Pipe Supports
Pipe Supports
FLUOR DANIEL
PIPE SUPPORTS
PURPOSE
This practice establishes guidelines and recommended procedures for the design of pipe
supports.
SCOPE
This practice includes the following major sections:
GENERAL
DESIGN LOADS
DESIGN OF PIPE SUPPORT COMPONENTS
REFERENCES
ATTACHMENTS
APPLICATION
This practice applies to all structures as described herein as pipe supports.
GENERAL
The term "pipe supports" describes a class of structures ranging from small supports
carrying light utility lines to the main multilevel pipeways loaded with air coolers.
There are 6 basic types of supports, as follows:
Sleeper supports
Usually, pipe supports, strutted or unstrutted, are designed as rigid frames, bents, in the
transverse direction. In the longitudinal direction, strutted pipe supports may be
designed with the longitudinal struts either acting with the columns transmitting all
longitudinal loads to vertical bracing, or as a continuous rigid frame. The design
approach used will depend on the job criteria. Unstrutted pipe supports are usually
designed as cantilever members in the longitudinal direction. Longitudinal and
transverse directions are defined in the attached figures.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 2 of 13
FLUOR DANIEL
PIPE SUPPORTS
The spacing of supports is based on the allowable span for piping and electrical cable
tray being supported. Typical support spacings are 20 to 25 feet; however, the bent
spacing can vary from 10 to 40 feet with intermediate beams being supplied when the
support spacing exceeds 20 to 25 feet. Pipe bridges are typically used when the spacing
between support bents exceeds 40 feet, which normally occurs at road crossings.
Clearances over, under, and around pipe supports are an important consideration in their
design. Normally, these clearances are established in the project design criteria. Due
consideration should be given to clearance requirements and existing and proposed
interferences prior to performing pipe support design calculations.
Computer programs and spreadsheets are available for the analysis and the design of
pipe supports; their use is greatly encouraged, but should be coordinated through the
project Lead Structural Engineer.
DESIGN LOADS
The design loads discussed below include gravity loads and lateral loads. Also,
combinations of these loads are defined.
Gravity Loads
Gravity loads include piping, electrical, structural, and equipment loads.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 3 of 13
FLUOR DANIEL
PIPE SUPPORTS
Piping
An average pipe deck load of 40 psf (Pounds Per Square Foot) should be used for major
pipe supports. This corresponds to an equivalent load of 8 inch pipes full of water,
spaced at 15 inches c/c, which is considered to be an average operating load condition
for pipe supports. The empty load condition may be taken as 60 percent of the operating
load condition. Preliminary piping and process information should be consulted to
determine if a heavier or possibly a lighter load should be considered. A concentrated
load should be added at pipes which are at least 2 sizes larger than the average on the
support. This concentrated load can be calculated using the tables attached to this
practice with the following formula:
P = s(w - pd)
where
P = Concentrated load
s = Support spacing
w = Weight of pipe per unit length
p = Pipe deck load
d = Pipe diameter.
When analyzing existing pipe supports, the actual piping supported on the pipe supports
should be considered. It is not necessary that the piping be applied to the structure as
individual concentrated loads except as described above. A uniformly distributed load
representative of the existing piping is preferable. A minimum operating load of 25 psf
should be used for piping on any pipe support, new or existing. Also, empty and future
areas on pipe supports should be considered loaded as described above.
For large vapor and flare lines, it should be established whether or not the line will be
hydrotested in place. Also, the normal operating weight of the line should be
established, since it is usually 10 percent to 30 percent of the full of water weight of the
pipe. This is especially important when adding to existing pipe supports.
Electrical
The electrical group should be consulted to determine the approximate weight and
location of electrical trays or conduits. A minimum weight of 20 psf should be used for
single level trays, and 40 psf for double level trays.
Structural
The weight of all structural members, including fireproofing, should be considered in
the design of the support. Usually, the calculation of fireproofing weight is made by
adding 2 inches of concrete cover to the nominal column, or beam flange, width and
depth, with the exception that the top flanges of beams are usually left exposed.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 4 of 13
FLUOR DANIEL
PIPE SUPPORTS
Equipment
Weights for equipment such as air coolers, including weights of all associated platforms,
ladders, walkways, and headers, should be obtained from suppliers engineering data and
piping layouts. For estimating purposes, typical air cooler loads are given in the
Attachment 03.
Unusual Loads
Special consideration should be given to unusual loads such as large valves, unusual
piping, or electrical configurations.
Lateral Loads
The lateral loads discussed below include wind and earthquake, friction and anchor
loads. These loads are described as acting in the transverse direction or the longitudinal
direction. Refer to the attached figures for definitions of transverse and longitudinal
directions.
Wind And
Earthquake Loads
Transverse wind loads will be applied to pipe supports as described in Structural
Engineering Practice 670.215.1215: Wind Load Calculation.
Longitudinal wind loads are usually small compared to other longitudinal loads and can
be disregarded unless air coolers or other unusual conditions are present.
