Permalite Roofing Manual 5.3.2
Permalite Roofing Manual 5.3.2
ALUMINIUM
Roofing Solutions
Walls
When you design Permalite® aluminium cladding into your
building you have a range of profiles from which to choose.
Whilst cladding obviously needs to keep out the weather, it
also has significant effects on the looks, cost and durability of
a building.
Roofs
There are many factors in designing roofs including:
• the shape: is the roof to be ‘flat’ or pitched
or curved?
Low Low
Coefficient of Thermal Expansion 24 x 106 per ºC (Approx. To get the best performance from our products in these
1.2mm/m over 50ºC) conditions, or other unusually corrosive environments, seek
advice from our technical representatives.
1.5 Thermal expansion
1.9 Storage & handling prior to use
Although aluminium has twice the coefficient of expansion of
steel (24 x 103 compared to 12 x 10-6 ºC) the effect of this is often Aluminium roofing requires care during handling and
over estimated. installation. Installation damage can be avoided by taking
reasonable care and following the recommendations of this
Usually aluminium cladding is fixed to a steel structure, which,
manual.
under the same thermal influence, expands or contracts also.
Keep the product dry and clear of the ground. If stacked or
The combination of these factors results in a low relative
bundled product becomes wet, separate it, wipe it with a clean
expansion between the aluminium cladding and the steel
cloth and stack it to dry thoroughly.
structure. It has been observed in practice that the theoretical
expansion of an aluminium roof, relative to the steel structure Sheet that has become wet during transport is to be unpacked
on which it is fixed, is reduced by up to 50%. immediately and each sheet dried thoroughly on both sides
before restacking. Stored sheet is to be clear of the ground
NOTE: As an approximation, aluminium expands 1.2mm/m over
when under cover or, for outside storage, fully covered with
50° temperature change.
tarpaulins or plastic sheeting with the sheet and wraps clear
of the ground. Contact with moisture, cement dust, lime
or abrasive dust is to be avoided. Mill finish is particularly
susceptible to this type of water staining.
Packs of sheet stored on the roof must be placed over trusses
or purlin supports.
Table 1.4 Acceptability of drainage from an upper surface to a lower metal surface
UPPER CLADDING OR ROOF DRAINAGE SYSTEM MATERIAL
LOWER ROOF DRAINAGE
GALVANISED COLORBOND® including COLORBOND® STAINLESS ALUMINIUM COPPER & GLAZED TILES,
SYSTEM MATERIAL ZINCALUME ®
ZINC LEAD GLASS & PLASTIC
STEEL ULTRA & METALLIC STAINLESS STEEL ALLOYS COPPER ALLOYS(1)
ALUMINIUM ALLOYS YES YES YES YES YES YES YES NO NO YES
ZINCALUME® YES YES YES YES YES YES YES NO NO YES
GALVANISED STEEL NO YES YES NO NO NO NO NO YES NO
ZINC NO YES YES NO NO NO NO NO YES NO
COLORBOND® STEEL (plus
YES YES YES YES YES YES YES NO NO YES
ULTRA®& METALLIC®)
COLORBOND® STAINLESS YES YES YES YES YES YES YES YES YES YES
STAINLESS STEEL YES YES YES YES YES YES YES YES YES YES
COPPER & COPPER ALLOYS(1) YES YES YES YES YES YES YES YES YES YES
LEAD YES YES YES YES YES YES YES YES YES YES
(1) MONEL - COPPER/NICKEL ALLOY
(2) FOR FURTHER GUIDENCE REFER TO AS/NZS 3500.3:2003
2.2.2 Fluorocarbons
In certain applications and colours, fluorocarbon paints may
offer improved colour and gloss retention levels over polyester
paints. However fluorocarbon paints have a lower scratch
resistance and as such are more susceptable to damage during
transportation and installation. This needs to be considered
against the additional cost of these paint systems. Ask our
Permalite® technical team for advice regarding your project.
2.2.3 Colour Range
2.1.3 Permalite Waveline®
The traditional corrugated style and 762/990mm cover width of Most Standard COLORBOND® steel colours based on minimum
this product provides minimum wastage and quick installation. order quantities of 2.5 tonne. Other colours avalable on
Whether you want a traditional style or the modern look, the application with minimum order quantities and extented lead
universal appeal of Waveline is the right choice. times.
