil from a separate system
which is dedicated to the turbochargers. Oil is forced under pressure to the tur-
Main bearing lubricating oil system bocharger bearings by means of one of the two turbocharger LO pumps. The
Crosshead bearing lubricating oil system pumps take suction from the main engine turbocharger LO sump tank and pass
the oil through a cooler as required in order to maintain the correct temperature
Cylinder oil system at entry to the turbochargers. An automatic bypass valve regulates the oil flow
Turbocharger lubricating oil system to the cooler, the bypass valve being set to maintain a temperature of 50°C at
entry to the turbochargers. A portion of the oil leaving the pump is directed
Main Bearing and Crosshead Bearing Lubricating Oil System through a Glacier filter unit and back to the main engine turbocharger LO
sump tank. The main oil flowing to the turbochargers passes through a fine
The main or crankcase lubrication system is supplied by one of two pumps, filter unit. Outlet oil flow from the turbocharger. is via sight glasses allowing
one of which will be operating and the other on standby and set for automatic the oil to be monitored.
cut-in should there be a lubricating oil pressure reduction or pump failure. The
main LO pumps take their suction from the main engine sump and discharge The turbocharger LO sump tank is replenished with oil from the main engine
oil to the engine via the main LO cooler and the automatic backflush filter. The LO system via valve L25. The turbocharger LO sump tank is emptied via valve
plate type LO cooler is part of the low temperature central cooling system and L24V using the LO transfer pump or the LO purifier pumps (see sections
it is circulated with fresh water from that system. Supply pressure in the main 2.8.3/4).
Main Engine LO Cooler and Filters
lubrication system is 5 kg/cm2 and each pump has a rated capacity of 387m3/h.
The main LO system supplies oil to the main bearings, the camshaft gear drive, Preparation for Operating the Main Engine Lubricating Oil System
cam boxes, vibration dampers and pistons where it acts as a coolant. The
cooling effect of the oil at the vibration dampers is important. Should there be a) Check the level of oil in the main engine sump and top up if
a failure of the higher pressure crosshead bearing supply system the crosshead necessary.
system can be supplied from the main system, but to avoid crosshead bearing Cylinder Lubrication System b) Supply steam to the main engine sump heating coil if necessary.
damage, the engine must be operated at reduced load. Main and crosshead
systems are connected at the engine by a non-return valve and the main system The power dependent lubrication of the pistons, cylinders and exhaust valve c) Ensure that all pressure gauge and instrumentation valves are
will automatically supply the crosshead system in the event of crosshead LO spindles, is performed by a separate cylinder lubrication system. High alkaline open and that the instrumentation is reading correctly.
pump failure. lubricating oil is supplied to the main engine cylinders on a once through basis,
in order to lubricate the piston rings to reduce friction between the rings and d) Ensure that water is flowing in the central cooling system and that
The main engine crosshead LO pumps take their suction from the main liner, to provide a seal between the rings and the liner and to reduce corrosive the LO cooler inlet and outlet valves W96V and W97V are open.
circulating system after the cooler and automatic backflush filter. From the wear by neutralising the acidity of the products of combustion. The alkalinity of
high pressure oil manifold at the engine, each individual crosshead is supplied the cylinder lubricating oil should match the sulphur content of the HFO supplied e) Ensure that the LO cooler LO bypass valve L105V is operating
via a toggle lever pipe system. As with the main lubricating system, one of the to the engine. The amount of cylinder oil supplied to each lubricating point can correctly.
pumps will be operating and the other on standby and set for automatic cut-in be individually adjusted and is also load dependent, the load dependent quantity
should there be a lubricating oil pressure reduction or pump failure. The main adjustment being made by the engine remote control system. The oil is injected f) Set up the valves as shown in the tables below:
engine crosshead LO pumps have a rated capacity of 70m3/h and deliver oil at into the cylinder through non-return valves, the oil being supplied by electrical-
a pressure of 12 kg/cm2. This system supplies oil to the crosshead bearings and ly driven lubricator pumps, each cylinder lubrication pump having its own oil Main Engine LO System
connecting rod bottom end bearings. It also provides oil for the exhaust valve supply box. The supply boxes are replenished with oil from a daily use tank or
actuator pumps and for actuating the reversing servo. cylinder oil measuring tank. The lubricator pump supply boxes are fed under Position Description Valve
gravity from the daily use tank, the oil flowing though a 250 micron filter with a
The oil from both systems drains from the crankcase back to the LO sump. The magnet, which removes any fine abrasive particles from the oil. The daily use Open No.1 LO pump discharge valve L102V
lubricating oil temperature is regulated by means of a three-way control valve, tank is topped up from one of the two cylinder oil storage tanks using the Open No.2 LO pump discharge valve L101V
which regulates the lubricating oil flow through the cooler in order to maintain cylinder oil shifting pump. In the event of failure of the electrically driven
an engine oil supply temperature of 45°C. cylinder oil shifting pump the hand pump may be used. Closed Pump discharge return to sump L103V
Operational LO temperature regulating valve L105V
TAH TAH
From Main LO
Storage Tank
TI TI
TAH TAH
TI
TI
L25V W184V
To Main Engine Turbocharger
Sump LO Cooler
L5V
L7V
Centrifugal LO
Filter
To Stern Tube
Tank Turbocharger LO L160V
Supply Pumps
LT Cooling
No.1 Temperature Inlet
W183V
Control Valve
L155V
L157V
L100V L99V L47V L24V
L154V
L8V
L156V
No.2
LO Transfer LO Purifier
Pump Feed Pump No.1
LO Purifier
Feed Pump No.2
Main Engine
Stern Tube LO Turbocharger LO
Sump Tank Sump Tank 2.64m3
Key
Lubricating Oil
LT Cooling
k) Switch the other crosshead LO pump to standby. Preparation for Operating the Main Engine Turbocharger LO System
l) Check pressures and temperatures throughout the system. a) Check the level of oil in the pumps take suction from the LO
sump tank and replenish as necessary.
Preparation for Operating the Main Engine Cylinder LO System
b) Ensure that pressure gauges and instrument valves are open and
a) Top up the cylinder oil measuring tank by pumping oil from one that instruments are reading correctly
of the cylinder oil storage tanks. Oil may be transferred using the
electrically driven cylinder oil shifting pump or the hand operated c) Open the cooling water inlet and outlet valves on the pumps take
pump. For using the electrical pump valves L138V and L140V suction from the LO cooler and supply cooling water to the cooler
must be open, whilst for the hand pump valves L139V and L141V from the LT central cooling system.
must be open. Note the tank gauge readings for measuring
purposes. d) Set the valves as in the following table:
Valves on the cylinder oil tanks are fitted with quick-closing devices and after Main Engine Turbocharger LO System
operation they must be manually reset locally.
Position Description Valve
b) Set up the valves as in the table below:
Open No.1 main engine turbocharger LO pump
Cylinder LO System suction valve L155V
Open No.1 main engine turbocharger LO pump Turbocharger LO Pumps
Position Description Valve discharge valve L157V
Closed No.1 main engine cylinder oil storage tank outlet valve L150V LO Sump Filling LO Sump Suction to
Open No.2 main engine turbocharger LO pump Valve L25V Purifier Valve L24V
Closed No.2 main engine cylinder oil storage tank outlet valve L116V suction valve L154V
Open Main engine cylinder oil measuring tank outlet valve L118V Open No.2 main engine turbocharger LO pump
discharge valve L156V
Open Cylinder oil line filter inlet valve L151V
LAL
MC
Stern Tube
L.O.
Gravity
Tank (High) LS
(0.17m3)
1m
1m
23.1m L130VL
L129V
17.61m L149V
CI CI
TX TI
L122V L121V
L136V
L132V L134V
L167V
LAL
L135V MC
Stern Tube L.O.
PI CI L137V
Sump Tank
LS (1.35m3) To Oily
L143V L142V Bilge Tank
Stern Tube LO
PI CI Circulation Pump
Key
L165V L164V
Lubricating Oil
If the level in the 20 litre tank falls continuously it is indicative of seal wear or d) Check the vessel’s draught and operate cock L149V to its correct
damage. If the level in that tank rises it is indicative of damage to the foremost position.
seal ring in the after stern tube seal. If there is water in the 20 litre tank the after
two sealing rings of the aft stern tube seal are likely to be damaged. e) Start the stern tube LO pump.
L5V
From No.3
Sump Tank Sludge Tank
L7V (22.54 m3)
LAL
Stern Turbocharger
Tube Main Lubricating Oil MC Key
Lubricating
Oil Tank Sump Tank Oil Sump Tank
(1.35 m3) (56.72 m3) LS (2.64 m3)
To Oily Bilge Lubricating Oil
Tank
Air
L5V
From No.3
Sump Tank Sludge Tank
L7V (22.54 m3)
LAL
Stern Turbocharger
Tube Main Lubricating Oil MC Key
Lubricating
Oil Tank Sump Tank Oil Sump Tank
(1.35 m3) (56.72 m3) LS (2.64 m3)
To Oily Bilge Lubricating Oil
Tank
Air
Description Valve d) Check the purifier gearbox oil level. a) Press the auto stop button on the control panel.
System Suction Valves
e) Check that the strainers are clean. The purifier will commence the shutdown sequence and then stop.
No.1 generator engine suction valve L23V
No.2 generator engine suction valve L22V f) Start the chosen purifier feed pump. Oil will bypass the purifier b) Apply the brake during the run down period.
by means of a three-way valve.
No.3 generator engine suction valve L21V
c) Shut off the steam supply to the heater.
Three-way valve for No.1 and 2 engine sump suctions L83V g) Slowly open the steam supply to the heater to be used.
d) Stop the supply pump.
Three-way valve for No.1, 2 and 3 engine sump suctions L85V
h) Set the temperature control valve to the required temperature.
Generator engine LO purifier pump suction from generator system L94V e) Shut off the water supplies.
i) Lubricating oil will now circulate through the heater to the tank
Generator engine LO settling tank suction valve L79V selected. f) Shut all valves.
(Note ! When taking oil from No.3 generator engine, valve L85V must be set
but when taking oil from generator engines No.1 or No.2, valves L83V and j) Open the domestic fresh water supply to the lubricating oil
L85V must be set.) purifiers.
System Discharge Valves k) Open the flushing and operating water supplies to the purifier to
be used.
Generator engine LO purifier pump discharge valve L92V
Generator engine LO purifier heater outlet valve to three-way valve l) Switch on the control panel of the purifier to be used.
Generator engine LO purifier bypass valve L96V m) Start the purifier to be used.
Generator engine LO purifier discharge valve to generator LO settling tank L90V
n) When the purifier has run up to speed, press the separator control
Generator engine LO purifier discharge valve to generator sumps L67V START button.
Three-way valve for No.1, 2 and 3 engine sump discharge L84V
The purifier will run through the start up sequence, including a sludge
Three-way valve for No.1, 2 engine sump discharge L82V discharge, before going on line.
Discharge valve to No.1 generator sump L20V
Flow can be regulated using the inlet valves, L51V for No.1 purifier, L49V for
Discharge valve to generator No.2 L19V No.2 purifier and L97V for the generator purifier.
Discharge valve to generator No.3 L18V
o) Check that the purifier is operating correctly and that there is
(Note ! When discharging oil to No.3 generator engine, valve L84V must be adequate throughput.
set, but when discharging oil to generator engines No.1 or No.2, valves L82V
and L84V must be set.) p) Ensure that there is no abnormal discharge from the water outlet
or sludge discharge.
Operating the Purifier(s) Generator Engine LO Purifier
The purifier will now operate on a timer, discharging sludge at preset intervals
Both the main and generator engine purifiers are operated in a similar manner. unless water is detected in the oil outlet flow in which case the sludging
Ensure that the correct valves are open in the system chosen to be purified. procedure will take place and the timed sludge cycle will then be resumed.
b) Ensure the purifier brake is off and the purifier is free to rotate.
Sludge Tank
L7V L5V (22.54 m3)
L25V L24V
L8V L6V
Main Engine
Turbocharger LAL
Stern
LO Sump Tube Main Lubricating Oil MC Key
(2.64m3) Oil Tank Sump Tank
(1.35 m3) (56.72 m3) LS
To Oily Bilge Lubricating Oil
Tank
Air
Sludge Tank
L7V L5V (22.54 m3)
L25V L24V
L8V L6V
Main Engine
Turbocharger LAL
Stern
LO Sump Tube Main Lubricating Oil MC Key
(2.64m3) Oil Tank Sump Tank
(1.35 m3) (56.72 m3) LS
To Oily Bilge Lubricating Oil
Tank
Air
All valves should be in the closed position. No.2 generator engine sump inlet valve L70V
No.3 generator engine sump inlet valve L81V
a) Open the following valves depending on the service selected.
b) Ensure that oil is being correctly transferred.
Main Engine System
c) When the required quantity of oil has been transferred, close all
Description Valve valves.
From main engine LO settling tank
d) Check and record the levels in all lubricating oil tanks and record
Main settling tank outlet valve L4V the amount of oil transferred.
Main settling/storage tanks crossover valve L65V
LO Transfer Pumps and Distribution Manifolds
S
(5m3/h) (Port) LAH
LS
MC
B86V Forward
Bilge To From PI Bilge Well
PX
Alarm LO MC (Port)
Incinerator
B81V Waste Oil Tank B40V Pump B5V
Direct Suction
PI LS PI CI LS B4V
B39V B37V B33V 18V
PI
84V 82V B8V
CI CI 16V
PI No.1
72V
Oily Bilge Sludge B88V
Bilge Fire & G.S. Pumps
Pump Pump
Bilge Separator (350/290m3/h)
(5m3/h) (30m3/h) 2V
Pump (5m3/h)
PI PI
75V 1V
B44V LS PI CI LS
17V B8V
From B27V
Fresh Water 85V 83V
15V No.2
Hydrophore Unit B43V B90V B36V B35V B34V B32V B31V
PI
73V 22V 3V
23V
LAH B26V
LS
No.3 main/COPT condenser cooling SW pump also has a direct emergency Discharge from oily bilge pump
bilge suction and so can pump out the engine room bilges. Water discharge from oily water separator when oil
content is above 15ppm.
Oily Bilge Pump
Oily Water Separator
Maker: Allweiler
No.of sets: 1 Maker: Blohm & Voss
Model: Shinko VPS-30 MDV Piston No.of sets: 1
Capacity: 50m3/h at 4 kg/cm2 Model: TurbuloTCS-5-HDS Oily Bilge Water Separator
Capacity: 5m3/h
S
(5m3/h) (Port) LAH
LS
MC
B86V Forward
Bilge To From PI Bilge Well
PX
Alarm LO MC (Port)
Incinerator
B81V Waste Oil Tank B40V Pump B5V
Direct Suction
PI LS PI CI LS B4V
B39V B37V B33V 18V
PI
84V 82V B8V
CI CI 16V
PI No.1
72V
Oily Bilge Sludge B88V
Bilge Fire & G.S. Pumps
Pump Pump
Bilge Separator (350/290m3/h)
(5m3/h) (30m3/h) 2V
Pump (5m3/h)
PI PI
75V 1V
B44V LS PI CI LS
17V B8V
From B27V
Fresh Water 85V 83V
15V No.2
Hydrophore Unit B43V B90V B36V B35V B34V B32V B31V
PI
73V 22V 3V
23V
LAH B26V
LS
Normally bilges should be pumped to the bilge holding tank, then pumped a) Check strainers and strum boxes are clean. a) Supply power to the oily water separator and its control system;
overboard from there via the oily water separator. Pumping directly overboard ensure that the oil in water monitoring equipment and the three-
should only be undertaken if there is a large quantity of clean water in the b) Open one of the following suction valves. way valve are functioning
bilges and there is no risk of contravening any pollution control regulations.
Description Valve b) Open the following valves:
a) Check that the strainers and strum boxes are clean.
Port forward bilge well B8V
Description Valve
b) Open one of the following suction valves. Starboard forward bilge well B7V
Inlet valve to OWS from bilge holding tank B26V
Main engine recess B45V
Description Valve Discharge valve from OWS pump
Engine cofferdam B46V
Port forward bilge well B8V Overboard discharge B42V
Aft bilge well B9V
Starboard forward bilge well B7V
c) Check the oil content monitor by passing fresh water through
Main engine recess B45V c) Open the oily bilge pump suction valve from the bilge main the sensor.
Engine cofferdam B46V B35V.
d) Check the reading and shut off the fresh water supply.
After bilge well B9V d) Open the oily bilge pump discharge to the bilge holding tank
B39V. The clean exit water will be discharged overboard. Oil contamination of
c) Open the bilge fire and GS pump suction valve from the bilge 15ppm or over will automatically recirculate back to the holding tank, through
main B4V, or valve B3V for pump No.2. e) Start the oily bilge pump. a solenoid valve, until the water is clean enough to discharge overboard. Any
oil collected at the top of the OWS will be discharged to the dirty section of
d) Open the bilge fire and GS pump discharge to the overboard f) Before the bilge well in use loses suction, open the valve on the oily bilge tank.
line B16V, or valve B15V for pump No.2. another well and close the one in use.
When taking suction from the bilge holding tank, the OWS discharge pump
e) Open the overboard discharge valve B20V. Bilge pumping should be monitored constantly, as running dry will damage will stop automatically when a pre-determined level is reached.
the pump.
f) Start the bilge fire and GS pump. e) After completion, stop the pump and close all valves.
g) When all wells are dry, stop the pump and close all valves.