Friction Loads
Friction loads caused by hot lines sliding across the pipe support during startup and
shutdown are assumed to be partially resisted by adjacent cold lines. Therefore, in order
to provide for a nominal unbalance of friction loads acting on a pipe support, a resultant
longitudinal friction load equal to 10 percent of the total pipe weight tributary to that
pipe support is assumed for main pipe supports. At individual supports (transverse
beams), a horizontal longitudinal load will be considered to act as a uniformly
distributed load across the member as follows:
For a given support, if considering only larger lines and ignoring smaller lines, resulting
in greater loads, these forces and associated friction coefficients shall be used instead of
considering all the lines.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 5 of 13
FLUOR DANIEL
PIPE SUPPORTS
Anchor Loads
Piping anchors (and guides) cause expansion movement to occur at desired locations in
a piping system. The Pipe Stress Engineer is responsible for locating anchors and
providing anchor loads. For this reason, it is important that the Structural Engineer
communicate with the Pipe Stress Engineer prior to starting and during the design of
any pipe support.
Anchor loads are usually small and adjacent pipes will transfer the load laterally to the
longitudinal beam struts. It is normally preferred to either have the anchors staggered
along the pipeway so that each support has only 1 or 2 anchors, or to anchor all pipes on
1 braced support. Special consideration should be given to pipe supports on which all or
most of the lines are anchored, or on which significant anchor loads are anticipated.
Anchor loads have 2 components, thermal and friction. The friction component is
related to the friction loads defined above. Engineering judgment will be exercised in
determining to what extent the friction and anchor loads are to be combined to design a
pipe support.
Since anchor loads are normally not available until the latter stages of a project, steel
pipe supports may be designed without considering anchor loads. When the anchor
loads become available, supports will be checked individually for the actual anchor load
and reinforced if necessary.
Since modifications to concrete pipe supports after construction are costly and time
consuming, an imaginary anchor load will be considered in the design when actual
anchor loads are not available. This imaginary anchor load will be equal to 2 kips for
beam spans greater than 15 feet, and 1 kip for beam spans less than 15 feet. This load
will be applied at the 1/4 span locations of the beam at each level. Thirty percent of the
imaginary load is to be considered the thermal component, and 70 percent is the friction
component.
Load Combinations
Pipe supports will normally be designed to resist the following combinations of loads:
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 6 of 13
FLUOR DANIEL
PIPE SUPPORTS
It is assumed that friction loads, including the friction component of anchor loads, do
not occur at the same time as wind or earthquake loads. Engineering judgment or
project design specifications may dictate otherwise. Also, project requirements
sometimes stipulate that test loads be combined with a reduced wind load.
Design Stresses
Usually, allowable steel stresses may be increased 1/3 for load combinations that include
wind or earthquake loads; however, the allowable stress increases must be specified in
the design specifications of the project.
When applying ultimate strength load factors for concrete design, all gravity loads will
be considered as dead loads. Although platform loads are mostly live loads, it is
acceptable to include them with gravity loads as long as they are small; less than 10
percent of the total gravity load on the member. Platform framing members should be
designed for live loads with live load factors. Friction and anchor loads should be
considered as dead loads for ultimate strength design.
Deflections Of Pipe
Supports
The deflection of structural members in a pipe support is an important consideration in
the design of the piping system. Whether the deflection is that of a transverse beam due
to piping anchors or lateral deflection of the bent due to wind loads, the criteria for the
deflection will be as specified in project requirements. However, where the Pipe Stress
Engineer indicates that the deflection of a particular anchor is critical, where multiple
anchors are located on the same support, or where there is an absence of other lines to
provide restraint, the deflection should be calculated and reviewed with the Pipe Stress
Engineer for concurrence.
DESIGN OF PIPE
SUPPORT
COMPONENTS
The components of pipe supports discussed below include rigid frames (bents),
longitudinal struts, vertical bracing, connections, and foundations. Refer to the attached
figures for reference. Also discussed are the structural elements of pipe bridges and
small supports.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 7 of 13
FLUOR DANIEL
PIPE SUPPORTS
Precast concrete bents will be analyzed for handling stresses induced from being
transported and lifted.
Transverse Beams
The beam must be designed to resist all forces, moments, and shears calculated from the
above analysis.
For the flexural design of steel beams, the unbraced length of the compression flange
should be considered 1/3 of the total span. However, for axial loads, the total span of the
beam should be used for the effective length and modified by the appropriate effective
length factor for each direction. This factor should be equal to 1.0 for the weak direction
of the beam. In the strong axis for moment connected ends, the effective length factor
should be 0.65.
Under normal loading conditions, torsional effects need not be considered since the pipe
supported by the beam limits deflection and rotation of the beam to the extent that
torsional stresses are minimal. However, torsion should be considered on an individual
basis when unusually large loads such as large anchor loads are applied to the beam
flange.