PERMALITE® Design Manual 2012 9
2.3 Design information 2.4 Permalite® LT7
2.3.1 Introduction to design data The versatility of this profile is due to its strength, water-
carrying capacity and fixing economy. It is widely used for
The following section is intended to provide the designer of the roofing and can be reversed for a bold wall effect.
building cladding with the data required to specify the most
cost effective use of the products and their efficient installation. Thickness Range: 0.70mm, 0.90mm, 1.2mm
The data applies to conventional structures in both cyclonic Length Range: 850mm to 23 metres
and non-cyclonic areas. Pan Cross Section Area: 26,000mm2
All design data is valid for the following conditions. Tolerances: Length +0mm, -15mm
Width +0mm, -3mm
• Minimum support member material is 1.9mm BMT G450 steel
Finishes: Mill, Stucco Embossed, Painted
• Overhang length does not exceed 100mm
• All spans are continuous (two or more spans) and equal
• Serviceability Limit State Design pressures are based on
deflection limit equal to (span/120+pan/30) according to
Section 5.5.1 of AS 1562.1:1992
If your requirement is outside these parameters you are invited
to call on the services of Permalite’s experienced technical
staff by contacting the Permalite® Sales Offices listed in this
publication.
19mm
57mm
38mm
127mm pitch
Notes:
1. The eave and ridge spans for 0.7mm and 0.9mm should be reduced by
20% and 25% respectively where access to the roof may be required.
Refer to Page 7 for trafficable spans.
2. Design capacities are only applicable for cladding and test
geometries used, with support spacings no larger than those tested.
3. Refer to BlueScope Building Solutions for any further details of
cladding installation not covered in this manual, details of test results
or other design matters.
4. These design capacities are based on legislation and standards that
are current at the time of publication and may be subject to change -
therefore the published capacities should be reappraised by the date
noted.
5. For 1.2mm BMT, use 0.9mm BMT values.
6. Assumes maximum unsupported overhang of 200mm.
216mm
52mm
30mm
114mm
Table 2.3 Profile properies Permalite® Alspan NOTE: Refer to page 7 for trafficable spans.
Notes:
1. The eave and ridge spans for 0.7mm and 0.9mm should be reduced by
20% and 25% respectively where access to the roof may 10.17
be required.
Refer to Page 7 for trafficable spans. 7.92
2. Design capacities are only applicable for cladding and6.10test
geometries used, with support spacings no larger than4.83 those tested.
4.07 of
3. Refer to BlueScope Building Solutions for any further details
cladding installation not covered in this manual, details3.39
of test results
or other design matters. 3.02
4. These design capacities are based on legislation and standards that
are current at the time of publication and may be subject to change -
therefore the published capacities should be reappraised by the date
noted.
5. For 1.2mm BMT, use 0.9mm BMT values.
6. Assumes maximum unsupported overhang of 200mm.
25.4mm
25.4mm
31.7mm
101.7mm
Notes:
1. The eave and ridge spans for 0.7mm and 0.9mm should be reduced by
20% and 25% respectively where access to the roof may be required.
Refer to Page 7 for trafficable spans.
2. Design capacities are only applicable for cladding and test
geometries used, with support spacings no larger than those tested.
3. Refer to BlueScope Building Solutions for any further details of
cladding installation not covered in this manual, details of test results
or other design matters.
4. These design capacities are based on legislation and standards that
are current at the time of publication and may be subject to change -
therefore the published capacities should be reappraised by the date
noted.
5. For 1.2mm BMT, use 0.9mm BMT values.
6. Assumes maximum unsupported overhang of 200mm.
16mm
76mm
762mm cover
820mm sheet
990mm cover
1048mm sheet
Thickness mm kg/m
(mm) Cover Width Length
0.90 762 2.3
0.90 990 2.29
Notes:
1. Design capacities are only applicable for cladding and test geometries
used, with support spacings no larger than those tested.
2. Refer to BlueScope Building Solutions for any further details of cladding
installation not covered in this manual, details of test results or other
design matters.
3. These design capacities are based on legislation and standards that
are current at the time of publication and may be subject to change -
therefore the published capacities should be reappraised by the date
noted.
4. For 1.2mm BMT, use 0.9mm BMT values.
6. Assumes maximum unsupported overhang of 200mm.
PERM
ALITE
Desig
n Man
ual
2010
PERM
ALITE
The du
Desig
n Man
rable s
olution
ual
to the
toughe
2010
st cond
itions
1
Figure 2.7
Hip support assembly
PERMALITE LT7 Fasten alternate ribs (Do not fasten overlap ribs unless all ribs are fastened.) PERMALITE LT7 Fasten all ribs with cyclonic washers
(s=side lap screw) (Do not fasten overlap ribs unless all ribs are fastened.)
