0% found this document useful (0 votes)
142 views11 pages

A Novel Open-Circuit Fault Detection and Location For Open-End Winding PMSM Based On Differential-Mode Components

Uploaded by

malini72
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
142 views11 pages

A Novel Open-Circuit Fault Detection and Location For Open-End Winding PMSM Based On Differential-Mode Components

Uploaded by

malini72
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

7776 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO.

8, AUGUST 2022

A Novel Open-Circuit Fault Detection and


Location for Open-End Winding PMSM
Based on Differential-Mode Components
Chunyang Jiang , Hongchen Liu , Member, IEEE, Pat Wheeler , Fellow, IEEE,
Fengjiang Wu , Senior Member, IEEE, Zhe Cai, and Ju Huo

Abstract—Detecting and locating the open-circuit (OC)


fault of an insulated-gate bipolar transistor (IGBT) rapidly
and accurately is very important to improve the security
and reliability of the drive system. However, due to the sym-
metry of the dual-inverter topology, it is difficult to achieve
fault detection for open-end winding permanent magnet
synchronous motor (PMSM). Thus, this article proposes a
fault diagnosis technology for open-end winding PMSM fed
by a dual inverter with a common dc bus. In this method,
the faulty phase and the faulty case are identified by the Fig. 1. Open-end PMSM fed by a dual inverter with a common dc bus.
average value of the output of the closed-loop controller,
which is used to eliminate the differential-mode current in
the system. Then, the faulty phase is isolated by remov- voltage utilization and fault-tolerant capacity, open-end wind-
ing the gate signals. Finally, the faulty IGBT is located by ing PMSM fed by a dual inverter has been adopted in many
restructuring the faulty phase and analyzing the current applications [1]. In addition, multilevel voltage modulation and
of the faulty phase. In this method, the OC fault can be abundant vector combination can also be achieved [2]. Two kinds
detected and the faulty IGBT can be located accurately.
Experimental results are shown to validate the proposed of open-end winding PMSM dual-inverter topologies exist [3].
detection method. However, a bulky isolation transformer is always needed in the
topology with two isolated sources, which can result in high
Index Terms—Average value, fault detection, open-
circuit (OC) fault, open-end winding permanent magnet
cost and large size. Therefore, the dual-inverter topology with a
synchronous motor (PMSM), proportional-resonant (PR) common dc bus is more suitable for industrial applications, as
controller. shown in Fig. 1.
A power electronic switch device is the most fragile com-
ponent in power converters, especially in extreme operation
I. INTRODUCTION conditions, such as abnormal conditions, bad environments, high
PERMANENT magnet synchronous motor (PMSM) has power stresses, system transients, and heavy loads. According
A been widely used in many areas, such as electrical vehi-
cles, subway, and electrical aircraft. Compared with an induction
to a converter fault investigation report, which includes more
than 200 devices from 80 companies, almost 60% of failures
motor, the PMSM has the advantages of high power density, are caused by the power electronic switch device [4], [5]. The
high efficiency, and high torque density. In order to increase the failure of the device may lead to performance degradation,
economic losses, and system shutdown. Therefore, it is impor-
Manuscript received January 19, 2021; revised April 16, 2021 and tant to develop a fast detection technology to increase system
June 4, 2021; accepted June 25, 2021. Date of publication August 26, reliability.
2021; date of current version March 1, 2022. This work was supported In general, open-circuit (OC) and short-circuit (SC) faults are
in part by the National Natural Science Foundation of China under Grant
51777043 and in part by the State Key Laboratory of Electrical Insulation the most common fault forms. Compared with the OC fault, the
and Power Equipment under Grant EIPE18208. (Corresponding author: current of the device in the SC fault is much higher than the
Hongchen Liu.) rating current, so the SC fault is more destructive and easier
Chunyang Jiang, Hongchen Liu, Fengjiang Wu, Zhe Cai, and Ju
Huo are with the School of Electrical Engineering and Automa- to be detected. Thus, industrial drives always have a standard
tion, Harbin Institute of Technology, Harbin 150001, China (e-mail: hardware circuit to protect the device, and the gate drive pulse
[email protected]; [email protected]; [email protected]; of an insulated-gate bipolar transistor (IGBT) would be cutoff
[email protected]; [email protected]).
Pat Wheeler is with the Department of Electrical and Electronics Engi- when the SC fault happens. As to OC faults, they can cause
neering, University of Nottingham, Nottingham NG7 2RD, U.K. (e-mail: distorted current and decrease the performance. If they are not
[email protected]). detected immediately, they can result in secondary faults. Hence,
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TIE.2021.3101005. the detection methods of the OC fault attract more attention to
Digital Object Identifier 10.1109/TIE.2021.3101005 ensure safe operation.
0278-0046 © 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
JIANG et al.: NOVEL OPEN-CIRCUIT FAULT DETECTION AND LOCATION FOR OPEN-END WINDING PMSM 7777

Fig. 2. Equivalent circuit of phase A.

