FN-4127-IO 16 Channel Input-Output Board-FN4127IO - Installation
FN-4127-IO 16 Channel Input-Output Board-FN4127IO - Installation
Ho
70
Bu
71
80
ht
Table of Contents
Section 1 – Introduction
......................................................................................................................................................... 3
1.1 Limitations of Fire Alarm Systems ........................................................................ 3
Limitation on Fire Alarm Effectiveness: A fire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of reasons. For example:
Importance of Maintenance: In general, fire alarm systems and devices will not work
without power and will not function property unless they are maintained and tested
regularly.
Alarm is Not Substitute for Insurance: While installing a fire alarm system may make
the owner eligible for a lower insurance rate, an alarm system is not a substitute for
insurance. Property owners should continue to act prudently in protecting the
premises and the people in their premises and should properly insure life and
property and buy sufficient amounts of liability insurance to meet their needs.
Care should be taken when wiring the system to avoid situations that would contribute to
inducing electrical noise from one wire to another. Induced noise can interfere with
telephone communications or cause erratic system operation. Follow these general
guidelines to plan your system wiring prior to installation.
Route high and low voltage wiring separately. Maintain a minimum 2” separation
between high and low voltage wiring throughout the building.
Route control panel wiring around the perimeter of the control panel enclosure. A
minimum .25” separation is required between high and low voltage wiring.
Identify which group each wire or cable is associated with from the list below.
Isolate each group’s wiring as much as possible. Avoid running a single multi-
conductor cable for multiple groups of conductors.
Keep wiring from different groups separated as much as possible. If you must
share the same conduit with different conductor groups consider using shielded
cable.
If shielded cable is used terminate the shield to the earth ground terminal block in
the main control panel and leave open at field side of cable. Do not ground at
both ends of cable.
The FN-4127-IO 16 channel Input/Output board provides input and output expansion
capability for the FireNET system. Each channel can be individually configured as either
an input or an output. Up to 32 FN-4127-IO boards can be connected to the FireNET
system via the RS485 bus, giving the system an additional 512 inputs/outputs.
Each FN-4127-IO board is available to the entire network which allows for network-wide
input/output mapping. Typical uses for the I/O module include graphical LED map
displays/annunciators, tabular LED zone display/annunciators, and input/output logic to
and from the fire system for secondary use such as access control, burglary, CCTV,
intercom, voice or other 3rd party systems.
The FN-4127-IO board should be installed in locations where it will NOT be exposed to
temperatures outside the range of 32o F – 120oF or humidity outside the range of 10%-
85% non-condensing.
Note that addresses must be set with no power applied to the board.
All wiring terminals on the FN-4127-IO board can accept wire gauges from 22AWG to
14AWG.
The I/O board requires 24 VDC power to operate. The AUX 24V terminals of the
FireNET panel can supply this voltage (500 milliamps maximum). You may also use an
external power supply that provides 24 VDC output.
Connections are provided on the I/O board for both incoming and outgoing power.
In addition to power, each I/O board requires a pair of conductors for data
communication. This wiring is connected to the COMMS + and - terminals on the
FireNET control panel. The communication wiring may also be connected to the
COMMS OUT + and - terminals of another RS485 bus device.
+ - + - + - + -
NAC 1 NAC 2 NAC 3 NAC 4
FIRE +
ROUTING
-
TROUBLE +
ROUTING
-
24V 0V 0V 0V
C10
PROGRAMMABLE +
I/O
XTL1
OUTPUT
- J1 U1 TO NEXT I/O
C3
C11
BOARD
1. TBL
R26
R54
R25
R24
R19
S1 TR1
3. INT
X
T
-
LED
0V RX
REMOTE 4. CNT
1 +
R23
R20
R36
CONTROL U7 SD1
AND AUX. 5. SIL
LED
SW
INPUTS
R22
2 J2 J3 J4
0V
LED
R38
R28
R30
R37
R32
R21
C9
C6
6. PR1 3
7. PR2
+
-
COMMS IN
8. PR3
+ U6
0V 24V 0V RX
l +
COMMS
ADDITIONAL
X2
I/O BOARDS
R31
R27
R33
R35
AUX
R29
R34
l +
IN
24X
+ C8
F1
R1
NETWORK C2 D1
l +
IN +
+
C7
U5
l +
NETWORK C L1
OUT 1
D17 +
NOTE: Inputs on the I/O board are not supervised. These inputs are not for
primary initiating or detection of fire or life safety conditions. These
inputs are programmable for secondary use only, and not used for
signaling Fire, Supervisory, or Trouble conditions. All primary
initiating or detection inputs must be connected to applicable SLC
devices listed for fire.
When configured as outputs, the I/O board channels supply a negative voltage (with respect
to the I/O board 24V power supply) via a transistor.
Because transistor elements can be damaged by excessive current drain, great care should
be taken when connecting to outputs. Particular care should be taken to ensure that
suppression diodes on relay coils are correctly polarized. Wrongly connected diodes will
damage the outputs. Diodes
should be connected with the
band to the positive 24V.
2.2k
NOTE: Outputs on the I/O board are not supervised. These outputs are not
for primary notification of fire conditions (i.e. not for use as NAC
circuits). These outputs are for secondary use only. All primary
notification output devices must be connected to applicable NAC
circuits on the FireNET panel.
When powering the I/O board from the FireNET Aux 24VDC power (limited to 500ma), the
following maximum wiring distances apply at the gauges noted:
Wire Distance
18AWG 875ft
16AWG 1400ft
14AWG 2300ft
12AWG 3700ft
When powering the I/O board from a separate Aux 24VDC UL Fire listed supply the
maximum voltage drop cannot exceed 4VDC.
LED indicators on the I/O board give some simple diagnostic information R44 R42 R40 R18
and show that the boards are communicating with the control panel. The R45 R43
OP4
D10
1
R41 R39
red LED (LED1) is on during receipt of a message from the control panel D11
2
C4
C12 U4
+ D12
and will turn off if the I/O board detects normal communication.
3
R52 R50 R48 R46
4
D13
OP3
5
D14
SERIAL NUMBER
D15
6
R53 R51 R49 R47
7
R8 R6 R4 R2
I/O CHANNEL
8
D18
OP1
operating normally. X1
9
D2
R9 R7 R5 R3
10
D3
If this LED is not lit - the board is not receiving data from the
11
C5
C13 U3 D4
12
control panel and the comms connection should be checked.
D5
R16 R14 R12 R10
ISSUE 01
13
D6
K6006
OP2
14
D7
15
R17 R15 R13 R11 D8
16
D9
0V 0V
C10
the comms connection should be checked for interference from
I/O
XTL1
J1 U1
C3
C11
0V RX TX 24V 0V
AC power or other noise generating sources.
OUT
R26
R54
R24
R25
R19
S1 TR1
COMMS OUT
LED1
R23
R20
R36
U7 SD1
The yellow LED (LED2) will flicker briefly every few seconds when the I/O
SW1
LED2
R22
J2 J3 J4
board responds to the main panel. If this LED does not flicker then it is LED3
R38
R21
R30
R37
R32
R28
C9
C6
+
not responding to the control panel and the comms connection should be
0V RX TX
COMMS IN
U6
checked. X2
0V 24V
R31
R27
R33
R35
R29
R34
IN
+
LED 1 C8
R1
F1
C2 D1
+
+
C7
U5
C1 L1
D17 +
LED 2
End of Manual
March 2009