Cooler Controller Manual

This document provides instructions for installing and operating the GW53605A Cooler Controller. It includes specifications, a panel diagram, common screens, operations, menus, parameters, manufacturer settings, fault lists, control logic, and electrical and installation details. The manual should be read carefully before installing the controller.

Uploaded by

eburbano12
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
444 views14 pages

Cooler Controller Manual

This document provides instructions for installing and operating the GW53605A Cooler Controller. It includes specifications, a panel diagram, common screens, operations, menus, parameters, manufacturer settings, fault lists, control logic, and electrical and installation details. The manual should be read carefully before installing the controller.

Uploaded by

eburbano12
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

GW53605A Cooler

Controller

Manufacturer Instruction Manual

Please read the in manual carefully before installing the controller!

Apr 20, 2020


Software Version : X1.GW53605A.TY.F01M V100C7
All rights reserved. Any reproduction of the manual will be prosecuted.
Table of contents

1 Instructions .......................................................................................................................................................................... 1
2 Specifications...................................................................................................................................................................... 1
3 Panel Diagram .................................................................................................................................................................... 1
4 First Power-on .................................................................................................................................................................... 1
5 Common Screens .............................................................................................................................................................. 2
5.1 Main Screen ............................................................................................................................................................... 2
5.2 Alarm Screen.............................................................................................................................................................. 2
6 Common Operation ........................................................................................................................................................... 2
6.1 Quick Modification of Setting Temperature .............................................................................................................. 2
6.2 Query/Reset Fault ...................................................................................................................................................... 2
6.3 Cut over the Chinese-English quickly........................................................................................................................ 2
7 Function Menu .................................................................................................................................................................... 2
8 Parameter Operation ......................................................................................................................................................... 3
9 User Parameters Table ..................................................................................................................................................... 3
10 Manufacturer Menu ......................................................................................................................................................... 3
10.1 Procedures of Entering Manufacturer Menu ............................................................................................................ 3
10.2 Details of Manufacturer Menu ................................................................................................................................. 3
10.3 Manufacturer Debugging ......................................................................................................................................... 4
10.4 Configuration Guide ................................................................................................................................................ 4
11 Fault List ............................................................................................................................................................................ 5
12 Control ............................................................................................................................................................................... 8
12.1 Control mode ........................................................................................................................................................... 8
12.2 Control logic ............................................................................................................................................................ 8
12.3 Defrost logic............................................................................................................................................................. 8
12.4 Logic of pump freeze protection .............................................................................................................................. 8
13 Manufacturer Parameters Table .................................................................................................................................... 9
14 Electrical Connection Diagram ......................................................................................................................................... 12
15 Installation Dimensions ................................................................................................................................................. 12
1 Instructions

Dear Customer:
Thank you for choosing our products!
For your convenience, please read the instructions carefully and follow the steps of the Manual.

2 Specifications
Specification Specification
No. Description No. Description
Parameter Parameter
Rated Input Switch
1 220-240V/AC 50/60HZ 6 5 relays 250VAC 2A
Voltage Output
Temperature Ralay Load DO1: Annunclator
2 -40~100℃ 7
Range Type DO2-5: Contactor
Measurement
3 0.1℃@25℃ 8 Switch Input 12 passive signal inputs
Accuracy
Working -10℃~60℃,≤85%RH
4 9 Analog Input 4 NTC temperature sensor
Environment non-condensation
Storage -20℃~70℃,≤85%RH
5 10 Current Input 4 ways of current (0.3~35A)
Environment non-condensation

3 Panel Diagram
Black out:Comp run is not allow
Twinkle:Com run is allow
In d u stria l C h ille r
Light:Remote
ON/OFF is allowed Light:Comp is running
Black out:Remote To switch the comp
ON/OFF is forbided run is Allow or not
远程 压缩机
Remote
Compres sor

故障 Black out:Pump stoped


Twinkle:Unit alarm A lar m
Twinkle:Pump stoping
Black out:No alarm 泵
Pump
Light:Pump running

