Quv Accelerated Weathering Tester
Quv Accelerated Weathering Tester
Weathering
Model: QUV
IMPORTANT POINTS TO REMEMBER:
For a more detailed discussion, refer to the appropriate
section in the QUV Accelerated Weathering Tester Op-
erating Manual.
# Repairs:
The QUV is designed so that virtually all repairs can
be made by the user. You may first wish to refer to
the Troubleshooting Guide on page 21. However, if
assistance is needed, you may contact the Q-Panel
Technical Service Department by facsimile mes-
sage at (216) 835-8738 or by phone (216) 835-
8700. Please be certain to state the cycle duration,
cycle temperature, lamp type, QUV serial number,
material tested and material end use. You may
reach the Technical Service Department between
8:30 a.m. and 5 3 0 p.m. (EST) weekdays Monday
through Friday. There is no charge for technical
assistance.
QUV and Q-Panel are trademarks of The Q-panel Company.
The Q-Panel Company
@ 1992,
TABLE OF CONTENTS
.
10 Important Safety Information ..........................2 8.0 Temperature Measurement ..........................12
Uncrating .........................................................
5 Condensation Cycle ......................................12
5.4 The Water System ..........................................6 Very High and Very Low Temperatures .......14
Water Level .....................................................6 Condensation Temperature Control .............14
Cathodic Protection.........................................
6 Cycle Timer ...................................................15
Water Cleaning ...............................................7 Test Duration ................................................15
7.0 The Ultraviolet Light System ...........................9 Repairs & Technical Service ........................15
Lamp Electrical ............................................... 9 Indicator Lights ..............................................15
Lamp Aging and Replacement .......................9 10.0 Test Sample Handling ..................................16
Lamp Cooling ................................................
10 Sample Mounting Precautions ......................17
Sunburn and eye inflammation are delayed If exposure to UV lamps is necessary, wear UV
reactions. Symptoms (pain, redness, hot sensa- absorbing goggles. Protect skin with opaque
tion) do not appear until 4 to 12 hours after UV clothing or a quality sunscreen lotion percent
exposure. PABA or sun protection factor of 20), not a
"suntan" lotion.
After severe sunburn and eye inflammation, Individuals light comp~ex~ons
are more
skin and eyes may be more sensitive to future susceptible to UV, and some individuals are
UV exposures, including sunlight. allergic to UV. Also, many common medica-
tions increase your sensitivity to UV (including
There is no UV hazard from the QUV in nor- sunlight).
mal operation with doors closed. With doors
closed, UV leakage from the QUV is less than Do not use the QUV lamps for any purpose
1/20 the intensity of the UV from sunlight other than QUV testing. When discarding the
transmitted through a closed window. With lamps, disable them to prevent unauthorized
doors open but with test panels in place, UV use. To disable lamps, remove two of the end-
leakage is still less than sunlight through a pins with a wire cutter or pliers (do not break
window. Note: the QUV does not produce any lamps). These lamps are not helpful for plant
appreciable infrared radiation. growth or similar purposes.
Figure 1.
One sample holder
removed. Hand 50
mm from lights
(same as sample):
Allowable daily
exposure 1 minute
for UV-I3 lamps
Figure 2.
One sample
holder removed.
Hand 30 cm from
lights: Allowable
daily UV-I3 lamp
exposure 6
minutes. Face Im
from lights:
Allowable daily
exposure 18
minutes,
Figure 3.
All sample
holders
removed. Hand
30 cm from
lights: Allowable
daily UV-I3 lamp
exposure 2
minutes.
2.0 4.0
General Description Specifications
The QUV Accelerated Weathering Tester is a labo- Functions
ratory simulation of the damaging forces of weather, UV Exposure
for the purpose of predicting the relative durability Choice of lamps for various applications. Exposure
of materials exposed to the outdoor environment. temperatures of 50" to 80°C (122" to 176°F).
