ABB Switzerland Ltd 1KHL501616

Version: -Date:
REB500 Firmware Update Sequences - 2016-04-01
Department resp.: Created: Approved: Distribution: Language: Page:
PSST-D 2013-11-28 2016-03-17 <project library> EN 1/6
Dominik Mangold Heinz Brodbeck
Effective for: Derived from: Replaces: Classification: File:
1KHL501616 REB500 Firmware Update
REB500 - - Approved Sequences.docx

Table of Contents
1 PURPOSE 1
2 SCOPE 1
3 PRECONDITIONS 1
4 FIRMWARE UPDATE SEQUENCES 2
4.1 Setup 2
4.1.1 Update over the REB500 internal process bus 2
4.1.2 Update over the REB500 front service interface 3
4.2 Procedure 4
4.2.1 REBSYS.8.10.xx.yyy to REBSYS.8.2.0.0.xxx 4
4.2.2 REBSYS.8.10.00.yyy to REBSYS.8.10.00.xxx 5

1 Purpose
This document describes the required firmware update sequences from one version to another version.

2 Scope
L4 Support.

3 Preconditions
Engineering PC being used for firmware update must be in the same subnet as targeted REB500.
REB500 user name and password are required.

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express
authority is strictly forbidden. © Copyright 2010 ABB
(2010-02-25) Form: 1KHL000228-0101 / _
Version: page:
REB500 Firmware Update Sequences - 2/6 1KHL501616

4 Firmware Update Sequences

4.1 Setup

4.1.1 Update over the REB500 internal process bus

Service Laptop

X1001
ABB REB 5 0

Re d
a y Sa
t rt T ir p

Stationbus
ABB
Switch
Central Unit I ES C 1 2

Me n u

L
R
3
Ce
l a r

He p
l

X10 05
X1
Process bus REB500
Switch ABB
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

X1
X1

X1
X1

ABB REB5 0

ABB REB5 0 ABB R EB 5 0


ABB REB5 0
Re d
a y Sa
t rt T ir p
Re d
a y Sa
t rt T ir p Re d
a y Sa
t rt T ir p
Re d
a y Sa
t rt T ir p

REB500 REB500
BU
Bay REB500 REB500
BU
BU BU
I ES C
12

Me n u

L
R
3
Ce
l a r

He p
l
I ESC
1 2

Me n u

L
R
3 C le a r

He p
l
Units I ESC
1 2

Me n u

L
R
3
Ce
l a r

He p
l
I ESC
1 2

M en u

L
R
3 Ce
l a r

He p
l

This setup is useful if all devices (bay units and central units) has to be updated.
By default the REB500 internal process bus is configured to the subnet 192.168.175.xxx.

The following IP addresses are reserved:


IP Changes
192.168.175.1 Central unit CIM
192.168.175.2 Central unit CPC
192.168.175.3 - AFS677 Switches
192.168.175.5
192.168.175.11 - Bay units
192.168.175.72

Use the following Network settings on the Service Laptop:

IP address: 192.168.175.100
Subnet mask: 255.255.255.0
Default gateway: . . .

Connect the Ethernet cable to an electrical port of the AFS677 switch.


Version: page:
REB500 Firmware Update Sequences - 3/6 1KHL501616

4.1.2 Update over the REB500 front service interface

Service Laptop

X1001
ABB REB 5 0

Re d
a y Sa
t rt T ir p

Stationbus
ABB
Switch
Central Unit I ES C
1 2

Me n u

L
R
3
Ce
l a r

H e lp

X1005
X1
Process bus REB500
Switch ABB
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

X1
X1

X1
X1

ABB REB5 0

ABB REB5 0 ABB R EB 5 0


ABB REB5 0
Re d
a y Sa
t rt T ir p
Re d
a y Sa
t rt T ir p Re d
a y Sa
t rt T ir p
Re d
a y Sa
t rt T ir p

REB500 REB500
BU
Bay REB500 REB500
BU
BU BU
I ES C
12

Me n u

L
R
3 Ce
l a r

H e lp
I ESC
1 2

Me n u

L
R
3 C le a r

H e lp
Units I ESC
1 2

Me n u

L
R
3
Ce
l a r

H e lp
I ESC
1 2

M en u

L
R
3 Ce
l a r

H e lp

This setup is useful if individual devices (bay units and central units) has to be updated.
By default the REB500 front interface is configured with IP address 192.168.0.1. In this case the DHCP
service is active on the device.