If there is an emergency which requires rapid removal of large quantities of
water from the engine room bilge, then the direct or emergency bilge suctions In Port or Coastal Waters
should be used. If the main/COPT condenser circulating pump is used then
the emergency bilge suction valve, B6V, should be opened. If No.1 bilge, fire Any bilges which require pumping when in port, should only be pumped to
and GS pump is used the direct bilge suction valve, B5V, at the pump suction the bilge holding tank using the engine room bilge transfer pump. The contents
main, should be opened. of the bilge holding tank can then be processed when the vessel is in open
water.
(Note ! Bilges should only be pumped directly overboard if it can be
determined that there is no oil in the particular bilge well, otherwise the bilge At Sea
should be pumped to the bilge holding tank and then overboard via the oily
water separator.) The engine room bilges and the contents of the bilge holding tank should only
be pumped overboard through the oily water separator system. Any oil will
Before any bilges are pumped directly overboard, it must be ensured that no then be separated out and discharged to the oily bilge tank and the clean water
local or international anti-pollution regulations will be contravened except will be discharged overboard if below 15ppm. If it is contaminated with oil, it
where safety of the ship or personnel is involved. will be diverted automatically back to the bilge holding tank.
From Fire
Wash Deck Line
Port Starboard
BG 01
BG 07 Upper Deck
Void Space
Chain Locker Chain Locker
Port Starboad
Bosun's Store
Chain Locker
From Fire
Port
Wash Deck Line BG 12
BG 01
BG 03 BG 07 BG 08 BG 09
Bosun's Store
2nd Deck
BG 08 Void Space
BG 02
BG 02
Chain Locker
Starboard BG 03 BG 04
BG 04 BG 12 Fore Peak
BG 09
Key
The cargo stripping pump is normally used to drain the pump room bilges. b) Start the stripping pump. A single bilge eductor, driven by sea water from the fire wash deck line, is
There are two bilge suctions, port aft OP262 and starboard aft OP261. The provided for the drainage of the bosun’s store, chain lockers and forward void
valves are operated manually, with a hydraulic isolating valve, OP263 operated c) Ensure the pump is attended during draining. space. Each suction point is equipped with a suction non-return valve.
from a deck stand unit situated on Upper deck. The suctions are located at:
d) Stop the pump before there is loss of suction.
Procedure for Draining the Pump Room Bilges Using the Cargo Oil Port bosun’s store
Stripping Pump e) Close all valves. Starboard bosun’s store
Set up the valves as in the following table: Centre bosun’s store
Port chain locker
Position Description Valve
Starboard chain locker
Open Port bilge suction OP262
Centre, forward void space
Open Starboard bilge suction OP261
Open Stripping pump discharge to starboard slop tank OD338 Procedure for Operating the Forward Bilge Systems
Open Pump discharge isolator OP276 a) Start the fire pump and pressurise the fire main.
Open Bilge suction isolator OP263
b) Open the overboard discharge valve BG12.
Closed COP filter and pump casing drain suction OP266
c) Open the appropriate eductor suction valves.
Set
33kg/cm2
A76V
A74V
A75V
Oil / Water
A77V Separator
PAL PI To Bilge Well
A3V A2V A1V
No.1
Generator Engine To Generator Engine
MDO Pump PIAL
PS
Main Engine MC
To Air Motor Starting Air
PS TS PI TI TS PI TI TS PI TI
PAL
No.2 W154V W155V W156V
Generator Engine S S S
PS A23V
To Air Motor
TI TI TI
Main Engine Control
and Safety Air
PAL W151V No.3 W152V No.2 W153V No.1
Starting Starting Starting
No.3 PS PS
A57V Air Compressor Air Compressor Air Compressor
Generator Engine (280 m3/h) (280 m3/h) (280 m3/h)
PS
To Air Motor
PAL PAL
MC MC Key
A24V Air
LT Cooling Water
Open No.2 reservoir inlet valve Closed No 2 reservoir air whistle outlet valve
Starting air is supplied from the reservoirs to the main engine and to the
generator engines through separate lines from the reservoirs. The main Open No.1 reservoir outlet valve to generator engine and main engine f) Ensure that the compressor cooling water is supplied from the low
reservoirs can supply the auxiliary engine starting air reservoir or they can control system temperature cooling water system.
supply air to the generator engines directly.
Closed No.2 reservoir outlet valve to generator engine and main engine g) Set one air compressor to auto. The compressor will cut-in and
control system cut-out depending upon the air pressure in the main air reservoir
No.3 main air compressor is fed from the emergency switchboard and under
dead ship conditions supplies the auxiliary air reservoir in order to start the Open No.1 reservoir outlet to main engine being filled. The unloader gear will operate, thus allowing the
generator engines. compressor to start and stop off load.
Closed No.2 reservoir outlet to main engine
The main compressors are cooled by the low temperature central cooling water Open Supply to generator engines air start line A155V h) Drain any liquid from the reservoirs and oily water separators.
system.
Open No.1 generator air master valve i) Check the operation of the automatic drain traps.
Switches at the local starter panel enable the compressors to be manually Open No.2 generator air master valve
started and stopped if required. j) Set the other main air compressor(s) to standby.
Open No.3 generator air master valve
The control air and general service air systems can be supplied from the main Closed Auxiliary air receiver outlet valve Under normal operating conditions only one reservoir would be in use.
air reservoirs through a reducing valve. A separate control air reservoir,
maximum pressure 8 kg/cm2, is supplied by two control air compressors . Closed Auxiliary air receiver inlet valve In emergency conditions, No.3 main compressor can be set to supply the
Open No.1 compressor low temp. cooling FW inlet valve A153V auxiliary air reservoir, which is then used to start the generators. This is
achieved by closing all the air inlet valves on the main receivers and the main
Open No.1 compressor low temp. cooling FW outlet valve A156V outlet valve to the generator engines, then opening the auxiliary air reservoir
filling valve from No.3 main air compressor.
To Safe Position
To Main Engine Cooling Buffer Unit
Outside Engine
PI
Casing Set
33kg/cm2 To Accommodation
No.1 A45V
To Workshop
Starting
PI Set
Air Reservoir A46V
A30V A79V (13.7m3) 8.3kg/cm2 To Deck Service
A42V A47V
PS PS PS
A44V To CO2 Room
A13V A26V
To Emergency Diesel Generator Room
To Econo. Soot
Release Unit A52V
Oily Water To 2nd Deck (Starboard)
Oily Water A14V
Separator
Separator A53V
Separately To Economiser Gas Seal Line
Led To A3V
Bilge Water To Boiler Atomising
A2V
A1V To Casing
Main Engine Main Engine
Control/Safety Air Starting A54V
System and Line TS PI TS PI TS PI A55V
Air Spring Make-Up To Main Engine Exhaust
Valve Grinding
Machine To Incinerator Purge Airline
S S S
No.3 No.2 No.1 A33V
Starting Starting Starting To Steering Gear Room
To Boiler Smoke
Air Comp. Air Comp. Air Comp. A56V
Indicator
(280 m3/h) (280 m3/h) (280 m3/h) To Main Engine Cooling Washing Plant
A15V
A58V
TI TI TI TI TI TI To Floor (Starboard)
Air A11V
To Diesel Generator Room (Starboard)
a) Ensure that all instrumentation valves are open. Open 3rd deck air supply (starboard) A59V
Open Engine room floor air supply (port) A50V
b) Check the oil level in the compressors.
Open Engine room floor air supply (starboard) A58V
c) Set up valves as shown in the table below: Open Steering gear room air supply A56V
Oil discharge monitoring equipment Control Air System Open Boiler FO unit A135V
Main engine safety air system Open Boiler FO pressure control valve A136V
Position Description Valve
Main engine control air system Open Economiser steam dump valve A142V
Open Outlet valve from No.1 control air compressor A163V
Main engine auto backflushing LO filters Open Oily bilge separator A123V
Open Outlet valve from No.2 control air compressor A164V
Main engine auto backflushing FO filters Open Feed filter tank temperature control valve A61V
Open Inlet valve to control air reservoir
Generator engine control systems Closed Line drain A153V
Open Outlet valve from control air reservoir
COPT condenser control Open Air filter/dryer inlet valve A111V A single valve off the air line is in the purifier room.
Economiser steam dump valve Open Air filter/dryer outlet valve A112V Open PRV generator engine MDO pump A18V
Oily bilge separator Closed Bypass valve for air dryers A113V
The control air line is accessed by valve A117V. The manifold is located in the
Sludge tank temperature control Closed Air supply valve from general service air system A167V purifier room.
Feed filter tank temperature control Open Master valve for pump room control systems A25V
Position Description Valve
18/10 kg/cm2 steam pressure reducing valve Open Master valve to inert gas generator system A16V
Open HO purifier unit 133V
18/7 kg/cm2 steam pressure reducing valve Open Master valve to draught gauge system A51V
Open Sludge tank temperature control valve 137V
Central cooling system Open Master valve to main engine controls A115V
Closed Line drain
Boiler control systems
Boiler FD fan control
Open Main engine LO discharge filter A121V Open Machinery alarm horn 2nd deck A67V Position Description Valve
Open Main engine LO temperature control valve A122V Open IS telephone alarm horn 2nd deck A29V Open Crossover valve from general service air system A167V
Open Air purge tank IG unit A143V Closed Air manifold drain A64V Close Outlet valve from control air reservoir
Open Main engine jacket cooling fresh water TCV A124V It is presumed that the general service air system has been set up to operate as
d) Start one of the control air compressors and check its automatic
in section 2.10.2
Open Central cooling FW temperature control valve A125V operation.
Open COPT condenser level control valve A144V Emergency Shut-off Valves
e) Fill the control air reservoir.
Closed Spare A62V
The emergency shut-off valves have their own dedicated air bottle and this is
f) Blow down the inlet to the control systems on a regular basis to
Open Oil discharge monitoring system A60V supplied from the general air system main via valve A44V. ( See section 4.3)
check the efficiency of the air dryer.
Closed Line drain A151V
Alarm air line located in the starboard generator engine room; no master
valve.
Valve A Valve B
Valve C Valve D
Unloading Unloading
Device Device
H1V H2V
Torque Torque
Motor Motor
Valve A Valve B
Valve C Valve D
Unloading Unloading
Device Device
H1V H2V
Torque Torque
Motor Motor
1. Oil level in No.1 tank goes down to the LOW position and the
audible and visual alarms are given on the navigating bridge and
in the engine room.
Local Instrument
Panel
Local Control
Panel
The engine is normally started by means of an electric starter motor. Power to a) Ensure that the MANUAL/AUTO switch is set to MANUAL.
the motor is supplied by batteries, which are on constant charge while the ship This will allow the engine to start only in the manual mode.
is in service. A hydraulic starter is also fitted, hydraulic power being manually
generated by a hand pump. An accumulator, which is charged by a hand pump, b) Check the level of oil in the engine sump and top up as necessary
drives a hydraulic motor connected to the flywheel and the stored energy is with the correct grade of oil.
released to start the engine. This system can be utilised when starting the
engine from the dead ship condition. The engine can be manually started c) Check the level of water in the radiator and top up as necessary
locally using either the electric or hydraulic starter motor, but when switched with clean distilled water.
to automatic operation, only the electric starter motor is utilised.
Emergency Switchboard
b) Check the level of oil in the hydraulic starter reservoir and top up
if necessary with the correct grade of oil.
g) Check that the engine is firing smoothly and check the operating
systems of the engine.
h) To stop the engine, turn the operation switch to the OFF position.
i) When the engine has stopped, switch the heater on and turn the
switch to REMOTE operation. Restore the engine to automatic
standby.
(Note ! Long periods of idling will result in poor combustion and build up of
carbon deposits.)
AC 220V No.2 Group No.2 AC 440V No.3 D.G. No.2 D.G. Synchronising Bus Tie No.1 D.G. No.1 AC 440V No.1 Group
Feeder Panel Starter Panel Feeder Panel Panel Panel Panel Breaker Panel Feeder Panel Starter Panel
LD
L M M M M
440/220V
Emergency 440/220V
24V Battery Transformer
24V System Main Board/
Main 440V Feed Emergency Board
Interconnector
Emergency
Switchboard
Key
Emergency Group Main Bd Emergency Generator 440V 230V
24V Battery Charge and Starter Panel Interconnector Panel Feeder Panel Feeder Panel
M Motor Discharge Board
Transformer
LD
M DG
440V Load: Group Starter L
and Distribution Boards
24V Services Emergency
LD Generator
Lighting and Small Power 24V System
L Emergency 440V Feed
AC 220V No.2 Group No.2 AC 440V No.3 D.G. No.2 D.G. Synchronising Bus Tie No.1 D.G. No.1 AC 440V No.1 Group
Feeder Panel Starter Panel Feeder Panel Panel Panel Panel Breaker Panel Feeder Panel Starter Panel
LD
L M M M M
440/220V
Emergency 440/220V
24V Battery Transformer
24V System Main Board/
Main 440V Feed Emergency Board
Interconnector
Emergency
Switchboard
Key
Emergency Group Main Bd Emergency Generator 440V 230V
24V Battery Charge and Starter Panel Interconnector Panel Feeder Panel Feeder Panel
M Motor Discharge Board
Transformer
LD
M DG
440V Load: Group Starter L
and Distribution Boards
24V Services Emergency
LD Generator
Lighting and Small Power 24V System
L Emergency 440V Feed
The 440V motors are in general of the squirrel cage induction type with a
standard frame designed for AC 440V three phase 60Hz. The exceptions are
the motors for domestic service and small capacity motors of 0.4kW or less.
Where continuously rated motors are used, the overload setting ensures the
motor trips at 100% of its full load current. The motors in the engine room are
of the totally enclosed fan cooled type.
Standby motors will start when no voltage is detected on the in-service motor
or when the process pressure is low. See section 2.13.7.
The starters are generally constructed in group control panels and power dis-
tribution panels. The drawings for the starter circuit are enclosed in a vinyl
envelope and kept in a pocket inside each starter panel.
Large motor starters are arranged in group starter panels located at the ends of
the main switchboard, with duplicated equipment starters split between each of
the main switchboard group starter panels. Interlocked door isolators are
provided for all starters. For group starter boards (LGSP), this switch is the
moulded case circuit breaker which functions as both disconnecting means and
overcurrent protection of the motor circuit.
Sequential Restarting
Essential service motors, which were in service before the blackout, are started
automatically on recovery of the main bus voltage. These motors are classified
into groups (consistent with voltage dip and overcurrent) to the generator and
will start according to the predetermined restarting sequence. Motors that were
selected for duty before the blackout are automatically returned to duty after
the blackout. Similarly, motors selected for standby are automatically returned
to standby.
Preference Tripping
VS FS SY
MS ES LVS CBO PAL CBC RCL
kWH
VI FI
G G G A V
SYL
GSP
FSS SSS HM PF
EC
PF1 PF2
kW kW kW
AO AC AO AC AO AC LT AR
I
HL
O
ESS ES
GEN STATUS GEN FAIL GEN STATUS GEN FAIL GEN STATUS GEN FAIL
Main Switchboard Synchronising Panel STOPPED START FAIL STOPPED START FAIL STOPPED START FAIL
RUNNING SYNC FAIL RUNNING SYNC FAIL RUNNING SYNC FAIL HS AS VS
STARTING SHUT DOWN STARTING SHUT DOWN STARTING SHUT DOWN
VI: Incoming Voltmeter STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP
READY ACB NON CLOSE READY ACB NON CLOSE READY ACB NON CLOSE
FI: Incoming Frequency Meter BLOCK BLOCK BLOCK
OUTPUTS OUTPUTS OUTPUTS
VS: System Voltmeter
START GOV RAISE START GOV RAISE START GOV RAISE
FS: System Frequency Meter STOP GOV LOWER STOP GOV LOWER STOP GOV LOWER Main Switchboard Generator Control Panel
SYNCHRO SYNCHRO SYNCHRO
MS: Main Switchboard Source Monitor Lamp ACB OPEN ACB OPEN ACB OPEN
ES: Emer. Switchboard Source Monitor Lamp AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
STOP START /KW STOP START /KW STOP START /KW RCL: Remote Control Available Lamp
LVS: Low Voltage (24V) Source Monitor Lamp
CONTROL MODE
TOTAL USED POWER
PAL: Power Available Lamp
kW: Kilowatt Meter SYNCHRONISING MAN AUTO
AVAILABLE POWER
GSP: Generator Status Panel LOAD SHARING MAN AUTO CBO: Circuit Breaker Open Lamp
LOAD DEPENDENT START MAN AUTO CBC: Circuit Breaker Closed Lamp
PF1: Preference Trip stage 1 Lamp
LOAD DEPENDENT STOP MAN AUTO WATCHDOG
PF2: Preference Trip stage 2 Lamp OL: Overcurrent Trip Lamp
EGS: Emergency Generator on Standby Lamp RL: Reverse Power Trip Lamp
EGR: Emergency Generator Running Lamp Main Switchboard Generator Status Panel ES: Engine Start Switch
LT: Lamp Test Switch
ESS: Engine Stop Switch
AR: Alarm Reset Switch
HL: Heater ON Lamp
GCM: Generator Control Mode Switch
HS: Heater ON/OFF Switch
SGS: Standby Generator Selection Switch
GRL: Governor Raise/Lower Switch VS: Voltmeter L1/L2/L3 Select Switch
VS FS SY
MS ES LVS CBO PAL CBC RCL
kWH
VI FI
G G G A V
SYL
GSP
FSS SSS HM PF
EC
PF1 PF2
kW kW kW
AO AC AO AC AO AC LT AR
I
HL
O
ESS ES
GEN STATUS GEN FAIL GEN STATUS GEN FAIL GEN STATUS GEN FAIL
Main Switchboard Synchronising Panel STOPPED START FAIL STOPPED START FAIL STOPPED START FAIL
RUNNING SYNC FAIL RUNNING SYNC FAIL RUNNING SYNC FAIL HS AS VS
STARTING SHUT DOWN STARTING SHUT DOWN STARTING SHUT DOWN
VI: Incoming Voltmeter STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP
READY ACB NON CLOSE READY ACB NON CLOSE READY ACB NON CLOSE
FI: Incoming Frequency Meter BLOCK BLOCK BLOCK
OUTPUTS OUTPUTS OUTPUTS
VS: System Voltmeter
START GOV RAISE START GOV RAISE START GOV RAISE
FS: System Frequency Meter STOP GOV LOWER STOP GOV LOWER STOP GOV LOWER Main Switchboard Generator Control Panel
SYNCHRO SYNCHRO SYNCHRO
MS: Main Switchboard Source Monitor Lamp ACB OPEN ACB OPEN ACB OPEN
ES: Emer. Switchboard Source Monitor Lamp AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
STOP START /KW STOP START /KW STOP START /KW RCL: Remote Control Available Lamp
LVS: Low Voltage (24V) Source Monitor Lamp
CONTROL MODE
TOTAL USED POWER
PAL: Power Available Lamp
kW: Kilowatt Meter SYNCHRONISING MAN AUTO
AVAILABLE POWER
GSP: Generator Status Panel LOAD SHARING MAN AUTO CBO: Circuit Breaker Open Lamp
LOAD DEPENDENT START MAN AUTO CBC: Circuit Breaker Closed Lamp
PF1: Preference Trip stage 1 Lamp
LOAD DEPENDENT STOP MAN AUTO WATCHDOG
PF2: Preference Trip stage 2 Lamp OL: Overcurrent Trip Lamp
EGS: Emergency Generator on Standby Lamp RL: Reverse Power Trip Lamp
EGR: Emergency Generator Running Lamp Main Switchboard Generator Status Panel ES: Engine Start Switch
LT: Lamp Test Switch
ESS: Engine Stop Switch
AR: Alarm Reset Switch
HL: Heater ON Lamp
GCM: Generator Control Mode Switch
HS: Heater ON/OFF Switch
SGS: Standby Generator Selection Switch
GRL: Governor Raise/Lower Switch VS: Voltmeter L1/L2/L3 Select Switch
b) Speed > 300 rpm, voltage build-up detected. b) The ACB opens on the generator to be released. c) ACB opens on the abnormal generator.
c) Automatic synchronisation. c) The engine stops on the generator released. d) Blackout.
d) Automatic circuit breaker (ACB) closes.
