Optimizing a circuit breaker's closing or opening moment is
of utmost importance when switching reactive loads
because random switching can sometimes result in high
transient overvoltages and inrush currents. These
transients generate stresses for all substation and network
equipment, leading to accelerated aging or - in the worst
case - destruction of equipment.
The RPH2 provides a reliable, low-cost way to reduce these switching transients to an acceptable
level. Serving as a control uni, it delays the switching order - phase by phase - unti the pre-
efined switching time (cepending on currentvoltage network characteristics) that reduces
switching transients to a minimum level. The RPH2 isa particularly important element when
switching large transformers, shunt reactors, capacitors and uncompensated lines.
« Load Type of operation [Controlled instant [Stress avoided
a Capacitive | Closing [Zero voltage Overvoltages inrush current
Capactive [Opening [Optimal arcing time [Restrikes overvoltages
Inductive [Closing Vottage peak Inrush current
Inductive [Opening [Optimal arcing time _[Restrikes overvoltages
Example: Switching of a capacitor bank
‘The tripping / closing impulse is sent to the RPH2, where tis delayed and released so as to
ensure switching at optimum time (frst zero-crossing of reference voltage after a coil order has
been received is the trigger signal for RPH2). The calculated delay depends on the load, the
circuit breaker and the various compensations performed inside the RPH2.
Reaching the optimum switching point requires thatthe circuit breaker operating times remain
very stable, whatever the conditions may be. In order to compensate the variations of operating
times according to environmental factors, the RPH2 monitors continuously ambient temperature,
control voltage, operating times and ~ in case of a hydraulic-operated driving mechanism
hydraulic pressure, Several compensation functions, adapted to each type of breaker, allow the
RPH2 to compensate forall deviaions of operating times, For long-term dri of operating times,
an adaptive contol facility is provided for, thus guaranteeing optimum switching accuracy
throughout the whole ife of circuit-breakers.MAIN FEATURES
> Microprocessor controlied device.
> Switching function ON and OFF available in one
device,
> Graphic display for setings and measured
values,
> Easy selting of parameters via keypad or via
PC-interface.
> Comprehensive alarm and signal functions.
> Archive function. The most important data of the
last 1,000 switching operations are stored in a
non-volatile memory.
> Comfortable PC-software for configuration and
reading archived data.
> An additional RS 232 port for connexion to a
modem ts available on request.
> Fixed switching programs for main applications,
(One program for special applications can be
defined by the user.
> Housing for mounting in 19°-rack or wall
mounting.
> Optional: Current module for measuring and
monitoring of current wave during switching
> Optional: Analogue modules for measuring of
CB-control voltage, ambient temperature and
pressure of hydraulic driving mechanisms as
‘well as compensation for the resulting CB
‘operating times. Adaptive control facilty to
consider ong time dri of the CB-mechanism
rive.
RPH21 | RPH2-1A3 RPH2-1SIA0
RPH218 [RPH2-1SI RPH2-1SIA1
RPH2-11_[RPH2-1SA0 RPH2-1SIA3,
RPH2-1A0 | RPH2-1SA1 RPH21...R
RPH2-1A1 | RPH2-1SA3
RPH2-2 | RPH2-243 RPH2-2SIA0
RPH2-2S_[RPH2-2SI RPH2-2SIA1
RPH2.21_[RPH2.2SA0 RPH2.25IA3
RPH2-280 [RPH2-28A1 RPH2-1..R
RPH2-2A1 | RPH2-2SA3
AREVA TaD Worldwide Contact Contre
Tel: +44 (0) 1785 250 070
Eon
Reference voltage 100/3V, 220/3V AC
(V.T secondary)
‘Operating range
[40 - 105 V, 90-230 V AG
Rated frequency 16 2/3 Hz, 60 Hz, 10%
(CB-contol volage [ae -250 VDC
‘Operaling range 27 -300V DC.
Power consumption =20W
Resolution of switching [0.1 ms
‘Switched current max. 18,8, 1886
Input current module Aor 5 A.100x1, 1 886
Input temperature transducer [4 .. 20 mA
Input pressure wansducer [4.20 mA
Models description
RPH2-1: basic device, one switching function
(opening or closing), graphic display, LED “device
alarm-LEDs, remote signal contact
“device ready," one remote alarm-contact
RPH2-2: as RPH2-1, but with two switching
functions (ON and OFF).
‘S: signal module with seven remote alarm contacts
and inputs for monitoring of CB-operating times
I: Current measuring module,
‘Ao: analogue module for measuring and
‘compensation of CB-control voltage and ambient
temperature.
A1: a8 AO, with an additional measuring and
‘compensation of one hydraulic pressure.
A3: as AO, with an additional measuring and
‘compensation of three hydraulic pressures.
R: additional RS 232 por atthe reat for connexion
to.a modem (available for all models),