Rain and dew are simulated by a revolutionary
condensation system. The damaging effects of sun- Condensation Exposure
light are simulated by fluorescent UV lamps. Expo- Direct condensation of distilled water on the test
sure temperature is automatically controlled, as is sample at temperatures of 40" to 60°C (104" to
the daily sequence of UV periods and condensation 140°F).
periods. In a few days or weeks, the QUV can pro-
duce damage that might occur over months or years Utilities
of outdoor exposure. Deterioration observed in-
Water Requirements
cludes fading, chalking, cracking, crazing, hazing,
Uses either tap or deionized water. Consumption is
blistering, gloss loss, strength loss, and
approximately eight liters per day. Automatic water
embrittlement.
feed is standard, including 114inch tubing and saddle
valve for simple hook-up. No drain is necessary.
3.0 Electrical
Maximum power consumption 1500 watts. Average
Warranty Information power consumption 700 watts. Available in 120V,60
Hz, or 230V, 50 Hz. Plugs in anywhere.
Free Replaceme~itParts for 5 years,
with ongoing purchase of lamps Physical Dimensions
Size: 54" x 21" x 53" high (137 x 53 x 135 cm);
Due to the QUV's record of outstanding Weight: 300 pounds (136 kg)
durability,Q-Panelis able to offer the following
warranty: As long as you buy all of your replace- Construction
ment lamps from Q-Panel,we will supply free re-
placement parts for all electrical parts (except Chassis and cabinet are all stainless steel and alu-
lamps and solenoid valve) that wear out within minum. Nothing to rust.
5 years of purchase. Damage due to accident
or abuse is not covered. Labor cost is not cov- Test Capacity
ered. 48 test samples 3" x 6" (75 x 150 mrn).Thickness
When parts fail, simply advise Q-Panel by up to 314" (20 mm). Panels are spring mounted on
phone or mail, giving serial no., volts and Hz. removable holders.
Q-Panel will ship the parts at no charge. This
saves you not only the cost of the part but also Lamp Usage
the cost of the paperwork for a purchase order Lamps are rotated every 400 hours. Lamp life is
or invoice.
1,600 hours.
The Q-Panel Company makes no other warran-
ties, including implied warranties of merchanta- Recognition
bility or fitness for a particular purpose, except The QUV conforms to ASTM G-53, D-4329, D-
a s may be expressly provided by The Q-Panel
Company in writing. The Q-Panel Company 4587, D-4799, SAE J2020, I S 0 4892 and numer-
shall not be liable for any incidental, conse- ous International Test Methods and Material Speci-
quential, special, or contingent damages aris- fication Requirements.
ing out of the sale or use of any product.
5.0 are 15A, each QUV should have its own circuit.
Each QUV has a built-in 15A circuit breaker, so if
Setting up the QUV you connect several QUV's to a high capacity cir-
cuit, each QUV will still have adequate over current
protection. We have found that a 60A overhead
Uncrating power-track buss is a very convenient way of con-
Cut the metal straps which hold the fiberboard car- necting multiple QUV's. This simplifies the wiring
ton to the skid. Lift off the fiberboard carton. Cut and keeps the power cords up off the floor and out
the metal straps connecting the unit to the skid. Lift of the way.
the unit off the skid and move into place. Remove
all adhesive tape from inside and outside the unit. Water Connections
Each QUV uses only about 8 liters of tap water per
Locate the QUV away from strong drafts, which day. The automatic water feed is connected to the
might adversely affect temperature uniformity. For tap line by a standard 114 inch (6 mm) flexible tube.
best temperature stability it is helpful, but not essen- We recommend connecting the 114 inch (6 mm)
tial, to locate the QUV in an air-conditioned room. tubes to the water line above the hung ceiling and
running the tube to the QUV through a small hole
Caster Installation in the ceiling tiles.
To install casters, prop up one end of the QUV on
a box and push the casters into the sockets in the Ventilation
legs. The 1984 revision of ASTM G-53 calls for a room
temperature kept below 86OF. We recommend keep-
ing the room temperature between 60' and 80°F.
Each QUV generates an average of 700 watts of heat
on a continuous basis. That's equivalent to 2400
BTU/hr. Each QUV also evaporates about 8 liters
of water per day. These loads should be taken into
account when designing air conditioning and ven-
tilation.
Organizational Considerations
Over the past 15 years, we've observed that the best-
run multiple QUV installations are invariably the
ones where a single individual has responsibility for
5.1 operation and maintenance of all the QUV's. This
Multiple QUVs Installations ensures that the lamps will be changed on the proper
schedule and that the'testers will be checked regu-
Floor Space Recommendations larly for proper operation.