(Note ! The load percentages and activation timing are adjustable via toggle e) ACB closes on the standby generator.
e) Automatic load sharing on. switches within the main switchboard.)
If the first standby generator fails to start or the ACB fails to close, the second
2. Automatic Parallel Running Activated by Heavy Load 5. Automatic Bus Connection due to Main Switchboard Trip Condition standby generator (if available) will start and follow the above sequence.
If the generator in use registers a high load of 882 kW (90% of the rated If, due to a trip condition, the bus voltage has become zero by the opening of
power), for 15 seconds, the standby generator will go through the following If the PMS detects that the bus abnormality has cleared during standby
the ACB of the generator in use, the first standby generator will go through the generator preparation, i.e. the bus voltage/frequency has stabilised, the standby
sequence: following sequence: generator will be synchronised and paralleled to supplement the original
a) Engine start. a) Engine starts. generator.
b) Speed > 300rpm, voltage build-up detected. b) Speed > 300 rpm, voltage build up detected. 7. Automatic Parallel Running due to Overcurrent
c) Automatic synchronisation. c) ACB closes. If the load on a running generator exceeds 1,078 kW (110%) for a period
d) ACB closes. exceeding 5 seconds, the standby generator will go through the following
If the first standby generator fails to start or the ACB fails to close, the second sequence:
e) Automatic load sharing on. standby generator (if available) will start and follow the above sequence.
a) Engine starts.
If the first standby generator fails to start or the ACB fails to close, the second 6. Automatic Change Over by Bus Abnormality
b) Speed > 300 rpm, voltage build-up detected.
standby generator will start, if available, and follow the above sequence. The normal voltage and frequency levels at the main switchboard bus are:
c) Automatic synchronisation.
(Note ! The load percentages and activation timing are adjustable via toggle Voltage: 440V
switches within the main switchboard.) d) ACB closes.
Frequency: 60Hz
e) Automatic load sharing on.
3. Automatic Parallel Run Activated by Heavy Consumer Request Under certain fault conditions the voltage and frequency may rise or lower
according to the fault. These fluctuating levels are undesirable for the Generator Protection Equipment
If a start request is received from a heavy consumer (e.g.: ballast pump), the operation of the ship’s plant.
start is blocked by an auxiliary contact in the main switchboard until sufficient The generator is protected from the abnormal conditions described below by
power is available. The standby generator will then go through the following There are bus abnormality limits for main bus voltage and frequency deviation means of the reverse power trip, short circuit trip, undervoltage trip and
sequence: and these are as follows: overcurrent trips.
a) Engine starts. 1. Abnormality Due to Undervoltage
Bus abnormality limits:
b) Speed > 300rpm, voltage build up detected. If the voltage of a generator decreases to between 35% and 70% of the rated
Low voltage: 418V for 5 seconds (95%)
value, the under voltage tripping device contained in the ACB will operate to
c) Automatic synchronisation. High voltage: 462V for 5 seconds (105%) trip the breaker. If a shortcircuit fault occurs, the generator voltage will reduce
d) ACB closes. Low frequency: 57Hz for 5 seconds (95%) and may cause the undervoltage tripping device (UVT) to operate. With this in
mind, a time delay device (of about 0.5 seconds) has been fitted to the under-
e) Automatic load sharing on. High frequency: 63Hz for 5 seconds (105%) voltage device to prevent the ACB from tripping immediately, allowing the
defective system circuit breaker to operate first.
f) PMS signals ‘start available’ at heavy consumer.
VS FS SY
MS ES LVS CBO PAL CBC RCL
kWH
VI FI
G G G A V
SYL
GSP
FSS SSS HM PF
EC
PF1 PF2
kW kW kW
AO AC AO AC AO AC LT AR
I
HL
O
ESS ES
GEN STATUS GEN FAIL GEN STATUS GEN FAIL GEN STATUS GEN FAIL
Main Switchboard Synchronising Panel STOPPED START FAIL STOPPED START FAIL STOPPED START FAIL
RUNNING SYNC FAIL RUNNING SYNC FAIL RUNNING SYNC FAIL HS AS VS
STARTING SHUT DOWN STARTING SHUT DOWN STARTING SHUT DOWN
VI: Incoming Voltmeter STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP STOPPING ACB ABN TRIP
READY ACB NON CLOSE READY ACB NON CLOSE READY ACB NON CLOSE
FI: Incoming Frequency Meter BLOCK BLOCK BLOCK
OUTPUTS OUTPUTS OUTPUTS
VS: System Voltmeter
START GOV RAISE START GOV RAISE START GOV RAISE
FS: System Frequency Meter STOP GOV LOWER STOP GOV LOWER STOP GOV LOWER Main Switchboard Generator Control Panel
SYNCHRO SYNCHRO SYNCHRO
MS: Main Switchboard Source Monitor Lamp ACB OPEN ACB OPEN ACB OPEN
ES: Emer. Switchboard Source Monitor Lamp AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
AUTO AUTO VOLT
RESET
STOP START /KW STOP START /KW STOP START /KW RCL: Remote Control Available Lamp
LVS: Low Voltage (24V) Source Monitor Lamp
CONTROL MODE
TOTAL USED POWER
PAL: Power Available Lamp
kW: Kilowatt Meter SYNCHRONISING MAN AUTO
AVAILABLE POWER
GSP: Generator Status Panel LOAD SHARING MAN AUTO CBO: Circuit Breaker Open Lamp
LOAD DEPENDENT START MAN AUTO CBC: Circuit Breaker Closed Lamp
PF1: Preference Trip stage 1 Lamp
LOAD DEPENDENT STOP MAN AUTO WATCHDOG
PF2: Preference Trip stage 2 Lamp OL: Overcurrent Trip Lamp
EGS: Emergency Generator on Standby Lamp RL: Reverse Power Trip Lamp
EGR: Emergency Generator Running Lamp Main Switchboard Generator Status Panel ES: Engine Start Switch
LT: Lamp Test Switch
ESS: Engine Stop Switch
AR: Alarm Reset Switch
HL: Heater ON Lamp
GCM: Generator Control Mode Switch
HS: Heater ON/OFF Switch
SGS: Standby Generator Selection Switch
GRL: Governor Raise/Lower Switch VS: Voltmeter L1/L2/L3 Select Switch
If the generator current exceeds 300% of the maximum rated current (4,714A),
the ACB will be tripped almost instantaneously (about 400msec) by the short
time delay trip fitted to the ACB. If the current exceeds 1,000% of maximum
rated current (15,716A) the ACB will trip instantaneously (zero time delay).
If the current on the running generator exceeds 110% of the maximum rated
current (441A) for 40 seconds the overcurrent relay will operate to trip the
generator ACB.
If the generator current exceeds 300% of maximum rated current (1,202A) the
ACB will be tripped almost instantaneously (about 400msec) by the short time
delay trip fitted to the ACB. If the current exceeds 1000% of maximum rated
current (4,009A) the ACB will trip instantaneously (zero time delay).
P2 Focsle
Distribution Board
Main
440/220V 440/220V
Transformers
Switchboard
AC 220V No.2 Group No.2 AC 440V No.3 D.G. No.2 D.G. Synchronising Bus Tie No.1 D.G. No.1 AC 440V No.1 Group
Feeder Panel Starter Panel Feeder Panel Panel Panel Panel Breaker Panel Feeder Panel Starter Panel
Bridge Alarm
Console
No.1 Group Starter Panel (Main Switchboard) No.2 auxiliary blower No.2 engine room vent fan (non-reversible)
No.2 COPT priming LO pump Local Group Starter Panel No.5 (LGSP 5) AC central unit fan
No.3 COPT priming LO pump Situated Purifier Room
Battery room exhaust fan
No.1 deck seal SW pump No.2 HFO purifier
Galley supply fan
No.2 deck seal SW pump No.2 HFO purifier supply pump
Foam room exhaust fan
Sewage treatment plant No.2 main LO purifier
CO2 room fan
Ballast pump priming LO pump No.2 main LO purifier supply pump
Paint and lamp store fan
HFO transfer pump No.3 HFO purifier
No.1 hose handling crane
FW ejector pump No.3 HFO purifier supply pump
10 ton provision crane
Main engine cylinder LO system No.2 generator engine DO service pump
Air conditioning room exhaust fan
Local Group Starter Panel No.2 (LGSP 2) Local Group Starter Panel No.6 (LGSP 6) Provision refrigeration fan
Situated Engine Room Floor Port Forward Situated Near Calorifier No.2 hose handling crane
No.1 bilge fire and GS pump No.1 cargo pump room fan Rescue boat winch
No.2 bilge fire and GS pump No.1 FW hydrophore pump Lifeboat winch
Scrubber CSW pump Incinerator No.1 and 2 hydraulic pumps for valve control
Local Group Starter Panel No.3 (LGSP 3) Main engine cylinder oil shift pump Galley hood fan
Situated Engine Room Floor Port Aft Mill pump for waste oil tank Econovent system
Oily bilge pump No.2 cargo pump room fan 3 ton provision crane
Sludge pump No.2 FW hydrophore pump P1 Distribution Board
Calorifier Situated Engine Room 2nd Deck in Workshop
Turning gear
Stern tube LO circulating pump FW generator distillate pump Drilling machine
OIly bilge separator ODME system Engine room crane
ICCP system (aft) Hot water circulating pump Grinding machine
Stern tube LO seal dosing pump Local Group Starter Panel No.7 (LGSP 7) Lathe
Situated By Air Conditioning Compressors
Spare Electric arc welder
Local Group Starter Panel No.4 (LGSP 4) No.1 main air compressor Hot water circulating pump for AC system
Situated Purifier Room No.1 control air compressor Hacksaw machine
No.1 FO purifier No.1, 2 and 3 vacuum pumps for auto strip unit Test panel
P2 Distribution Board Fire and general alarm system Main engine cylinder LO system
Situated in Bosun’s Store Bridge alarm console Elevator
Bosun store exhaust fan AC room 220V feeder panel No.2 steering gear starter (low speed)
Lighting panel L7 AC Room 220V Feeder Panel No.2 generator engine LO priming pump
Situated in C Deck Accommodation Cable Duct No.3 generator engine LO priming pump
Electric arc welder
ICCP system (forward) G2 distribution panel Emergency generator engine room heater
Auxiliary function panel for forward deck L3 lighting panel Emergency generator engine FO preheater
G1 Galley Distribution Board L4 lighting panel No.2 hydraulic power unit for valves
Situated in Dry Provisions Room L5 lighting panel FW spray pump
Convection oven N1 distribution panel (wheelhouse equipment) No.3 engine room vent fan
Tilting frying pan Gas detection panel Emergency Switchboard 220V Section
Universal mixing machine S band radar control panel
Distribution board N1 (navigation equipment)
Waste disposal unit IGS main control panel (main feed)
Distribution board E1
G3 laundry distribution board IGS main control panel (auxiliary feed)
Distribution board E2
Deep fat fryer C JB CO
220/42V transformer for lifeboat battery charging
Spares (2) MF/HF radio equipment
Navigation lighting panel
G3 Laundry distribution board Tank level system
Emergency generator engine battery charger
Situated in Laundry
Emergency Switchboard 440V Section Fire/general alarm system
No.1 and 2 tumble dryers Situated in Emergency Generator Room ECR console
Hydro extractor Emergency generator engine room lighting
Steering gear No.1
No.1, 2 and 3 washing machines Emergency generator engine cooling water preheater
Autopilot No.1
Ironing machine C JB CO
Steering gear and emergency fire pump room fan
Main Switchboard 220V Feeder Panel Emergency fire pump MF/HF radio
L1 lighting panel Battery charger Steering gear escape lighting
L2 lighting panel Electric whistle relay box Main engine electric governor
AC 220V No.2 Group No.2 AC 440V No.3 D.G. No.2 D.G. Synchronising Bus Tie No.1 D.G. No.1 AC 440V No.1 Group
Feeder Panel Starter Panel Feeder Panel Panel Panel Panel Breaker Panel Feeder Panel Starter Panel
LD
L M M Interlocking M M
440/220V
Circuit Breaker I O R S T
24V Battery Charge and MCB Emergency Group Main Bd Emergency Generator 440V 230V
Discharge Board Starter Panel Interconnector Panel Feeder Panel Feeder Panel
Max Current:
M Motor PST VS
400Amps
Transformer
LD
24V Services MCB: Circuit Breaker M DG
440V Load: G.S. PST: Phase Sequence Test Switch L
and Distribution Boards VS: Voltmeter Switch
SSA: Shore Supply Available Lamp Emergency
LD PSI: Phase Sequence Indicator Generator
24V System
L Lighting Boards Emergency 440V Feed V: Voltmeter
The shore power connection feeds the main switchboard at panel C. d) Ensure the voltage is approximately 440V.
A circuit breaker closed indicator lamp, a shore power alive indicator lamp, a e) Adjust the frequency of generator to approximately 60Hz.
kWh meter, an ammeter, a voltmeter and a 400A isolating circuit breaker are
provided at the main switchboard. f) Open the shore supply breaker at the main switchboard.
The shore power breaker is rated for 440V AC, 3ph, 60Hz, 400A. g) Close the generator ACB.
Interlocking is provided to prevent the shore supply being paralleled with any h) Check the voltage and frequency.
other supply.
i) Change the PMS mode to automatic, if required.
Procedure for the Operation of Shore Power Reception
j) Change the emergency switchboard back to normal supply.
a) Isolate the emergency generator to ensure it does not start.
k) Ensure the emergency generator is enabled to start if required.
b) When it is intended to receive power from the shore, confirm the
POWER AVAILABLE light is on. Shore power connection details may be found in:
Drawing GE-2642-112,item No. IE-43 in box No.32 in the engine room
c) Isolate all non-essential services, including sequential restart. technical library located in the engine control room.
Shore Power Connection Pane
d) Check the shore supply voltage.
f) Close the breaker for shore power at the shore connection box.
Excitation Current
Auto Synchronising
Unit
Governor Control
Circuits Governor
Exciter Stator
Diodes (6)
I O
Exciter Rotor Busbars to Alternator Rotor
Alternator Stator
Alternator Rotor
Generator Panel
Varistor (preset)
General Description
Three main diesel generators are provided. Each alternator is rated at 980kW
at 450V AC, 3ph, 60Hz. They are of the totally enclosed, self-excited,
brushless type. The load voltage is kept constant by the automatic voltage
regulator (AVR), which controls the excitation current to the exciter. Output
power from the stator is fed into a current/voltage compound transformer and
the thyristor regulated output of this is fed through the exciter stator windings.
The magnetic field in the exciter stator induces AC into the exciter rotor, which
is rectified by the rotating three phase bridge connected rectifier set and passed
to the main rotor DC windings. In this way the excitation levels are boosted for
heavy loads and reduced for light loads. This provides a constant output
voltage independent of load levels. Initial voltage build-up is by residual
magnetism in the rotor.
Passing air over an integral fresh water cooler, using a closed circuit air supply,
cools the generator. The cooling spaces are fitted with internal baffles to
prevent water reaching the stator windings in the event of cooler leakage.