A number of OC fault detection methods for a conventional


motor have been proposed in recent years. These methods can
Fig. 3. Space voltage vectors of the dual inverter.
be classified into voltage-, current-, and model-based methods.
As to the voltage-based methods [6], they can achieve fast detec-
tion. However, additional hardware circuits are needed, which current values should be calculated to detect the faults, not only
increase the system cost and volume. As to the current- and in normal condition but also in faulty condition. All of these
model-based methods, they are usually cheap and noninvasive, would lead to a heavy burden for the DSP.
so they can be widely used in the drive systems of the PMSM. No previous research has considered the OC fault in the
Park’s vector method and the average current Park’s vector open-end winding PMSM system. Because of the existence of a
method are reported in [7] and [8]. The normalized current dc zero-sequence circuit and the symmetry of each phase, detection
component method is presented in [9]. In order to decrease the methods of the conventional three-phase PMSM cannot be
load effect, a diagnosis method is proposed in an induction motor applied directly. In this article, the differential-mode voltage
drive based on the Concordia stator mean current vector [10]. generated by the dead time and the output of the PR controller
Frequency- and time-domain processes are applied to obtain are analyzed. And a method with two main steps is proposed
the harmonic of the fault [11]–[13]. Jlassi et al. [14] present a for the open-end winding PMSM driving system to detect and
technology to detect the multiple-IGBT OC fault and the current locate the faulty switch. The rest of this article is organized
sensor fault. A dc flux injection method for fault detection as follows. In Section II, the model and current features of
in a direct-torque-controlled PMSM is presented in [15]. A the open-end winding PMSM are analyzed. In Section III,
cost-function-based OC fault detection method is studied for the features of the output of the zero-sequence controller are
a conventional PMSM driving system, the output of the cost analyzed to detect the fault case. In Section IV, the method to
function in the model-predictive current control is utilized to locate the IGBT with the OC fault is shown. The experiments are
monitor system conditions, and the phase angle difference is verified in Section V. Finally, Section VI concludes this article.
used to judge the fault phase [16]. In [17], an OC fault diagnosis
method based on the fuzzy logic is proposed for the PMSM II. MODEL OF AN OPEN-END WINDING PMSM
using average current. A method based on small low-frequency
information of currents for a multiswitch fault is proposed in A. Voltage Vectors and Zero-Sequence Current
[18]. Detection methods are also proposed for the multiphase As shown in Fig. 1, the output voltage of the dual-inverter
PMSM in [19] and [20]. topology can be obtained, and it can be expressed as
As to open-end winding PMSM driving systems, studies
are about fault-tolerant control [21]–[24]. In [21], a simplified Uo = U1o − U2o . (1)
tolerant modulation strategy under fault condition is proposed.
In this method, the circulating current can be suppressed. In [22], Considering that each inverter can generate eight voltage
Song et al. propose a fault-tolerant predictive control strategy vectors, the number of possible voltage vectors for the dual
without reconfiguration. However, few detection methods are inverter is 64. The space voltage vector distribution is shown
reported. In the existing detection methods for the conventional in Fig. 3. The eight voltage vectors of inverter I are referred as
PMSM, some based on current or voltage can be used in this 1–8, and the eight voltage vectors of inverter II are referred as
topology. However, they should be modified or need more 1 –8√
. According to [25], the medium vectors with the amplitude
hardware circuits for the open-end winding PMSM. Besides, of 2 3Udc /3 are used to obtain the reference voltage vectors,
the four IGBTs of one leg, as shown in Fig. 2, are symmetrical. which are in red color in Fig. 3.
The currents under the OC fault of S11 and S22 are the same. It According to [26], in the system of the open-end winding
is hard for conventional detection methods based on current to PMSM with a common dc bus, a differential-mode current
distinguish which one is under the OC fault. Compared with neu- (DMC) circuit exists, as shown in Fig. 1. The DMC circulates
tral connected PMSM driving systems, the open-end winding in the phase winding and dc link. In normal condition of the
PMSM driving systems would increase the calculating time of motor, due to the symmetry of the motor, the main frequency
the digital signal processor (DSP) because of the zero-sequence of the DMC is three times that of the fundamental wave. Thus,
proportional-resonant (PR) controller and 12 IGBTs. Besides, it is also called zero-sequence current (ZSC) in many papers.
for many existing detection methods, at least three average According to (1), the ZSC and the zero-sequence voltage (ZSV)

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
7778 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO. 8, AUGUST 2022

Fig. 4. Control scheme for the open-end winding PMSM.

Fig. 6. (a)–(c) Equivalent circuit of one phase under the OC fault.

zero-sequence controller is used to extract the position via a


synchronous phase-locked loop-based position observer. In this
article, the output signal of the zero-sequence controller is used
to detect whether an OC fault exists in the system.

Fig. 5. Relation between the output of the zero-sequence controller B. Current Analysis in a Faulty Condition
and i0.
For the open-end winding PMSM, the two bridges connected
to each phase can be analyzed independently, which is different
of the system are
from the conventional PMSM. In this article, phase A is used as
1 an example. In Fig. 6(a), S11 and S22 are in the ON state. S12 and
i0 = (ia + ib + ic ) (2)
3 S21 are in the OFF state. The passive phase current flows through
1 S11 and S22 , as the red arrow shows. The voltage of phase A
u0 = (ua + ub + uc ). (3) is +Udc . Assuming that an OC fault occurs in S11 during this
3
period, the current of S11 will be zero and the current path would
For the convenience of analysis, the symbols of i0 and u0
change. It will flow through S21 and the antiparallel diode of
can contain the fundamental component and the third-harmonic
S12 . The voltage of phase A is zero. So, the current of phase A
component in this article.
will decrease to zero. However, if the OC fault occurs in S22 in
In the applications of a voltage-source inverter, the dead time
this period, as shown in Fig. 6(b), the current of phase A will
is used to avoid the shoot through of one leg at the same time.
pass through the antiparallel diode of S21 . The voltage of phase
However, in dual-inverter systems, the dead time can generate
A will also change from +Udc to zero. So, the waveforms of
the ZSC due to the conduction of the antiparallel diodes. In the
phase current are the same since the voltages after the fault are
open-end winding PMSM driving systems, device voltage drop,
the same. In Fig. 6(c), if S11 and S22 have the fault at the same
dead time, and electromotive force (EMF) could cause the ZSC.
time, the current will decrease to zero faster.
Compared with the ZSC generated by device voltage drop, the
If the fault occurs in S21 or S12 during this period, the stator
dead time and EMF are the main reasons of the ZSC in healthy
current will not be affected, because these two devices are in
condition, and they would be analyzed next.
the OFF state and there are no currents flowing through these
The principle and current conducting paths in healthy condi-
two switches. The current will be affected in the next half cycle,
tion are expressed in [27]. Besides, the ZSC direction is only
where S21 and S12 are in the ON state.
related to the directions of the stator currents. In order to elimi-
From the analysis, the faulty currents of S11 and S22 (S12 and
nate the ZSC, closed-loop control is introduced in [2]. As shown
S21 ) are the same. According to the currents after the OC faults,
in Fig. 4, the durations of zero-voltage vectors are redistributed
the OC faults can be classified into three categories in one phase:
according to the output of the zero-sequence controller. The
Case I: the OC fault occurs in S11 or S22 (or together); Case II:
output of the zero-sequence controller can compensate the ZSC
the OC fault occurs in S12 or S21 (or together); and Case III:
generated by the dead time, so the ZSC is controlled to zero.
Cases I and II happen together, such as S11 and S12 ; the current
In early studies, a proportional—integral (PI) controller is
will lose both the positive and negative half cycles.
used. In order to improve the performance in variable-speed sys-
tems, the PR controller is used to eliminate the ZSC. According
to [28], the output of the PR controller contains information of III. DETECTION OF THE FAULT CASE
the ZSV. As shown in Fig. 5, assuming that i0 is controlled to In this article, the detection method is divided into two main
zero, which means the output of the PR controller can keep up steps. The first step is to detect which fault case happens. The
with the change of i0 , the waveforms of i0 and u0 are similar, second step is to locate the device under the OC fault. In the
and the direction of u0 is opposite to the direction of i0 so actual systems, the asymmetric phase current, dead time, and the
that ZSV can be compensated. So, in [28], the output of the EMF can generate the ZSC. The zero-sequence controller would

