Spec No.
: ZTT 21-XJ00486
TECHNICAL SPECIFICATION
A April 22, 2021 Jason Vivian Felix
Version Date Prepared Reviewed Approved
Address: No.5, Zhongtian road, Nantong economic and technological development zone, Jiangsu Province, China
Tel: +86-513-89191138 Fax: +86-513-8359 9670 Zip code: 226010 Website: www.zttcable.com
1. SCOPE
This specification covers the general requirements and performance of conductor which ZTT offered
including electrical characteristics, mechanical characteristics, packing information etc.
2. QUALITY CONTROL STANDARD
ISO 9001 Quality Management Systems
ISO 14001 Environmental Management Systems
OHSAS 18001 Occupational Health and Safety Management Systems
3. TEST AND INSPECTION
ZTT® ET EXPRESSWAYTM AAAC shall be accordance with applicable standard of ZTT® ET
EXPRESSWAYTM AAAC and requirements of customer. The following test items shall be carried out
according to corresponding reference.
No Item Reference
Tests for AA Wire
1 Dimensions IEC 60104
2 Tensile strength IEC 60104
3 Elongation IEC 60104
4 Wrapping IEC 60104
5 Resistivity test IEC 60104
Tests for Conductor
1 Dimensions IEC 61089
2 Lay ratio and direction of lay IEC 61089
3 Number and type of wires IEC 61089
4 Mass per unit length IEC 61089
www.zttcable.com All Rights Reserved Copyright © 2021 Page 1 of 3
4. CONSTRUCTION AND SPECIFICATION FOR ZTT® ET EXPRESSWAYTM AAAC
4.1. Conductor Structure
ZTT® ET EXPRESSWAYTM AAAC-Greeley
Aluminum-Alloy Wire
4.1.1. Conductor Technical Structure
Parameter Unit Value
Center: Aluminum-Alloy wire 1/4.02
Layer 1: Aluminum-Alloy wire 6/4.02
Structure Nos./mm
Layer 2: Aluminum-Alloy wire 12/4.02
Layer 3: Aluminum-Alloy wire 18/4.02
Standard / IEC 61089 / 60104
Stranding direction of outer layer Direction Right-hand
Conductor diameter mm 28.14
Cross section mm2 469.6
Conductor weight kg/km ≤1295.0
Rated tensile strength kN 135.68
Modulus of Elasticity GPa 55.0
Coefficient of linear expansion 10-6/℃ 23.0
Max. DC Resistance at 20℃ Ω/km 0.0706
18 wires layer:10-14
Lay ratio times 12 wires layer:10-16
6 wires layer:10-17
4.1.2. Properties of Aluminum Alloy Wire (Before Stranding)
Parameter Unit Value
Diameter and tolerance mm 4.02±0.04
Min. tensile strength MPa 294
Min. elongation at 200mm % 4.0
Max. resistivity at 20℃ Ω·mm2/m 0.03250
Note: All Sizes and Values are Nominal Value
www.zttcable.com All Rights Reserved Copyright © 2021 Page 2 of 3
5. PACKING AND DRUM FOR CONDUCTOR
The required marking shall be printed with a weather-proof material on the outsides of drum according
to customer’s requirement.
strap
wood lagging
Drum Drum Dimensions Gross Weight
Drum
Cable Type Length D±10 d±10 Max.B b±10 A (Approx.)
Type
(m) mm mm mm mm mm kg
AAAC-Greeley 2800 2200 1000 1070 900 105 3930 Steel-wooden
Note: 1) Wood lagging is sealed inside. 2) The strap is made of plastic tape.
www.zttcable.com All Rights Reserved Copyright © 2021 Page 3 of 3