Intermediate transverse beams are sometimes required to reduce the span for smaller
pipe and cable trays. Also, they are required at pipe bridges. Generally, intermediate
transverse beams are supported by struts or the chords of pipe bridge trusses. They are
designed as simply supported beams.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 8 of 13
FLUOR DANIEL
PIPE SUPPORTS
Columns
The columns must be capable of resisting all forces, moments and shears calculated from
the rigid frame analysis. The frame analysis should be made using the following column
base conditions:
Strutted - fixed base in both the transverse and longitudinal directions, or pinned base in
both the transverse and longitudinal directions, with the major axis of the column in the
transverse direction. In general, the fixed base condition results in a smaller
superstructure and a larger foundation with smaller lateral deflections. The pinned base
condition results in a larger superstructure and smaller foundations with larger lateral
deflections.
Unstrutted - fixed bases in both directions, with the major axis of the column in the
longitudinal direction. A common design concept is to provide bracing in the transverse
direction.
Fixed at the top of the socket (for socket type footings) or the base plate.
The effective length factors for the design of columns will be as follows:
Longitudinal
Strutted - Table C-C2.1, Pages 5 - 135, AISC (American Institute for Steel
Construction) ASD 9th Ed.
Unstrutted - K = 2.0 or lesser value approved by the Project Lead Structural Engineer.
Transverse
Steel - Table C-C2.1, Pages 5 - 135, AISC ASD 9th Edition, or Figure C-C2.2, pages 5 -
137, AISC ASD 9th Edition, or another method approved by the Project Lead Structural
Engineer.
A design check should be performed for the temporary lifting of precast concrete bents.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 9 of 13
FLUOR DANIEL
PIPE SUPPORTS
Longitudinal Struts
In areas where gravity loading on struts is anticipated, beam struts should be used.
Beam struts should be designed for the greater of 50 percent of the gravity loading on
the most heavily loaded transverse beam or the actual loading. The 50 percent loading
accounts for the usual electrical conduits and piping takeoffs. This loading should not
be added to the design load for the column or footing, since pipes contributing to the
load on the struts reduces the load on the transverse beams. Prior to issuing any pipe
support drawings as AFC (Approved for Construction), the Design Engineer should
check piping drawings to verify that any struts subjected to unusually large loads have
been given special consideration.
Longitudinal struts will be designed to resist axial forces produced by longitudinal loads.
For normal conditions, longitudinal loads may be assumed to be transmitted to the struts
at each column without reconsidering column bending in combination with the rigid
frame analysis. However, if the vertical dimension between transverse beam and the
strut in question is large (exceeding 3 feet), or large anchor loads occur on the transverse
beam, the column stresses must be reconsidered.
Vertical Bracing
Vertical bracing may be used to transmit longitudinal loads from the struts to the
foundations. K-bracing (inverted chevron bracing) is most often used for this purpose.
Normally, the maximum spacing of braced bays should be limited to 150 feet.
Operating access is an important consideration when locating bracing. The Structural
Engineer will coordinate the placement of bracing with the Piping and Electrical groups.
Slotted strut connections are sometimes used to isolate the longitudinal loads on a run of
pipe support to specific braced bays. The locations of slotted connections should be
reviewed with the Pipe Stress Engineer.
Connections
Connection details described below include moment connections, base plates, and other
connections commonly used in pipe support design.
Moment Connections
Moment connections shall be designed in accordance with Structural Engineering
Practice 670.215.1209: Bolted End Plate Moment Connections.
Base Plates
Base plates will be designed in accordance with Structural Engineering Practice
670.215.1208: Base Plate Design Criteria, with anchor bolts designed in accordance
with Structural Engineering Practice 670.215.1207: Anchor Bolt Design Criteria.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 10 of 13
FLUOR DANIEL
PIPE SUPPORTS
Other Connections
Bracing and framed beam connections will be designed in accordance with the AISC
Manual. These connections will be as specified and detailed in the project standard
drawings; however, where the standard details are not appropriate or adequate, proper
details will be shown on the construction drawings.
Special attention will be given to standard shear connections used in situations with high
tension loads such as struts of large pipe supports, and especially when dealing with
longitudinal air cooler loads. The connection angles should be checked according to the
Hanger Type Connections section of the AISC Manual.
Suggested references for unusual steel connections are Salmon and Johnson, Steel
Structures Design and Behavior and Blodgett, Design of Welded Structures.
For connections between steel struts and concrete columns, which are usually required
when using precast concrete bents, some type of insert will be required. Embedded
plates cast into the concrete member with welded rebar or headed studs for anchorage or
through bolts with sleeves cast in bents may be used. Expansion anchors are not
preferred. In addition, the PCI Design Handbook describes the design of various types
of connections. The selected connection detail should be used uniformly throughout the
project in order to be economical.
Foundations
The type of foundations to be used will be dictated by the site conditions. Foundations
will be designed using the support reactions at the column bases from the rigid frame
analysis and the braced bay. Foundation design parameters are normally stated in the
project design specifications.