Menu, Cancel, Back, Shift


功能
Func tion
向上
Up
向下
Down
确定
OK
Units ON/OFF

6531- 1-001-10 0

Add value, Change page,


Choose parameter

Decrease value, Change OK, Query, Reset, Enter


page, Choose parameter

4 First Power-on
The controller needs to be configured when powered on for the first time. Please refer to 10.4 Configuration
guide for specific operation.
5 Common Screens
Commonly used screens include the main screen and the alarm screen.
5.1 Main Screen 5.2 Alarm Screen
The system will enter the main screen after In case of unit failure, the alarm screen is as follows:
countdown, which displays as follows:
PV ℃ PV 20.5 ℃ Liquid temperature
Liquid temperature
Alarm ! Display flickeringly

Fn Menu 12.0 Set



Control temperature Fn Menu OK Query Silence&Query

Press + for 3 seconds on the main screen


can change the language quickly.

6 Common Operation

6.1 Quick Modification of Setting Temperature 6.2 Query/Reset Fault


If the user parameter [Lock T.set] is set to "No", In case of fault, the alarm screen will automatically
the setting temperature can be modified directly in the pop up. The operation details of query and reset faults
main screen, with operation details as follows: are as follows:
Main screen Change set temperature Main screen Alarm screen Current Fault Main screen
PV ℃ PV ℃ PV ℃ PV 20.5 ℃ Probe break PV ℃
Alarm !
Fn Menu 12.0 Set
℃ Fn Menu 11.9 Set
℃ Fn Menu 11.9 Set
℃ Fn Menu OK Query Fn Back OK Reset Fn Menu 12.0 Set

Note: the setting temperature can also be modified in


the user parameters.
6.3 Cut over the Chinese-English quickly

Press at the same time + 3 seconds in the main screen cut over the Chinese-English quickly
behind .

Note: The language establishes can also be modified in the user parameters.

7 Function Menu

Press the button on the main screen to enter the Function Menu, which includes five items as the
table below:
No. Menu Item Funtion Remark
1 Temp. Query To query all the temperature value
For number of user parameters and their
2 User Setting To display user parameters implications, please refer to: 9 User
Parameters Table.
To display the current operating status Current value is not displayed when current
3 Unit Status
of the unit module is not used.
4 History List Allowing the query of the last 10 faults Press for 2s to clear the fault history.
Comp Total To display the cumulative operation
5
Run time of the compressor
6 Version To check the current software version
8 Parameter Operation

For the modification operation of parameter value, the user’s modification of setting temperature will be
described as an example.
Enter parameter
Function Menu Enter user setting Choice parameter value set Set parameter value Save parameter value
1:Temp Query Lock T.set: T.setpoint: T.setpoint: T.setpoint: T.setpoint:
2:User setting No 12.0 ℃ 12.0 ℃ 11.9 ℃ 11.9 ℃
3:Unit status
Fn Back OK Enter Fn Back OK Set Fn Back OK Set Fn Cancel OK Ok Fn Cancel OK Ok Fn Back OK Set

9 User Parameters Table

The implication of each parameter in the user parameters is listed in the following table:
No. Parameter Factory Setting Range Remark
Name Default
Yes: the set temperature can not be modified on
the main screen when locked.
1 Lock T.set No Yes ~ No
No: the set temperature can be modified on the
main screen.
[T.setpoint min] Setting range is limited by the manufacturer
2 T.setpoint 12.0℃
~[ T.setpoint max] parameters [T.setpoint max], [T.setpoint min].
T. Set: The control temperature = [T.setpoint].
Control
3 T. Set T. Set ~T. Environ T. Environ: The control temperature =
mode
Environment temp + [T.Environ diff].
4 Contrast 32 20~44 Adjust the LCD contrast
Local: the unit can only start and stop locally.
Local + Remote: the start and stop of the unit
Local / Local +
5 On/Off type Local can be controlled both locally and remotely.
Remote / Remote
Remote: the unit can only start and stop
remotely.
6 Backlight On 0 0~255 minute(s) 0: backlight is not turned off.
7 Language Chinese Chinese~English Select the display language.
T.Environ This parameter is useful when [Control mode] is
8 0.0℃ -20.0~20.0℃
diff set “T. set”.
Note: if [Probe-ROOM] = Forbid,[Control mode] will hide and default to T. Set.