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
JIANG et al.: NOVEL OPEN-CIRCUIT FAULT DETECTION AND LOCATION FOR OPEN-END WINDING PMSM 7779

output a ZSV to compensate the ZSC generated by three causes.


The ZSC generated by the back EMF contains the fundamental
and third components. However, the fundamental component is
much larger than the third. So, only the fundamental component
of the back EMF in fault condition is considered. In order to ana-
lyze the output of the zero-sequence controller, the fundamental
currents and dead time are analyzed, respectively.
Fig. 7. Theoretical waveforms of fundamental stator currents and i0 in
A. ZSC Generated by Fundamental Phase Currents case I.
Under healthy condition, the fundamental phase currents of
three phases can be expressed as


⎨ia (t) = Im sin(ωt)
 
ib (t) = Im sin ωt − 23 π (4)

⎩  
ic (t) = Im sin ωt + 3 π
2

where Im is the current amplitude in normal condition and ω


is the angular frequency. Space vector pulsewidth modulation
Fig. 8. Theoretical waveforms of fundamental stator currents and i0 in
(SVPWM) is used to control the two inverters. The positive half- case II.
cycle stator current is established by means of the top transistor
and the bottom antiparallel diode of the corresponding leg in
the other inverter. Assuming that an OC fault occurs in S11 , the
stator current of phase A will lose its positive current in the first
half cycle. It can be expressed as

0, 0 ≤ t ≤ T2
ia (t) = . (5)
Im sin(ωt), 2 ≤ t ≤ T
T

In the period of the first half cycle, ia is 0. The currents in the


Fig. 9. Theoretical waveforms of fundamental currents and i0 in
dq frame could be obtained by T2 case III.

   

idf 2 cos θ − 23 π cos θ+ 23 π ibf


=     (6) lose the positive (0 ≤ t < T /2). The amplitudes of ib and ic
iqf 3 − sin θ − 2 π − sin θ+ 2 π
3 3
icf
will increase. However, in the negative half cycle, the three
where idf and iqf are the corresponding currents in the faulty currents will not change. In the positive half cycle, i0 caused
condition. In PMSM drive systems, the field-oriented control is by fundamental stator current is also fundamental.
widely used. Therefore, in healthy conditions, id is controlled to 2) Analysis of Case II: As shown in Fig. 8, assuming that
0 and iq is controlled to a certain value. In the faulty condition, idf S12 of phase A has an OC fault, ia will lose the negative half cycle
and iqf also can be controlled to the previous values, but ripples (T /2 ≤ t < T ). Similarly, the frequency of the zero-sequence
exist. The inverse matrix of T2 can be expressed as controller output is changed. However, the direction of i0 caused

   
by fundamental stator current is positive. This is different from
ibf √ −sin θ+ 2 π − cos θ + 2 π idf
= 3  3   3  . (7) case I.
icf sin θ − 23 π cos θ − 23 π iqf 3) Analysis of Case III: From the analysis of cases I and
II, the feature of case III is a combination of cases I and II. The
In
√ the faulty conduction, the amplitude of phase currents polarity of i0 would change in one fundamental period, as shown
is 3 times the amplitude in the normal conduction, and the
in Fig. 9.
sum of three fundamental currents is not zero. In the normal
In order to obtain i0 in real systems, i0 generated by dead
condition, the three stator currents are symmetrical. However,
times is analyzed next. In the period of 0 ≤ t < T /2, ia would
in the faulty condition, the two stator currents (B and C) are not
be 0. The antiparallel diode would not conduct. Therefore, the
symmetrical. The fundamental phase currents and i0 generated
ZSC generated by ia does not exist. Only phases B and C can
by the fundamental currents are shown in Fig. 7. In Fig. 7, it can
generate i0 .
be seen that the fundamental currents do not generate i0 in the
ideal normal condition. However, if the stator current of phase
A is zero, the other two currents would change their amplitudes B. ZSC Generated by Dead Times
and phase. Therefore, the fundamental currents would generate In order to analyze i0 generated by dead time, the current
i0 . The frequency of i0 is fundamental. The three fault cases have paths during the dead time are shown in Fig. 10. Only two
different features of i0 , and they are analyzed as follows. current modes are shown. V00’ –V13’ means the switching state
1) Analysis of Case I: As shown in Fig. 7, assuming that is changed from V00’ to V13’ and the current path during this
S11 of phase A has an OC fault, it is the case I fault. ia will dead time is shown in Fig. 10(a). In Fig. 10(a), when ia < 0

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
7780 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO. 8, AUGUST 2022

Fig. 10. Current paths during the dead time for V13’ , V24’ , and V77’ under (a) ib < 0, ic > 0 and (b) ib > 0, ic > 0.