The stability ratio shall be checked for the most critical overturning condition. For high
wind areas, the empty load condition generally controls. In high seismic zones, the
heaviest load results in higher overturning forces. When a rigid frame is supported on 2
or more foundations, the stability of the entire system will be considered. Engineering
judgment will be used to determine if the stability of the foundation system or an
individual foundation within the system is more critical.
Pipe Bridges
Prior to making a pipe bridge design, the Design Engineer should verify with the Piping
group where pipes will be supported on the bridge. A pipe bridge should be designed as
individual components including vertical trusses (or girders), horizontal trusses, and
bridge bents. Refer to the Attachments 04 and 5. A computer space frame solution for a
pipe bridge is generally not required or recommended due to the excessive amount of
time required to make the computer model. However, where complex loading or
unusual geometric configurations are present, a space frame solution is desirable.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 11 of 13
FLUOR DANIEL
PIPE SUPPORTS
Vertical Trusses
The vertical truss of a pipe bridge should be designed as a plane truss supporting gravity
loads only. In many cases, the vertical truss can be fabricated as a single shop welded
unit. The connections of the truss should be designed to accommodate field assembly of
the truss as individual members or as a unit.
Horizontal Trusses
Horizontal trusses should be designed as plane trusses to resist all lateral loads applied
to the truss such as wind or lateral earthquake loads. Also, consideration should be
given to providing lateral support to intermediate transverse beams, especially where
anchors or large diameter pipes are present.
Bridge Bent
The bridge bent is designed similar to a typical pipe support bent with the exception that
truss loads are applied as concentrated loads to the bent. Should the member sizes of the
bridge bent become excessive, transverse vertical bracing should be used with the
approval of the client.
Small Supports
Small supports include T-supports, sleeper supports, and miscellaneous pipe supports
requested by the Piping/Pipe Stress groups. Refer to Attachments 04 and 05. These
supports usually require a minimal amount of structural analysis; however, they often
require a significant amount of design time to ensure that geometric constraints are
satisfied.
T-Supports
T-supports are usually single columns with short cantilevered beams attached to support
piping or electrical conduit/cable trays. The effective length factor, K, of the column in
both the transverse and longitudinal direction, is generally equal to 2.0. Where
engineering judgment is exercised to allow a lower value for K, especially in the
longitudinal direction (in the weak axis of the column), the value and base assumptions
will be approved by the Project Lead Structural Engineer. Guide to Pipe Support Design
by C. V. Char provides more details on effective length factor.
Sleeper Supports
Sleeper supports are used to elevate pipes at low levels above the ground. Their design
is relatively simple; however, close coordination with pipe stress is required to ensure
that anchor loads are properly handled and settlement sensitive areas addressed.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 12 of 13
FLUOR DANIEL
PIPE SUPPORTS
Miscellaneous Pipe
Supports
Most miscellaneous pipe supports such as base ells and hangers are provided by the
Piping group; however, there are cases where the Structural group is required to provide
these supports, especially in the case of hold-downs at compressors. When designing
small individual pipe supports, the usual safety factors applied to larger structures do not
adequately reflect the uncertainty of the loading that the small support will subjected to.
Engineering judgment should be exercised to ensure a safe and economical design.
REFERENCES
ACI (American Concrete Institute) 318-95
PCI (Prestressed Concrete Institute). Precast and Prestressed Concrete. PCI Design
Handbook. Third Edition, Chicago, 1985.
Char, C. V. Hydrocarbon Processing. Guide to Pipe Support Design. Vol. 58, 1979.
Salmon, Charles G. and John E. Johnson. Steel Structures Design and Behavior, 2nd
Edition, Harper & Row, Publishers, New York 1980.
Structural Engineering
Practice 670.215.1207: Anchor Bolt Design Criteria
Structural Engineering
Practice 670.215.1208: Base Plate Design Criteria
Structural Engineering
Practice 670.215.1209: Bolted End Plate Moment Connections
Structural Engineering
Practice 670.215.1215: Wind Load Calculation
Structural Engineering
Practice 670.215.1216: Earthquake Engineering
Structural Engineering
Practice 670.215.1231: Drilled Pier Foundations
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Page 13 of 13
FLUOR DANIEL
PIPE SUPPORTS
ATTACHMENTS
Attachment 01: (11Oct96)
Weights Of Pipe
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 01 Page 1 of 1
FLUOR DANIEL
WEIGHTS OF PIPE
D = Nominal Diameter
OD = Outside Diameter
t = Wall Thickness
We = Empty Weight of Pipe
Ww = Weight of Water
WF = Weight of Pipe Full of Water
* = Maximum Stock Size
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 02 Page 1 of 1
FLUOR DANIEL
To determine the weight per foot of any piping insulation, use the pipe size and nominal insulation thickness to
find the insulation weight factor, F, in the chart shown below. Then, multiply F by the density of the insulation in
pounds per cubic foot.
