0% found this document useful (0 votes)
128 views11 pages

ASCE 7 Wind Load Calculation Guide

This document outlines the 7 step windload calculation process according to ASCE-7-10. It involves determining the risk category, basic wind speed, windload parameters, velocity pressure exposure, velocity pressure, external pressure coefficients, and calculating wind pressure values. The maximum applicable negative windload is determined to be -0.87 kPa.

Uploaded by

Muraleedharan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views11 pages

ASCE 7 Wind Load Calculation Guide

This document outlines the 7 step windload calculation process according to ASCE-7-10. It involves determining the risk category, basic wind speed, windload parameters, velocity pressure exposure, velocity pressure, external pressure coefficients, and calculating wind pressure values. The maximum applicable negative windload is determined to be -0.87 kPa.

Uploaded by

Muraleedharan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 11

Windload Calculation to ASCE -7-10

1 Step.1
Determine Risk category ( Tale 1.5.1-Chapter 1 -Page 2)
Catgory II

2 Step.2
Determination of Basic Wind speed
Taken as 45 m/sec

3 Step.3
Determination of Windload parameters

Kd = 0.85 (26.2 page 250)


Exposure category B ( page 251)
Kzt 1 (26.8.2)
Enclosure class Enclosed ( Ofice Builidng)
Gcpi =+/-0.18 ( Table 26.11, page 258)

4 Step.4
Determination of Velocity pressure exposure

Kh = 0.92 Table 30.3-1 pagHeight considered= 23.85


kz = 0.7 height =5.65M
5 Step.5
Determination of Velocity pressure
qh = 0.613*Kh*Kzt*Kd* V2 =
970.71615 0.97 Kpa
qz= 0.613*Kz*Kzt*Kd* V2 =
738.588375 0.74 Kpa
6 Step.6
Determine external pressure co-efficient Gcp
Effective area =47.04
Zone 4 & 5 -Positive(+) = 0.6
Zone 4 - Negetive(-) = -0.7
Zone 5-Negetive(+) = -1

7 Step.7
Calulation of wind pressure
p1 = qz{ ( GCP-GCPi(+)} GCPi(+) = 0.18
p2 = qz{ ( GCP-GCPi(-)} GCPi(-) = -0.18
With Kh with Kz
P4&5 POSTVE1 = 0.31 Kpa
P4&5 POSTVE2 = 0.58 Kpa
P4 NEGTVE1 = -0.65 Kpa
P4-neg2 = -0.38 Kpa
P5-neg1 = -0.87 Kpa
P5-neg2 = -0.61 Kpa

Maximum load
CONSIDER (-0.87Kpa )S APPLICABLE Negative WINDLOAD
Determination of Kh and Kz h=23.85 Z=5.65

Co- Co- Co-


efficient efficient efficient
for for for
Catgaory Required Catgaory Catgaory
Ht Z C Value C Ht Z C

24.4 0.93 4.6 0.7


23.85 0.9245
27.4 0.96 6.1 0.7

Area 12.22 x 3.85 47.047 sqM

Determination of Gcp
Positive 4 & 5

46.5 0.6
47.04 0.6
92.9 0.6

Negetive 4

46.5 -0.7
47.04 -0.7
92.9 -0.7

Negetive 5

46.5 -1
9.9 -1
92.9 -1

Negetive 3

9.9
9.3 -2
9.9 -2
18.6 -2
Co-
efficient
for
Required Catgaory
Value C

5.65 0.7