ELECTRICAL COMPONENTS OF MHP
Electrical Component Design
Standard Electrical Components of MHPs Generator Control Equipment Protection Equipment Earthing System Transformers Primary Distribution System Secondary Distribution System Power Limiting Device Metering Equipment
Generators
Types Synchronous Generator(SG) Asynchronous Generator(Induction Motor as Generators or IMAG)
Synchronous Generator(SG)
Asynchronous Generator(Induction Motor as Generators or IMAG)
Principle of Synchronous Generator
Exploded View-Synchronous Generator
Schematic diagram of an Induction Generator
Principle of an Asynchronous Generator
Exploded View of an Squirrel Cage Induction Machine
Comparison Between SG and IMAG
Synchronous Generator(SG)
Generally competitive in high
power range >100kVA Not readily available in developing countries Complicated & liable to breakdown; High maintenance cost Complicated Needs to be ordered
Asynchronous Generator(IMAG) Generally competitive in small power range <30kVA Readily available in small power range Rugged & simple; Reliable and low maintenance cost Simple Possible with normal design (4P or more)
Comparison Between SG and IMAG contd
Synchronous Generator(SG)
Self exciting Can supply reactive power Higher full load efficiency; good
Asynchronous Generator(IMAG)
External source needed for excitation External source needed for supplying
part load efficiency High Rotor Inertia Good Voltage regulation Generally good technical support available Good over load and motor start capacity Can be made to sustain SC and clear fault Fairly simple Selection, calculation
reactive power Lower full load efficiency; poor part load efficiency Low Rotor Inertia Poor Voltage regulation Technical support generally does not exist May de-excite under such condition De-excites under SC and might need re-magnetization Needs calculation and re-adjustment
Types based on relative position of Armature and Field Winding
Rotating Armature Type(Brushed Type) Generally not preferred in MHPs due to high maintenance cost(Slipring and Brush) Rotating Field Type(Brushless Type) Exciter Armature is mounted in the same shaft as that of the main generator and AC voltage generated in the rotating exciter armature is converted to DC voltage though the use of 6 Nos of rotating diodes to feed to the main generator rotating field winding
Synchronous Generators(bit more)
Generally Cylindrical Rotor Type and Salient Pole
Type
Cylindrical Rotor Types(4/2Pole machine) are high
RPM(mostly 1500/3000RPM for a 50Hz Generation and 1800/3600RPM for 60Hz Generation) and invariably used with Steam Turbine/Gas Turbine Salient Pole machines are generally low RPM type and generally manufactured in RPM range starting from 142.8 RPM and upto 1000RPM for a 50Hz system.
Practical Approach
As standard Diesel Engines (as prime mover for DG
sets) manufactured in Indian Subcontinent have RPM as 1500, off the shelf Salient Pole Generators are also designed for an RPM of 1500 to suit direct coupling. In MHPs of Nepal,1500RPM Synchronous Generator becomes natural choice. Few renowned manufacturers of Synchronous Generators(in Mini/Micro Hydro range) of India origin are KEL, Kirloskar Electric company,Cummins,Crompton,Greaves,Jyoti etc.
Practical Approach
KEL make Generators have Compounding
Transformer based Excitation System(to maintain voltage within +-5%) and no need of electronic AVR for size upto 125kVA,Starting Current Capability upto 2-3 times rated current.
Compounding Transformer based Excitation System
Synchronous Generator Sizing
Various Factors to Consider Temperature factor(A) Altitude factor(B) ELC Correction Factor(C) Power Factor(D) Generator kVA=Installed Capacity in kW/(A*B*C*D)
Generator rating Factors
Maximum ambient temperature A (oC) 20 1.10 1000 25 1.08 1250 30 1.06 1500 35 1.03 40 1.00 45 0.96 2250 50 0.92 2500 55 0.88 2750 Temperature factor Altitudes (m)
1750 2000
B1
Altitude factor
1.00
0.98
0.96
0.945 0.93
0.915
0.90
0.88
Altitudes (m)
3000
3250
3500
3750 4000
4250
4500
B2 C D
Altitude factor ELC correction factor Power factor
0.86
0.845
0.83
0.815
0.8
0.785
0.77 0.83
When load is only light bulbs When load includes tube lights and other inductive loads
1.0 0.8
Synchronous Generator Sizing contd
Generator size as calculated above is multiplied by 1.3 to allow for the following conditions
The output of the turbine could be higher than expected due to better design(efficient design) If large motors (> 10% of generator size) are supplied by the generator, the generator should be able to handle the starting current. The generator is always generating rated power when using an ELC
Practical Calculation
Suppose we need to find Correct Generator Size for a 15kW
installed capacity scheme.