TABLE I voltage of the dual inverter. For the convenience of analysis, the
VOLTAGES GENERATED BY THE DEAD TIME
average value of the ZSV is shown in Fig. 11.
From the analysis of i0 generated by stator current and dead
time, it can be seen that the frequency of i0 , which is three times
the fundamental waveform, will be fundamental when ia is zero
in the faulty condition. Therefore, this feature of i0 can be used
to detect if an OC fault occurs in the system.

C. Detection of the Fault Case


The previous analysis of the different fault features shows
that each failure has different impacts on the zero-sequence
controller output. Hence, the proposed fault detection method
has two steps to detect the fault case of certain phase. The
first step is to judge the fault case using the output of the
zero-sequence controller. The second step is to detect the phase
with the OC fault. To simplify the proposed method, the output
of the zero-sequence controller should be normalized, which is
Fig. 11. Theoretical waveforms of fundamental stator currents and calculated by dividing the maximum amplitude of u0 [19]. The
average value of the ZSV generated by the dead time. (a) case I. (b) normalized average value of the output of the zero-sequence
case II. controller is

ω 3ω u (t)
0
and ib > 0, both switches of the second leg of inverter II during u0av = dt (8)
V00’ –V13’ are OFF. S14 and the antiparallel diode of S24 are turned 6π 0 U0
ON. Therefore, the two terminals of phase B are connected. The where U0 is the maximum amplitude of u0 , u0av is evaluated
phase B voltage is zero. Similarly, the phase C voltage is also in a moving window made of n samples, and n is calculated
zero. Therefore, u0 is zero in this period. When ib > 0 and ic > 0, according to the frequency of the ZSC. In order to determine the
the analysis of u0 is shown in Fig. 10(b). sign of the average value of the zero-sequence controller output,
The relation between i0 and current modes is shown in Table I. a threshold u0th is defined as follows.
The frequency of i0 is the same as the stator current. In other
words, i0 generated by the dead time is also fundamental. The I. If u0av > u0th , the sign of <u0ref > is “+.”
two current modes (ib < 0, ic > 0 and ib > 0, ic < 0), which II. If –u0th < u0av < u0th , the sign of <u0ref > is “0.”
have the same phase voltage, do not generate u0 . III. If u0av < –u0th , the sign of <u0ref > is “–.”
Thus, i0 would not be generated. Fig. 11 shows the theoretical
waveforms of the ZSC and ZSV generated by the dead time In one fundamental period, three signs of u0av can be obtained.
in case I. The values of the ZSV are –Udc /3 and Udc /3, and Then, the fault case can be detected according to the three signs.
the duration in each switching period is based on the reference The detection signatures of the fault case are shown in Table II.

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
JIANG et al.: NOVEL OPEN-CIRCUIT FAULT DETECTION AND LOCATION FOR OPEN-END WINDING PMSM 7781

TABLE II
PROPOSED FAULT CASE DETECTION APPROACH

From previous analysis, the fault case can be detected. The


next step is to detect which phase has the OC fault. In the normal
condition, |u0av | < u0th .When |u0av | > u0th , the number of three
Fig. 13. Equivalent circuits of S11 with gate signals. (a) State 1.
stator current samples, in which |ij | < imin (j = a, b, c), would be (b) State 2.
counted. imin is a threshold of the stator current, which means
the current of this phase is zero (ij = 0, j = a, b, and c). If the
number (ns ) is bigger than nmax in one fundamental period, the
phase with the OC fault can be detected. The relation between
fault indicators and fault cases is shown in Table II. According
to the sequence of the three signs of the average value in one
fundamental period, the fault case can be detected.
Two types of fault indicators are used to ensure the accuracy
of detection. Besides, ns would not be counted in the normal
condition, so the burden of the controller would not increase.

IV. LOCATION OF OC IGBTS Fig. 12. Current waveforms of phase A.

In Section III, the method of detecting the fault case and the
fault phase is expressed. The next step is to locate the IGBT(s) or S22 or both) is still unknown. Assuming that the fault switch
under the OC fault. is S11 , according to (10), the voltage of phase can be obtained.
Supposing that S11 of phase A has an OC fault, the voltage Assuming the eaf is in forward direction as assuming eaf in
equation of phase A in the normal condition does not exist in the forward direction as shown in Fig. 13, because S11 is faulty
positive half cycle. Therefore, under the faulty condition, the and S22 is healthy, no current is detected when S11 is given a
voltage equations of phases B and C of the motor are expressed pulsewidth modulation (PWM) gate signal. This can prove that
as S22 is healthy. In order to further confirm whether S22 is healthy,