When you get several QUV Weathering Testers in
the same room, it's very helpful to maintain proper WALL
4
24" mWmum
spacing between testers, and between testers and the 1
wall. If the QUV's are jammed together too tightly,
it becomes difficult to open the doors, remove
24" mlnlmum
T
samples, and perform maintenance. The attached
drawing shows the spacing that we recommend
from our experience. We recommend that QUV's
r q ?a".Isle
1 4 54' --c
not be stacked one above the other, because the heat remmmnded
(30"mlnlmum)
rising from the lower QUV makes it difficult to
control temperature and to achieve condensation on
the upper QUV. (6- mlnlmum)
Electrical Connections
The maximum instantaneous electrical load from a
QUV is 1500W at 120V. If your electrical circuits Floor Plan - Mutliple QUV Installation
5.2 ally condenses on the test panels, which are kept at
Room Tempera'ture a lower temperature by room air on their back sur-
face. Condensation runs off the test panels and back
The QUV operates best in a room where tempera- into the water pan.
ture remains between 60°F and 80°F (16" and
27°C). In no case should room temperature be lower Since the water becomes distilled as it vaporizes
than 50°F (10°C) or higher than 95°F (35°C). Room from the pan, the condensation on the test panels has
temperatures outside of this range or fluctuating a high degree of chemical purity. A vent slot around
room temperatures such as those in buildings where the top of the water pan assures that the condens-
the air conditioning is turned down at night may be ing vapor is saturated with oxygen. Some vapor will
the cause of inconsistent test results. It is important escape through this vent and some will be lost from
to maintain a t least a 12°C difference between around the panels.
room temperature and the Condensation Cyck
test temperature. High room temperature can Water Feed
also prevent proper condensation by reducing
sample cooling.
The optimal place for a QUV is in an air-condi-
tioned lab or office. The QUV will not strain ordi-
nary air-conditioning, because it produces only as
much heat as two persons.
To avoid inconsistent test results, the QUV should
be located away from strong drafts, which can cause
one end of the machine to be cooler than the other.
5.3
Electrical
Be sure to supply your QUV with voltage within +
10 percent of its voltage rating.
Saddle Valve
\ !
(Alternate)
Plastic tubing is supplied with the QUV but copper tubing may also be used. Water supply is added to the Water Feed Unit
Control Functions
5. Heater On lndicator Light.
1. Total Time Shows that the Ultraviolet thermostat (No. 4
Hours that the unit has been in operation above) is calling for heat.
2. Test Time
Re-settable timer shows time (in hours) into test 6. Cycle
Used to program timing of UV and Condensa-
3. Ultraviolet Cycle Indicator Light tion cycles.
Shows that the QUV is operating in the UV
cycle. 7. Condensation Cycle Indicator Light.
Shows that the QUV is operating in the Conden-
4. UV Cycle Thermostat. sation Cycle.
Used to adjust the panel temperature during the
UV cycle. 8. Condensation Cycle Thermostat.
Used to adjust the panel temperature during the
Condensation Cycle.
Totel Llght
rime nme
9. Heater On lndicator Light.
Shows that the Condensation thermostat (No. 8
above) is calling for heat.
~
Lamps
~ u o r e m -/$
\ cwllng
LAMP LAMP
Replacing the UV Lamps is as simple as Note: If the rubber socket is loose and falls off
changing ordinary fluorescent tubes. the lamp pins, squeeze the socket with a pair of
pliers to tighten the bushings inside the socket
9
Lamp Cooling 7.1
A Choice of Lamps for
The light output from fluorescent lamps decreases the QUV
as bulb temperature increases, because the mercury
vapor pressure inside the lamp rises above the op- Four types if fluorescent UV lamps are now avail-
timum level. The curve below shows this relation- able for the Q W : two types of W - B lamps and two
ship. The coolest spot on the bulb wall controls the UV-A lamps The particular application determines
mercury vapor pressure and hence the output. which lamp should be used. All of these lamps
produce mainly ultraviolet rather than visible or
A Lamp Cooling Blower is located at each end of infrared light, and all are electrically the same as an
the control housing. These blowers force room air ordinary 40 watt fluorescent. The lamps differ in the
over the tips of the lamps to create a cool spot total amount of W energy emitted and in the wave-
which controls output (air from the Lamp Blowers length spectrum. Differences in lamp energy output
does not enter the test chamber). The Lamp Cool- or wavelength spectrum can cause significant dif-
ing Blowers operate during the entire UV cycle. To ferences in test results.
check their operation, listen for a a faint hum at
either end of the control housing, or open up the Wavelength Regions of the UV Spectrum
control housing.