Example: For 4 inch pipe with 4 inch nominal thickness insulation, F = 0.77. If the insulation density is 12
pounds per cubic foot, then the insulation weight is 0.77 x 12 = 9.24 lb/ft.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 03 Page 1 of 1
FLUOR DANIEL
Wind Load:
Wind Couple, Vertical +/- 4.5 k/col +/- 4.5 k/col +/- 4.5 k/col
Longitudinal Shear
(at braced bay only) 18 k/bay 18 k/bay 18 k/bay
Note!!! Wind loads shown are based on a design wind speed of 110 mph. For other design wind speed,
2 2
V, multiply wind loads above by V /110 .
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 04 Page 1 of 1
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 05 Page 1 of 1
FLUOR DANIEL
Figure 1
Figure 2
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 1 of 12
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 2 of 12
FLUOR DANIEL
9
XXX.215.5210
SHEET 1
4A
XXX.215.5210
SHEET 1
TYP. W/ 3/4"
END PLATE
9
XXX.215.5030
TYP. W / 1 - 1/2"
DIAM. A.B.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 3 of 12
FLUOR DANIEL
5
XXX.215.5210
12
XXX.215.5170
SHEET 2
14
XXX.215.5170
SHEET2
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 4 of 12
FLUOR DANIEL
HPPEL =100'
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 5 of 12
FLUOR DANIEL
References
AISC Manual of Steel Construction, ASD 9th Edition
Piping Drawings
Materials
Steel - ASTM A36 (Allow 1/3 increase in allowable stresses for wind.)
Bolts - ASTM A325N
Transverse Wind:
Wind on Piping and Struts, Joint Loads: 3.4K @ JT.2, 5.6K @ JT.3, 1.3K @ JT.4
Wind on Columns, Member Loads: 0.07KLF on members 1 thru 3, 11, 12.
Note: Wind load calculations not shown for brevity. See practice 670.215.1215 "Wind Load
Calculations" for procedures.
Load Combinations
Note: Allow 1/3 increase in allowable stresses (0.75 factor in computer run) for combinations with wind.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 6 of 12
FLUOR DANIEL
REQUIRED
Determine steel member sizes, connections, and the foundations for the given loading conditions.
SOLUTION
Design Model
24" Flare Header
25'-0"
2'-6" 2'-6"
T.O.S. EL 101'-0"
Fixed @ base.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 7 of 12
FLUOR DANIEL
Member Design
fa
f a = 15.1 = 1.28 KSI, = 1.28 = 0.21 > 0.15
11.8 F a 6.19
76.9 (12) f bx
f bx = = 17.78 KSI , = 17.78 = 0.74
51.9 F bx 24
fa C mx f bx 0.85 (0.74)
+ = 0.21 + = 0.85 < 1.33 O.K.
Fa fa 1 − 1.28
1 − F bx 103.42
F ex
fa f
= bx = 1.28 + 0.74 = 0.80 < 1.33 O.K.
0.6F y F bx 22
Use W12 x 40
Since loads are close to those for the bottom beam, Try a W12x40 beam
Check weak axis bending using operating load comb. 5, P = 14.9K + Friction Loads
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 8 of 12
FLUOR DANIEL
fa
f a = 14.9 = 1.26 KSI, = 1.26 = 0.20 > 0.15
11.8 F a 6.19
35.2(12) f bx
f bx = = 8.14 KSI, = 8.14 = 0.34
51.9 F bx 24
7.6(12) f by
f by = = 8.29 KSI, = 8.29 = 0.31
11.0 F by 27
fa C mx f bx C my f by 0.85 1.0
+ + = 0.20 + (0.34) + (0.31)
Fa fa fa 1 − 1.26 1 − 1.26
1 − F bx 1 −
F by 103.42 6.19
F ex F ey
= 0.20 + 0.29 + 0.39 = 0.88 < 1.0 O.K.
Use W12 x 40
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 9 of 12
FLUOR DANIEL
fa
f a = 19.2 = 1.98 KSI , = 1.98 = 0.17 > 0.15
9.71 F a 11.88
68.2(12) f bx
f bx = = 23.38 KSI , = 23.38 = 1.06
35.0 F bx 22
fa C mx f bx 0.85
+ = 0.17 + (1.06) = 1.08 < 1.33 O.K.
Fa fa 1 − 1.98
1 − F bx 229.92
F ex
fa f
+ bx = 1.98 + 1.06 = 1.15 < 1.33 O.K. ⇐
0.6F y F bx 22
BRACED BAY
Friction Force:
16 Bents
20
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 10 of 12
FLUOR DANIEL
(20)2
M = 0.63 = 31.5 Ft − K
8
Σ Fii = 13.9
f
+ 31.5 = 0.15 + 0.61 = 0.76 < 1.0 O.K.
95 52
BRACING
KL 20.2(12)
r X min = 1.25 = 194 < 200 O.K.
Connections
MOMENT CONNECTION
Note: Moment Connections not shown for brevity. See technical practice 670.215.1209 " Bolted End Plate
Moment Connections" for procedures.