ub = Rs ib + M didta + L di the controller turns OFF S11 and generates a PWM gate signal
dt + M dt + dt
b dic dϕb
(9) to S22 . The waveforms of phase A current and gate signals of
uc = Rs ic + M didta + M didt + L dt + dt
b dic dϕc
S22 are shown in Fig. 12. Since S11 is under the OC fault, the
where ia , ib , and ic are the stator currents, Rs is the equivalent current in forward direction will not be detected. Two working
resistance, L is the stator self-inductance, ϕa , ϕb , and ϕc are modes are expressed as follows.
the flux of permanent magnets, and M is the mutual inductance. Stage 1 (t0 –t1 ): S22 turns ON at t0 ; a forward direction current
However, the voltage of stator winding of phase A still exists, generated by eaf flows through S22 and the antiparallel diode of
and it can be expressed as S12 . This current increases during the period when S22 is ON.
  Therefore, the current sensor of phase A will sample a positive
dib dic dϕa T
eaf = M +M + 0≤t≤ . (10) value of this current, as shown in Fig. 13(a).
dt dt dt 2 Stage 2 (t1 –t2 ): S22 turns OFF at t1 ; the phase current flows
From (10), it can be seen that a voltage of stator winding through the antiparallel diodes of S12 and S21 . The voltage of
still exists. This voltage is generated by the mutual inductance stator winding changes to Udc . So, this current decreases during
between phases B and C and the fundamental magnet flux. This this period in Fig. 13(b).
voltage can be used to locate the position of the IGBT(s) with Similarly, if S22 has an OC fault, the controller first generates
the OC fault. the PWM signal to S11 ; there is a forward current detected. Then,
After the fault case is detected, taking S11 of phase A as an the controller turns OFF S11 and generates the PWM signal to
example, the gate signals of the four devices (S11 , S12 , S21 , S22 ; no phase current in the forward direction can be generated,
and S22 ) connected to phase A should be turn OFF. So, phase A as shown in Fig. 14. Besides, if both S11 and S22 have OC faults,
is isolated. Fault-tolerant control strategies can be used for the phase A current will remain zero; even the controller generates
other two healthy phases. Since the rotor keeps running in this PWM signals in the two IGBTs.
period, eaf can be generated. It is an almost sinusoidal waveform. The same method of locating the position of devices under
Assume that case I fault of phase A is detected in the first step the OC fault for case II can be used. For case II, the direction of
and the four IGBTs connected to phase A are isolated. Although eaf should be in the opposite direction in case I. So, according
the fault case I is detected, the location of the faulty switch (S11 to (10), when eaf is in the reverse direction, the gate signals are

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
7782 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO. 8, AUGUST 2022

the peak values of the stator currents are smaller than the values
in Fig. 19(a). Besides, smaller ZSC can reduce the ripples in
torque.
The phase currents of the other two phases are changed by
the PR controller, which can decrease the ripple of the speed.
Therefore, by comparing the waveforms in Fig. 19(a) and (b),
if the fault case is detected in the first step, the PR controller
should be enabled when the faulty phase is isolated. From
Fig. 19(b), it can be seen that the performance of suppression
of the zero-sequence components decreases obviously, because
Fig. 14. Equivalent circuits of S22 with gate signals. (a) Stage 1. the frequency of the zero-sequence components is no longer the
(b) Stage 2. resonant frequency of the PR controller, and as the increase of
the zero-sequence components, the zero-voltage vectors are not
given to the devices. Case III is combination of cases I and II, enough to compensate. For the output value of the PR controller,
so the controller should generate PWM signals to four devices it is sensitive to the speed of the motor. In the proposed method,
connected to the faulty phase in turn in one fundamental period. the robustness of the proposed method is mainly affected by the
When the controller generates PWM signals in one device, if a first step.
current in the corresponding direction is detected, this device is
healthy. If not, this device is under the OC fault. The operational B. Immunity Test
flowchart of the proposed is shown in Fig. 15.
In order to increase the robustness, step change of reference
In order to control this current, a closed-loop strategy is shown
speed is given to the system. The initial speed in Fig. 20(a) is
in Fig. 16, where Iref is the reference current.
1000 r/min. Then, it is changed to 1400 and 1000 r/min. The
frequency of the stator currents is changed according to the
V. EXPERIMENTAL VERIFICATION
reference speed. But i0 can be suppressed by the PR controller in
The experimental platform of the open-end winding PMSM this period of time. Because the EMF of the permanent magnets
is shown in Fig. 17. A TMS320F28335 evaluation board from would change with the speed of the rotor, the amplitude of
Texas Instruments has been adopted as the main control chip. the output of the PR controller increases when the speed is
The sampling frequency is 10 kHz. An analog-to-digital con- 1400 r/min. Fig. 20(b) shows the waveforms of load change from
verter chip AD7606 is used for capturing voltages and currents 0.8 to 1.2 Nm. Several factors, such as the transient process
of the main system. The dead time is 2.3 μs. The dc bus voltage induced by speed and load changes, switches, and sensors noises
is 100 V. The parameters of the motor are listed as: rating power should be selected accounted when the threshold values are
750 W, self-inductance 7.5 mH, mutual inductance 0.8 mH, and selected. In this article, u0th is set to 0.5. Although a ripple exists
winding resistance 2.1Ω. The load torque is 1 Nm. when the speed and load are changed, the average value of the
The control scheme is shown in Fig. 4. The reference speed PR controller output can stay within the predefined threshold
is 1000 r/min. The reference current iq is generated by a speed u0th = 0.5, without emitting false alarms. This can show the
PI controller. And the reference current id is equal to zero so high immunity against false alarms and the robustness of the
that the maximum torque per ampere can be achieved. The OC method under different operating conditions.
fault is obtained by shutting down the gate drive signal to the
considered IGBTs. C. Fault Detection Test
The performance of the proposed OC fault diagnostic method
A. PR Controller Test
of S11 fault for fault case I is shown in Fig. 21. The stator currents
In Fig. 18, the comparison between the condition with and i0 , u0, and u0av are given out. The speed is 1000 r/min. The load
without the PR controller is shown. According to [2], the PR torque is 1 Nm. In the normal condition, the stator currents
controller is designed to suppress the ZSC i0 . The resonant are symmetrical. And the frequency of the output of the PR
frequency of the PR controller is set according to the reference controller is three times that of the fundamental. When the gate
speed. It can be seen that the ZSC can be suppressed obviously. signal of S11 of phase A is removed, the current of phase A loses
Fig. 19 is shown to verify the performance of the PR controller its positive half cycle. Currents of phases B and C are distorted.
after the fault. In Fig. 19, the drive signals of the four IGBTs The output of the PR controller starts to increase. The frequency
connected to phase A (S11 , S12 , S21 , and S22 ) are removed. In is also changed. So, the average value starts to increase. When
Fig. 19(a), the PR controller is also disabled at the same time. it is larger than u0th , the controller starts to count the number
So, the output of the PR controller is set to zero. In Fig. 19(a), of current samples, which is zero. In one fundamental period,
it can be seen that the stator currents increase obviously. This the signs of u0av is “++0,” and the sample number of phase
can lead to the action of SC protection circuits. Compared with A is larger than nmax = 20. So, fault case I of phase A can be
the stator current waveforms in Fig. 19(a), the PR controller in detected. Then, the four IGBTs is isolated. The PR controller
Fig. 19(b) continues to work after the drive signals of the four would continue to work in order to limit the peak value of the
IGBTs are removed. The stator currents also increase. However, other two stator currents. Then, PWM gate signals are given to

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
JIANG et al.: NOVEL OPEN-CIRCUIT FAULT DETECTION AND LOCATION FOR OPEN-END WINDING PMSM 7783

Fig. 15. Operational flowchart of the proposed OC fault detection and location.