(s=side lap screw)
PERMALITE ALSPAN 4 Fasteners per sheet width PERMALITE ALSPAN 4 Fasteners per sheet width,
Fasten all ribs with cyclonic washers
PERMATITE V-RIB 5 Fasteners per sheet width PERMATITE V-RIB 5 Fasteners per sheet width.
Fasten all ribs with cyclonic washers
PERMALITE WAVELINE 762 5 Fasteners per sheet at alternate ribs. (Fasten at overlap ribs.) PERMALITE WAVELINE Fasten all ribs with cyclonic washers. (Fasten at overlap ribs.)
PERMALITE WAVELINE 990 7 Fasteners per sheet at alternate ribs. (Fasten at overlap ribs.)
S= Side lap fasteners as per Section 3.18.
Figure 3.2 Fastener positions
NOTES: 1. Side lap fasteners are not required for Alspan.
2. Screws should be placed on every rib in non cyclonic areas to get better wind pressure capacity.
3. Pan fixing uses the same pattern as shown here for crest fixing.
3.15 Pierce-fixed roof fixing 3.16 Types of Pierced Fixings
The Permalite® Positive Fix System provides for thermal Hard Fixing
expansion of the roofing sheet by “hard” fixing at the top “Hard” fixing is used where sheet lengths are such that thermal
of the sheet slope with “expansion” fixing being used to expansion in not a significant issue ie 9m or less.
accommodate expansion towards the lower end of the sheet In applications where Taptite fasteners (RA014, RA015, RA013)
slope. or Type 17 (RATH1450, RA10, RA014) are used, the appropriate
For both types of fastening the screw should be screwed down pilot hole should be drilled through the sheet and purlin as per
until it presses on the washer with a medium pressure. Under Table 3.4. The hole in the Permalite sheeting should then be en-
no circumstances should the screw be overtightened to the larged to 6-6.6mm diameter after which the fastener is installed.
point where the formed washer, or the bonded washer under In applications where (RA010, RA018, RA019, RA115 RA116
the screw head, commence to distort RATH1450, RASH1450) Self drilling screws are used, then a
6- 6.5mm diameter hole should be drilled through the sheet prior
to installation of the fastener.
Expansion fixing
Screw For roof lengths in excess of 9m, “Hard” fixing is used for the
Bonded washer first 9m from the ridge or skillion head. Expansion fixing is used
Formed for the remainder of the sheet length and follows the same pro-
washer cedure as hard fixing with the exception that the hole in the rib
crest is slotted after drilling the tapping hole, using tool RA165
Rib seal Slot
for LT7, Alspan and V-Rib profiles. For Waveline, expansion is
provided by drilling an 8mm hole in lieu of slots noted above. On
Teflon® large projects contact your Permalite® sales representative
side up regarding use of this tool (RA165). Note that for expansion fixing
Rib Rib
a rubber washer with an elongated hole and Teflon facing on
one side is used. This washer must be installed with the Teflon
Expansion side facing up toward the head of the screw.
Hard Fixed fixed Wall cladding
Figure 3.3: Permalite® Positive Fix fastening system 3.3 Non cyclonic wall sheets may be pan “Hard” fixed up to
23m in length using fasteners as per table 3.1.
Cyclonic wall sheets must be crest “Hard” fixed with washers
up to 23m in length. Long lengths of flashings may likewise be
“Hard” fixed. However in regions of high temperature variations
it is is advisable to consider expanding sheeting holes to 7mm
for both flashing and wall sheeting applications.
Figure 3.4 Slot
24 PERMALITE® Design Manual 2012
Self Tapping Screws
Pilot holes are to be drilled in accordance with the following chart:
Table 3.4 Pilot hole Drill Diameter (mm) - Metal Thickness (mm)
Aluminium Steel Timber
Fasteners upto up to 2.0mm - .42mm to 1.2mm - 5.0mm -
Hardwood Softwood
1.2mm 2.01mm 5.0mm .75mm 5mm 6.5mm
304 / 316 RA015, RA013 N/S 5.2 5.3 N/S 5.6 5.7 N/S
grade RA010, RA019 Self drilling 4.5 5 Self drilling N/S 4 Self drilling
Stainless RA114, RA115, RA116, Self drilling N/S Self drilling N/S N/S
Steel RA018 Self drilling 3.5 4 Self drilling N/S Self drilling
Notes: N/S = Not Suitable
At speeds over 300RPM lubrication may be required when driving fasteners into hot rolled steel sections especially using 316 stainless steel fasteners.