The UV spectrum is divided into three regions:
W - A Region, 315 to 400 nanometers
W - B Region, 280 to 315 nanometers
W - C Region, below 280 nanometers
Fluorescent UV lamps are usually categorized as
W - A or W - B lamps, depending on the region into
which most of their output falls.
UV-B Lamps
The W - B region includes the shortest wavelengths
found in sunlight at the earth's surface and is respon-
sible for most polymer damage. Because of this, fluo-
rescent W - B lamps are the most widely used lamps
Bulb Wall Temperature "C
for simulating the damage caused by outdoor sunlight.
For most applications, they are the fastest and most
cost efficient lamps. Two types of W - B lamps are
available. They emit different amounts of total energy,
but produce the same W wavelengths in the same
relative proportions. The peak emission of these lamps
is at 313 nrn. Most of their output is in the W - B
region, with some output in the UV-A and visible
regions. The two types of W - B lamps are:
The UVA-35 1 is the recommended lamp for simu- UVB Lanips vs. Sunlight
lating sunlight filtered through window glass. It is
most useful for indoor or automotive interior appli-
cations. These lamps are manufactured to our speci-
fications to produce closer control than commer-
cially available UV-A sources.
IMPORTANT:
DO NOT MIX DIFFERENT TYPES OF LAMPS.
Thermometer dial
12
Every Six Months Break-In Procedure
Repairs:
The QUV is designed so that virtually all repairs can
be made by the user. If assistance is needed, contact
the Q-Panel Technical Service Department by fac-
simile message at (216) 835-8738or by phone (216)
835-8700. Please be certain to state the cycle dura-
tion, cycle temperature, lamp type, QUV serial
number, material tested and material end use. You
CV-261-S switch-
for Cycle Timer CV-261M Motor may reach the Technical Service Department be-
for Cycl Timer tween 8:30 a.m. and 5:30 p.m. (EST) weekdays
/ Monday through Friday. There is no charge for
technical assistance.
Indicator Lights
CV-261 Cycle Timer Assembly The indicator lights are designed for an average life
(includes switch and motor) in excess of 10 years. For replacement, just snap the
light out of the control panel.
10.0 The standard test sample holder accommodates 2
panels 3 x 6 inch (75 x 150 mm) or 1 panel 3 x I 2
Test Sample Handling inch (75 x 300 mm). Other sample holders are avail-
able to accommodate wider, thicker or odd shapctl
samples. Call Q-Panel for details.
An essential feature of QUV's condensation syslem
is that panels actually form the side wall of the test
chamber and provide the closure that keeps the h o ~
water vapor inside the chamber. Room air on the back
side of the panels cools them to a few degrees below
the vapor temperature. This temperature difference
causes liquid water to condense on the panels.
The swing-up door covering the panels does not seal,
but instead allows room air to reach the backs of the
Standard panel holder containing 2 panels 3 test panels. However, the swing-up door does regu-
x 6" (75 x 150 mm) is installed by resting it in late the way that convection currents cool the panels,
a slot on the QUV's frame. and it reduces fluctuations in panel temperature due
to drafts and room temperature changes.
Thick specimens of insulating material, such as wood
or rubber, may exhibit inadequate condensation be-
cause of poor heat transfer. To increase condensation,
increase heat transfer by:- 1)propping open the swing-
up door 10 or 20 mm with a bent aluminum test panel;
2) moving the QUV to an air-conditioned room;
3) increasing the condensation cycle temperature.
Sample Mounting Precautions
The test panels are actually the side wall of the test
chamber. To seal in vapor, it's important to have all
panel holders in place, and it's important to have all
To seal in vapor, have all panel holders in holders filled with test specimens or blank panels.
place and all holders filled with test Missing panels will cause vapor loss, poor conden-
specimens or blank panels. Close all gaps
larger than 1/32 inch (1mm). sation, and loss of temperature control. In addition,
mount the test panels so that the holes are masked
by the holder, and close all gaps larger than 1/32
inch (1 mm).