Fig. 16. Closed-loop control for the proposed method.

Fig. 19. Stator currents and i0 after phase A is isolated. (b) Without
the PR controller. (b) With the PR controller.

Fig. 17. Experimental platform.

Fig. 20 Waveforms of the transient process. (a) Speed change.


(b) Load change.

Fig. 18. Stator currents and i0 after the PR is enabled in the normal
condition.

S11 and S22 . Iref is 0.1 A. A positive current can be detected Fig. 21. Fault diagnosis process of S11 under the OC fault.
when the signal is given to S22 . As a result, OC is located to
S11 of phase A. The red dotted lines are the signs of the alarms. to confirm S22 , the alarm is obtained after the current of S22 is
When the signs rise, the corresponding alarms are detected. In detected.
case I, the alarm fault case is obtained at the end of step I. When Fig. 22(a) shows the diagnostic process when S22 of phase A is
S11 is given a PWM signal, the alarm does not rise. In order broken. This process is similar with the process in Fig. 19. When

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
7784 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO. 8, AUGUST 2022

Fig. 22. Fault diagnosis process of different IGBTs. (a) S22 . (b) S11 and S12 . (c) S11 and S21 .

Fig. 23. Fault diagnosis process of S11 under the OC fault with no load Fig. 24. Fault diagnosis process of S11 under the OC fault with
100 r/min. 1.2 Nm and 1400 r/min.

the fault. Compared with Fig. 24, i0 is very large. This is because
the gate signals of S21 of phase A are removed, the current loses the time of zero-voltage vectors is not enough to compensate
its negative half cycle. The sequence of the three signs in one i0 when the modulation index is in very high area. Besides,
fundamental period is “– – 0” and phase A current is zero. So, the proposed method can detect the faulty phase and locate the
fault case II of phase A can be detected. Then, PWM gate signals faulty switches. The threshold values and the number of current
are given to S12 and S21 ; a positive current can be detected when samples should be selected carefully. If the threshold values are
the signals are given to S12 . As a result, OC is located to S21 of selected too high, the average value may not be detected. If they
phase A. are too small, the probability of wrong detection increases. If the
Experimental results of two faulty IGBTs combinations are first step detects the fault wrongly, the second step can further
shown in Fig. 22(b) and (c). Fig. 22(b) shows the waveforms of confirm the fault. Assume that the combination of S11 and S22
S11 and S12 under the OC fault, which two faulty switches are faults is detected in the first step; however, in the second step,
in the same leg. The current is zero in the period. And the u0av is two positive currents are detected when the PWM signals are
changed from negative to positive direction. When |u0av | > u0th , given to S11 and S22 , respectively.
the number of zero current samples will be counted. As to the number of the samples, if it is selected too large,
Fig. 22(c) shows the waveforms of S11 and S21 under the OC the detection time would be affected. The detection time of the
fault, which two faulty switches are top switches in different faulty case is 15 ms, and the location time is 15 ms, both nearly
legs. The phase currents after the fault are very similar to that the current period, which proves that the proposed method is fast
in Fig. 22(b). And the order of locating the faulty switches is and effective.
different. In Fig. 22(b) and (c), two alarms exist in step II. For
example, in Fig. 22(b), the alarm of S11 rises after the current
VI. CONCLUSION
of S22 is detected.
In order to verify the performance of the proposed method In this article, a new method to detect and locate the IGBT OC
in different operating conditions, Figs. 23 and 24 show the fault fault in an open-end winding PMSM fed by a dual inverter was
diagnosis processes under 100 r/min with no load and 1400 r/min presented. The causes of the DMC generated by fundamental
with 1.4 Nm. In Fig. 23, it can be seen that i0 is near zero after stator current and dead time in the faulty condition were

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
JIANG et al.: NOVEL OPEN-CIRCUIT FAULT DETECTION AND LOCATION FOR OPEN-END WINDING PMSM 7785