10 Manufacturer Menu

Press + in the main screen to enter the Enter Password screen and enter the correct
manufacturer password (default 4561, which is recommended to change). Then enter the Manufacturer Function
Menu, which includes five items.

10.1 Procedures of Entering Manufacturer Menu


enter password If password is right,
Main Screen Enter password screen Chang password Shift to next has accomplished enter the factory menu
PV ℃ Enter password Enter password Enter password Enter password 1:Manuf.Setting
+ 0*** ***1 2:Manuf. Debug
4*** *0**
3:Config Guide
Fn Menu 12.0 Set
℃ Fn Shift OK Ok Fn Shift OK Ok Fn Shift OK Ok Fn Shift OK Ok Fn Back OK Enter

10.2 Details of Manufacturer Menu


The details and function of manufacturer menu are shown in the following table:
No. Parameter Item Function Remark s
1 Manuf.setting To set the parameters commonly Refer to 13 Manufacture
used by the manufacturer Parameters for specific parameters.
To debug the abnormal operation Not available during the unit
2 Manuf.Debug
of each electrical part of the unit operation.
Not available during the unit
Commonly used parameters of operation.
3 Config guide
config the unit The screen will pop up when
powered on for the first time.
For initialize all parameters of the Parameters for the initial values of
4 Initialize
machine. the parameters.
To set the password to enter The default value is 4561, which is
5 Password Set
manufacturer menu. recommended to change.

Note: Press + in the manufacturer menu for 2 seconds can reset the accumulative operation
time of the compressor.

10.3 Manufacturer Debugging

Manufacturer debugging is mainly used to test whether the operation of each electrical part of the unit is
normal, which is not available when the unit is under operation.
Method: to determine whether the unit is normal by testing three-phase power input, nine alarm inputsand 5
relay outputs. For alarm input, it only displays the test result. If the result is normal the wiring is good and
parameter settings are correct; if it alarms, with flashing display of alarm characters, then make sure whether the
external wiring is good and the parameter settings are consistent.

Factory debug screen Enter factory debug The result of I/O input Press or choice Relay output Relay stop output
Manuf. Debug High1 Press: Low1 press: Pump: Cool: Pump: Cool: Pump: Cool:
Normal Alarm Comp: Alarm: Comp: Alarm: Comp: Alarm:
Heat: Heat: Heat:
Fn Cancel OK Enter Fn Back Fn Back Fn Back OK ON Fn Back OK OFF Fn Back OK ON

10.4 Configuration Guide

Configure the common parameters of the machine. For the number of parameters of configuration guide
and the significance, please refer to 13 Manufacturer Parameters Table. Access is not available during the unit
operation.
Refer to the Parameter Operation for specific configuration method. The Configuration guide screen will pop
up when powered on for the first time. And if you click “Cancel” operation without configuring at this point, the
Configuration guide screen will still pop up when powered on next time. Once you have entered the
Configuration guide, the Configuration guide screen will not pop up when powered on and you can only enter the
Configuration guide through the Manufacturer Menu.
One-Key start: the number of parameters of
Forbid configuration guide and the
Enter:the screen will significance, please refer to 13
Config Guide not pop up when Fn Back OK Set Manufacturer Parameters Table
Config Guide powered on next time