Space heaters are fitted, which are energised when the generator circuit
breakers are open, which protect against internal condensation during shut
down periods. The breakers are normally operated by the PMS, but can be
operated manually at the main switchboard. An embedded sensor monitors the
stator temperature in each phase, A water leakage detector and temperature
sensor are also fitted in each air cooler. The two main bearings have
temperature sensors.
One diesel generator provides electrical power under normal conditions at sea,
with the remaining two on standby. The priority order of the standby generator
is selected using the PMS system, described in detail in section 2.13.2
a) The emergency generator is set to MANUAL. e) Close the main switchboard tie breaker.
b) The operator presses START at the generator control panel. f) The emergency switchboard is now supplied from the main
switchboard.
c) Emergency generator speed > 700 rpm. Voltage is established.
g) Shutdown the emergency generator and leave in automatic mode.
d) The ACB closes.
There is a test key switch on the emergency switchboard to test the automatic
The emergency generator now feeds the emergency switchboard. start facility of the emergency generator. This simulates the opening of the bus
tie breaker. The generator ACB will not close in this situation.
G1 Galley Distribution Board LGSP No.5 After a blackout the following auxiliary machinery
will be restarted sequentially when power is restored:
No.1, 2 and 3 Aft Deck Machinery No.3 Engine Room Fan 2 5 Main COPT Pump
Provision Refrigeration Fan 1) Motors which were selected to duty before the blackout will return to duty
after the blackout. Similarly, motors selected as standby will
automatically return to standby.
Galley Hood Fan
2) Where power is only restored to the emergency switchboard motors will
Econovent System start irrespective of selection.
V A
Battery
Alarm/Insulation Low Alarm
Magnetic Compass
Loran C Receiver
Lamp Test
Pushbutton Navigation Light Panel
MCCB 1
Main Feed Bridge Main Console
Circuit
Breaker
Earth Test Bridge Alarm Console
Pushbutton
Automatic Telephone Exchange
No.1 Gyrocompass
MCCB 2 No.2 Gyrocompass
Em. Feed VOLTMETER AMMETER
Circuit RECT RECT Electric Clock
Breaker
BATT BATT Satcom Power Supply
FEED FEED
Cargo Control Console
DESCRIPTION POWER EARTH OVER UNDER OVER Engine Room 24V Distribution
SYMBOL CONTENTS FLOAT EQ SOURCE FAIL LEAK CURRENT VOLT VOLT
H DROP QCR Engine Control Console
L DROP VD
AH OVERVOLTAGE Hospital Call System
AL UNDERVOLTAGE
AI POWER FAIL I/P TIMER B/Z B/Z
EI EARTH I/P TIMER SET UP DOWN FLOAT EQ RESET LAMP STOP Lighting Control Panel
DI OVERCURRENT I/P TEST
HI OVERVOLTAGE I/P No.1 GPS Receiver
ALARM SETTING MODE CHARGING MODE ALARM MODE
LI UNDERVOLTAGE I/P
No.2 GPS Receiver
24V Charge/Discharge Board Panel 24V Charge/Discharge Board Monitoring/Alarm Panel 24V Power Distribution
The radio/GMDSS equipment is backed up by a separate battery/UPS system. When an earth is present on an outgoing circuit, the earth leakage alarm will
sound. Operation of the earth test pushbutton will cause one earth lamp to glow
A separate 24V battery and charger system is provided for the emergency bright and the other earth lamp to dim. Careful isolation of the outgoing
generator starting arrangements. circuits (mindful of essential consumers), will locate the faulty circuit, the
lamps returning to equal brilliance and the alarm clearing once the faulty
The 24V emergency system consists of a battery charge/discharge distribution circuit is isolated.
board backed up by a separate 24V battery. This provides a smooth changeover
to a constant power source upon loss of the ship’s main or emergency power. Operating Procedure
These 24V batteries are normally on a floating charge, with the rectifier The battery charger is a fully automatic charging device which automatically
supplying the load. charges the 24V storage battery.
24V Batteries The charger has a facility to adjust the charging voltage. This, however, should
not be altered once the charger has been commissioned.
Battery: Lead-acid sealed
Capacity: 2V 300Ah/10 hour Floating and Equalising Charge Modes
Type: SLD300-2
Voltage (nominal): 24V (total) While the storage battery is fully charged, it is subjected to a floating charge.
Voltage (max): 26.4V In this condition, the charger supplies the 24V system with power. During
Voltage (min): 21.8V periods of high demand and failure of the power source, the battery will take
Number of cells: 12 over. A constant voltage is applied to the battery, regardless of any load, power
or temperature variation and the charging current varies according to charged
24V Charge/Discharge Board Battery Charger state thus maintaining the battery in a fully charged condition.
Manufacturer: Seun Electric Co. If the battery has been subjected to a period of duty due to power failure, on
Model: SU-BC-9600 restoration of the power supply, the battery charger is automatically transferred
Voltage (supply): 440V to equalising charge and this rapidly charges the battery. As soon as the battery
Voltage (float): 26.7 - 27.2V becomes fully charged, it reverts to floating charge. The charge performed
Voltage (equalising): 28V after the recovery from a power interruption is controlled by the SCR control
Rated current: 40A system, which protects the battery and charging circuits from excess current.
Rating: Continuous
Max. charging current: 60A DC Maintenance
The battery charger has two 440V supplies either the emergency switchboard The 24V charge/discharge board is designed for continuous operation and is
440V feeder section or the No.1 440V feeder section on the main switchboard. practically maintenance free. However, the unit should be kept clean and dry
and a visual inspection of connection integrity, cable condition etc, made once
The board contains the following equipment: a year. At this time the charging voltage should be checked using a high quality
24V DC voltmeter for feed, battery and rectifier monitoring digital voltmeter.
Ammeter for feed, battery and rectifier monitoring All the ship’s batteries should be kept clean and dry. The battery poles and
Earth leakage monitoring connections must be kept covered with acid free vaseline. The cell voltages
should be checked and logged once a month and the connection terminals
Isolation switches checked for tightness once a year.
Alarm function test facilities
Steering
Gear Room
225A Anode Ref. Anode 225A Anode 100A Anode Ref. Anode
Frame 16 Frame 29 Frame 41 Frame 104 Frame 116
Port and Starboard Port and Starboard Port and Starboard Port and Starboard Port and Starboard
Port
225A Anode Reference Cell 225A Anode 100A Anode Reference Cell
Input
440 V AC
225A Anode Reference Cell 225A Anode 100A Anode Reference Cell
Starboard
Maker : Korea Cathelco Ltd. Protection is achieved by passing low voltage DC current between the hull Forward System
Type: Impressed Current metal and anodes, insulated from the hull, but in contact with the sea water.
Power Supply: AC 440V, 60Hz, The electrical potential of the hull is maintained more negative than the The forward system has a power supply and control unit fitted in the bosun’s
anodes, i.e. cathodic. In this condition corrosion is minimised. Careful control store which feeds two 100A anodes, one port and one starboard. The control
The vessel is provided with an Impressed Current Cathodic Protection (ICCP) is necessary over the flow of impressed current, which will vary with the ship’s unit receives reference levels from two reference cells, one port and one
system. This method of corrosion protection automatically controls electro- speed, salinity and temperature of the sea water and the condition of the hull starboard.
chemical corrosion of the ship’s hull structure below the waterline. Cathodic paint work. If the potential of the hull is made too negative with respect to the
protection can be compared to a simple battery cell, consisting of two plates in anode, then damage to the paint film can occur electrolytically or through the The forward unit is supplied from P2 focsle 440V distribution board.
an electrolyte. One of the battery plates in the electrolyte will waste away evolution of hydrogen gas between hull steel and paint. The system on this
through the action of the flow of electrical current if the two battery electrodes vessel controls the impressed electrical current automatically to ensure Propeller and Rudder Stock Earthing
are connected electrically. When two metals are immersed in sea water, which optimum protection. Current is fed through 6 titanium electrodes situated
acts as the electrolyte, one of the metals acts as the anode and will waste away. forward and aft on the ship. The titanium prevents the anodes themselves from To avoid electrolytic corrosion of shaft bearings and rudder stock, brushes are
Which metal, in any pair, acts as the anode depends upon their relative corroding and the anode surfaces are streamlined into the hull. Fixed zinc fitted and bonded to the ship’s structure. In the case of the shaft, a slip ring is
positions in the electrochemical series but steel will act as an anode to copper, reference electrodes forward and aft are used to compare the potential of the clamped to the shaft and is earthed to the hull via brushes. A second set of
brass or bronze. The strength of the electric current generated in the corrosion hull with that normally found between unprotected steel and zinc electrodes. brushes, insulated from earth, monitors the shaft mV potential and this signal
cell, and hence the rate at which wastage takes place, depends upon the metals Sufficient current is impressed via the anodes to reduce this to a level of is fed to a millivolt meter. To ensure efficient bonding, the slip ring should be
involved and the strength of the electrolyte. between 150 and 250 mV. cleaned on a regular basis.
Operation
If a third electrode is added to the cell and a current is made to flow then the The rudder stock is earthed via a 70mm2 flexible earth cable between the
new third electrode acts as the cathode and the old anode will act as the new The system is completely automatic in normal use. The system can be deckhead and rudder stock to minimise any electrolytic potential across
cathode. This is how an impressed current cathodic protection system controlled by four pushbuttons on the power supply front panel. There are four bearings and bushes.
functions. When a vessel is fitted with ICCP the hull steel is maintained at an operating modes:
electrical potential more negative that the surrounding sea water. For this Routine checks
Standby: All output currents are zero
reason, loading and discharging terminals normally comply with the ISGOTT
Recommendation 20.6, Earthing, Bonding and Cathodic Protection, which Manual: Output currents at manually adjustable set values Record the output current and all voltages on a daily basis. If the
states, referring to IMO recommendations for the safe transport, handling and output current display is set to percentage, press ENTER to toggle
Automatic: Outputs vary to provide constant electrode potential
storage of dangerous substances in port areas, that ship shore bonding cables to amps.
should be discouraged. High currents that can occur in earthing cables and Configuration: To adjust controller set points
metallic connections are avoided. These are due to potential differences Check the reference electrode voltage on a daily basis. Pressing
between ship and terminal structure particularly due to the residual potential To change modes, press the CTRL button, the four modes are displayed and
up or down buttons toggles the display to read electrodes 1 and 2
difference that can exist for up to 24 hours after the shipboard ICCP has been the up/down arrows are used to scroll through them. When the desired mode is
or 3 and 4.
switched off. These terminals usually utilise insulating flanges on hose highlighted, the ENTER button is pressed. Configuration mode is only
connections to electrically isolate the ship and terminal structure. During accessible on entering an access code.
Check and clean the propeller shaft slip ring and brushes every
preparations for berthing at terminals where such insulation is not employed, week.
Electrical Installation
or where earth connections are mandatory by local regulation, or when bunker
barges come alongside, the ICCP should be switched off at least 24 hours in Inspect the rudder stock earth strap every month.
Two sub-systems consisting of a Controller Power Unit (CPU), reference
advance.
electrodes and anodes are installed, one forward and one aft, with a data
connection to a central remote monitoring unit mounted in the ECR. System Return completed log sheets to Cathelco for scrutiny.
Fresh Water Operation
status readings are available at the monitoring unit and these should be
inspected and logged each day. The control units are also equipped with an Inspect and clean the control unit cooling fans and grills every
When the vessel enters a river estuary the fresh or brackish water may limit the three months.
alarm to give warning of any system abnormalities.
spread of current from the anodes, due to the higher resistance of the water.
Normally this would cause the voltage output to increase to compensate for Sacrificial Anodes
Aft System
this. This would be accompanied by very low current levels and the reference
electrode potentials may indicate under protection. However, in this system, Sacrificial zinc anodes are provided within the water ballast tanks including
The aft system has a power supply and control unit fitted in the engine room
the output is taken care of by the computer and the system will automatically the fore peak tank. Aluminium anodes are fitted to the rudder and sea chests.
which feeds four 225A anodes, two port and two starboard. The control unit
return the hull to the optimum protective level when the vessel returns to sea
receives reference levels from two reference cells, one port and one starboard.
water.
To FW Exppansion Tank
To Purifier Room
Workbench
To IG Blower
D52V
To To
To Hot System For
Drinking Washing
Accommodation
From Fire Water Tube
Main Fountain D81V
Distilled Water Fresh Water Fresh Water
To Public
Tank Tank (S) Tank (P) To Boiler
Toilet Washing Water
(110.48 m3) (142.78 m) (253.26 m3) To
Hot Water
Wash Basin
Circulation D23V D45V
TI Pump
Exhaust Gas Ecomoniser
Fresh Water (2m3/h) CI Water Washing
Spray D56V To PI
Pump S Purifier D83V
D22V
(54 m3/h) Room PI
D80V D73V D74V D5V D3V D1V D6V D4V D2V To Purifier Room
CI PI
S To Port Calorifier
(300 litres) To Purifier Room Workbench
To Boiler Diesel D24V D51V
Feedwater D54V D55V Generator
Tank S Room D21V
D44V 2nd Deck Service
To Starboard
Diesel
PI
Generator
Steriliser Room D42V
PS
(1,500 l/h) To Boiler Sampling Cooler
D9V
D37V
D82V
D13V D10V D79V D53V To Boiler Chemical
Control Fresh Water
Dosing Unit
Panel D8V Hydrophore D40V
D43V D85V
Tank
Mineraliser To Foam Room
(1.0 m3)
(1,500 l/h) D11V
To No. 2 PI PI To No.1 To Generator Engine
S Main LO HFO Room (P)
Purifier Purifier
To Generator Engine
TI Fresh Water
Evaporator D58V D57V D12V Room (S)
From Sea Water PI 36 ton/day
Line
3rd Deck Service
D39V
To Generator Engine To No. 3
From LO Purifier HFO To Public Toilet
Distillate Purifier
Salinity Pump To Main Engine Charge Air
Panel Discharge Cooler Washing Plant
Distillate To No.1 To No. 2 To Main Engine Jacket Water
Pump Main LO HFO Feed and Drain Tank
PI SA Purifier Purifier
PI
FI 33V D38V
Stern Tube (Floor)
Cooling S
WaterTank Key To Oily Bilge Separation
Chemical
(82.79 m3) Dosing Tank
Domestic Fresh water To Vacuum Pump Unit
High Salinity
D7V Return to Evaporator Electrical Signal To Oil Vacuum Stripping Unit
Eductor Extraction
To ODME System
The silver ion concentration in the water leaving the unit should be checked Cold water make-up is taken from the hydrophore outlet line and circulated
periodically, at least once each year, in order to ensure that the unit is having continuously throughout the system by the hot water circulating pump. All
the correct effect. The sterilising unit operates automatically and it changes the pipes in the hot water system are lagged to prevent heat loss. Make-up to the
direction of the current flowing between the electrodes every two minutes thus hot water system comes from the cold water system via a non-return valve,
each electrode acts as anode and cathode and wear on the electrodes is located after the hydrophore outlet, thus the hot water system is maintained at
equalised. The silver electrodes should be inspected and changed when all the the same pressure as the cold water system. The water is passed through a
silver coating has depleted. The unit will issue an alarm when the anodes are calorifier, which can be either steam or electrically heated to raise the water to
exhausted. The dosing of the water is automatic and is set depending on the the correct temperature.
flow of the water.
To FW Exppansion Tank
To Purifier Room
Workbench
To IG Blower
D52V
To To
To Hot System For
Drinking Washing
Accommodation
From Fire Water Tube
Main Fountain D81V
Distilled Water Fresh Water Fresh Water
To Public
Tank Tank (S) Tank (P) To Boiler
Toilet Washing Water
(110.48 m3) (142.78 m) (253.26 m3) To
Hot Water
Wash Basin
Circulation D23V D45V
TI Pump
Exhaust Gas Ecomoniser
Fresh Water (2m3/h) CI Water Washing
Spray D56V To PI
Pump S Purifier D83V
D22V
(54 m3/h) Room PI
D80V D73V D74V D5V D3V D1V D6V D4V D2V To Purifier Room
CI PI
S To Port Calorifier
(300 litres) To Purifier Room Workbench
To Boiler Diesel D24V D51V
Feedwater D54V D55V Generator
Tank S Room D21V
D44V 2nd Deck Service
To Starboard
Diesel
PI
Generator
Steriliser Room D42V
PS
(1,500 l/h) To Boiler Sampling Cooler
D9V
D37V
D82V
D13V D10V D79V D53V To Boiler Chemical
Control Fresh Water
Dosing Unit
Panel D8V Hydrophore D40V
D43V D85V
Tank
Mineraliser To Foam Room
(1.0 m3)
(1,500 l/h) D11V
To No. 2 PI PI To No.1 To Generator Engine
S Main LO HFO Room (P)
Purifier Purifier
To Generator Engine
TI Fresh Water
Evaporator D58V D57V D12V Room (S)
From Sea Water PI 36 ton/day
Line
3rd Deck Service
D39V
To Generator Engine To No. 3
From LO Purifier HFO To Public Toilet
Distillate Purifier
Salinity Pump To Main Engine Charge Air
Panel Discharge Cooler Washing Plant
Distillate To No.1 To No. 2 To Main Engine Jacket Water
Pump Main LO HFO Feed and Drain Tank
PI SA Purifier Purifier
PI
FI 33V D38V
Stern Tube (Floor)
Cooling S
WaterTank Key To Oily Bilge Separation
Chemical
(82.79 m3) Dosing Tank
Domestic Fresh water To Vacuum Pump Unit
High Salinity
D7V Return to Evaporator Electrical Signal To Oil Vacuum Stripping Unit
Eductor Extraction
To ODME System
Filling the starboard tank. Operate the domestic FW system as in parts a) to e), then set valves as follows: Operate FW system as in parts a) to e) above then set valves as follows:
Set up the valves as follows: Position Description Valve Position Description Valve
Open Hydrophore tank outlet valve D10V Open Cold water outlet valve to ER services D85V
Position Description Valve
Open Flow back preventer inlet valve D79V Open Cold fresh water services supply valve D37V
Open FW generator outlet valve
Open Flow back preventer outlet valve D53V
Open Inlet three-way cock to mineraliser Operate the following valves as required:
Operational Flow back preventer D86V
Open Outlet three-way cock from mineraliser
Open Supply valve to cold FW system D37V Hot water to purifier room work bench D52V
Open Steriliser inlet valve
IG blower
Open Steriliser outlet valve f) Open inlet valves to all the cold water fountains.
