PROJECT:
PACKAGE: XYLENE
DOC. TITLE: DATASHEETS FOR PRESSURE VACUUM SAFETY VALVE Sheet: 1 of 1
DOC. NO.: FS22-015-PR-DS-002 Rev: A
1 Tag No.: PVSV-001/002/003/004
2 Manufacturer: VTA
3 Service: Vent for spare chemical tank
4 P&ID number: FS22-015-PID-001
5 Equipment Number: T-001/002/003/004
GENERAL
6 Pipe Class Inlet: 150
7 Pipe Class Outlet: 150
8 Type Breather valve
Design Type
9 Model VTA
10 NACE MR0175 N/A
11 Fluid State Air Gas
12 Required Capacity (Inbreathing/Outbreathing) Nm3/hr of air 77.3 / 18.2
13 Molecular Weight g/mol -
14 Design Pressure barg WATER FULL + 0.6 / -0.002
15 Set pressure barg +0.6 / -0.002 barg
PROCESS
16 Design Temp. °C 65
CONDITIONS
17 Relieving Temp. °C Amb
18 Relief Density kg/m3 -
19 Relief Viscosity cP -
20 Design Code API 2000
21 Rupture Disc N/A
3
22 Total out breathing Nm /hr 18.2
3
23 Valve out capacity Nm /hr VTA
24 Setting pressure barg 0.6
25 Total in breathing Nm3/hr 77.3
3
26 Valve in capacity Nm /hr VTA
27 Setting vacuum barg -0.002
VENTING
28 Size Inlet in Size Outlet in 2 (VTA) 2 (VTA)
CAPACITY
29 Rating Inlet (Note 1) VTA
SPECIFICATION
30 Rating Outlet (Note 1) VTA
31 Body VTA
32 Pressure cover/ Vacuum cover VTA
33 Pressure Seat/ Vacuum seat VTA
34 Spring/ Screen/ Gasket VTA
35 Nut Bolt VTA VTA
36 Test Gag No
OTHERS 37 Hydro Test 1.5
38 Painting N/A
NOTES:
1. Smooth Finish (125 to 250 MICRO- INCH AARH per ASMEB16.5)
2. Zn Plating + PTFE Top coat are required
3. All products shall be pickled, passivated and solution annealed
4. Vendor to advise suitable material for xylene storage tank application.