Fn Cancel OK Enter
PV ℃

Cancel:the screen will


still pop up when Set
Fn Menu 12.0 ℃
powered on next time
11 Fault List

Fault Description Test Conditions Troubleshooting Solution


Test when the compressor button has
Comp.P high High pressure of compressor
pressed
If the [LP detect dly] is 0, test when the Check if the input is consistent with
compressor button has pressed; the switch setting.
Comp.P low Low pressure of compressor
If the [LP detect dly] is not 0, then
compressor runs the test. Stop compressor only
without affect other Check if the input is consistent with
Comp overload The compressor overload
equipments to work. the switch setting.
The current of compressor is Check if the rated current of
Comp.I high Compressor runs the test.
too high compressor1 is input is reasonable.
The current of compressor is Check if the measure tool of the
Comp.I low
too low compressor1 current is connect.
Check if the input is consistent with
OverHeat The temp of heat is too high Power on to test Stop Heat
the switch setting.
Stop the compressor and
Check if the Liquid temperature is
The liquid temperature is too delay to stop the cool
Temp.low AL lower than the set temperature of
low pump, and do not stop the
Liquid protection.
cold pump.
Check if the Liquid temperature is
The liquid temperature is Alarm only without affect
T.high warn higher than the set temperature of
higher than the warn value. other equipments to work.
Liquid warn.
Test after cold pump starts If the [Temp.high AL] is set
“Pump keep”,Stop the
compressor and delay to
Check if the Liquid temperature is
The liquid temperature is too stop the cool pump, and
Temp.high AL higher than the set temperature of
high do not stop the cold pump;
Liquid protection.
If the [Temp.high AL] is set
“Pump stop”, Stop the unit
in case of fault.
Anti-freez.AL Antifreeze alarm Power on to test Stop all the compressor Check if the antifreeze input is
and cool pump, and do not consistent with the switch setting.
The liquid temperature sensor stop the cold pump.
Probe break
is break
The liquid temperature sensor
Probe short
is short
The environment temperature
Environ break
sensor is break
The environment temperature
Environ short
sensor is short Check if the temperature probe is in
The evaporator temperature proper contact.
Evap break
sensor is break
The evaporator temperature
Evap short
sensor is short
The condenser temperature
Condns break
sensor is break
The condenser temperature
Condns short
sensor is short
If the [T.AFR Low Deal] is
set “Pump keep”,Stop the
compressor and delay to
Check if the evaporator temperature
The evaporator temperature is stop the cool pump, and
T.Evap low Power on to test is lower than the set temperature of
too low do not stop the cold pump;
Liquid protection.
If the [T.AFR Low Deal] is
set “Pump stop”, Stop the
unit in case of fault.
Check if the condenser temperature
The condenser temperature is
T.Condns high Power on to test Stop the unit is higher than the set temperature of
too high
Liquid protection.
Check if the fan1 overload input is
Cool overload The cool pump or fan overload
Stop compressor and cool consistent with the switch setting.
Test after Cool pump starts
The current of cool pump or pump or fan only Check if the rated current of cool is
Cool.I high AL
Fan is too high input is reasonable.
The current of cool pump or Check if the measure tool of the cool
Cool.I low AL
Fan is too low current is connect.
If the [Lack of medium] is
set “Pump keep”, Stop
compressor and cool
Test after the cold pump starts for Check if the cold liquid flow input is
Inadqt flow AL Lack of liquid flow pump in case of fault.
[Pump on delay] time consistent with the switch setting.
If the [Lack of medium] is
set “Pump stop”, Stop the
unit in case of fault. Stop
heat.
Check if the cold pump overload
Pump overload The cold pump overload input is consistent with the switch
setting.
The current of cold pump is Test after cold pump starts Stop the unit Check if the rated current of cold is
Pump I high AL
too high input is reasonable.
The current of cold pump is Check if the measure tool of the cold
Pump I low AL
too low current is connect.
Check if there is default phase or
The three-phase power input
Phase AL Power on to test Stop the unit anti-phase in the three-phase power
is alarm
input and if the switch is correct.
If the [Low liquid lv] is set
“Pump keep”, Stop
compressor and cool Check if the liquid level input is
Medium lv.AL The liquid level is low Power on to test
pump in case of fault. consistent with the switch setting.
If the [Low liquid lv] is set
“Pump stop”, Stop the unit
in case of fault. Stop heat.
The total time of compressor The unit cannot start once stops (the accumulative operation time
Need Maintain Test after cold pump starts
run over the allow value of compressor exceeds the set value).
12 Control

12.1 Control mode


a) When [control mode] is set “T. Environ”, the Control temperature = Envrionment temperature + [T.Environ diff];
① if Envrionment temperature + [T.Environ diff] > [T.setpoint max], Control temperature = [T.setpoint max];
② if Envrionment temperature + [T.Environ diff] < [T.setpoint min], Control temperature = [T.setpoint min].
b) When [control mode] is set “T. Set”, the Control temperature = [T.setpoint].