Fresh water expansion tank
Closed Steriliser bypass valve D13V g) Water will now be automatically supplied to the cold water
Hot system for accommodation heating
Open Starboard FW tank inlet valve D1V system from the hydrophore tank.
Boiler wash water D81V
Closed Port FW tank inlet valve D2V Procedure for Operating the Hot Water System
Economiser water washing D45V
Operation of Domestic Water System to the Hydrophore Tank
Operate the FW system as in parts a) to e) and set the hot water system valves Purifier room D83V
(Starboard FW tank and No.1 FW pump in use)
as follows:
HFO purifier service air D57V
Set up the valves as follows:
(Hot water circulating pump in use) LO purifier service air D58V
Position Description Valve Purifier room work bench D51V
Position Description Valve
Open Starboard FW tank outlet valve D3V 2nd deck services D44V
Open Hot water system inlet valve from hydrophore D21V
Closed Port FW tank outlet valve D4V 3rd deck services D39V
Open Calorifier outlet valve D22V
Open No.1 domestic FW pump suction valve 9V Engine room floor services D38V
Open Hot water circulating pump inlet valve D23V
Open No.1 domestic FW pump discharge valve Boiler sample cooler D42V
Open Hot water circulating pump outlet valve D24V
Closed No.2 domestic FW pump suction valve D8V Boiler chemical dosing unit D82V
h) After opening the hot water system inlet valve D21V, allow the
Closed No.2 domestic FW pump discharge valve system to fill from the hydrophore tank. Foam room D40V
a) Open the valves as per above table. Generator engine room D11V and D12V
i) Ensure that the hot water circulating pump is primed.
Public toilet
b) Ensure that No.1 pump is primed with water.
j) Start the hot water circulating pump. Main engine air cooler cleaning
c) Start the pump, fill the hydrophore tank to approximately ¾ full HT and LT FW expansion tanks
k) Open the steam supply or switch on the electrical supply to the
and stop the pump.
calorifier and set the system temperature.
Oily water separator
d) Open the air supply valve to the hydrophore tank, raising the Vacuum pump unit
l) Check that the system is circulating correctly and that the
pressure to 5.5 kg/cm2.
temperature is maintained.
Cargo oil system vacuum stripping pump
e) Put the pump in auto mode at the control panel, in order that it will
cut in and cut out as required to maintain pressure in the system
and level in the tank.
PI T T PI T Key
Refrigerant Gas
Refrigerant Liquid
LT Cooling Water
Meat Room Dairy Room
-20˚C 20 m3 + 2˚C 12 m3 Lubricating Oil
Instrumentation
Evaporator Unit 3
Evaporator Unit Oil Pressure Control
T Thermostat
Oil Separator
Heat
Exchanger
DPS 1 2 PI PI 2 1 DPS
3 3
Refrigerant Refrigerant
No. 2 No. 1
Open To Open To
Release Air Release Air
PI TI TI PI
TT TT
To and From To and From
LT Cooling Condenser Condenser LT Cooling
System System
TI TI
Filter Filter
and and
Dryer Dryer
Charging Charging
Connection Connection
PI T T PI T Key
Refrigerant Gas
Refrigerant Liquid
LT Cooling Water
Meat Room Dairy Room
-20˚C 20 m3 + 2˚C 12 m3 Lubricating Oil
Instrumentation
Evaporator Unit 3
Evaporator Unit Oil Pressure Control
T Thermostat
Oil Separator
Heat
Exchanger
DPS 1 2 PI PI 2 1 DPS
3 3
Refrigerant Refrigerant
No. 2 No. 1
Open To Open To
Release Air Release Air
PI TI TI PI
TT TT
To and From To and From
LT Cooling Condenser Condenser LT Cooling
System System
TI TI
Filter Filter
and and
Dryer Dryer
Charging Charging
Connection Connection
To Put the Cooler Rooms System into Operation Check the moisture indicators
a) Check that the fans are operating and that air is circulating freely Check the suction and discharge pressure and temperature and
through the evaporators. any unusual variations should be investigated
b) Open the refrigerant supply to one cooler room. Check all the room temperatures and evaporation coils for any
sign of frosting
c) Open the refrigerant returns from the cooler room. Repeat for the
cooler room. Stopping the Plant for a Short Period (about 2 -3 Days)
Defrosting a) Close the liquid supply line valve for the evaporator for 5 minutes
before stopping the plant.
The air cooler in the meat room is fitted with electrical defrosting equipment
i.e. the evaporator and drip trays are provided with electrical heating elements. b) When the compressor stops on low pressure, press STOP on
Defrosting is carried out automatically and the frequency of defrosting is control panel.
chosen by means of a defrosting relay built into the starter panel. The
defrosting sequence is as follows: c) When stopping for a short period it is not necessary to close the
suction and discharge stop valves. Close the oil return valve.
a) The compressor stops and all the solenoid valves in the system
close. Stopping the Plant for a Long Period (more than 2 - 3 Days)
b) The fan in the meat room stops working but the fan in the a) Close the main stop valve after the condenser. Evacuate the
vegetable room continues the circulation of the warm air over the evaporators.
coolers, in this way keeping the cooling surfaces free from ice.
b) Allow the temperature rise in the evaporators, repeat after
c) The electric heating elements in the meat room switches on. evacuation.
d) As long as the cooler is covered with ice, the melting takes nearly c) When the suction pressure is slightly over atmospheric, stop the
all of the heat supplied and the temperature of the cooler and the compressor, close the compressor suction and discharge stop
refrigerant is constantly kept near zero. When the ice has melted, valves and the oil return stop valve.
the refrigerant temperature rises in the meat room. When the
temperature reaches the set point (approximately +10°C) of the d) Stop the condenser cooling water and drain.
defrosting thermostat, the heating elements are switched off.
e) Switch off the main and control circuit electrical supplies.
Refrigerant Gas
LT Cooling Water
TI TI Lubricating Oil
Instrumentation
T Thermostat
Oil Separator
Heat
1 1 DPS 2 PI Exchanger 1 1 DPS 2 PI
Heat
T T Exchanger
3 3
Refrigerant Refrigerant
No. 1 No. 2
T EVR10 T EVR10
Open To Open To
Release Air Open To Release Air Open To
Release Air BMSL12 Release Air BMSL12
PI 2 TI PI 2 TI
TI TI
Filter Filter
and and
Dryer Dryer
Charging Charging
Connection Connection
Expansion
Tank
(In Funnel Casing
Top Level)
W168V
From To
Accommodation Accommodation
PI
W130V
FW Topping-Up
Line
Heater
T171V T169V
W145V W146V
PI PI
Air Conditioning Plant Accommodation
T191V W170V Accommodation Heating
To Drains 1
FW Circulatng Pumps
2 Reheating Unit
Cooler TI
T184V T182V
PI PI
W139V W140V
Key
FW Heating System
Steam
Condensate
The engine room workshop is equipped with ‘packaged’ type air conditioning Prior to operating the unit the cooling water inlet and outlet valves must be
units. These are stand alone units and they maintain a satisfactory environment opened.
in the engine control room and the workshop. The engine control room is
provided with two units, one at each side of the control room, and the The unit can be used as a heater or a cooler by operation of the COOL/HEAT
workshop with a single unit. changeover switch mounted on the front panel. The compressor does not
operate until the start operating sequence for cooling has taken place and this
Make: Kyung Won Century Ltd starts the fan to ensure that there is air circulation before the refrigeration
Cooling system: R404A direct expansion system operates. The heating sequence will not start until heating has been
Voltage: 440V, 3ph selected. A twist switch allows the level of cooling or heating to be selected
and the unit will operate to comply with the setting, operating the cooling or
Engine Control Room heating system according to demand and the temperature of the incoming air.
Type: MPG5HF3
Capacity: 15,000 kcal/h The unit is equipped with protection devices against high and low refrigerant
pressure and high compressor current. A fusible plug is located at the
Workshop condenser to protect against abnormal pressure rise should cooling fail. The
Type: MPG7.5HF3 plug is set to operate at approximately 72ºC.
Cooling capacity: 22,500 kcal/h
Maintenance of the unit under normal operation should be limited to a monthly
Although the workshop and engine control units are of different sizes they are check for refrigerant loss and cleaning of the air filter. Every three months the
identical in operation and the same description below applies to both types. condenser zinc anode condition should be checked. A more intensive
inspection should be carried out every year which should include a check of
The cooling system is regulated automatically by the thermostat sensing the the fan belt tension and condition.
intake air temperature. Automatic regulation is effected by an R404A high/low
pressure switch. More detailed information is available in the manufacturer’s handbook for this
equipment.
The compressor is of the hermetically sealed reciprocating type, where the
compressor and motor are encased in a single casing.
The condenser is a water cooled shell and finned tube type, the cooling water
coming from the LT central cooling system (see section 2.5.2). The pressurised
refrigerant is led into the steel body and transfers its heat into the water passing
through the cooling tubes.
The air conditioner is also equipped with a circulating fan, filter and strainer.
Public
Toilet
P3V P4V
Basin Urinal
3rd Deck
P16V P18V
P12V
P11V
P14V To Bilge
Holding
PI
tank
P17V P6V
Compressor
Chlorinator
Screen
Sewage Treatment
P8V P7V LS
Plant
Aeration
Tank Chlorination LS P9V PI0V
Clarification
Tank
Tank
Air Diffuser
LS
PI CI
Key
1 P15V
P2V P1V To Bilge
Sewage Pipes Discharge
From Bilge/Fire Holding
PI CI Pump's
Air and Tank
2 General Service
P13V Pump
Incoming sewage enters the aeration compartment and passes through a screen
which separates any items which cannot effectively be treated by the unit. The
screen also breaks the sewage into smaller particles. The aeration compartment
is supplied with air from the compressor and there is also a return line from the
clarification tank. An air lift arrangement, supplied with compressed air,
encourages activated sludge from the clarification compartment to flow into
the aeration tank; this activated sludge containing the bacteria digests the
sewage. There is also a return from the surface of the clarification
compartment which brings back debris skimmed from the surface of that
compartment. The aeration compartment is provided with a vent to release the
carbon dioxide produced by the bacterial action. Incoming oxygenating air
ensures that the contents of the tank are mixed with the incoming sewage and
the activated sludge. Sewage under treatment remains in the aeration
compartment for about 24 hours before passing through to the clarification Sewage Treatment Plant
section.
Ship Operational Garbage Cabin Garbage & Public Room Galley & Messroom Garbage
Deck Engine Room Officers Crew Galley Stores Galley & Messroom
1.Plastic 1.Plastic 1.Plastic 1.Plastic 1.Plastic 1.Food waste
2.Floating dunnage 2.Floating dunnage 2.Paper, rags, glass, bottles, 2.Paper, rags, glass, bottles, 2.Packing material 2.Plastics
3.Lining/packing materials 3.Lining/packing materials metal, etc. metal, etc. 3.Paper, glass, bottles, 3.Packing material
4.Paper, rage, glass, metal, 4.Paper, rage, glass, metal, metal, etc. 4.Paper, glass, bottles,
bottles, etc. bottles, etc. metals, etc.
5.Oily rags 5.Oily rags
6.Solid oily waste 6.Solid oily waste
7.Waste oil 7.Waste oil Separation Separation
Generated garbage Generated garbage
separated at source into the separated at source into the
marked receptacles by the marked receptacles by the
Chief Cook Chief Cook & 2/Cook
Yes No
Location of Location of Location of Location of Collected
Collected by Collected by Collected by
receptacles receptacles receptacles receptacles by
Bridge 4-8 GP1 Work shop Motorman Cabin 2/Cook Cabin Occupant
Radio room 4-8 GP1 E.C.R. Motorman Cleaning gear Cleaning gear Lk.
Location of Processing of Food Waste Location of
C.C.R. 4-8 GP1 Engine Store Motorman Lkr on A&C-Dk 2/Cook on upp.&B-Dk GP2 Collected by Collected by
receptacles Food waste will be processed receptacles
Laundry GP2 E/R Decks Motorman Conf. room 2/Cook Crew smoking GP2
Deck stores GP2 Off. smoking 2/Cook room Inside Store 2/Cook using chafe cutter or disposer Inside galley 2/Cook
room Suez room GP2 and will be disposed to the Officers mess 2/Cook
infirmary 2/Cook Gymnasium GP2 sea. Chief Cook is responsible Crew Mess GP2
for the operation of the
DISPOSER located in the
galley.
To Sea
Storage Storage
WATER TIGHT GARBAGE ROOM WATER TIGHT GARBAGE ROOM
LOCATED : ON UPP. DECK AFT LOCATED : ON UPP. DECK AFT
The collected garbage to be brought The collected garbage to be brought
every morning to the garbage room every morning & evening to the garbage
as per designated duties for storage. room as per designated duties for
storage.
Storing Garbage In Garbage Room (Located On Upper Deck Aft Starboard Side)
Red Receptacle Blue Receptacle Yellow Receptacle Green Receptacle Black Receptacle
For incineration For sea disposal For sea disposal Food waste For landing ashore
Examples >25 nm >25 nm for sea disposal
Examples
1.Burnable dunnage outside special area outside special area >25 nm
2.Paper, rags, etc outside special area 1. Paint
Examples Examples
3.Oily rags 2. Chemicals
1.Floating dunnage 1.Paper, rags, glass, metal, Examples
4.Solid oily waste 3. Oil soaked material
2.Lining bottles, crockery & similar 1.Food waste 4. Plastic
5.Waste oil
3.Packing materials refuse
2.Incinerator ash
Collected By
GP2 & GP1
Under supervision
of C/O and taken Sea Disposal Disposal To Shore Facility
to incinerator 1.Under the supervision of 2/E 1.Under the supervision of 2/E
2.Obtained permission from Bridge 2.All Disposals to be recorded in the
3.All Disposals to be recorded in the garbage log
garbage log
Incineration
By 2/E By GP2 and assisted by GP1
Under supervision
of 2/E
Incinerator Unit
The incinerator has the following built-on main components: Disposal of plastics including plastic ropes and garbage bags is prohibited.
Other Waste
Primary blower for cooling and combustion air Floating dunnage, lining and packaging are allowed when over 25 miles
offshore. Oily rags may be burnt in the incinerator in small quantities.
Sludge burner
Sludge pump Paper, rags, glass, bottles, crockery and other similar materials are allowed Cans that have contained oils or chemicals must be stored before discharge
over 12 miles offshore. ashore.
Primary burner for primary combustion chamber
Control panel, CP-1 and CP-3 All other garbage including paper, rags etc. are allowed when over 3 miles Incinerator ash must be stored on board in a specially dedicated location site if
offshore. less than 12 miles offshore. Otherwise the ash can safely be dumped
Thermocouples for detecting temperatures and alarm in primary overboard.
combustion chamber
Food waste can be disposed of in all areas over 12 miles off shore.
Thermocouples for detecting high flue gas temperature and alarm Procedure for the Operation of the Incinerators
Due regard should also be taken of any local authority, coastal, or port
Automatic built-on non-flareback sluice Preparation for Start-up of the Incinerator
regulations regarding the disposal of waste. To ensure that the annex to Marpol
The combustion chamber is fitted with a feeding door, to admit garbage, and a 73/78 is complied with, waste is treated under the following cases:
a) Ensure that there is MDO in the tank and that the supply and
slag door to allow removal of ash and slag when incineration is completed. Food waste return valves to and from the MDO pump are open.
Flue gas from the incinerator is vented via the exhaust ducting/funnel to the
atmosphere. Burnable dry waste, plastic and others
b) Open the inlet and outlet valves on the sludge tank and the air
Non-burnable dry waste supply.
Control of the incinerator, the diesel oil pump, waste oil circulating pump and
flue gas fan are from the local control panel. Other waste, including oily rags and cans, chemical cans and c) Ensure that the air inlet to the primary blower is clear and that the
incinerator ash flue gas outlet is clear. The flue gas damper should always be
Provision is made for local indications of combustion chamber temperatures,
fully open and should only be used if there is too much draught in
together with a flue gas high temperature alarm. Garbage Disposal Procedures the funnel uptake; this is indicated by the negative pressure in the
combustion chamber dropping below 50 mmWG.
The unit is provided with its own MDO service tank, which can be filled from Food Waste
the MDO transfer pump. The incinerator’s own DO pump takes suction from
d) Ensure that there is a power supply to the incinerator and activate
this tank to the burner unit. The sludge burner is fitted with atomising air from Food waste production for approximately 50 people is given as 15 to 25kg per the main switch on the control panel.
the general service air system. day or 75 to 125 litres per day without compacting.
e) Reset the alarm lamps. Make sure that the lamps are working by
Summary of Regulations The daily food waste produced is collected in bags in the galley. activating the pushbutton for lamp test on each lamp.