Taptite screws (RA015, RA013, etc.) should not be installed with impact driver-type screw guns as this may damage screw threads.
Pierce-fixed
through pan
Figure 3.6
Fastening V-Rib
Figure 3.5
Side-laps
PERMALITE® Design Manual 2012 25
3.19 Fastener Specifications
LT7® V-RIB®
RA015 RA015
14X65 hex. head stainless steel 14X65 hex. head stainless steel
Taptite® self tapping screw with Taptite® self tapping screw with
aluminium bonded washer aluminium bonded washer
RA010 RA010SP
14X75 hex. head stainless steel 14X35 hex. head stainless steel
Type 17 screw with aluminium Type 17 screw with aluminium
bonded washer bonded washer
RA010SP
RA018
14X35 hex. head stainless steel
12X20 hex. head stainless steel
Type 17 screw with aluminium
stitching screw with aluminium
bonded washer
bonded washer
RA018
RA114
12X20 hex. head stainless steel
14X31 hex. head stainless steel
stitching screw with aluminium
Teks® self drilling screw with
bonded washer
aluminium bonded washer
RA114
14X31 hex. head stainless steel RA115
Teks® self drilling screw with 14X70 hex. head stainless steel
aluminium bonded washer Teks® self drilling screw with
aluminium bonded washer
RA115
14X70 hex. head stainless steel RA014
Teks® self drilling screw with 14X25 hex. head stainless steel
aluminium bonded washer Taptite® self tapping screw with
aluminium bonded washer
RA014
14X25 hex. head stainless steel
BP082
Taptite® self tapping screw with
57x27mm aluminium formed
aluminium bonded washer
washer with 6mm diameter hole
RA023
57x20mm aluminium formed
washer with 6mm diameter hole
RA041
50X25x2mm EPDM/Teflon flat
washer with slot with Teflon face
on one side.
RA033
22X20x2mm EPDM/Teflon flat
washer with slot. Teflon faced RA039
on one side 50X26x2mm EPDM flat washer
with 6mm diameter hole
RA036
22X20x2mm EPDM flat washer
with 6mm diameter hole
RA019 RATH1450
14X90 hex. head stainless steel 14X52 hex. head stainless steel
Type 17 screw with aluminium Type 17 screw with aluminium
bonded washer bonded washer
RA018
RA018
12X20 hex. head stainless steel
12X20 hex. head stainless steel
stitching screw with aluminium
stitching screw with aluminium
bonded washer
bonded washer
RA114
14X31 hex. head stainless steel RA114
Teks® self drilling screw with 14X31 hex. head stainless steel
aluminium bonded washer Teks® self drilling screw with
aluminium bonded washer
RA116
14X90 hex. head stainless steel RASH1450
Teks® self drilling screw with 14X52 hex. head stainless steel
aluminium bonded washer Teks® self drilling screw with
aluminium bonded washer
RA014 RA014
14X25 hex. head stainless steel 14X25 hex. head stainless steel
Taptite® self tapping screw with Taptite® self tapping screw with
aluminium bonded washer aluminium bonded washer
RA137
65x30mm aluminium formed
washer with 6mm diameter hole RAWLCYCP
Waveline stainless steel cyclonic
plate
RA041
65X25x2mm EPDM/Teflon flat
washer with slot. Teflon faced on
one side RAWLCYSW
Wavelinecyclonicsealing washer
for under cyclonic plate (Hard fix
only)
RA039
50X25x2mm EPDM flat washer
with 6mm diameter hole
Figure 4.6
Small penetration with sleeve (Dektite® sleeve illustrated)
PERMALITE® Design Manual 2012 29
4.7 Flashing large roof penetrations
Penetrations through ribbed cladding block the valleys (or
pans), and thus affect the free flow of rainwater down a roof.
All flashings have to weatherproof the cladding – but on the
uphill side of large penetrations, they also have to channel
rainwater sideways into valleys that run unobstructed to the
eaves.
Support framing
Wherever one or more of the sheet ribs are cut, you must
provide framing to support the cut ends of the roof cladding Figure 4.7 Method 1: Head gutter and apron flashings
each side of the penetration.