12.2 Control logic


a) When [Heat type] is set “Heat Null”,
The Compressor OFF when the Liquid temperature < Control temperature – [Close COMP];
The Compressor ON when the Liquid temperature > Control temperature – [Open COMP].
b) When [Heat type] is set “Four valve”,
The Compressor and Valve ON when the Liquid temperature < Control temperature – [Open warp], and the
Compressor and Valve OFF when the Liquid temperature higher than the Control temperature;
The Compressor ON when the Liquid temperature > Control temperature – [Open refrige], and the
Compressor OFF when the Liquid temperature lower than the Control temperature.
c) When [Heat type] is set “Elec. heat”:
The Heat ON when the Liquid temperature < Control temperature – [Open warp] ], and the Heat OFF when
the Liquid temperature higher than the Control temperature;
The Compressor ON when the Liquid temperature > Control temperature – [Open refrige], and the
Compressor OFF when the Liquid temperature lower than the Control temperature.

[Note]: If [Heat type] is set “Four valve” or “Elec. heat”, and [Close heat] is set nonzero, the Valve or Heat OFF
when the Liquid temperature ≥ [Close heat].

12.3 Defrost logic

Enable the defrost function while [Heat type] is “Four valve” and [Defrost choose] is “Use”
a) Conditions of activing defrost
 T.Condns < [Defrost temp1] lasts for 180S.
 T.liquid > [T.low protect]
 Time of frost deposit > defrost interval
Start defrosting while conditions all the above meet.
[Note]: Time of frost deposit means time the compressor had run for since last defrost action,which will be
cleared if the units stop.
Defrost interval is 120MIN if T.Condns < [Defrost temp1];
Defrost interval is 60MIN if T.Condns < [Defrost temp2];
Defrost interval is 30MIN if T.Condns < [Defrost temp3];

b) Conditions of stopping defrost


 T.Condns > [StopDefrs temp].
 Defrost action lasts for [Defrost time].
 Comp.P high occurs.
 T.liquid < [T.low protect].
Stop defrosting while one of conditions above meet.

c) Conditions of manual defrost


 T.Condns < [StopDefrs temp] .
 T.liquid > [T.low protect]
 The compressor had run for [Comp protect]

Pressing + for 2S at main screen will start defrosting while conditions all the above meet.

12.4 Logic of pump freeze protection


a) When [T.freeze prot] = “forbid”, there is no pump freeze protection.
b) Otherwise under the idle state:
if SV ≤ [T.freeze prot], the pump opens;
if SV ≥ [T.freeze prot] + 2, the pump will close after 10 seconds.