analyzed. The DMC frequencies of both causes were changed [14] I. Jlassi, J. O. Estima, S. K. E. Khil, N. M. Bellaaj, and A. J. M. Cardoso,
from fundamental to triple in the faulty condition. Thus, the “A robust observer-based method for IGBTs and current sensors fault
diagnosis in voltage-source inverters of PMSM drives,” IEEE Trans. Ind.
output of zero-sequence controller was also changed according Appl., vol. 53, no. 3, pp. 2894–2905, May 2017.
to DMC. This information was used to detect the occurrence [15] J. Hang, H. Wu, S. Ding, W. Hua, and Q. Wang, “A DC-flux-injection
of fault by the signals of the average value of the output of the method for fault diagnosis of high-resistance connection in direct-torque-
controlled PMSM drive system,” IEEE Trans. Power Electron., vol. 35,
zero-sequence controller. Then, the faulty phase was isolated no. 3, pp. 3029–3042, Mar. 2020.
and the PI strategy based on the voltage of the faulty phase was [16] J. Hang, H. Wu, J. Zhang, S. Ding, Y. Huang, and W. Hua, “Cost function-
introduced to locate the position of the faulty switch. In this based open-phase fault diagnosis for PMSM drive system with model
predictive current control,” IEEE Trans. Power Electron., vol. 36, no. 3,
method, IGBTs with the OC fault can be located accurately, pp. 2574–2583, Mar. 2021.
and only one average value is needed so that the computational [17] H. Yan, Y. Xu, F. Cai, H. Zhang, W. Zhao, and C. Gerada, “PWM-VSI
resource can be saved. The results show that this method can fault diagnosis for a PMSM drive based on the fuzzy logic approach,”
IEEE Trans. Power Electron., vol. 34, no. 1, pp. 759–768, Jan. 2019.
detect and locate the faulty switches accurately so that the drive [18] Z. Huang, Z. Wang, X. Yao, and H. Zhang, “Multi-switches fault diagnosis
can take appropriate tolerant operation actions to protect the based on small low-frequency data for voltage-source inverters of PMSM
system. drives,” IEEE Trans. Power Electron., vol. 34, no. 7, pp. 6845–6857,
Jul. 2019.
[19] P. F. C. Gonçalves, S. M. A. Cruz, and A. M. S. Mendes, “Open-phase
fault diagnosis in six-phase PMSM drives based on the harmonics of the
measured secondary subspace currents,” in Proc. 46th Annu. Conf. IEEE
REFERENCES Ind. Electron. Soc., Singapore, 2020, pp. 4863–4868.
[20] H. Chen, J. He, N. A. O. Demerdash, X. Guan, and C. H. T. Lee, “Diagnosis
[1] S. Jain, A. K. Thopukara, R. Karampuri, and V. T. Somasekhar, “A single of open-phase faults for a five-phase PMSM fed by a closed-loop vector-
stage photovoltaic system for a dual-inverter-fed open-end winding induc- controlled drive based on magnetic field pendulous oscillation technique,”
tion motor drive for pumping applications,” IEEE Trans. Power Electron., IEEE Trans. Ind. Electron.,vol. 68, no. 7, pp. 5582–5593, Jul. 2021.
vol. 30, no. 9, pp. 4809–4818, Sep. 2015. [21] W. Hu, C. Ruan, H. Nian, and D. Sun, “Simplified modulation scheme
[2] H. Nian and W. Hu, “A sensorless drive strategy for open-end wind- for open-end winding PMSM system with common DC bus under open-
ing PMSM with common DC voltage based on lower switching fre- phase fault based on circulating current suppression,” IEEE Trans. Power
quency,” IEEE Trans. Energy Convers., vol. 34, no. 3, pp. 1553–1562, Electron., vol. 35, no. 1, pp. 10–14, Jan. 2020.
Sep. 2019. [22] Z. Song, F. Zhou, Y. Yu, R. Zhang, and S. Hu, “Open-phase fault-tolerant
[3] W. Hu, H. Nian, and D. Sun, “Zero-sequence current suppression strategy predictive control strategy for open-end-winding permanent magnet syn-
with reduced switching frequency for open-end winding PMSM drives chronous machines without postfault controller reconfiguration,” IEEE
with common DC bus,” IEEE Trans. Ind. Electron., vol. 66, no. 10, Trans. Ind. Electron., vol. 68, no. 5, pp. 3770–3781, May 2021.
pp. 7613–7623, Oct. 2019. [23] W. Zhao, B. Wu, Q. Chen, and J. Zhu, “Fault-tolerant direct thrust force
[4] C. S. Zhang, Z. X. Li, J. Liu, H. Y. Cao, and X. Zhang, “Voltage vector control for a dual inverter fed open-end winding linear Vernier permanent-
error fault diagnosis for open-circuit faults of three-phase four-wire active magnet motor using improved SVPWM,” IEEE Trans. Ind. Electron.,
power filters,” IEEE Trans. Power Electron., vol. 32, no. 3, pp. 2215–2226, vol. 65, no. 9, pp. 7458–7467, Sep. 2018.
Mar. 2017. [24] Y. Zuo, X. Zhu, X. Si, and C. H. T. Lee, “Fault-tolerant control for
[5] I. González-Prieto, M. J. Duran, N. Rios-Garcia, F. Barrero, and C. Martín, multiple open-leg faults in open-end winding permanent magnet syn-
“Open-switch fault detection in five-phase induction motor drives using chronous motor system based on winding reconnection,” IEEE Trans.
model predictive control,” IEEE Trans. Ind. Electron., vol. 65, no. 4, Power Electron.,vol. 36, no. 5, pp. 6068–6078, May 2021.
pp. 3045–3055, Apr. 2018. [25] M. Baiju, K. Mohapatra, R. Kanchan, and K. Gopakumar, “A dual two level
[6] D. Zhou, H. Qiu, S. Yang, and Y. Tang, “Submodule voltage similarity- inverter scheme with common mode voltage elimination for an induction
based open-circuit fault diagnosis for modular multilevel convert- motor drive,” IEEE Trans. Power Electron., vol. 19, no. 3, pp. 794–805,
ers,” IEEE Trans. Power Electron., vol. 34, no. 8, pp. 8008–8016, May 2004.
Aug. 2019. [26] J. Kalaiselvi and S. Srinivas, “Bearing currents and shaft voltage re-
[7] H. Guo, S. Guo, J. Xu, and X. Tian, “Power switch open-circuit fault duction in dual-inverter fed open-end winding induction motor with re-
diagnosis of six-phase fault tolerant permanent magnet synchronous motor duced CMVPWM methods,” IEEE Trans. Ind. Electron., vol. 62, no. 1,
system under normal and fault-tolerant operation conditions using the pp. 144–152, Jan. 2015.
average current Park’s vector approach,” IEEE Trans. Power Electron., [27] J. L. An, Z. Peng, L. Sun, and L. Sun, “Dual-space vector control of
vol. 36, no. 3, pp. 2641–2660, Mar. 2021. open-end winding permanent magnet synchronous motor drive fed by dual
[8] J. O. Estima, N. M. A. Freire, and A. J. M. Cardoso, “Recent advances in inverter,” IEEE Trans. Power Electron., vol. 31, no. 12, pp. 8329–8342,
fault diagnosis by Park’s vector approach,” in Proc. IEEE Workshop Elect. Dec. 2016.
Mach. Des., Control Diagnosis, 2013, pp. 279–288. [28] H. Zhan, Z. Q. Zhu, and M. Odavic, “Nonparametric sensorless drive
[9] W. Sleszynski, J. Nieznanski, and A. Cichowski, “Open-transistor fault method for open-winding PMSM based on zero-sequence back EMF with
diagnostics in voltage-source inverters by analyzing the load cur- circulating current suppression,” IEEE Trans. Power Electron., vol. 32,
rents,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4681–4688, no. 5, pp. 3808–3817, May 2017.
Nov. 2009.
[10] D. Diallo, M. E. H. Benbouzid, D. Hamad, and X. Pierre, “Fault
detection and diagnosis in an induction machine drive: A pattern
recognition approach based on Concordia stator mean current vec-
tor,” IEEE Trans. Energy Convers., vol. 20, no. 3, pp. 512–519,
Sep. 2005.
[11] A. Sapena-Bañó, M. Pineda-Sanchez, R. Puche-Panadero, J. Martinez Chunyang Jiang received the B.S. degree in
Roman, and D. Matić, “Fault diagnosis of rotating electrical machines in electrical engineering from the Harbin University
transient regime using a single stator current’s FFT,” IEEE Trans. Instrum. of Science and Technology, Harbin, China, in
Meas., vol. 64, no. 11, pp. 3137–3146, Nov. 2015. 2014, and the M.S. degrees in electrical en-
[12] S. S. Kuruppu and N. A. Kulatunga, “D-Q current signature-based faulted gineering in 2016 from the Harbin Institute of
phase localization for SM-PMAC machine drives,” IEEE Trans. Ind. Technology, Harbin, where he is currently work-
Electron., vol. 62, no. 1, pp. 113–121, Jan. 2015. ing toward the Ph.D. degree in power electronics
[13] A. Kontarček, P. Bajec, M. Nemec, V. Ambrožič, and D. Nedeljković, and electrical drives in electrical engineering.
“Cost-effective three-phase PMSM drive tolerant to open-phase His current research interests include dc–dc
fault,” IEEE Trans. Ind. Electron., vol. 62, no. 11, pp. 6708–6718, topology and motor drives.
Nov. 2015.