Existing flashing
If you have to re-use lead flashings that are built into the
structure, special protection is needed.
Polystyrene boards
Expanded and extruded polystyrene is also used for the
same purposes as blankets and batts. The boards are Figure 4.9 Typical roof insulation with foil or combined foil
more rigid and relatively less compressible which demand and blanket insulation
different fixing to that mentioned above. Seek advice from
manufacturers of polystyrene insulation.
57mm
RA154
RA092 Foam closure strip 25mm WAVELINE
Foam closure strip 25mm - external 854mm long
- external 890mm long
56mm RAWL762
Foam closure strip
RA156 - internal/external 762mm long
RA093 20mm
Foam closure strip
Foam closure strip 25mm - internal 860mm long
- internal 890mm long
20-40mm
20-40mm
All Profiles
Expansion Slot Punching Tools
RA185 Slotting Tool (Hammer) for LT7 or Alspan/V-Rib
RA161 Spare blade for RA185
RA165 Slotting Tool (Standing) for LT7 or Alspan/V-Rib
RA166 Spare blade for RA165
RA190 Profile adaptor for RA165 or RA185
New So
ES PTY.L S TD
SOCIAT
AND ASing as RPA ENGINEE
R
UD
R.E.PRO Trad
ABN 51
1 451
006 73
om.au
lliance.c
eridiana
rpa@m
N
– DESIG
pliance
at e of com
Certific
Proud
Ross Eric
39 t 3350
No. EC10 Street, Ballara
gistered ia 3354
From: ner Re 14 Victor 25 Bakery Hill
Practitio x 21
Building P.O . Bo
Address:
ldings n Manua
l
pe Bui g Desig
Bluesco Sheetin
ium Roof Roof
Builder:
in
luminum e
ite Alum
orks
Permal malite A
e “Per renc refe
tion of W gn of th listed in
Descrip the desi awings
reby certifies as detailed in dr
ificate he t
nce:
Complia ural Design Cert d projec anual
entione Design M
ct above m Sheeting
This Stru stem” for the iu m Roof
ti ng Sy eA lu m in
Shee Permalit
listed
tation: tions: ts of the
Documen th e regula ce with the requ
iremen
isio ns of
ing prov signed in accordified design load
an s.
e follow
s with th s have been desustain the spec
Complie f Sheet ards to
Roo nd
ring Sta
Enginee tion
Part/Sec
Volume ples her actio
ns
al Princi and ot
Australia Part 0:
Gener
ent, impo
sed
Code of ctions: art 1: Perman
Building Standards esign A P
ra lian tructural D ign Actions: C2,C3)
Aust .0:200 2 S
al Des ures 2,N3, N 4,
1170 tructur Struct ating N
AS/NZS 1170.1:2002 S formed Steel sing (Wind R
d-
AS/NZS 4600:2005 Col Loads for Hou e
ZS W in d Cod
AS/N 006 ures
4055:2 0 Steel Struct al Framing
AS/NZS 99 estic M
et
4100:1 s
AS/NZS 3623-1993 Dom f Drilling Screw
ZS S el
AS/N 66.1-2002
35
AS/NZS ual
Man
ts: g Design
ocumen Sheetin
Design D m Roof
al ite Aluminiu
Perm
Signed
.08.2011 Nor
Date: 02 ther
Ross Prou
d
n Te
EC1039 ROAD, rrito
SUITE 17
P.O.BOX
71
0 MAIN
109 – 11 AH, HOBART
MOON