Assume ambient temp of 40 deg Celcius,A=1 Altitude above mean sea level as 1250m,B=0.98 ELC correction Factor,C=0.83 Load as a mix of predominantly Incandescent lighting(PF:1) plus some inductive load like FT(PF:0.5) so as to give an average power factor, D = 0.8 Generator Size in KVA considering safety factor of 1.3 =1.3*15/(1*0.98*0.83*0.8)=29.966=30kVA Hence we see that for all practical purposes the Generator Size in kVA to be chosen is 2 times the installed capacity in kW
IMAG
IMAG is Squirrel Cage Induction Motor run as
Induction Generator Induction motor when rotated above its rated synchronous speed by some prime mover(hydraulic turbine in case of MHP)and fed required excitation though capacitors or through import of reactive power from Grid, Generates Electrical Power. Slip in such case is negative. Very Rugged Construction due to general ruggedness of squirrel cage rotor. Highly common to use in Pico/Peltric Sets.
Practical Approach
Though IMAG is cheaper in range up to 30kVA size, SG
is preferred over IMAG in sizes above 10kW due to practical considerations IMAG is however used almost invariably in Pico/Peltric (Pletric: Pelton+Electric Generator) sets upto 5kW
MHP in operation: Synchronous Generator in Focus
MHP in operation: Double Jet Pelton Turbine in Focus
Control Equipment
Voltage Control Equipment Compounding Transformer for voltage regulation in the range of +-5% for generators upto 125kVA Additionally fitted electronic AVR for sizes >125kVA Frequency Control Equipment
Electronic Load Controller(ELC) upto installed capacity 100kW Hydromechanical/Electronic/Digital Governor for installed capacity>100kW
Electronic Load Controller(ELC)
An equipment which allows constant power
generation( no flow control) and maintains constant system frequency by dumping additional generated power to electric immersion heaters used as ballasts. ELCs are considered to be cheaper alternatives of costly flow control governors in case of MHPs. Since ELCs use Thyristors as switching device, a lot many harmonics are generated requiring derating of generators(ELC correction Factor: C)
ELC Panel Board
Inside View of an ELC Panel Board
ELC Continued
Sizing of ELC and associated Ballast for installed
capacity upto 50kW
Size of ELC=Installed Capacity in kW Size of Ballast=1.2*Installed Capacity in kW(to take care
of possible additional power generated due to better system efficiency)
Sizing of ELC and associated Ballast for installed
capacity > 50kW and upto 100kW
Size of ELC=0.6*Installed Capacity in kW Size of Main Ballast=1.2*0.6*Installed Capacity in kW Size of Extension=0.4*Installed Capacity in kW
Protection Equipment
Plant protection Equipment Outdoor Protection Equipment
Plant protection Equipment
Overcurrent Protection Thermal Adjustable Type Moulded Case Circuit Breaker
for Protecting generator from normal overload/short circuit in the distribution line(Rating:25% oversized) for Protecting ELC power components(Thyristors etc) from short circuit/earth fault occurring in ballast circuit
HRC fast fuse
Plant protection Equipment contd
Overvoltage/Undervoltage Protection(set at 110% and 85%) Under voltage Protection optional for plants <30kW Over Frequency/Under Frequency Protection
(set at 51.5Hz and 48.5Hz)
Under frequency Protection optional for plants <30kW
Varistor (to protect ELC board components from transient
over voltages)
Outdoor Protection Equipment
Lightening Arrestors to protect lines from Lightning 0.5kV Metal Oxide(Gapless)Arrestors for 400Volt Line 9kV,5kA Metal Oxide(Gapless) Arrestors for 11kV Line Drop Out(DO) Fuse to Protect Transformers from Over Current
Earthing System
All non current carrying metal parts to be earthed to
protect equipment/human being from safety hazard An earth Continuity Conductor(ECC) to run though the perimeter of the powerhouse Generator body, Turbine Enclosure, Belt Guard, ELC Panel board, Ballast Tank, Metallic Door, Window Frame etc (if used) all to be connected to ECC
Earthing System Continued
Generator(Star Connected) Neutral to be earthed
separate from the earthing of non current carrying metal parts Lightning Arrestors fitted at first pole should have separate earthing from that of neutral GND. 600mm*600mm*3.15 mm copper plate is used for earthing purposes(weighs around 10kg) Earth Resistance value <5 Ohm is desirable but in no case should exceed 10 Ohm.