4.1.2.1 CPC and BU

Use the following Network settings on the Service Laptop:


· obtain an IP address automatically

Connect the Ethernet cable to the front service interface if a local HMI is available or to the X0 on the rear
side of the bay unit

4.1.2.2 CIM

Use a free IP address of the station bus.

Connect the Ethernet cable to the X1001 on the rear side of the central unit. An electrical to optic Ethernet
converter or a switch with electric and optic connection is required.
Version: page:
REB500 Firmware Update Sequences - 4/6 1KHL501616

4.2 Procedure

4.2.1 REBSYS.8.10.xx.yyy to REBSYS.8.2.0.0.xxx


Start command line application REB500fwu_8.2.000.xxx.exe
After several seconds following context menu shall appear:

#########################################################
# #
# (C) Copyright 2015 - 2016 ABB. All rights reserved #
# #
# REB500 IED firmware update application #
# #
#########################################################

Select firmware update option:


1) One IED update - press: 1
2) All IEDs update - press: 2

Follow the context dialog and in each step provide requested information.
After few minutes update shall be done, total update time will be displayed and the final dialog will follow:

#########################################################
# #
# Please note that it is extremely important #
# that you will report back to us via SA-T #
# Supportline when the update of the concerned #
# IEDs has been completed. This information is #
# needed to keep our product register updated #
# and ensure right information to right local #
# ABB units also in the future. #
# #
# E-mail : [email protected] #
# Subject: REB500 8.X update #
# State the new version number and please attach #
# the generated file: #
# %path%/PTRC_Data.csv #
#########################################################

Press ENTER to finish this application.

Confirm it with ENTER to close the application.


Restart updated REB500 system.

Report all updated IED’s (CU and BU’s) at SA-T Supportline see 4.2.1.1

4.2.1.1 Update OAA Database

Please note that it is extremely important that you will report back to us via SA-T Supportline when the
update of the concerned IEDs has been completed. This information is needed to keep our product
register updated and ensure right information to right local ABB units also in the future.

via e-mail: [email protected]

Subject of your e-mail: “REB500 8.X update”

Please attach the generated file “%path%/PTRC_Data.csv” to the mail.


Version: page:
REB500 Firmware Update Sequences - 5/6 1KHL501616

4.2.2 REBSYS.8.10.00.yyy to REBSYS.8.10.00.xxx


Start command line application REB500fwu_8.10.000.xxx.exe
After several seconds following context menu shall appear:

##################################################
# #
# (C) Copyright 2014 ABB. All rights reserved #
# #
# REB500 IED firmware update application #
# #
##################################################

Select firmware update option:


1) One IED update - press: 1
2) All IED's update - press: 2

Follow the context dialog and in each step provide requested information.
After few minutes update shall be done, total update time will be displayed and the final dialog will follow:

##################################################
# #
# Please note that it is extremely important #
# that you will report back to us via SA-T #
# Supportline when the update of the concerned #
# IEDs has been completed. This information is #
# needed to keep our product register updated #
# and ensure right information to right local #
# ABB units also in the future. #
# #
# E-mail : [email protected] #
# Subject: REB500 8.X update #
# State the new version number and the serial #
# numbers of the loaded IED’s #
# #
##################################################
Press ENTER to finish this application.

Confirm it with ENTER to close the application.


Restart updated REB500 system.

Report all updated IED’s (CU and BU’s) at SA-T Supportline see 4.2.2.1

4.2.2.1 Update OAA Database

Please note that it is extremely important that you will report back to us via SA-T Supportline when the
update of the concerned IEDs has been completed. This information is needed to keep our product
register updated and ensure right information to right local ABB units also in the future.

via e-mail: [email protected]

Subject of your e-mail: “REB500 8.X update”

Please state the serial number of the IED’s (CU and BU’s) which has been updated in the mail.

The serial number can be found on:


· name plate of the IED
· LHMI /Diagnostic Information/Product Identifiers
Version: page:
REB500 Firmware Update Sequences - 6/6 1KHL501616

Document History
Version Chapter Changes Responsible Date
- all Initial revision D. Mangold 2013-11-28
- 4.1 add setup section H. Brodbeck 2015-10-21
- 4.2.2 removed section for version 8.0 H. Brodbeck 2016-01-07
- several 8.10 to 8.2 update sequence added D. Mangold 2016-02-19