30 DE VONPOR
T ry
DE,
ES ARCA
CHURCH
SUITE 1, STREET, DEVONP
ORT R.E.P
ART
16 STEW X 7130 DEVONP
ORT
PHONE
03 6278
3190 R OU
RAT
ET, BALLA 54
P.O.BO 1611 DA
RIA STRE L 33 PHONE
03 64 24
NOR ND
14 VICTO 25, BAKERY HIL
THE ASS
21
P.O.BOX 5327 7477 RN OC I
PHON E 03
Prac SECT TER
RIT Trad AT E
PA E S PTY.L
B ing
titio
ner’s ION 40 UILDIN ORY O rpa@ A
as R
G AC F AU
Nam CER mer BN 51 NGINE TD
ICA T 199
Cate e D E T IF STR idia
gory
of R
SIGN
/ CO TE OF 3
ALIA nall 006 731 ERS
ianc
Buil eg istra R oss P (D elete N
as a STRUC
C OM
P e.co 451
der: tion rou p p ro T LIAN m.au
Stru d pria ION CE
Des c tura te )
crip l En
tion gine
o
f Wo lues B erin
Co m rks cop g
p
This liance: Per
eB
uild NT R
S
She tructur
mali ing egis
te s trat
e a
Doc ting Sys l Design
Alum ion
u me
iniu Num
t
ntat em” for Certific
m Roo ber
ion: ate f Sh 561
the h e re e e 21 E
ab o by c
ting S
Com ve m e
D esig
plies e ntio r tifie nM
with n ed p s the a n ual
the Perm r ojec d e
t as sign of
Roo
f
Sta f Sheets ollowin alite deta th
nda ha g pr Alum iled e “Per
to s ve bee ovision iniu m
rds in d
Buil usta s of m Roo raw alite A
n de
t f ings lu
d
Aus ing Cod
in the s ig he
spe ned in regula
She
etin liste miniu
d in m
trali
AS/N an S
e o f Au cifie ac
d de corda t io ns:
g D esig refe Roof
s n renc
AS/N ZS 11 tandard tralia sign nc
load e with
Man
ual
e
Z 70
AS/N S 11 .0:20 s s. the
requ
AS/N ZS 46 70.1:20 02 Stru Volu irem
me
AS/N ZS 40 00:200 02 Stru ctural D ents
of th
5 5
AS/N ZS 41 5:200 Cold- ctural D esign A e lis
ted
Z 0 0 6 W fo rmed es c ti P art Eng
AS/N S 36 :199 ind ign ons /
ZS 2 3 0 L o S te A c : P Sectio inee
356 -1993 Steel S ads fo el Str tions: P art 0: G n ring
6.1- Dom truc r Ho uctu a e
D es 200 tu u r r t 1: n
Per eral Pr
ign D 2 S estic M res C sing (Wes man incip
P e rm ocum elf D
rillin
etal ode indR ent, le
alite e g S Framin imp s
Alum nts:
atin
crew g gN ose
iniu s 2,N d an
mR 3,N
4,C d o
oof 2,C ther
Shee 3) acti
I he t in ons
r g D es
requ eby ce ig nM
irem rtify a
ents that nua
o f th t l
e bu he wor
ildin k CE R
g co s desc TIFIC
…… de o rib ATIO
Sign … … f Au ed ab N
atur ……… stra ove
lia an h
e …… d th ave be
…… e No en
rthe d
rn T esigned
……
14 V …… errit
ory /comple
IC ……
P.O.B TORIA
S … Buil
PHO OX 212 TREET,
NE 0 5, B B A ding ted in
AK LLA Re g a
ulat ccorda
3 53
27 7 ERY HIL RAT
477 L 33
54 ions nce
. with
the
SU
16 S ITE 1, C
02.0
TEW HUR …… 8.201
P.O.B ART STR CHES A
OX EET RCA
D
Date ……… 1
PHO 7130 D , DEVO E, ……
NE 0 E N .……
3 64 VONPO PORT ….
241 R
611 T
SUIT
E 17
109
– 11
0
P.O.B MOO MAIN
OX 7 NAH ROA
, D,
PHO 130 DEV HOBAR
NE 0 O T
3 62 NPORT
78 3
190
South
Austra
lia
R.E.PRO
UD AND
ASSOCIA
TES PTY.