Typical Values for Soil Resistivity
Type of soil Moderate climate, high rainfall (>500mm/year) Typical value (m) Clay Porous limestone Sandstone Quartz, marble, carbonaceous limestone Granite Slate, petrification, gneiss, rock of volcanic origin 10 50 100 300 Range of measured values (m) 5-20 30-100 30-300 100-1000 Desert climate (<250 mm/year) Range of measured values (m) 10-1000 50-300 >1000 >1000
1000 2000
Transformers
Few very simple practical formulas as below VHV / VLV = THV / TLV , where the terms have their usual meanings.(Note that the voltages in the formula are to be phase voltages and not line to line voltages and the formula equally applies for both single phase and three phase transformers) IHV =kVA/(3*kV HV) and ILV =kVA/(3*kV LV) for a 3 Phase Transformer and IHV =kVA/kV HV and ILV =kVA/kV LV for a 1 Phase Transformer
Transformers contd.
Type based on purposes Step Up Transformer(Used outside MHP P/H to step up voltage level form generation voltage ie 400V to primary distribution voltage ie 11000V) Step Down Transformer(Used at loadcentres to reduce primary distribution voltage of 11000V to utilization voltage of 400V)
Oil Immersed Transformer
Plan and Legend of a Transformer
TYPICAL RATINGS AND FEATURE FOR 100kVA STEP UP TRANSFORMER TABLE 1
Type Rated capacity Rated voltage Three-phase, 11/0.4 kV 100kVA Primary 400V Secondary 11000 V
Highest system voltage Primary 440 V Secondary 12kV Rated Frequency 50 Hz Connection Primary Gnd. Wye Secondary Delta Cooling System ONAN Vector group YNd 11 Rated impedance voltage 3.5 - 4.5% BIL for windings and bushings for secondary side 75 kV Withstand voltage, 50 Hz, 60 Sec. - Primary 28 kV - Secondary 3 kV No load tap changer 2.5% to 5% on HV side Mounting Platform Insulation levels (IEC) 76 LI 75 AC 3/AC 28 Insulation temperature class (IEC 76) A Maximum allowable noise level at 3 metre hemispherical radius <44 dB Applicable standard IEC
TYPICAL RATINGS AND FEATURE FOR 50kVA STEP DOWN TRANSFORMER TABLE 2
Type Rated capacity Rated voltage Three-phase, 11/0.4 kV 50kVA Primary 11 kV Secondary 400/230 V
Highest system voltage Primary 12 kV Secondary 440 V Rated Frequency 50 Hz Connection Primary Delta Secondary Gnd. Wye Cooling System ONAN Vector group Dyn 11 Rated impedance voltage 3.5 - 4.5% BIL for windings and bushings for primary side 75 kV Withstand voltage, 50 Hz, 60 Sec. - Primary 3 kV - Secondary 28 kV No load tap changer 2.5% to 5% on HV side Mounting Platform Insulation levels (IEC) 76 LI 75 AC 28/AC 3 Insulation temperature class (IEC 76) A Maximum allowable noise level at 3 metre hemispherical radius <44 dB Applicable standard IEC
Sizing of Transformers
Size of Step Up Transformer is based on following factors Installed plant capacity Average Power Factor of Load Calculating size for 30kW Installed Plant size with average
power factor of load as 0.8
kVA Rating of Transformer required=Installed Plant
Size/Power factor=30/0.8=37.5 Now since 37.5kVA not being an standard transformer rating, we should chose nearest higher rating ie 50kVA Necessary provisions may have to be incorporated for the possibility of future load growth(in case it is planned to replace turbine generator set at a later date with more efficient turbine and suitable size generator)
Transmission and Distribution(T& D)
Types Suspended Overhead on Poles(Overhead Line) Buried Cables(Underground Cable) OH Line(Features) Less Expensive Frequent Maintenance Required Less cost per maintenance Does not look aesthetically good in dense locality Not preferred in areas which experience heavy snowfall
T& D contd
UG Cable Costly Installation(if done per standard 6 times costly compared to OH) Less Maintenance Higher cost per maintenance Highly desirable in densely located areas Obvious choice for areas which experience heavy snowfall Design Criteria of OH distribution line(as MHPs can not afford
the luxury of UG cable)
Maximum allowable voltage drop at the farthest end shall not
exceed 10% Maximum TL line to line voltage in case of isolated MHPs is 11kV ACSR(Aluminium Conductor Steel Reinforced) conductors are the norms of the day(as against hard drawn copper which were used in earlier days)
Transmission and Distribution(T& D) contd