The rubber end seals are necessary to prevent the
vapor from escaping. Install the seals with the end
marked "TOP" up. We recommend that you mount
only one sample in the top and one sample in the
bottom of each panel holder. The reason for this is
that the center of each panel holder has slightly
higher UV intensity than the extreme top or bottom.
I ' I
Flat panels up to 114" thick (6 mm) are
fastened to the holders by snap-in rings.
Simply push the ring snuggly against the
panel. For proper tension, keep the opening
of the ring in the center of the holder, away
from the edge, as shown. To remove the
ring, pick up one side near the opening.
To mount odd-shaped samples, first attach Extra large samples can be mounted to a
them to a 3 x 6 (75 x 150 mm) aluminum large aluminum blank which is installed on the
blank. Then mount the blank in the standard frame in place of several holders. The blank
panel holder. Use water-resistant glue or must be 12.75 high (325 mm) and exactly as
fasteners made of corrosion-resistant metal wide as the holders it replaces.
(brass, aluminum or stainless steel - not
plated steel). To insure adequate cooling for
condensation, odd shaped parts should be
mounted to give reasonably good thermal
contact with the blank panel.
I I I I
For samples thicker than 114" (6mm), such Thin , flexible film samples are mounted by
as wood, use the optional Thick Panel simply wrapping them around an aluminum
Retainer springs. Part No. V-133. blank.
Disassembly Instructions
To Change Water Pan or Water Heater
(serial Number 89-5212-38 and up)
\ I
Z(J
1. UV Thermostat
CV-236
2. Air ~ e f l e c t o r
V-1348
3. Condensation Thermostat
CV-236
4. Ther~iionieterBulb
V-161
5. Orifice Cap
V-138
6. Air Pipe
CV-212
7. M a g n e s i ~ ~Anode
m
CV-207 (not shown)
CONNECTION DIAGRAM
Electrical - -
n connections
#7, Cond.
Main Power
#6, Blower @*
E $ \ male push-on
/
Y Remove knob & dial-plate
connectors
OFF-DELAY OPERATION - timing begins when start signal is off (clutch de-energized); (Cond.)
timer resets when clutch is energized. (UV)
TIMER COMPONENTS TIMING SEQUENCE I
Item Wiring Operation Before Start During End of Cycle
All power off Timing
When de-energized, engages tooth clutch; also (uv) (Cond) (Cond)
Clutch 2 actuates instantaneous contact. When energized, energized de-energized de-energized
Coil
4~ timer resets to before start condition.
Motor Drives cam toward zero (or end of cycle) position de-energized energized de-energized
when tooth clutch is engaged. (by D2)
Delayed Tripped by motor-driven cam at end of cycle. @6
Contact *$Resets to position shown when clutch 11
7 a 7
D2 solenoid is energized.
Delayed Tripped by motor-driven* cam at end of cycle
Contact (after dial-set time). Resets to position shown 9
9
Dl when clutch is energized. 8 @a
20 8
Instanta-
a 3 .3
neous •3 Transfers to the before start condition when the
4
Contact clutch solenoid is energized.
5 5
T T
. .
WIRE COLOR CODE:
BK
W -
-8bdc
Whiie IGammon
BN
BL -
- 8 r M
Blw
R
Y --
-Red
Yallow
z
. . ,
GN
GR -
Grsen
Gray
-
-
OR
v
BKlW
--
-Orange
Violet
BlWhlte
'Note: Earlier aerlal nunhrs had green wlrss
for lower blower Instead of bladdwhite R w . 6/89
GNIY I GreenPlellow Serlal No. 84j212-38
and up
. .
QUV WIRING DIAGRAM (220v150hz)
(to ballast) (to ballast)
t t
GN -Oman
GR -Gray
OR
V --
-Orange
Vblet 'Nole: Earfbr mrlal numbem had green wires
BKIW
GNlY - BlddWhiie
Grwflellow
for 1r- blower lnste~dd bladdwhtte Rev. 6/89
Serial No. 84W12-38
and up