D
Trading LT
A EN as RP
Certifica
te of co ABN 51 GINEERS
rpa@m
mplian eridiana 006 731 451
Purs ce te lliance.com
Designe (SA dev uant to regu chnical expert .au
r: elopme la
nt regu tion 88
Ross Eric lations
Project: Proud – 1993
)
Bluesco
pe
Extent of Permalit Buildings
Certificat e Alumin
e: ium Roo
f Sheeti
This Stru ng Desig
ct n Manua
“Permal ural Design Ce l
ite Alum rtificate
project inum Ro hereby
as detaile of Shee certifies
Permalit d ting the desi
Complie e Alumin in drawings liste System” for th gn of
s with th ium Roo d e above the
Roof S e following pr f Sheeti in reference D m
heets ha ovisions ng Desig ocumen entioned
Standar ve of the re n Manu tation:
ds to su been design gu la ti al
stain th ed in ac on s:
e co specified rd
design ance with the
Building loads. require
Code of ments
Australia of the lis
ted
Enginee
AS/NZS Australia ring
AS/NZS 1170.0:2002 n Standa
S rds
AS/NZS 1170.1:2002 tructural Desig
S n
AS/NZS 4600:2005 Col tructural Desig Actions: Par
n Actio t
AS/NZS 4055:2006 W
d-formed
Steel ns: Par 0: General Prin
in t 1: Per
AS/NZS 4100:1990 Ste d Loads for H Structures manen ciples
3623-199 el Structu ousing (Win t, impo
AS/NZS sed an
3566.1 3 Domestic M res Code d Ratin
g N
d othe
r actions
-2002 S 2,N3,N
elf Drillin etal Framing 4,C2,C
3)
I, Ross Pr g Screw
oud,
Prac
s
the Stru
ctural R ticing Professi
equirem onal En
ents of gi
1. Inst the build neer, Hereby ce
ing code rt
allation
an d of Austr ify that Structur
good pr Co nstructi alia, subj al Compo
ect to co
2. All In actice. on shall
be in accord nditions nents Comply
put data an . with
This Ce of this Sp ce with
ec the atta
3. Build rtificate becom ific project is ched sp
ec
Signed in g Co es in valid if th ex cl ud ed from if ic at ions and
de of Aus
tralia or ere this Cert accepted
relevant are any pertin ification.
technica en
l data w t to the relevant
hich po Austral
st date
Date: 02
.0 this Cert ian Standards
Ross Prou 8.2011 ificate. or the
d
Dip CE (1
972) MIE
Aust CP
ENG
14 VICT
OR
P.O.BOX IA STREET, BALL
2125, BA ARAT
PHONE KERY HI
03 5327 LL 3354
7477
SUITE 1,
16 STEW CHURCHES AR
ART STRE CA
P.O.BOX ET, DEVO DE,
7130 DE NPORT
PHONE VONPOR
03 6424 T SUITE 17
1611 109 – 11
0 MAI
PHONE
03 6278 MOONA N ROAD,
3190 P.O.BOX H, HOBA
7130 DE RT
VONPOR
T
ROAD,
0 MAIN
109 – 11 AH, HOBART
SUITE 17 MOON T
VONPOR
7130 DE
DE, P.O.BOX
ES ARCA Date:
CHURCH ORT
SUITE 1, STREET, DEVONP 02/08/2
ART ORT 3190 011
16 STEW X 7130 DEVONP 03 6278
RAT P.O.BO 11 PHONE
ET, BALLA 54 16
03 6424
RIA STRE L 33 PHONE
14 VICTO 25, BAKERY HIL
21
P.O.BOX 5327 7477
03
PHONE
Western Australia
R.E.PROUD AND ASSOCIATES PTY.LTD
Trading as RPA ENGINEERS
ABN 51 006 731 451
[email protected]
Design Documents:
Permalite Aluminium Roof Sheeting Design Manual
Signed
Date: 02.08.2011
Ross Proud
EC1039
14 VICTORIA STREET, BALLARAT SUITE 1, CHURCHES ARCADE, SUITE 17 109 – 110 MAIN ROAD,
P.O.BOX 2125, BAKERY HILL 3354 16 STEWART STREET, DEVONPORT MOONAH, HOBART
PHONE 03 5327 7477 P.O.BOX 7130 DEVONPORT P.O.BOX 7130 DEVONPORT
PHONE 03 64241611 PHONE 03 6278 3190
Except to the extent to which liability may not lawfully be excluded or limited, BlueScope Steel Limited
will not be under or incur any liability to you for any direct or indirect loss or damage (including, without
limitation, consequential loss or damage such as loss of profit or anticipated profit, loss of use, damage
to goodwill and loss due to delay) however caused (including, without limitation, breach of contract,
negligence and/or breach of statute), which you may suffer or incur in connection with this publication.
Ph: 1300 850 389 Fax: 1800 850 481 web: www.bluescope.com.au
blueScope, Permalite®, V-Rib®, LT7®, Alspan®, Waveline®, Sahara®, Enduro Green®, Perpetual Green®, Glacier White® and Moon Shadow®
are registered trademarks of BlueScope Steel Limited, ABN 16 000 011 058. Tek® is a registered trademark of ITW Buildex. The Permalite® range of
36 is made by BlueScope Steel Limited trading
products PERMALITE
as BlueScope Design Manual 2012
®Building Solutions. 200 PM 16/8/12