Annex V of Marpol 73/78, the regulations for the prevention of Pollution by Burnable Dry Waste f) Check the rotational direction of the primary air blower by
Garbage from Ships, controls the way in which waste material is treated on
starting the incinerator for a short period.
board ships. Although it is permissible to discharge a wide variety of garbage Dry waste production for approximately 50 people is given as approximately
at sea, preference should be given to disposal by utilising shore facilities where 30kg per day or 1,000 to 1,500 litres per day. The volume can be reduced by a
available. A summary of the garbage disposal regulations are given below. factor of 5 by shredding the waste.
b) Activate the INCINERATOR START switch on the control panel. c) After a preheating period of about 13 minutes with the primary
The incinerator will start automatically and ignite the primary burner operating, the sludge burner starts automatically.
burner.
d) The incinerator will operate in the set temperature range, 850 to
c) The incinerator will operate in the set temperature range, 850 to 950ºC. If the incinerator goes out it must be reset by means of the
950ºC. If the incinerator goes out it must be reset by means of the RESET FLAME FAILURE BURNER.
RESET FLAME FAILURE BURNER.
e) When the DELAY PRIMARY BURNER is switched to
d) Add solid waste to the incinerator primary combustion chamber AUTOMATIC the primary burner operates for 25 seconds to
using the automatic non-flare-back sluice by activating the ignite the sludge burner automatically. If the DELAY PRIMARY
pushbutton on the control panel CP-3. Before adding more solid BURNER is switched to MANUAL the primary burner operates
waste ensure that the incinerator has sufficient capacity by continuously with the sludge burner.
looking through the sight glass. .
Stopping the Incinerator
! CAUTION
Do not put incombustible materials such as glass in the primary a) Activate the switch INCINERATOR STOP.
combustion chamber.
b) When the incinerator temperature drops below 145ºC the
Do not put wet solid material in the primary combustion chamber more incinerator stops automatically.
than one hour before starting.
c) When the incinerator has stopped, switch off the main switch on
When burning oily material do not add more than 15 litres of oily material the control panel.
per charge.
! CAUTION
Never add more than 10 kg of highly combustible material such as plastics Never stop the incinerator on the main switch during operation as this will
at each charge. cause melt-down of the burners.
Do not overload the incinerator. The following conditions trip the incinerator :
Power source failure
Ideally add waste materials in bags of no more than 10 kg per bag in order
to ensure optimum burning. Flue gas temperature high
Burner trip
Remove slag carefully and do not knock or hammer the sides of the
primary combustion chamber to dislodge slag. Sludge/steam pressure low
Fan trip
WARNING
Never put explosive material such as closed containers or aerosols in the DO pressure low
incinerator.
Burner and trash door open
Combustion chamber temperature high
Emergency stop
Chief Eng. 1st Eng. 2nd Eng. 3rd Eng. Officers' Officers' Duty Gymnasium Conference Control
Mess Room Saloon Mess Room Centre
Main
X16 WA / X16 WB
Computer
Unit No.3 BZ BZ BZ
Bridge Buzzers
Net A
Engine Control
Net B
Room
Emergency
Alarm Log
Supply
Printer Printer
21" 21"
1X 16.5 2X 16.5
Monitor Monitor
220V
AC A.C.
UPS Unit
220V
AC Operator's Operator's
Panel No.1 Panel No.2
OPERATOR CONTROL PANEL
Net A
Net B
2X15
2X16.4
1X15 1X16.4
SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU
S.S.U. A.C. 4
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10 No. 11 No. 12 No. 13
RL
Remote Operator Station The alarm data available, which includes the general alarm signal, plus the Alarm limits and delays are adjustable from the OCP.
normal-status data and the system control facilities, are summarised below.
Operator Control Panel: OCP8810/SW Version 49
A counter function is provided to keep track of running hours for engines,
Available Data System Control Facilities pumps and other related items. This function is also capable of accumulating
The operator control panel, together with the colour graphic monitor, forms the
operator station. flow data. The counter values may be shown on the ECRT or printed at the
When an alarm occurs, the alarm signal is distributed as described above. The logging printer.
following text summarises the available data and the system control facilities
Signal Acquisition Unit (SAU)
provided at the various locations. Selection of engineers for watch-call duty is carried out at the OCP. All
The signal acquisition unit is a general purpose data acquisition unit. It has a
available engineers, whether on duty or not, may be called to the ECR in the
front panel where the operator can locally inspect the status of monitored In the Machinery Spaces case of an emergency by activation of the CALL ALL ENG key on the OCP.
signals.
Detailed information on the type of alarm and its source is available at the Machinery watch responsibility may be changed from the ECR to the bridge
Full monitoring and alarm facilities are provided in the Engine Control Room acquisition unit that originated the general alarm signal. In addition, detailed and back to the ECR.
(ECR). information about the normal status of the machinery monitored by the
acquisition unit is always available at the unit.
Sufficient facilities are also provided for a machinery watch on the bridge, with
a watch calling sub-system enabling engineers to be automatically called to the If an acquisition unit is isolated from the rest of the system by a communica-
ECR when they are on watch-call duty in the accommodation. Both the tion break-down, or if the MCU develops a serious fault, all the necessary
machinery and the ECR may safely be left unmanned while the machinery alarm and monitoring functions, normally associated with the machinery
watch is carried out on the bridge. monitored by the acquisition unit, are available locally at the acquisition unit.
Chief Eng. 1st Eng. 2nd Eng. 3rd Eng. Officers' Officers' Duty Gymnasium Conference Control
Mess Room Saloon Mess Room Centre
Main
X16 WA / X16 WB
Computer
Unit No.3 BZ BZ BZ
Bridge Buzzers
Net A
Engine Control
Net B
Room
Emergency
Alarm Log
Supply
Printer Printer
21" 21"
1X 16.5 2X 16.5
Monitor Monitor
220V
AC A.C.
UPS Unit
220V
AC Operator's Operator's
Panel No.1 Panel No.2
OPERATOR CONTROL PANEL
Net A
Net B
2X15
2X16.4
1X15 1X16.4
SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU SAU
S.S.U. A.C. 4
No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10 No. 11 No. 12 No. 13
RL
Facilities are provided for indicating and accepting the transfer of machine These indicators are labelled to request deck officers to perform a correcting
watch responsibility to or from the bridge. action such as slowdown or shutdown of the propulsion engines.
When the bridge is on machinery watch, one or more engineers must be on Non-Critical Alarm Indicators
watch call duty. The machinery monitoring general alarm signal will call the
engineer to the ECR if an alarm condition arises. The visual alarm data on the These indicators are normally labelled, as for general alarm(s). These alarms
bridge panel consists of single or group alarm indicators. When an alarm is do not affect the normal operation of the ship and no action from the bridge
acknowledged or cleared in the ECR, appropriate indications are given on the will affect them.
bridge panel.
Extended Alarm and Watch Calling System Summary
(Note! The DC 2000 system prevents the bridge from assuming watch respon-
sibility if there are no engineers on watch call duty.) The purpose of this system is to transfer the responsibility from the engine
control room to the bridge, the duty engineer’s cabin and the mess room, when
The bridge personnel may call the duty engineer from their accommodation at the unmanned machinery period starts.
any time for consultation. An indication for the acknowledgement of such calls
is provided. The transfer of the responsibility is requested by the operator in the engine
control room and accepted by the operator on the bridge.
If the bridge personnel are not on machinery watch, alarm indications can still
be provided, with indicators showing when an alarm has been acknowledged One of the engineers must be selected as duty engineer.
in the ECR.
When the alarm system is in the bridge mode, the bridge panel, duty engineer
The operator’s control panel on the bridge differs from the ECR operator cabin unit and mess room units will be active and all alarms will be transferred
panels in that the watch buttons are not shown. to these units.
In The Engineers’ Accommodation ‘Call duty engineer’ is included in the watch calling system and has two
functions.
If an engineer has been assigned to on-call duty (from the ECR), the alarm
Call duty engineers from the bridge
signal will cause a buzzer to sound and an indicator lamp to illuminate, both in
the engineer’s cabin and in the general accommodation. The engineer would Call all engineers from the ECR
then normally go to the ECR to find the cause of the alarm. If the engineer does
not acknowledge the alarm within a specified time, the alarm signal is repeated The functions are independent of watch mode and may be used both in the
in the engineers’ accommodation and on the bridge until acknowledged. engine mode and the bridge mode.
Similar indications (buzzer and lamp) are provided to call an engineer to the
bridge or the ECR when no alarm conditions exist.
The Extended Alarm and Watch Call System comprises machinery alarm
indicators and communication between the ECR, engineers’ accommodation
and the bridge.
The following alarms are provided for both the bridge panel (WBU) and the
engineers’ accommodation panel (WCU). The alarm group indicators are
optional and have the same function for both bridge and engineers’ accommo-
dation panels.
POWER
CONTROL
SYSTEM
& SHAFT
SYSTEM
COOL W.
SYSTEM
AIR & EXH
GAS SYS
BRIDGE
WATCH
ENG.
WATCH
ENG.
ON DUTY
ALL
ENGINEERS
EXH GAS
TEMP
/ * - +
M/E No.1 G/E & No.2 G/E & No.3 G/E & IST 2ND 3ND CALL
FUEL OIL
SYSTEM
GENERATOR
SYSTEM
GENERATOR
SYSTEM
GENERATOR
SYSTEM
ENG.
ON DUTY
ENG.
ON DUTY
ENG.
ON DUTY
DUTY
ENG
7 8 9
GEN. COMMON No.1 No.1 BOILER COMM
ELEC PWR
SYSTEM
BOILER
SYSTEM
BOILER
SYSTEM
& ECON
SYSTEM
4 5 6
STEERING PUMP & E/R DEVIATION
BILGE
SYSTEM
GEAR CRTL
SYSTEM
MOTRO FAIL
SYSTEM
STROAGE
TANK SYS
PARAM.
CONFIG.
1 2 3
NAV & AUTO SELECTED INHIBIT
MISC. FIRE GROUP
SYSTEM SYSTEM
COMM
SYSTEM
LOG
CONFIG.
POINTS
LOG
LOG
POINTS
LOG 0 .
SET SELECTED SELECTED SELECTED
DATE & POINTS BARGR TREND
TIME CONFIG. CONFIG. CONFIG.
Cursor Control
Trackball
3. Extension of the alarms to the bridge and to the engineer on By pressing the button, the buzzer will be deactivated.
Enter:
watch, while in the unmanned condition.
Alarm Summary: Ends a sequence of numeric input / activate editing.
Operator Control Panel (OCP) All active alarms, in all groups, are displayed on the VDU. Up to 20 alarms can
Description be displayed on each page. Previous:
To enable the user to operate the system, different functions are provided. The Displays the previous page of the selected page group.
interface between the operator and the remote operator station consists of An alarm is displayed only once. If the number of alarms fills more than one
graphic displays and control panels. page, turn the pages by activating the NEXT PAGE button. Next Page:
Alarm History: Displays the next page of the selected page group.
The operator control panel is a dedicated functional keyboard, with illuminated
pushbuttons for direct activation of functions. One push will normally activate Displays up to 200 alarms, 20 on each page, with time and date. The latest
one function together with one display. activated alarm is always added to the top of the list and the alarm at the Arrow Keys:
bottom of the list is deleted. To turn the pages, activate the NEXT PAGE Moves the cursor or the field highlighted.
The OCP buttons are grouped into the following sections: button. The page up and page down buttons allow for movement between
Alarm system pages. The unacknowledged active alarms are marked with an asterisk. Standard Functions
POWER
CONTROL
SYSTEM
& SHAFT
SYSTEM
COOL W.
SYSTEM
AIR & EXH
GAS SYS
BRIDGE
WATCH
ENG.
WATCH
ENG.
ON DUTY
ALL
ENGINEERS
EXH GAS
TEMP
/ * - +
M/E No.1 G/E & No.2 G/E & No.3 G/E & IST 2ND 3ND CALL
FUEL OIL
SYSTEM
GENERATOR
SYSTEM
GENERATOR
SYSTEM
GENERATOR
SYSTEM
ENG.
ON DUTY
ENG.
ON DUTY
ENG.
ON DUTY
DUTY
ENG
7 8 9
GEN. COMMON No.1 No.1 BOILER COMM
ELEC PWR
SYSTEM
BOILER
SYSTEM
BOILER
SYSTEM
& ECON
SYSTEM
4 5 6
STEERING PUMP & E/R DEVIATION
BILGE
SYSTEM
GEAR CRTL
SYSTEM
MOTRO FAIL
SYSTEM
STROAGE
TANK SYS
PARAM.
CONFIG.
1 2 3
NAV & AUTO SELECTED INHIBIT
MISC. FIRE GROUP
SYSTEM SYSTEM
COMM
SYSTEM
LOG
CONFIG.
POINTS
LOG
LOG
POINTS
LOG 0 .
SET SELECTED SELECTED SELECTED
DATE & POINTS BARGR TREND
TIME CONFIG. CONFIG. CONFIG.
Display selected bar graphs. Select group then enter or The group is displayed with the tag at The buzzer and the ‘Call from
press the desired group button: the top highlighted. Bridge’ indicator will flash in the
Tag Details: duty engineer’s cabin.
Group/Alarm Toggle Display
Menu for the input and display of alarm and measuring point Select GROUP DISPLAY: See Auto Log. Press SOUND OFF in the cabin: The buzzer is deactivated.
parameter values.
Press GROUP/ALARM: Each press toggles the display To Call all the Engineers
Group Display: between all tags and those in an alarm
Press CALL ALL ENGINEERS on The ‘Call all Engineers’ indicator
Display a group of measuring points. state.
the OCP panel: illuminates on the OCP.
Group/Alarm: Alarm History Display The ‘Call from Engine’ indicator will
Press ALARM HISTORY: The alarm history is displayed. flash on all cabins and mess/day
Toggle between all measuring points and the points currently in room panels and the buzzers sound.
alarm in a group. Change from Attended to Unattended Engine Room
The ‘Call from Engine’ indicator will
Log Functions flash in accommodation and cabins.
Press the button for the engineer The pushbutton illuminates at the
Group Log: on duty: OCP responsible for the watch. Press SOUND OFF: The buzzer is deactivated.
Prints a group of measuring points.
The indicator ‘On duty’ illuminates Change from Unattended to Attended Engine Room
Inhibit Points Log: at the engineer’s cabin.
Press the ‘Engine Watch’ button The pushbutton illuminates and the
Prints all inhibit source signals. The indicator ‘Eng. on duty’ at the OCP: buzzer is activated.
illuminates on the bridge panel.
Auto Log: Configure; The pushbutton ‘Engine Watch’ will
Menu for enabling and adjusting time for printout of auto log. Press BRIDGE WATCH at the OCP: The pushbutton illuminates and the flash on the bridge unit and the
buzzer in the engine room sounds. buzzer is activated.
Selected Points Log:
The pushbutton BRIDGE WATCH Press the ENGINE WATCH button The buzzer on the OCP and bridge
Printing of selected points. on the bridge unit: unit is deactivated.
illuminates on the bridge unit and the
Test Functions buzzer sounds.
Push 1st. ENG button on the OCP The pushbutton light is turned off
Alarm Test: in the engine room: on the OCP in the engine room, the
Press the BRIDGE WATCH button on The buzzers on the OCP and bridge
Alarm test on - press the button. Test off, press the button again. cabin unit and the bridge panel unit.
the bridge unit: unit are deactivated.
NORCONTROL 99-01-23
Automation ALARM SUMMARY PAGE 2 09:56:32
Date Time Tagname Tag Description Func Value Eng. Unit Alarm
Select Alarm No. Will be Displayed when Entering SELECTED ALARM No.
Message Area
The basic screen displays are shown in illustration 3.1.3a. The following functions are included: This function will print all tags configured as auto log. The tag details function
High process alarms (open or closed) shows whether a tag is configured for inclusion in the auto log printout. The
Alarm and Monitoring Displays system will print the tags according to a user configurable timetable.
Return to normal detection
There are several display pages for presenting the alarms and monitored Inhibit Points Log
process values. Time delay of alarm triggering and return to normal messages
The alarm pages comprise the following: Alarm Detection for On/Off Signals with Line Check This function will print all the inhibited alarm/monitoring points
An alarm group display page The following functions are included: Group Log
An alarm summary page, containing a list of all active alarms High process alarms (open or closed)
This function will print a selected group.
An alarm history page, containing a list of time-stamped alarms Line broken alarm
Complete Log
The monitoring pages comprise the following: Line short alarm
A group display containing a list of all measuring points within an Return to normal detection The complete log function will print all measuring points in the system.
alarm group Alarm Summary Log
Time delay of alarm triggering and return to normal messages
A selected point display (and log)
Alarm Indication The alarm summary log prints all currently active alarms.
Tag details giving detailed information about each measuring point
in the system Any alarms detected by the system will be indicated in the lower right corner
Selected Points Configuration
of the VDU. The alarm tag, description and state will also be displayed.
Alarm Group To inspect tags from different groups simultaneously, use the selected points
The following states are used by the system: configuration (configure a text display with items from different groups). A
All alarms and monitored values are divided into alarm groups. maximum of 5 different displays (logs) with 20 measuring points each may be
Alarm States
configured. This display is called a log.
Each alarm can only be represented in one group.