13 Manufacturer Parameters Table


Parameters set by the manufacturer and parameter meanings are listed as follows: ("*" is for parameters of
the configuration guide)
Setting Name of Factory
Setting Range Remark
Item Parameter Default
Forbid: the compressor is allowed to ON only when
*One-Key press the compressor button;
Forbid Forbid ~ Use
start Used: the compressor allows ON when press the pump
button.
Use: the unit starts automatically when powered on;
Forbid: the unit doesn’t start automatically when
Auto start up Forbid Forbid ~ Use powered on;
When the user parameter [On/Off type] is set to
be"Remote", the electrical autostart is invalid.
Keep when Keep when mute: Press the “Alarm output” parameter to
Keep
mute; take action once a fault occurs;
Alarm output when
Stop when Stop when mute: Press the “Alarm output” parameter to
mute
mute take action in case of no fault after silencing.
If [DO1 fuction] is “Alarm signal”
N.O: the alarm relay is ON in case of faults;
N.C: the alarm relay is OFF in case of faults.
If [DO1 fuction] is “Run signal”
Alarm type N.O N.O~N.C
N.O: The alarm relay is OFF when the unit is normal
running;
N.C: The alarm relay is ON when the unit is normal
running.
Pump stop: stop the cold pump in case of low liquid level
*Low liquid Pump Pump stop ~ fault;
lv. stop Pump keep Pump keep: do not stop the cold pump in case of low
liquid level fault.
Func. Pump stop: stop the cold pump in case of cold liquid flow
Setting *Lack of Pump Pump stop ~ fault;
medium stop Pump keep Pump keep: do not stop the cold pump in case of cold
liquid flow fault.
*Current Use: there is a current detection module;
Use Forbid ~ Use
detect Forbid: no current detection module
*Comp.I
0.3A 0~35.0A
rating
0A: do not detect the current fault.
*Pump. I
0.3A 0~25.0A When [Current detect] is set “Forbid”, those parameter is
rating
not displayed.
*Cool. I
0.3A 0~25.0A
rating
Cool Cool overload;
DI1 input opt Selection of switch DI1 input function
overload Anti-freezing
On Board: use the controller’s own three-phase power
Phase On_boar On_board ~
protection;
monitor d IO_input
IO input: use an external three-phase power protection.
Alarm Alarm signal; [DO1 fuction] is “Alarm signal”,
DO1 function
signal Run signal [DO1 fuction] is “Run signal”
Heat Null; Heat Null: DO5 do not output.
Heat type Heat Null Four valve; Four valve: DO5 output as Four Valve
Elec. heat Elec. Heat: DO5 output as Heat.
T.AFR Low Pump Pump stop ~
\
Deal stop Pump keep
Probe-ROO Use: with T. Environ function
Use Forbid ~ Use
M Forbid: without T. Environ function
Probe-CON Forbid Forbid ~ Use Use: do not check T.Condns high
D Forbid: check T.Condns high
Use: do not check Anti-freez.AL
Probe-FRZ Forbid Forbid ~ Use
Forbid: check Anti-freez.AL
Forbid: Disable the defrost logic.
Used: Enable the defrost logic while [Heat type] is “Four
Defrost
Forbid Forbid ~ Use valve”.
choose
This Parameter is hidden while [Heat type] is not “Four
valve”.
Pump stop: stop the cold pump in case of Temp.high
Temp.high Pump Pump stop ~ fault;
AL keep Pump keep Pump keep: do not stop the cold pump in case of
Temp.high fault.
Open COMP 1.0℃ 0~10.0℃ Temperature deviation of load the compressor
Close COMP 1.0℃ 0~10.0℃ Temperature deviation of unload the compressor
T.setpoint
30.0℃ 0~99.9℃
max
To limit the temperature of user set.
T.setpoint
5.0℃ -38.0~99.9℃
min
Fault of “Temp.low AL” warning is reported when the
T.low protect 4.0℃ -40.0~99.9℃
liquid temperature is lower than the set value.
Fault of “Temp.high warn” warning is reported when the
T.high warn 50.0℃ 0~99.9℃
liquid temperature is higher than the set value.
Fault of “Temp.high AL” warning is reported when the
T.high alarm 60.0℃ 0~99.9℃ liquid temperature is higher than the set value. And Stop
the compressor and delay to stop the cool pump.
If liquid temperature<[T.high alarm]–[T.high reset],
manual reset of “Temp.high AL” fault is allowed;
T.high reset 5.0℃ 0~99.9℃
If liquid temperature<[T.high warn]–[T.high rese], the
“Temp.high warn” fault is automatically reset;
Fault of “T.Evap low” warning is reported when the
T.evap alarm 3.0℃ -38.0~15.0℃
evapprator temperature is lower than the set value.
T.condn Fault of “T.Condns high” warning is reported when the
68.0℃ 60.0~80.0℃
Temp. alarm Condensor temperature is higher than the set value.
Setting Open warp 4.0℃ 0~10.0℃ Temperature deviation of open heat
Open refrige 2.0℃ 0~10.0℃ Temperature deviation of open refrigerate
Liquid bias 0.0℃ -9.9~9.9℃ Compensation for the liquid temperature
Compensation for the environment temperature,
Environ bias 0.0℃ -9.9~9.9℃
Hide when Probe-ROOM = Forbid
Compensation for the evapoartor temperature
Evap bias 0.0℃ -9.9~9.9℃
Hide when Probe-FRZ = Forbid
Compensation for the condensor temperature
Conds bias 0.0℃ -9.9~9.9℃
Hide when Probe-COND = Forbid
0: this parameter has no effect.
Close heat 0.0℃ 0.0~30.0℃ Non-0: The Heat OFF when the Liquid temperature is
higher than the set value.
Defrost The defrost interval is 120 Minu while T.Condns <
-4.0℃ -38.0~30.0℃
temp1 [Defrost temp1]
Defrost The defrost interval is 60 Minu while T.Condns <
-6.0℃ -38.0~30.0℃
temp2 [Defrost temp2]
Defrost The defrost interval is 30 Minu while T.Condns <
-10.0℃ -38.0~30.0℃
temp3 [Defrost temp3]
StopDefrs
15.0℃ 0.0~30.0℃ Stop defrosting while T.Condns > [StopDefrs temp]
temp
T.freeze prot forbid forbid~15.0℃ No such function when set to forbid.
Pump on
10 S 1~255 S Delay after cold pump startup.
delay
Time Cool on
10 S 1~255 S Delay after cool pump startup.
Setting delay
Control the compressor ON/OFF every [Capacity ctrl.]
Capacity ctrl. 5S 0~255 S
interval time;
For double-compressor control, if the conditions of two
compressors ON are satisfied, then one of the
compressors ON and the other after the time of
[Capacity ctrl.].
To avoid frequent ON/OFF the compressor, the interval
Comp
60 S 0~255 S between the start of two compressors must be greater
protect
than the set value.
Input stable 2S 0~255 S The time General fault stable.
It is considered to be valid only when the water flow
L.flow stab. 5S 0~255 S
alarm continue for the time.
Compressor low-pressure fault input is allowed only
LP detect dly 60 S 0~255 S
when the compressor has run for the set time.
LP stable 5S 0~255 S Low-pressure fault stable time
0: this parameter has no effect.
Comp Non-0: the compressor cannot start when the
0H 0~9999 H
operation accumulative operation time is greater than the set
value.
Comp.I 2S 1~255 S The current fault of compressor can only be detected
avoid after compressor has started for the set time.
(When the [Current detect] is set “forbid”, the parameter
is not displayed.)
The current fault of cold pump can only be detected after
Pump. I it has started for the set time.
2S 1~255 S
avoid (When the [Current detect] is set “forbid”, the parameter
is not displayed.)
The current fault of cool pump can only be detected after
it has started for the set time.
Cool. I avoid 2S 1~255 S
(When the [Current detect] is set “forbid”, the parameter
is not displayed.)
Stop defrosting while the accumulative defrosting time >
Defrost time 180S 10~600S
[Defrost time]
*Cool
N.C N.O ~ N.C
overload
*Freez
N.O N.O ~ N.C
overload
*Cold L.flow N.C N.O ~ N.C
*L.level
N.C N.O ~ N.C
switch
*Comp Selection of switch input mode
Input N.O N.O ~ N.C N.O: switch off with no fault;
overload
Setting N.C: the switch is closed with no fault.
*Low
N.C N.O ~ N.C
pressure
*High
N.O N.O ~ N.C
pressure
*Phase error N.O N.O ~ N.C
*Anti-freez N.O N.O ~ N.C
N.O ;
OverHeat Forbid N.C;
Forbid