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.
7786 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 69, NO. 8, AUGUST 2022

Hongchen Liu (Member, IEEE) received the Fengjiang Wu (Senior Member, IEEE) received
B.S. degree from Northeast Agricultural Univer- the B.S., M.S., and Ph.D. degrees in electrical
sity, Harbin, China, in 2001, and the master’s engineering from the Harbin Institute of Tech-
and Ph.D. degrees from the Harbin Institute of nology (HIT), Harbin, China, in 2002, 2004, and
Technology (HIT), Harbin, in 2003 and 2007, 2007, respectively.
respectively, all in electrical engineering. Since 2007, he has been with the Department
In 2009, he joined the Department of Electri- of Electrical Engineering, HIT, where he is cur-
cal Engineering, HIT, as a Lecturer, where he rently an Associate Professor. He has authored
has been a Professor of Electrical Engineer- or coauthored more than 100 top-tier journal
ing since 2020. From 2008 to 2012, he was a and conference papers. His research interests
Postdoctoral Fellow in measuring and control- include renewable energy generation, energy
ling technology and instrument specialty. He has authored more than 60 storage systems, solid-state transformers, and microgrids.
technical papers published in journals and conference proceedings. His Dr. Wu is an Associate Editor for IEEE ACCESS and IET Power
current major research interests include dc–dc converters and inverters Electronics.
in photovoltaic systems, matrix converters, and nonlinear dynamics in
power electronics.

Zhe Cai received the B.S. degree in electrical


engineering in 2020 from the Harbin Institute of
Technology, Harbin, China, where he is currently
Pat Wheeler (Fellow, IEEE) received the B.Eng. working toward the M.S. degree in electrical en-
(Hons.) degree in electrical engineering from gineering.
the University of Bristol, Bristol, U.K., in 1990, His research interests include dc–dc power
and the Ph.D. degree in electrical engineering conversion and motor drives.
for his work on matrix converters from the Uni-
versity of Bristol in 1994.
In 1993, he joined the University of Notting-
ham, Nottingham, U.K., where he was a Re-
search Assistant with the Department of Elec-
trical and Electronic Engineering. In 1996, he
became a Lecturer with the Power Electronics,
Machines and Control Group, University of Nottingham, where he has Ju Huo was born in Hebei, China, in 1977. He
been a Full Professor, since January 2008. From 2015 to 2018, he was received the B.S. and M.S. degrees in electrical
the Head of the Department of Electrical and Electronic Engineering, engineering in 1999 and 2001, respectively, and
University of Nottingham, where he is currently the Head of the Power the Ph.D. degree in control science and engi-
Electronics, Machines and Control Research Group and the Global neering in 2007, all from the Harbin Institute of
Director of the Institute of Aerospace Technology. He was the Li Dak Technology, Harbin, China.
Sum Chair Professor in Electrical and Aerospace Engineering. He has He is currently a Professor and a Doctoral
authored or coauthored more than 750 academic publications in leading Supervisor with the Simulation and Control Cen-
international conferences and journals. ter, Harbin Institute of Technology. His current
Dr. Wheeler is a member of the Administrative Committee of the IEEE research interests include vision measurement,
Power Electronics Society (PELS). He is also the Vice-President for camera calibration, and system simulation.
Technical Operations of the IEEE PELS.

Authorized licensed use limited to: VIT University- Chennai Campus. Downloaded on June 02,2022 at 16:40:24 UTC from IEEE Xplore. Restrictions apply.

You might also like