To visually distinguish between the alarm states, different colours have been
used. The meaning of the different colours is listed below: Selected Points Display
Each group is dedicated to one button at the operator control panel (OCP). A
flashing (unacknowledged) or steady (acknowledged) light in the button will Normal state: Green This function will display the tags configured in the selected points
indicate active alarms. configuration.
Alarm state, not acknowledged: Red
Alarms State changed from not acknowledged alarm to normal: Red Selected Trend Configuration
Alarm for Analogue Signals Alarm state, acknowledged: Yellow This function will configure the selected tags for display as curves. A
Alarm state, inhibited: Blue maximum of 5 display screens (trend screens) with up to 8 tag parameters on
The following functions are included: each are available.
System Information Display
Instrument failure alarms
Each tag’s trend curve and data will have a different colour.
Low-low process alarms with action (Shutdown) Activate Logs
Printouts are activated from this menu. Selected Trend Display
Low process alarms
High process alarms Log Functions This function will display the tags configured in the selected trend
configuration.
High-high process alarms with action (Shutdown) The following log functions are available on the OCP:
Return to normal detection with dead-band to avoid fluctuations Selected Bar Graphs Configuration
Selected Points Log
Adjustable filter factors to filter fluctuations in the incoming signals
This function will display the tag values as bar graphs. A maximum of 5
This function will print the information in a selected points configuration. display screens with up to 6 parameter tags each are available.
Time delay of alarm triggering and return to normal messages
NORCONTROL 99-01-23
Automation ALARM SUMMARY PAGE 2 09:56:32
Date Time Tagname Tag Description Func Value Eng. Unit Alarm
Select Alarm No. Will be Displayed when Entering SELECTED ALARM No.
Message Area
The alarm and monitoring points are contained in the following groups and Main engine safety system abnormal
This function will display the tags configured in selected bar graph configura-
tion. their condition can be accessed via the operator station. Some alarms, such as Main engine bridge control power failure
‘situation abnormal’, give a general warning and require the operator to check
the local panel for precise information. Main engine power supply unit failure
Group Display
Main engine oil mist detection failure
Details of the alarms and monitoring system can be found in the manual `Final
This function is for inspecting one or several channels in a group. Values and DWG for ER Monitoring System`, item No IE-13-A in box 28 of the technical Main engine oil mist in crankcase high
alarm limits are displayed. library located in the ECR.
Main engine wrong way alarm
Group/Alarm Group List for the Monitor Display
Main engine auxiliary blower failure
Group 1 MC: Main engine control system
This function enables the display to be toggled between the group display (all Main engine shutdown activated
channels in the group) and the channels which are currently in alarm within Group 2 ML: Main engine LO and shaft system
this group. Main engine slowdown activated
Group 3 MW: Main engine cooling water system
Main engine rpm reduction
Special Functions Group 4 MA: Main engine scavenge air and exhaust gas system
Main engine start failure
Group 5 MF: Main engine fuel oil system
Deviation Parameter Configuration Main engine start air pressure low
Group 6 GA: No.1 generator engine and generator system
This function enables the setting of a low limit for alarm blocking. When a Main engine control air pressure low
Group 7 GB: No.2 generator engine and generator system
cylinder temperature is below the low limit there will be no deviation alarms. Main engine safety air pressure low
The high mean temperature and deviation both low and high may be set. Group 8 GC: No.3 generator engine and generator system
Main engine exhaust valve spring air pressure low
Profile correction is a function for correcting each cylinder temperature. As Group 9 EP: Generator common and electrical power system
Main engine remote control system abnormal
long as the average temperature is used as reference for the deviations, it is Group 10 BA: No.1 boiler system
necessary to correct each cylinder to get the same temperature in all cylinders. Main engine MAPEX/SIPWA unit abnormal
This correction is done during a full load period when all temperatures have Group 11 BB: No.2 boiler system
Load indicator
stabilised. The correction can be carried out automatically, the computer Group 12 BC: Boiler common and economiser system
calculates the value, or it can be done manually. Main engine rpm
Group 13 BS: Boiler system
Passive failure
Repose Groups Group 14 SG: Steering gear control system
Emergency lubrication on
Alarm points associated with a single item of machinery are inhibited as a Group 15 PP: Pump and motor failure system
Auxiliary blower failure
group when that item of machinery is shut down. Group 16 TK: Engine room storage tank system
Main engine slow turn failure
For example: Repose group IH05 is number one generator. When this Group 17 MS: Miscellaneous system
Main engine start blocked
generator is shut down any alarms initiated after the shutdown will be inhibited Group 18 FA: Fire system
until the generator is started again. However, any alarms due to equipment Main engine overspeed
malfunction, such as a wire break alarm, will be initiated. Group 19 NC: Navigation and communication system
Main engine emergency stop switches
Group 25 IH: Inhibit
Main engine shutdown cancelled
Group 28 SYS System
Main engine slowdown cancelled
Group 1 MC: Main Engine Control System
Main engine critical rpm
Main engine electric governor system abnormal
RPM detector failure
Main engine telegraph system power fail
Main engine loop failure emergency stop valves and switches
Main engine telegraph system abnormal
Repose Groups
IH01: Main engine: Finished with engines
IH02: Main engine: Low load condition
IH03: Main engine: Diesel oil used
IH04: Main engine stop
IH05: No.1 generator stop
IH06: No.2 generator stop
IH07: No.3 generator stop
IH08: Generator diesel oil used
IH09: No.1 boiler stop
IH010: No.1 boiler HP mode
IH011: No.1 boiler LP mode
IH012: No.2 boiler stop
IH013: No.2 boiler HP mode
IH014: No.2 boiler LP mode
IH015: Boiler diesel oil used
IH016: No.1 steering gear stop
IH017: No.2 steering gear stop
IH018: Defrosting
IH019: Spare group 1
IH020: Spare group 2
NORCONTROL 99-01-23
Column Information Bar Automation SEL. POINTS TRENDS 1 09:56:32
CA008 STARTING AIR M.E. 1 6.7 MO1 - P15 MAIN ENGINE LOAD 20356
CA014 CHARGE AIR M.E. 1 1.12
CA018 CHARGE AIR TEMP. M. E. 1 143
CA034 SERVICE AIR RESERVOIR PRESSURE 86 Process Values
4
13.3 01.5 108 108 13000
3
2
08.0 01.0 095 85 9000 Scale Values
1
5
Bar graphs can be configured to display values. Press 1 then press enter. The trend curves will then be
displayed. The sampling interval is
Up to 5 trend curve screens can be displayed with 8 parameter tags displayed 30 seconds.
simultaneously on the screen. Press SELECTED TREND DISPLAY Enter trend display time: will be
twice for changing sample displayed in the bottom left of the
Up to 5 bar graph screens can be displayed with 6 parameter tags displayed time window. screen.
simultaneously on each screen.
There are two CRT displays and two selector panels so it is possible to have Set the new sample time The display will be updated and sampling
two sets of data selected at any one time from display or trending. Both CRT starts
displays may be programmed in the same way using their dedicated
programme and display selection panels. The two displays may select from the Select Bar Graph Configuration
same menu of engine and auxiliary machinery data. Action Result
Press SELECT BARGRAPH The prompt ‘Log no:’ is displayed
Data is normally sampled every 30 seconds from each sensor point and the configuration. at the lower left.
display is automatically updated after 30 seconds; the sampling time may be
changed. Trending graphs enable changes in operating conditions to be Press LOG No. and ENTER Add Delete: is displayed at the top
observed over long and short periods of time and if the two displays are used of the screen.
together long and short term trending may be observed. It should be
remembered that if the trending selection time is reduced the data collected Use the arrow key to highlight Select group: is displayed in the
over the longer time will be lost. ADD then press ENTER. lower left of the screen.
Procedure for the Operation of the Trend and Bargraph Functions Press one of the groups to The tags of the selected group are
Action Result configure. displayed on the right hand side. Use
Select Trend Configuration. NEXT PAGE to scroll if necessary.
Press Select Trend Configuration The prompt ‘Log no:’ will be
displayed in the lower left of the Use the arrow key to highlight The tag is displayed in the left side
screen. the tag and then press ENTER. of the screen.
Press LOG No and then Add Delete: is displayed at the Delete function will be as for the ‘Add’, starting from first operation point.
press enter top of the screen.
Use the arrow key to highlight Select group is displayed in the lower Tag Details Display
ADD then press ENTER left of the display.
Action Result
Press one of the groups to The tags of the selected group are Push GROUP DISPLAY. Select group: will be displayed on the
configure displayed on the right hand side. Use lower left side of the display.
NEXT PAGE to scroll when necessary.
Select a group, then ENTER or The group is displayed with the tag
Use the arrow key to highlight The tag will be displayed on the left press a GROUP button. at the top highlighted.
the tag and then press ENTER. side.
Push Tag details. The display is shown opposite.
Bridge
Watch
X10 / X15 Bridge
Unit
X16 WA / X16 WB
WBU AUTOMATION
Watch Bridge Unit
M.E. REPEAT
BRIDGE COMMON
LOW LOAD
SYSTEM MACHINERY
CONDITION ALARM
WCU WCU A-WCU WCU WCU
BRIDGE
WATCH Chief Eng. 1st Eng. 2nd Eng. 3rd Eng. Officers'
Mess Room
CONTROL
SYSTEM
ROOM
FAILURE
WATCH BZ BZ BZ
Buzzers
2ND
CALL ENG.
ALL ON DUTY
ENGINEERS Engine Control Room
3RD
SYSTEM ETO COMM.
ENG.
FAILURE ON DUTY ERROR
ON DUTY
SOUND
OFF
TEST
FAIL
SAFE
CALL
DUTY
CABIN
ACK.
WCU AUTOMATION
1X 16.5 1X 16.5
ENGINEERS Watch Call Unit
Main Main
Computer Computer
Unit No.1 Unit No.2
Watch Bridge Unit Panel Cabin and Mess Areas Watch Call Unit Panel Watch Call System Overview
a) When summoned by the extension alarm system, the duty j) The duty engineer proceeds with the normal inspection.
engineer proceeds to the Engine Control Room.
(Note ! It is essential that the duty engineer imparts as much information as
b) The duty engineer ensures that the patrol man alarm system has possible to the relieving engineer if the ship is to continue in manned engine
been activated. room mode. Verbal and written information should be presented and the duty
engineer must be satisfied that the relieving engineer is fully aware of the
c) The duty engineer informs the bridge of manned condition and engine room situation before the engineer going off duty leaves the engine
the alarm cause. room.)
d) The duty engineer switches watchkeeping control to the ECR. The keynote to the safe operation of the ship is information transfer and any
matter relating to the operation of the engine room must be recorded for
e) The duty engineer rectifies any alarm conditions and if imparting to a relieving engineer. The bridge must be kept informed as to
necessary, calls for assistance. changes in engine room manning personnel.
Normal Handover
b) The patrol man alarm should be in use until the arrival of other
members of the ER personnel.
.
c) The duty engineer informs the bridge of manned condition.
Filing Fire
Cabinet Water Mist Notice Extinguisher
Control Panel Board
Blackboard Tank Sounding
Unit Board
Cooler Mapex
Pipe Computer
Table Engine Control Console Cabinet
Cover Desk
Unit Cooler Pipe Cover
With Lifejacket Box
Unit
Cooler Smoke
Detector Unit
Cooler
Smoke
Air Air
Detector
Diffuser Diffuser
Main Switchboard
Escape
Thermal
Filing Cabinet Trunk
Detector
REGULATOR ACTUATOR
CHANGE
DGU 8800e
DIGITAL GOVERNOR UNIT
CONTROL
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
ERGENC
EM
Y
CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV CMD RPM PITCH SCAV
STATUS WARNING
STOP
CONTROL CONTROL
ETU
AutoChief 4 CONTROL
CONTROL
REGULATOR ACTUATOR
AUTOMATION
DGU 8800e
DIGITAL GOVERNOR UNIT
CONTROL
CONTROL
The engine control console contains the following equipment: Main engine standby rpm indicators
Main engine control, telegraph, safety and governor units Main engine fuel pump mark (load) indicator
Upper Deck
BF34 BF33 BF67 BF68 Nav. Deck
Cable Washers
BF35 BF65 BF66 E Deck To (P&S)
Bosun
From Bilge
Store
Engine BF63 BF64 D Deck Eductor
In
Room Void
Chain
PI BF61 BF62 C Deck Space Locker
Void
BF59 BF60 B Deck Space
Key
Hydraulic Oil
To Alarm Monitor In
Engine Control Room
P P P P P P
PS PI Vent Vent
M M Stop M M Stop
Engine Pump
Room Room
244 Bottles
P P P P P P
P P
Power Supply
83 Bottles AC 220V
Required Quantity Of Cylinders
To CO2 Alarm
Total: 327 Bottles
Engine Room: 327 Bottles
Key
Pump Room: 83 Bottles
CO2 Cylinder
Vent Vent
Engine Room M M Stop M M Stop
Pilot Cylinder
Steering Gear A
Room
Instruction
Chart
Workshop A
Key Box
Engine Control A
Console Room Electrical Signal
Purifier Room A
Accommodation Space Pilot Line
Floor E
Relay Box
7kg/cm2
No.1 Diesel E Air Supply
Generator Room
No.2 Diesel E
Generator Room
Pump room 5,180 3,700 83 l) Open valve No.2 which operates the gang release system. f) Ensure that all personnel have evacuated the pump room and have
been accounted for.
The main system consists of a rack of 327 high pressure cylinders each of 45kg m) All cylinders will release after a short time delay and discharge
capacity. into the engine room. If the system fails to operate, the main valve g) Close all doors, hatches and fire flaps.
can be opened manually from the CO2 room and the cylinders
Main Engine Room CO2 Flooding System released by hand. To open manually, turn the main handle as h) Open one pilot cylinder valve.
marked on the valve handle, remove the safety pin on the actuator
Maker: NK Fire Protection Ltd and pull the lever downwards. i) Open valve No.1, which opens the main isolation valve.
Type: High pressure
Capacity: 327 cylinders each containing 45kg n) Do not re-open the engine room for at least 24 hours. Do not re- j) Open valve No.2 which operates the gang release system.
Discharge time: 90% of CO2 charge in 2 minutes open the space until all reasonable precautions have been taken.
Maintain boundary inspections, noting cooling down rates and/or k) All cylinders will release after a short time delay and discharge
WARNING any hot spots which may have been found. After this period, an into the pump room. In the event of failure to release CO2 charge
Release of CO2 into any space must only be considered when all other assessment party donning breathing apparatus can enter the space at the fire control station go immediately to the CO2 room release
options have failed and then only on the direct instructions of the Chief quickly through a door which is then shut behind them. Check cabinet.
Engineer who will have consulted the Master. that the fire is extinguished and that all surfaces have cooled prior
to ventilating the engine room. Premature opening could cause re- l) Allow time for the CO2 to extinguish the fire and the space to cool
ignition if oxygen contacts hot combustible material. down.
Isolating Valve to
the Pump Room
Isolating Valve to
the Engine Room
CO2 Room
Should any cylinder discharge accidentally, it will pressurise the main line up
to the stop valve. This line is monitored by a pressure switch which will
activate the CO2 alarms. Overpressure of the main line is prevented by a safety
valve, which will vent the gas to atmosphere.
Should the system power supply fail, the CO2 POWER FAILURE alarm will
operate in the control room.
(Note ! All the ship’s officers must be familiar with the operation of the CO2
system and understand fully the steps required to be taken before release of
CO2 into the engine room or pump room. All ship’s personnel must be familiar
with the alarms which indicate that the CO2 system is about to operate.)
After the CO2 system has been activated the charge will have been used and
there is then no CO2 smothering system available until the system is recharged
as soon as possible after use.
To Safety
Area
Generator Engine Generator Engine Incinerator Incinerator Incinerator
PAL Lubricating Oil Lubricating Oil Marine Waste Oil Waste Oil
PS Settling Tank Storage Tank Diesel Oil Service Tank Settling Tank
MC Generator Engine
Group No.1
PI Air
Bottle Main Engine And Other Groups
for Group No.2 L-79V L-17V F-293V F-292V F-291V
Emergency
N.O. Shut-Off
Valve
MDO
M25V M30V Service Tank
Engine Room
Fan (Starboard) Purifier Room
Exhaust Fan
M28V M33V
Funnel Louvre
Funnel Louvre (Port)
(Starboard)
Inner Outer Outer Aft Forward
Heavy Fuel Oil Heavy Fuel Oil Heavy Fuel Oil Heavy Fuel Oil Heavy Fuel Oil
Bunker Tank Bunker Tank Bunker Tank Bunker Tank Bunker Tank
M29V M34V (Port) (Port) (Starboard) (Starboard) (Starboard)
Funnel Louvre
(Port)
Key
Engine Room Ventilation Damper
Air
Issue: 1 4.3 Quick Closing and Remote Closing Valve System Page 1 of 2
Cylinder oil measuring tank Outlet valve L118V Open Line valve to funnel louvers (starboard lower) M29V
The tanks are grouped into two systems with a single control three-way valve
operating each system. In normal conditions the control valve is set so that the Cylinder oil storage tank No.2 Outlet valve L116V Open Line valve to funnel louvers (starboard upper) M28V
line connecting to the valves in that group is vented to atmosphere. However, Open Line valve to engine room fan (starboard aft) M27V
Cylinder oil storage tank No.1 Outlet valve L150V
when the valve is opened, air is supplied to the group line and to a piston on
each valve in the group causing collapse of the bridge of the valve which MDO storage tank Outlet to MDO purifier pump F33V Open Line valve to engine room fan (starboard fwd) M27V
results in its immediate closure. Open Line valve to welding area exhaust fan M25V
MDO storage tank Outlet to IG generator and boiler F108V
The valves are reset by venting the valve group air supply line and operating No.1 HFO service tank Outlet to boiler F304V Open Line valve to funnel louvers (port upper) M34V
each valve handwheel in a close direction to reset the bridge mechanism and Open Line valve to funnel louvers (port lower) M35V
then opening the valve in the normal way. No.1 HFO service tank Outlet to purifier pump F31V
No.2 HFO service tank Outlet to boiler F305V Open Line valve to engine room fan (port aft) M33V
The fire dampers fitted to various rooms are kept open by means of air pressure Open Line valve to engine room fan (port fwd) M32V
acting on the damper cylinder. The pneumatic cylinders are supplied through a No.2 HFO service tank Outlet to purifier pump F30V
three-way control valve directly from the air inlet line to the quick-closing HFO settling tank Outlet to boiler F306V Open Line valve to purifier room exhaust fan M31V
valve air reservoir. The control valve is set so that that the air supply line to the Open Line valve to generator engine room exhaust fan M30V
damper cylinders is normally pressurised. Venting the damper air line removes HFO settling tank Outlet to purifier pump F32V
air pressure from the damper cylinders and allows the balance weights to close Fore HFO bunker Outlet Valve F85V a) Open the air line master valve. Open the line cock 36V. This will
the dampers. Dampers may be closed by operating the damper control valve in immediately open the exhaust and supply fan dampers.