Typical 3 Phase 4 Wire LT distribution
Primary Distribution Line Hardware and Fittings
Voltage Drop Calculation
distribution =3 * I* (R*Cos +X*Sin )Volt Where I is the load current in ampere, R is the Resistance/Phase in ohm, X is the reactance/Phase in ohm ,and is the power factor angle. Voltage Drop in case of 1-Phase 2 wire system = 2 * I* (R*Cos +X*Sin )Volt Where symbols have their usual meaning
L-L Voltage Drop in case of 3-Phase balanced
Sizes and designations of ACSR conductors used in microhydropower schemes
Name Current rating in still air (amp) Resistance (/km) Inductive reactance at 50 Hz and 50 cm spacing (/km) Approximate weight (kg/km)
0.355 Squirrel (20 SQ.MM AL) 76 1.374 0.349 85 1.098 0.345 95 0.9116 0.335 135 0.5449 0.328 185 0.3434 0.315 205 0.2745
80
Gopher (25 SQ.MM AL)
106
Weasel(30 SQ.MM AL)
128
Rabbit(50 SQ.MM AL)
214
Otter(80 SQ.MM AL)
339
Dog(100 SQ.MM AL)
394
Minimum vertical clearance for overhead conductors
Place Low tension High tension (1-11 kV)
Off road
4.5 m
5m
Beside motorable road Across from motorable road
5m 5.5 m
5.5 m 6m
A horizontal clearance of at least 1.2 m shall be observed in all cases.
The minimum sag for conductors up to 11 kV can be calculated by the following empirical formula:
d =
where,
172 .8
d = sag in m L= length of span in m Sag for spans of overhead cables The value of sag should be included when determining the ground clearance of a transmission line.
Span (m) Minimum sag (mm)
20 13
30 30
40 54
50 84
60 121
80 210
Poles used in MHPs
Due to cost consideration , LT(Low Tension) poles are
entirely made out of hard wood. Seasoned Pole would be better option. Other possibilities could be PSC(Pre Stressed Concrete) pole or steel tubular pole(where there is no cost constraint) or steel telescopic poles Steel Tubular(either swaged type or folding type) poles are the norms for 11kV Distribution Line and also for the double pole structure which supports transformers.
Pole specification for hardwood poles
Minimum length (m) Maximum span (m) Buried length (m) Minimum top diameter (mm) 6.0 35 1.0 125 7.0 35 1.2 140 4.6 8.0 35 1.5 150 5.5 8.5 35 1.7 175 5.8 9.0 35 2.0 175 6.1
Minimum ground clearance (m) 4.0
Insulators and Hardware
Shackle Insulators of suitable voltage ratings (suitable
creepage path)---Up to 1000V OH Line Shackle Insulators --- Supported(Clamped)by D-Iron set which is a clamp made out of galvanized steel Pin Insulators of suitable creepage path are used for straight runs of 11kV Line Disc Insulators along with suitable tension Set are used for deadening a line. Suitable Stay sets are provided at first pole, at line end, at all poles set at an angle and at every fifth pole even if the poles are in a straight line
Shackle Insulator specifications
S. N 1 2 3
Size Small Mediu m Large
Dimensions 55 mm x 55 mm 75 mm x 90 mm 100 mm x 110 mm
Weight 200 gm 600 gm 1300 gm
Corresponding conductor Squirrel, service wire Gopher, weasel and rabbit Dog
Spacing between Conductors
Conductor spacing 300mm upto 400V system 400mm upto 1000V System 600mm in case of 11kV line Horizontal or Triangular alignment(ACSR conductor) Spacing between conductors=(d+V/150) Where Spacing in m, V is the L-L voltage in kV and d is the sag in metres. In general,70% should be added as safety factor on the value calculated above.
Service Wire
Should be double insulated Additional voltage drop in service wire not to exceed
2% Service wire shall be of the same material as that of line conductor to avoid electrolytic corrosion. Minimum size of 4-6 sq.mm. to be used depending on the span
Power Limiting Device
MCB of suitable rating is generally used 0.5A(Rated Current),5kA(Breaking Current) MCBs are
used for prescribed power of 100W The purpose is to disconnect the line against sustained overload(control) and also to provide protection against short circuit in the household wiring.
Metering
Types available Electromechanical Type(Cheap but less accurate) Static Type(Costlier than EM type but far more accurate) Digital Type(Multifunctional Meter):Far more costlier than Static Type but has tremendous advantages like far superior accuracy, Possibility of data logging, data communication, Multifunction Capability, Possibility of field adjustment