7011B Data Sheet 6, 8, 10, 12 kVA
The 7011B UPS from Mitsubishi is a true on-line,
double conversion single phase UPS that will About us
protect your equipment from disruptions in
Since 1964, Mitsubishi Electric has
power, such as brown-outs, line noise, voltage manufactured precision-engineered, high
transients, and power outages. quality uninterruptible power supplies
to protect its customers’ mission critical
equipment during times of power instability.
The 7011B provides the most complete protection Mitsubishi Electric leads the industry in
designing and manufacturing reliable,
for voltage-sensitive equipment. Utilizing a
environmentally friendly UPS systems
space saving footprint and transformerless to extend uptime, prevent data loss and
technology, the 7011B is an ideal backup solution protect against power surges. Mitsubishi
Electric Power Products’ UPS division offers
for individual computers, small networks, systems in both single- and multi-module
communications systems, security systems, and configurations and a broad range of kVA
capacities, from 6 kVA to over 2 MVA.
point of sales systems.
our services
Available in 6, 8, 10, and 12 kVA sizes with
internal batteries, with the option of adding
external battery cabinets for longer runtimes,
the 7011B is simple to start up, operate, and With more than 250 certified technicians in
the field, Mitsubishi Electric offers around the
Ideal for IT closet applications. maintain. clock protection, keeping your operations safe
against outages, grid decay and other crucial
threats to the flow of business. Offerings
include routine maintenance checks, priority
demand on parts and service, and 24/7
Features & benefits Load % 6kVA 12kVA
25 86.7 87.4
communication with experienced technical
support staff. Comprehensive maintenance
inspections include UPS diagnostic reports,
• Space saving footprint 40 89.4 90.1 complete battery testing, and site hazard
50 90.6 90.9 checks to keep your systems running at
• True on-line double conversion maximum efficiency. Other services include
75 91.3 91.4 factory witness testing and collaborative
100 91.2 91.1 engineering. With their highly skilled
• Up to 91.5% efficient technicians, day and night technical support,
and premier equipment, Mitsubishi Electric
• Transformer-less design using full has the resources to keep customers safe
IGBT power electronics LCD 6kVA 12kVA from the unexpected.
touchscreen display MTBF[hr] 84,289 69,034
7011B
Rated Output kVA 6 8 10 12
Bypass Module Rated Output kW 4.2 5.6 7 8.4
AC INPUT
Configuration 1 phase 3 wire
UPS Modules (2) Voltage 240/120W, 208/120V
Frequency 50/60Hz +/- 5%
Power Factor .98 Lagging
I/O Module Current THD 4% typ. at 100% load; 7% typ. at 50% load
BATTERY
Type VRLA
Backup Time 10 minutes 18 minutes 18 minutes 10 minutes
Battery Module
Nominal Voltage 216 Vdc
Minimum Voltage 173 Vdc
Number of Cells 108
AC OUTPUT
Configuration 1 phase 3 wire
Voltage 240/120V, 208/120V
Voltage Stability +/-2% steady state
Voltage Unbalance 2% typical at 100% unbalanced load
Voltage THD 2.5% typical THD at 100% linear load 5% THD at 100% non-linear load
Transient Response +/-5%
Transient Recovery Time 50 ms
Frequency 50/60 Hz
Optional Maintenance Frequency Regulation +/-0.05% in free running mode
Bypass Switch Phase Displacement 1deg Typical at 100% load
Optional Distribution Panel 7011B w/ Optional External
(On Rear) Battery Cabinet Power Factor 0.70
Power Factor Range 0.7 to 1.0 lagging (within ouput kW rating)
NOTE: Above illustrations are not to scale.
Overload Capacity 150% for 1 minute
ENVIRONMENTAL
it’s time to rethink your ups. Cooling
Operating Temperature
Forced Air
32°F to 104°F (0°C to 40°C). Recommended 59°F to 77°F (15°C to 25°C)
Relative Humidity 30% to 90% non condensing
Altitude 0 to 3300 feet no derating
Location Temperature-controlled, indoor area free of conductive contaminants
Clearance Required Top: 23.5 in. Front: 39.2 in. Rear: 23.5 in.
GENERAL
Weight (lbs) 298 496 496 496
Dimensions (WxDxH) 13.8 x 29.9 x 27.8 (in) 13.8 x 29.9 x 40.6 (in) 13.8 x 29.9 x 40.6 (in) 13.8 x 29.9 x 40.6 (in)
Heat Rejection (kBTU/Hr) 1.4 1.9 2.4 2.8