Calculating The Size of A Server Room Air Conditioner
Calculating The Size of A Server Room Air Conditioner
This article is a quick guide to how to work out your requirements for an air conditioning unit for your Server Room or Data Center*. In principle it's easy to calculate the size of air conditioning unit you need for your Server Room, just add together all the sources of heat and install an air conditioning unit that can remove that much. In practice it's rather more complicated. Fire regulations often require that Server Rooms have levels of insulation far above that of a normal office. Providing sufficient cooling is essential to ensure reliable running of servers, routers, switches and other key equipment. Failure of the air conditioning can have serious consequences for the equipment itself and for your company. Early warning of problems and spare capacity in the cooling system are both highly desirable.
the calculation. If, however there are windows you need to take the size and orientation into account. South Window BTU = South Facing window Length (m) x Width (m) x 870 North Window BTU = North Facing windows Length (m) x Width (m) x 165 If there are no blinds on the windows multiply the result(s) by 1.5. Obviously if you are in the Southern Hemisphere you would swap the conversion factors as the heat on North facing windows is then greatest. Add together all the BTUs for the windows. Windows BTU = South Window(s) BTU + North Window(s) BTU
Occupants
Purpose built Server Rooms don't normally have people working in them, but if people do regularly work in your Server Room you will have to take that into account. The heat output is around 400 BTU per person. Total Occupant BTU = Number of occupants x 400
Equipment
Clearly most heat in a Server Room is generated by the equipment. This is trickier to calculate that you might think. The wattage on equipment is the maximum power consumption rating, the actual power consumed may be less. However it is probably safer to overestimate the wattage than underestimate it. Add together all the wattages for Servers, Switches, Routers and multiply by 3.5. Equipment BTU = Total wattage for all equipment x 3.5
Lighting
Take the total wattage of the lighting and multiply by 4.25. Lighting BTU = Total wattage for all lighting x 4.25