1756 ControlLogix Communication Modules Specifications
Table 4 - Technical Specifications - 1756 EtherNet/IP Modules(1)
Attribute 1756-EN2F/B 1756-EN2T/D, 1756-EN2TR/C, 1756-EN4TR/A 1756-ENBT/A 1756-EWEB/B
1756-EN2F/C 1756-EN2TSC/B, 1756-EN3TR/B
1756-EN2TP/A
EtherNet/IP 10/100 Mbps 10/100 Mbps 10/100 Mbps
communication rate 1 Gbps
Current draw @ 5.1V DC 1.2 A 1A 700 mA
Current draw @ 24V DC 3 mA — 3 mA
Voltage and current ratings 5.1 V DC, 1.2A — 5.1 V DC, 1.2A —
Power dissipation 6.2 W 5.1 W 6.12 W 3.7 W
Thermal dissipation 21.28 BTU/hr 17.4 BTU/hr 20.9BTU/Hr 12.6 BTU/hr
Isolation voltage 30V (continuous), Basic 30V (continuous), Basic Insulation Type, 30V (continuous), Basic 30V (continuous), basic insulation type, Ethernet
Insulation Type, USB to Ethernet to Backplane, USB to Backplane, Insulation Type, network to backplane
Backplane and USB to Ethernet(4) Ethernet to Backplane, Type tested @ 707V DC for 60 s
Type tested at980V AC Type tested at 980V AC for 60 s USB to Backplane, and
for 60 s USB to Ethernet
Type tested at 860V AC
for 60 s
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75, 1756-PC75, 1756-PH75
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Ethernet port 1 Ethernet fiber 1 Ethernet RJ45 2 Ethernet RJ45 Category 5E 1 Ethernet RJ45 Category 5
Category 5 Category 5
Ethernet cable Multimode fiber, LC 802.3 compliant shielded or unshielded twisted pair
connector
USB port(2) USB 1.1, full speed (12 Mbps) —
Wiring category(3) 3 - on USB ports 2 - on Ethernet ports 2 - on Ethernet ports 2 - on Ethernet ports
3 - on USB ports
North American temp code T4A
ATEX temp code T4
IECEx temp code T4
Enclosure type rating None (open-style)
Transmitter launch power -19 dBm into 62.5/125 μm —
at Beginning of Life (BOL), fiber, N/A = 0.275
min -22.5 dBm into 50/125 μm
Allow -1 dB at End of Life fiber, N/A = 0.20
(EOL)
(1) Includes the K conformal coating catalog numbers.
(2) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations.
(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
(4) Applies only to these modules/series: 1756-EN2T/D,1756-EN2TSC/B, 1756-EN2TR/C,1756-EN3TR/B.
Rockwell Automation Publication 1756-TD003M-EN-E - March 2019 7