Aft HFO bunker Outlet valve F16V
the fire control station or by operating the damper control valve, M36V located
tank Starboard
just outside the engine room casing door on the upper deck. Dampers have b) Close the individual line cocks as required.
individual three-way valves which may be operated individually to close Outer HFO bunker Outlet valve F1V
particular dampers. tank Starboard Remote Opening and Closing Valves
Outer HFO bunker Outlet valve F2V
The main sea water suction and overboard valves are opened and closed Hydraulically operated sea valves operated remotely from deck stands.
tank port
remotely from their hydraulic control deck stands, on the 2nd deck for the
suction valves and the 3rd deck for the overboard discharge valves. Inner HFO bunker Outlet valve F17V Valve Description Valve Location of Remote
tank port Control
The emergency generator diesel oil tank quick-closing valve is operated by a
directly connected wire from outside the emergency generator room. Group 2 Generator Engine Valves High sea chest (port) SW suction S2V 2nd Deck
Low sea chest (starboard) SW suction S1V 2nd Deck
Generator engine LO Outlet valve L17V
storage tank Vacuum condenser SW overboard S69V 3rd Deck
Generator engine LO Outlet valve L79V Atmospheric condenser SW overboard S21V 3rd Deck
settling tank
Issue: 1 4.3 Quick Closing and Remote Closing Valve System Page 2 of 2
To Paint Store
CI PI
D3V D4V
D54V D55V S S S
D56V
Fresh Water Spray Pump
(54m3/h)
Fire Water
D7V
The fire spray pump takes its supply from the domestic FW tanks (port
253.26m3, starboard 142.78m3) or if necessary the stern tube cooling water
tank (82.78m3). Fine spray nozzles are strategically placed around the
protected areas, giving a water mist blanket. Due to the potential hazard
involved in using this system in the purifier and generator areas, it is
imperative that all the appropriate electrical supplies have been shut down
prior to use.
The discharge branch lines to the protected areas are each isolated by
individual solenoid valves which are operated from the fire control station or
the control panel in the ECR. The spray pump is fed from the emergency 440V
switchboard and is started from the fire control station or bridge.
If necessary it is possible to supply the spray system from the SW fire main
system via isolating valve D56V.
Operation
Should a fire occur in any of the above spaces, the procedure is as follows:
Spray Pump and Discharge Mainfold
a) Ensure all personnel are clear of the area.
Spray Pump Start and Valve Selection Panel in the
b) Shut down the machinery and electrically isolate the area in the Engine Control Room
compartment on fire.
Located On A
Deck
FM08
No.5 Water Ballast Tank No.4 Water Ballast Tank No.3 Water Ballast Tank No.2 Water Ballast Tank No.1 Water Ballast Tank
(P&S) (P&S) (P&S) (P&S) (P&S)
Slop
Tank
No.5 Wing COT No.4 Wing COT No.3 Wing COT No.2 Wing COT No.1 Wing COT
(P)
(P&S) (P&S) (P&S) (P&S) (P&S)
For Fresh
Water
Flushing FM29 FM27 FM25 FM23 FM21 FM19 FM17
Foam Tank
FM38 FM34
FM37 FM35
FM31
Filter
To FM36
Accommodation
Foam
Bosun's
Pump Void Store
FM33 FM07 FM06 FM05 FM04 FM03 FM02 FM01
BF36 BF34 Proportionator FM16
Pump
Slop
B18V B17V Tank Foam
Bilge, Fire (S) Applicator
and GS Pump No.1 No.2 Bilge, Fire
and GS Pump
FM09
Key
Fire Water
Foam Liquid
Located On A
Deck
Foam Mixture
FW Flushing
Foam for fire fighting purposes is supplied to the main deck, when required, g) Open the monitor or hydrant valves as required and fight the fire.
from a single 6,000 litre foam tank situated in the foam room located on the
Fighting Oil Fires on Deck
starboard side of the accommodation at the upper deck level. Foam compound
is supplied from the tank, via a foam liquid pump, to an automatic proportion-
Never direct the foam mixture directly on to the burning oil as this will cause
er, where it is automatically mixed with the correct proportion of sea water and
the oil to splash and spread the fire.
then supplied to the deck foam main.
Direct the foam mixture to flow over the surface of the burning oil, so that it
The proportioner mixes the foam compound and sea water in the ratio of 3% gradually covers and smothers the fire. Use the prevailing wind or slope of the
foam compound to 97% sea water. deck to assist the flow wherever possible.
The sea water is supplied from the fire main. The foam main runs the length of Use one monitor and/or two applicators to fight the fire. If more are used, the
the main deck and supplies nine foam monitors sited so that the entire deck effectiveness of each unit will be reduced.
area can be covered. Seven of the monitors are on the centre line on the deck
itself and two are at the forward corners of the accommodation block. Foam Stopping the System
hydrants are fitted to the foam supply pipes branched off before each monitor
for use with hoses. They are situated at both sides of the vessel. Isolating a) Stop the fire pump and foam pump.
valves, which are normally open, are fitted to the foam main just forward of
each monitor to enable damaged sections of the main to be isolated, so b) Close foam tank outlet valve FM34 and sea water supply valve
allowing the system aft of the damaged section to operate normally. BF34 to the foam main.
The foam hydrants are used with hoses and foam nozzles when required. The c) Open flushing valves FM37 and FM35, and connect the fresh Foam Pump
foam mixture is aerated at the foam monitors and nozzles to give the required water supply hose from valve FM38.
consistency. The hoses and nozzles can be used to supply foam to the cargo
tanks if required. Sets of portable foam making branch pipes are stored in d) Start up the fresh water and foam pumps, operate the forward
labelled cabinets along the main deck for use with the foam if required. monitor on the deck until clear fresh water is discharged. Then
operate all other monitors for a few seconds.
The capacity of the deck foam system is designed to give 20 minutes operation
of one monitor supplying 9,042 litre/min of foam mixture. The selected e) Stop the fresh water and foam pumps.
monitors have a capacity of 7,000 litre/min with a throw of 62 metres in still
f) Revert all valves to the standby position, ensuring that flushing
air at an inlet pressure of 5 bar.
valves FM35 and FM37 are closed. All valves in the foam room,
monitor inlet valves and hydrant valves should be closed. All
Operation of the Main Deck Foam System
intermediate valves between the monitors and the pressure gauge
cock in the foam room should be open.
Procedure for Fighting a Fire, after First Raising the Alarm
g) Refill the foam tank as soon as possible.
a) Supply sea water to fire main.
b) Open the sea water inlet valve BF34 to the foam main.
c) Confirm that the flushing valves FM35 and FM37 to the foam
pump are closed.
Operate all ship’s side valves regularly, so that they can be operated easily
when required. Valves such as fire pump suction valves, which are normally
open, should be closed regularly to prevent a build up of marine growth.
Ensure that hydraulic valve actuation systems function correctly. Check valve
packing and ensure that there is no leakage.
Before opening sea water filters for cleaning, make sure the shut-off valves are
shut tight by opening the vent in the filter box cover. In any case break the
cover joint before removing all cover bolts. The same applies when opening
coolers and pipelines anywhere in the system. If a valve is not fully closed
there will be appreciable leakage and because the bolts/nuts are still in place it
is possible to retighten the cover.
Personnel should be familiar with the position of bilge suctions and the pumps
that can be utilised for bilge pumping duties. They should also be familiar with
the position of main sea suction and overboard discharge valves and know
which main suction is currently in use.
REMOTE CONTROL
10
START A
H 9
E
A 8
0
RUN D
2 1
7 AUX BLOWERS SAFETY SYSTEM
Fuel Rack
3
No 1 No 2 No 3
4
6 Regulating Rod
5
RUN AFT FWD SHUT
OVER
SLOW
6
DOWN DOWN
RUNNING RUNNING SPEED
7
REMOTE ACTIVE ACTIVE
5
8
CONTROL
9
10
4 PRE PRE
SHUT EMERG RESET
Load Indicator SELECT SELECT
DOWN
CANCEL
STOP SAFETY
-LED ACTIVE SYSTEM
3
RUN A
S 2 SHUT EMERG LAMP
T OFF OFF DOWN
CANCEL STOP TEST
E
R 1
START N
0
STOP
REMOTE
CONTROL
ETU EMERGENCY SYSTEM NOR
Connecting Rod Engine Telegraph Unit CONTROL
EMERGENCY REMOTE
SUBTELEGRAPH MODE CONTROL
Detail of Plate TELEGRAPH
STAND
FWE FAOP FULL
BY
A
H HALF
E
A SLOW
D DEAD
SLOW
NOR
ETU EMERGENCY SYSTEM CONTROL
Engine Telegraph Unit
CONTROL LOCATION
FULL STOP
EMER
A Fuel Control GENCY
NORMAL
DECREASE INCREASE
Lever (3.12)
H HALF
TELEGRAPH STATUS
E
DEAD
A SLOW NEW
COMMAND
A SLOW
MANUAL
FEED
CONTROL
D DEAD Manoeuvring Control S
SLOW SLOW
Lever (5.03) T
E
HALF
CONTROL LOCATION SYSTEM
R
EMER STOP
LAMP SOUND INTERNAL
N
NORMAL FULL
GENCY TEST OFF FAILURE
TELEGRAPH STATUS
Stop / Run
Lever (5.07)
NOR
CONTROL
NEW DEAD
COMMAND
A SLOW
S
SLOW
T
E
HALF
SYSTEM
R
LAMP SOUND INTERNAL
N
FULL
TEST OFF FAILURE
Pump Control
Knob
Unloading Control Valves with Lock Ring Steering Gear Pump Control Knob Mounted on Torque Motor
General Description
The steering gear is fitted with an automatic safety system. This system is used
to isolate the hydraulic power circuits in the event of a hydraulic oil loss from
the oil tanks or other part of the hydraulic system.
In accordance with IMO regulations, the hydraulic pumps used in the steering
gear are supplied with power from two independent sources. In the event of
power failure from the main switchboard both pumps can be supplied from the
Emergency Switchboard.
b) At the rudder servo unit, located on the port side of the steering
gear compartment, turn the switch to the LOCAL position.
! CAUTION
When operating under local control the rudder angle limiter does not
function and so the rudder must not be worked over its maximum angle
of 35º.
Electric Motor
Non-Return Valve
Fire Pump
Unit
Hydraulic Motor
Manufacturer: IMO, Sweden
Model: D4F 038N-LRBE-A070
AUS Stripping Pump System Emergency Fire Pump Discharge Line
Drain Tank
The emergency fire pump is located in the pump room at bottom plate level,
its drive coming from the directly mounted hydraulic motor. The location of
the pump ensures that there is always a positive suction head even under light
ship conditions. Hydraulic pressure to drive the pump motor comes from the
electrically driven hydraulic pump unit mounted in the steering gear room. A
cooler is provided for the hydraulic system, cooling water being taken from the Emergency Fire Pump Sea
pump discharge. Suction Isolating Valve BF45V
The pump is fed from the emergency switchboard 440V feeder panel located
in the emergency generator room.
Starting and stopping the pump can take place from three locations; Emergency Fire Pump Sea Suction
Weed Blow Valve A20V
Locally at the hydraulic pump unit in the steering gear compartment.
The emergency fire pump draws from an independent sea water chest, in which
the pump suction valve and discharge valve are always maintained in an open
position. The pump discharges into the fire main.
Emergency Fire Pump Sea Suction and Weed Blow
The pump and suction valves should be operated and lubricated weekly. The
pump suction line can be proved clear by use of the steam blowing line.
Fireman's Fireman's
Outfits Outfits
Locker Locker
Box For
International
Shore
Connection
CO2 Release
Cabinets,
Engine Room Cargo Control
and Console
Pump Room
Emergency
Stop
Buttons
Emergency Shut-Off
Valve Control Box Ships Control
Centre
i) Activate the emergency shutdown system in agreement with the d) Start the emergency generator and put on load.
terminal duty personnel.
e) Trip the quick-closing valves and the engine room auxiliary
j) Conduct a crew check. machinery from the fire control centre.
k) Organise the crew for fighting the fire. f) Count all personnel and ensure that none are in the engine room.
l) Inform the local fire brigade even though the fire appears to be g) Close all fire flaps and funnel doors.
under control.
I.S. Power
Power Source (AC 220V)
Supply
Cargo Pump
Turbine Area
Wall Type Flush Type Wall Type Desk Type Telephone and Alarms
Bell
Cargo Pump
Satcom Turbine Area
Selector
For Shore Connection
Remote Alarm
Cargo Control
Automatic
AC 110/220V Room Telephone
Telephone Exchange
Power
Source DC 24V Cargo Control
Room Selector
To Public
Address System
Pump Room
Wall Type Wall Type (Hazardous Area)
Beacon
Bell Bell
Air Horn S
Air
(8kg/cm2)
Junction
I.S. Selector
Box
I.S. Telephone
Generator Handle Wall Type
Emergency Terminal Box
Bell Rotary
Light Horn Pump Room Entrance
Headset
Relay
Box
Sound Powered Telephone Automatic Telephone System Intrinsically Safe Telephone System
Rotating lights and horns are activated in the machinery spaces when the
b) Set the station selector to the required extension number.
engine room telephones are accessed.
c) Turn the call generator handle until a loud beep is heard at the
Telephones on the vessel are divided into four classes of service:
user’s own station (approximately 10 turns).
‘A’ class telephones have the following facilities:
d) Duplex communication is now possible for approximately 15
minutes. Speech time may be extended by winding the call
Extension to extension calling
generator handle again.
Paging facility via the PA system
Stations within machinery spaces are fitted with headsets to provide commu-
nication within the noisy environment. The headsets are selected by operating Priority
the headset/handset toggle switch on the telephone unit. Trunk access
Intrinsically Safe Telephone System ‘B’ class telephones have the following facilities:
The two telephones in the pump room (one in the entrance area) can call and ‘D’ class telephones have the following facility:
receive from the cargo control room and the cargo pump turbine area.
Extension to extension calling
M M
M
M Microphone
Aft Mooring Deck Public Address System Central Control Unit G/A
Alarm Emergency
Out General
Alarm Stop
DC 24V In
From Automatic
Telephone
Exchange
Steering Gear
Manufacturer: Marine Radio Co. When the SPEAKER SELECTOR button is set to the EMERG position, the The public address system can be activated from the telephone system for
Type: MPA-2100A emergency announcement is made through all cabins, passages and machinery paging purposes if required.
spaces. In this case the volume setting is neglected and the maximum setting
The public address system is provided to communicate important announce- is automatically used.
ments throughout the vessel. Speakers are provided in the accommodation
alleyways, public rooms, working spaces and outside decks. There is a facility Illustration 6.2b Public Address Unit
to play a radio tuner or a cassette from the unit in the wheelhouse. The system
is supplied from the main 220V system with back up from the emergency 24V
system. EJECTOR
Public announcements may be carried out from the control panels installed in
the wheelhouse and ship’s control centre. Broadcasting is selected from the UP VOLUME
AUTO REVERSE 100:C CASSETTE
M1 M2 M3
selection switch mounted on the control panel. TUNE POWER
M4 M5 BAND DOWN
There is a talkback facility to allow the system to be used for communication SCAN BAND ENTER
during docking etc. The forward and aft mooring decks have microphones and ENTER ALARM TIME
The shipboard management system exists to ensure that the vessel is managed
safely and efficiently.
Meetings are held at regular intervals to ensure all personnel are aware of the
objectives of the system.
A safety meeting is held each month, with a minimum of one meeting every 3
months.
Main Engine Jacket Cooling Fresh Water Pump Boiler Water Circulating Pump
Maker: Shinko Maker: Shinko
Type: SVA 200M Type: BT 40-5
Capacity: 262m3/h at 30 mth Capacity: 16m3/h at 40 mth
Rating: 37kW at 1,800 rpm Rating: 5.5kW at 3,600 rpm
Auxiliary Sea Water Cooling Pump Main Engine HT Circuit Feeding Pump
Maker: Shinko Maker: Shinko
Type: SVA 250M Type: GJ40-25M
Capacity: 400m3/h at 23 mth Capacity: 0.5m3/h at 75 mth
Rating: 37kW at 1,800 rpm Rating: 5.5kW at 3,600 rpm