REVISION
NO. DATE
48'-11"
WET LOCATION NOTES
ELECTRICAL NOTES
9'-9" 8" 15'-2" 5" 22'-11" 1. ALL ELECTR. EQUIP. EXPOSED TO WEAVER SHALL COMPLY TO NEC 312.2
1. ALL ELECTRICAL WORK SHALL COMPLY W/THE LATEST NATIONAL ELECTRICAL CODE
(2017), F.B.C. 7TH EDITION (2020) AND ALL OTHER APPLICABLE CODES. 2. SWITCHES OR CIRCUIT BREAKERS IN WET LOCATION OR OUTSIDE OF A BUILDING SHALL
1'-10 1/2"
BE ENCLOSED IN A WEATHERPROOF ENCLOSURE OR CABINET PER NEC. 404.4
(E) 2 B-3 2 (E) 2 (E) 2. ALL ELECT. WORK TO BE DONE BY A LICENSED ELECTRICAL CONTRACTOR AFTER
machinery A PERMIT IS ISSUED. 3. NO SWITCHES SHALL BE INSTALLED WITHIN WET LOCATION.
area machinery area
(E) B-3 storage area 3. CONDUIT UNDERGROUND TO BE PVC SCHEDULE 40
2 (E)
B-3
(E) B-1 NOTE
16'-2"
4. CONDUIT EXPOSED TO WEATHER TO BE IMC.
13'-6 1/2"
COMPRESSOR
(E)
-RECESSED LIGHTS OUTSIDE OVERHANG TO BE WEATHER PROOF.
ep2 connected
5. WIRE INSTALLED ELSEWHERE TO BE ROMEX.
MACHINE
with the ep 1
B-8/10
B-1 B-1
(E) (E)
2 EPB
-RESIDENTIAL STAIRS MIN. 1 FT CANDLE INSIDE AND OUTSIDE STAIRS. FBC R303.6
2 (E) 6. FLEXIBLE CONDUIT SHALL BE SEAL TITE.
TURNING bath (E) -SMOKE ALARMS ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING AREAS. FBC 907.
MACHINE office (E)
7. OUTLETS INSTALLED OUTDOORS, GARAGE AND BATHROOMS SHALL HAVE GROUND
B-2
(E) (E) (E)
32'-9"
bath FAULT INTERRUPTER
32'-4"
2 2 2
5"
(E)
8"
storage EPA
(E)
2 (E) 4 (E)
(3) 8. ELECTRICAL OUTLETS ( RECEPTACLES AND LIGHTING BELOW BASE FLOOD
area (E) ELEVATION SHALL BE INSTALLED AT THE HIGHEST PERMITTED CIRCUITS FROM THOSE
4
(E) (E) (E) (E) IN THE HABITAT AREA.
ELECTRICAL LEGEND PULL STRING FAN WITH LIGHT
13'-7 1/2"
reception and 9. NO APPLIANCES OR APPLIANCE OUTLETS SHALL BE INSTALLED BELOW BASE
240V RECEPTACLE
15'-11"
waiting area FLOOD ELEVATION.
CEILING MOUNTED LIGHT FIXTURE
110 V DUPLEX RECEPTACLE
10. A/C COMPRESSORS SHALL BE INSTALLED ABOVE BASE FLOOD ELEVATION.
(E) WALL MOUNTED LIGHT FIXTURE
110 V DUPLEX RECEPTACLE GFCI
2
11. MAIN CIRCUIT BREAKERS PANELS SHALL BE LOCATED ABOVE BASE FLOOD
1'-7 1/2"
SWITCH EXHAUST FAN
a.c
ELEVATION.
2 (E) 4 (E) 2 (E)
1'-3"
2W
2-WAY LIGHT SWITCH SD 120V SMOKE DETECTOR WITH
12. IT SUGGESTED THAT YOU CONFER WITH FLORIDA POWER & LIGHT TO LOCATE THE
M BATTERY BACK-UP.
ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY MANAGEMENT AGENCY
ELECTRICAL PANEL
a.c REQUIREMENTS. SD
CM SMOKE AND CARBON MONOXIDE
9'-9" 8" 37'-6" 1'-0" M ELECTRIC METER DETECTOR WITH BATTERY BACK-UP.
13. ALL 120v SINGLE PHASE, 15 AND 20 A BRANCH CIRCUITS SUPPLYING OUTLETS OR
DEVICES INSTALLED IN DWELLING UNIT KITCHENS, FAMILY ROOMS, DINING ROOMS,
12260 SW 8th ST Suite #224
DISCONNECT SWITCH EXTERIOR CEILING MOUNTED LIGHT FIXTURE
LIVING ROOMS, BEDROOMS, CLOSETS, HALLWAYS, LAUNDRY, OR SIMILAR ROOM
CONSULTING ENGINEER:
PHONE : (786) 502-2096
48'-11" AREAS, SHALL BE PROTECTED BY AFCI BY ANY OF THE MEANS DESCRIBED IN EXit sign
210.12(A) (1) THROUGH (6). THIS INCLUDE TRASH COMPACTOR AND MICROWAVE OVEN.
ARSHAD VIQAR, P.E.
Emergency light / exit
14. 90% OF NEW LAMPS MUST BE HIGH EFFICIENCY.
FL. LIC. No. 38863
MIAMI, FL 33184
15. IN ALL AREAS SPECIFIED IN 210.52, ALL NONLOCKING-TYPE 125-VOLT, 15 AND 20
1 EXISTING electric floor PLAN AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES
e-1 SCALE: 3/16"= 1'-0"
SMOKE DETECTOR
DIAGRAM
M
ELECTRICAL 3 # 3/0 THWN. CU. IN 2" CONDUIT RGS
METER
EXISTING EXISTING
200A PANEL PANEL A PANEL PANEL B
ELECTRIC PLAN
A B TYPE: LOAD CENTER MAIN BUS: 125 AMPS
200-A (120/ 240 125-A (120/ 240 SERVICE: 240/ 120V 1 o 3W M.L.O.
VOLT, 200 VOLT, 125 LOCATION: UTILITY AIC: 10K SERIES RATED
AMP. 2 P) AMP. 2 P)
BRK POLES WIRE KW CONDUIT DESCRIPTION CKT CKT DESCRIPTION CONDUIT KW WIRE POLES BRK
Your location 3 # 2 THWN. CU. IN 2" CONDUIT RGS
INTERSYSTEM 1 # 8 THWN.(G) CU. IN 1 1/2" CONDUIT RGS
BONDING
BLOCK
5
CONNECTED TO TWO 8 " X 10"
3# 3/0 2"CONDUIT GROUNDING RODS SPACED 6' DRAWN BY:
UNDERGROUND SERVICE
6'-0" BOND TO A 43" COPPER CHECKED BY:
TO FPL POWER SUPPLY
WATER PIPE STUB-OUT AT DATE:
METER LOCATION &
SCALE:
FOUNDATION STEEL
RODS TO BE DRIVEN 8' SHEET:
MIN. BELOW GRADE
ELECTRICAL RISER DIAGRAM
N.T.S. E-1