BASE PLATE
Note: Base Plate design not shown for brevity. See technical practice 670.215.1208 " Base Plate Design
Criteria " for procedures. Also see practice 670.215.1207, Anchor Bolt Design Criteria, for anchor bolt
design procedure.
Use STD. Base PL detail 9 / XXX.215.5030 for W10 column, with 1-1/2 " φ Anchor Bolts
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 11 of 12
FLUOR DANIEL
Note: Where WT bracing is used w/ flange attached to the gusset PL, it is required that the eccentric
moment due to the offset between the centerline of the column / beam and the centroid of the WT
be considered in the design of the WT section.
14 / XXX.215.5170, Sheet 2
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 06 Page 12 of 12
FLUOR DANIEL
For 3/8" x 5-1/2" LG clip angles , b = 2, TAllow = 5.5 x 1.27 = 7.0K < 13.9K N.G.
Foundation Design
Note : Foundation design not shown for brevity. See technical practice 670.215.1231 for drilled pile
foundations. See technical practice 670.215.1232 for driven pile supported foundations.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 1 of 21
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 2 of 21
FLUOR DANIEL
TYP.
TYP.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 3 of 21
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 4 of 21
FLUOR DANIEL
4 # 9's
4 # 9's
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 5 of 21
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 6 of 21
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 7 of 21
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 8 of 21
FLUOR DANIEL
References
ACI- 318-95
AISC Steel Manual -ASD 9th ed.
Piping Plans
Air Cooler Vendor Data
Materials
Concrete : fC' = 4000 PSI for P/R Bent, fC' = 3000 PSI for Foundation, γ
C = 150 PCF
Reinforcing Steel : fy = 60 KSI
Steel : fy = 36KSI - Bolts : 3/4" φ A325N
Anchor Bolts : A36
Soil : Allow Net Soil Bearing = 3 KSF @ 5' Below grade. ( Allow 1/3 increase due to wind )
γS = 120 PCF
Water Table Depth = 6' Below Grade
Design Loads
Gravity
Transverse Wind
Note : Wind Calculations not shown for brevity. See technical practice 670.215.1215 for procedures.
Joint Loads:
Fx : 2.9K @ JTS. 3 & 4, 11.2K @ JTS. 5 & 6 .
Mz : -12.5Ft - K @ JTS. 5 & 6
Load Combinations
Basic Loads ( Note: Since Live Load on air coolers is small; multiply live load by (1.7/1.4) and include
with piping.)
1. Gravity Load without piping & air cooler live loads.
2. Piping ( Wt of piping and contents) & air cooler live loads.
3. Transverse wind loads.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 9 of 21
FLUOR DANIEL
- Factored
REQUIRED
Design concete members and detail connections for the given loading.
SOLUTION
Computer Model
Y
30'-0"
T.O.C. EL 125'
24" 24"
T.O.C. EL 119'
20" SQ.
BB PL
EL 101' 0"
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 10 of 21
FLUOR DANIEL
Member Design
Beams : Try 20" wide x 24" deep beams. ( d = 24 -2-1/2" = 21- 1/2" )
Design Cases:
Member 5, Joint 3, Comb. 15, Mu- = 299'K
Member 5, Joint 4, Comb. 13, Mu+ = 135'K
2 20(21.5)2
F = bd = = 0.770
12000 12000
1200(1.125)3.31
L dh = 4 = 17.7" ≈ ( 20" -2" cover = 18 " )
4000
Note: Since max lateral bending moment occurs @ midspan and max vertical bending moment occurs @
JTS. - Assume 1- #9 top and 1 - #9 bottom bar are available at midspan for lateral bending.
AS PROV'D = 2 x 1.0 = 2.0 in2 > 0.56 in2 O.K.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 11 of 21
FLUOR DANIEL
Beam Shear
Design Case : Member 5 @ JT. 3, Comb. : 15, VU = 41.03K, @ d, VU = 33.29K
bw s 20(10)
AV REQ'D = 50 = 50 = 0.167 in 2
fy 60, 000
Columns
Design Case : member 2 @ JT.2, Comb. 13, PU = 64.53K , VU = 23.33K , MU = 236.73 k-ft
Check Slenderness
EI c 13333 + 13333
Σ
Lc
ΨB = = 18 6 = 7.7, ϕ n = 1.0 (Fixed End)
EI B x 0.5 11520
Σ 30
LB
1.8(18)12
K = 1.8, KL
r = 0.3(20) = 64.8 > 22 , also 64.8 < 100
Cm 1.0
δb = pu = = 1.17
1− 1 − 64.53
φ(p cb ) 0.7(627)
p cs = 2 x 627 = 1,254K
δs = 1.0 = 1.08
1 − 64.53
0.7(1254)
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 12 of 21
FLUOR DANIEL
mC = δ
b m b2 + δ
S m 2S = 1.17(10.89) + 1.08( 236.73 - 10.89 ( 0.9 / 1.4 )) = 12.7 + 248.1 = 260.8
γ= 20 − 4 = 0.80
20
pu mc 260.8(12)
= 64.5 = 0.16 , = = 0.39
A g (20)2 h Ag (20)3
k-ft
Use W24 x 104 Beam (MAllow = 435 )
Braced Bay
Longitudinal Force
Note : Wind calculations not shown for brevity. See
technical practice 670.215.1215 for procedures.