[Note]: remote switch, if the remote control is used, the unit will start up when remote switch input is closed and
stop when remote switch input is disconnected.
14 Electrical Connection Diagram

X1.GW53605A.TY.F01M.Electrical Connection Diagram


N(+) ① Comp
DO1:Annunclator Connect GW122B 号
DO1 Alarm/Run Signal GW122B
250VAC 2A
FU COM1
GW53605A L2 ② Cold Pump
L(-) DO2
RY1
CUR1 号
RY2 Cool pump(Fan) L1
DO2-5: DO3 L2 Cool Pump

Contactor
250VAC 2A DO4
RY3 Cold pump CPU CUR2
L1 号
RY4 Compressor GW122B
DO5
AI1
T1 ②
N
220-240VAC RY5 Four valve/Heat 号
AI2
T2
L
FU COM2 AI3
T3
AC220V
AI4
R T4
Phase Input DI2 DI1
S
AC220V ICOM DI12 DI11 DI10 DI9 DI8 DI7 DI6 DI5 DI4 DI3

T
L N

250VAC 2A

220-240VAC

DI1:Cool overload DI6:Compressor overload T1:Liquid temperature


DI2:Remote switch DI7:Low pressure of compressor T2:Environment temperature
DI3:Pump overload DI8:High pressure of compressor T3:Evaporator temperature
DI4:Liquid flow switch DI9:Phase switch T4:Condensor temperature
DI5:Liquid level switch DI10:Antifreezing switch
DI11:OverHeat switch

15 Installation Dimensions