Friction
( Use 10% of beam end shear for piping oper. load+30% anchor)
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 13 of 21
FLUOR DANIEL
Σ Fi = 22.4/95 +
fi
33.5/52 = 0.88 ≤1.0 O.K.
Bracing
Connections
Splice : VMax = 64.5K , # Bolts REQ'D = 64.5/9.3 = 7 (Bolts are in single shear )
Use PL 1/2" x 6" x 20-1/2" with 7 - 3/4" A325N bolts on one beam
& 5/16" Fillet weld on other beam.
12.75(0.75)24
# Bolts REQ'D = = 12 bolts
2(9.8)
Use PL 3/4" x 13" x 21" with 24 bolts., Typ. top and bottom
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 14 of 21
FLUOR DANIEL
9.4(2)12 55.5
TAC = - = 0.2K
2(8) 4
Note : Anchor bolt design not shown for brevity. See technical practice
670.215.1207 for procedures.
Note : For brevity, the design of these connections is omitted. The details shown were designed for the
compression and/or tension force component perpendicular to the face of the column in combination with
the shear force parallel to the face of the column, using headed studs. For these types of connections,
headed studs, rebar, embedded inserts, anchor bolts, or sleeved threaded rods can be used. For design
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 15 of 21
FLUOR DANIEL
Foundation Design
( f'C = 3 KSI )
Pier Design ( Use 3' - 0" Square Pier , Say height is 4' - 6" )
36(33.5)2
F= = 3.37
12000
Footing Design
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 16 of 21
FLUOR DANIEL
SBGROSS = 188
6(1.70)
1± = 4.41 KSF < 4.6 KSF allowable = (1.33 x 3 + 5 x 0.12 ) O.K.
84 10.5
136 4(10.5)
SBGROSS = = 3.60 KSF < 4.6 KSF O.K.
84 3(10.5 − 2(2.1))
P1 = 114.7 + 56.5 + 30.3 = 201.5K, MRS = 684'K , SR = ∞ , e = 0.52', SBMax = 3.32 KSF
P2 = 108.4 + 56.5 - 30.3 = 134.6K , MRS = 660'K , SR = 2.93, e = 0.77, SBMAx = 2.53 KSF
MOT = 17.3 x 6 ± 30.3 x 4 = 103.8 ± 121.2 = -17.4 k-ft, 225 k-ft O.K.
Design Cases
- Factored : 1 Joint 1, Load Comb. 15, PU = 142K , VU = 25.5K , MU = 252 k-ft
4(10.5)
SBGROSS = 206 = 5.23 KSF
84 3(10.5 − 2(1.97))
2(206)
x= = 9.85'
8(5.23)
d = 18 - 3.5 = 14.5"
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 17 of 21
FLUOR DANIEL
12(14.5)2
F= = 0.210
12000
Determine C.G.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 18 of 21
FLUOR DANIEL
X
Item WT X Y WT*X WT*Y
1 10.04 0 12 0 120.48
2 10.04 30 12 301.2 120.48
Y
3 14.19 15 17 212.85 241.23
4 14.19 15 23 212.85 326.37
Σ 48.46 726.9 808.56
Use air cooler support beam seat connection for lifting points "A".
Use y = 24 - ( 24 - 16.69) x 2 = 9.38' , say 9' 4-1/2" for lifting points "B".
96(12)
AS REQ'D = = 1.44 in2 < 2 - #9's ( AS = 2.0 in2 ) O.K.
(0.9)2 (60)16.5
- Column : PU = 12.75K
(13.62 + 7.62)
R1 = 12.75 x + 0.71 x 14.62/2 - 31.23/14.62 = 21.58K
14.62
V = 0 @ x = 7'-0",
57.2(12)
AS REQ'D = = 0.81 in2 < 3 - #9's ( AS = 3.00 in2 ) O.K.
(0.9) (60)17.5
2
T = 48.46/2 x ( 1 + 25% impact) = 30.3K Use 25% impact per FD construction V1 = 30.3 /2 = 15.2K
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 19 of 21
FLUOR DANIEL
(20)2
PC = φ4 f C A C = 0.65(4) 4000 = 65.8K ⇐ Governs
1000
Use e1 = 5 - 1/2"
Base Plate
k-ft
MPL = (30.3 x 8) / 4 = 60.6
6(60.6)
tPL REQ'D = = 1.06"
12(27)
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 20 of 21
FLUOR DANIEL
Use 3" radius to out side of lug plate. ( width = 6", O.K. )
- For Tension
p = V = 15.2K , L =11", K =0
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 07 Page 21 of 21
FLUOR DANIEL
T = 15.2K ( Max)
Side Plates
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 1 of 11
FLUOR DANIEL
GIVEN
Refer to SK-1 through SK -7 of sample design #2. The plan, elevation, sections, & details shown in
sample design #2 are acceptable for this design except as shown below. Note that the base plate detail in
sample design #2 is no longer required since a socket is used for this design.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 2 of 11
FLUOR DANIEL
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 3 of 11
FLUOR DANIEL
1. After erection of concrete bents , including plumbing, plug drain pipe and fill socket with water.
Allow water to remain for 3 hours.
2. Unplug drain pipe , pump and blow out the water just prior to grouting. Leave concrete surfaces
moist but not wet. Replug drain pipe.
3. Install temporary grout dams ( made of styrofoam or similar material ) on opposite faces of a
column and pour grout ( sand cement or non-shrink - per job spec ) from side only until grout starts
flowing out on the other side, indicating complete filling of the underside of the column.
Design Data
This sample design demonstrates concrete design using ACI - 318 - 89, Ch. 21 in a UBC seismic
zone 4. It also includes the design of a socket foundation.
References and materials from sample design #2 are used for this design.
Design Loads
Design Model
REQUIRED
Detail/ Design concrete members and connections used in sample design #2 for seismic forces.
SOLUTION
Member Design
Beams
The design performed in sample design #2 is valid except for the following requirements.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 4 of 11
FLUOR DANIEL
- Longitudinal Reinforcement (Code minimum requires 2 bars continuous at top and bottom)
200(20)16
A-S = 4.00 in2 & A+S = 4.00 in2 ≥ (200 bwd / fY) = = 1.07 in2 O.K.
60000
ρ- = 0.0125 & ρ+ = 0.0125 ≤ 0.025 O.K.
A+S = 4.00 in2 > A-S / 2 = 2.00 in2 O.K.
Ld = 0.04 x 1.00 x 60000 2 = 19" > 18" PROV'D , therefore hook bottom bars.
4000 4
- Transverse Reinforcement
Place stirrups starting @ 2" from col. face with 5" spacing over 2 x h = 2 x 24 = 48" , otherwise use 9"
spacing.
- Shear Strength
A S (1.25)f Y 4.0(1.25)60
a= = = 4.41”
0.85 f c b 0.85(4)20
Columns
The design made in sample design #2 is valid except for the following requirements.
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 5 of 11
FLUOR DANIEL
or ASh = 0.09 s hC fC' / fyh = 0.09 x 4 x 17.38 x 4/60 = 0.42 in2 per ACI
or ASh = 0.12 s hC fC' / fyh = 0.12 / 0.09 x 0.42 = 0.56 in2 per UBC ⇐ Governs
or LO = 18"
f Yd b 60000(9/8)
Ldh = = = 16.4" < 18.5" O.K.
65 4000
65 f C
- Transverse Reinforcement
Use #4 ties with #4 cross ties @ 4" spacing on column within joint.
2
- Shear Strength = 12 f C A U = 12 4000 20 = 304 K >> Actual and factored shear across the joint. O.K.
1000
Socket Design
Design Data M
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 6 of 11
FLUOR DANIEL
Design Assumptions
Zero adhesion is assumed between the column and the socket walls,
since cement based grout may be used.
Socket Dimensions
A S REQ D
= 12 = 1.0
A S PROV D 12(1.0)
d REQ'D = 42.00 in
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 7 of 11
FLUOR DANIEL
Design Model
R 2
Total
Determine f1 due to VU :
VU L
M=
2
V U 6M V U 6V U L 4V U
f 1V = + = + =
BL BL 2 BL 2BL 2 BL
V U 3V U − 2V U
f 2Y = − =
BL BL BL
Determine f1 due to MU :
6M U
f 1M = f 2M =
BL 2
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 8 of 11
FLUOR DANIEL
x = f1 / ( f1 - f2 )L = 23.69 in
R1 = 0.5 f1 ( B )x = 133.46 kips
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 9 of 11
FLUOR DANIEL
Design Ties
"D" Ties - Design for bending at midspan & for shear friction.
MU = R * / 10 = 24.47 ft-kips
K = MU / F = 52.92
aU = 4.45
AS = MU / ( aU * d) = 0.41 in2
AS / FT = AS / b = 0.16 in2 / ft
A Vf A S1
= A Vf - (( A S PROV’D ”E”) - = 0.09 in2 /ft
FT FT
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 10 of 11
FLUOR DANIEL
VU = R1 / 2 66.73 kips
W = 2 * Socket wall thickness + B = 54.00 in
φ = ( ACI 9.3.2.3 ) = 0.85
d = 0.8 * W = 43.20 in
νU = VU / ( φ* h * d) = 113.58 psi
νC = 2
f C = 109.54 psi
Shear reinforcing is required
Structural Engineering
Practice 670 215 1250
Publication Date 11Oct96
Attachment 08 Page 11 of 11
FLUOR DANIEL
By Comparison :
Use "E" ties same as "F" ties.
Structural Engineering