0% found this document useful (0 votes)
141 views8 pages

Wold Life-Safety Reports On Center Cass School District 66 Schools

This is the health-life-safety report by Wold Architects & Engineers about Center Cass School District 66 schools.

Uploaded by

David Giuliani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views8 pages

Wold Life-Safety Reports On Center Cass School District 66 Schools

This is the health-life-safety report by Wold Architects & Engineers about Center Cass School District 66 schools.

Uploaded by

David Giuliani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Center Cass School District No.

66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Elizabeth Ide Elementary School

Priority
Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Exterior (X#)
X1 Exterior Doors b BOCA 1996 Rusting at lintels - multiple locations Grind, Prep, and Paint 8 $ 7,560
1403.1, PM-
304.6
X2 Exterior Walls c 185.390L(1-6) Masonry Cracking - multiple locations. Allowing water Tuckpoint masonry 65 sf $ 2,080
infiltration and could lead to structural deterioration
and mold.
X3 Exterior Openings c BOCA 1996 Missing Sealant - multiple openings Seal sills, multiple locations allow $ 5,000
1403.1, PM-
304.6
X4 Roof x n/a Recurring roof leak Investigate and repair
X5 Roof x n/a Bubbling at roof membrane Investigate and repair
X6 Roof x n/a Standing water on roof adjacent to mechanical curbs Provide tapered insulation to provide 2 loc $1,500
drainaige
X7 Door c Illinois Exterior Access at exit doors Install accessible sidewalk 360 sf $ 4,320
Accessibility
Code

X8 Door c BOCA PM Weather infiltration at exterior HM gym doors Replace hardware/weatherstripping 1 $ 300
702.1,
185.370m2Aii
X9 Exterior Walls c IECC Masonry Control Joint Exposed - multiple locations Replace sealant allow $ 2,200
X10 Exterior walls b IPMC 303.3 Sharp edges at sill flashing - cut hazard repair sill 2 loc $ 500
X11 Site Gate b n/a Recommendation by local first responders to include Add Exit gate at NE corner of the site allow $ 1,500
exit gate in existing fence on the north edge of the Subtotal - Exterior: $ 24,960
Architectural (A#)
A1 Gymnasium c n/a Replace Gym Floor - Inappropriate athletic surface Replace with cushioned floor 4500 sf $ 128,000
A2 Existing Gym Doors b 185.390g5Bi, Original wood doors, failing - multiple locations Replace doors and hardware 2 $ 4,000
185.390m6Biii
A3 Room 135 c Temperature control difficulties - Room 135 Diagnose HVAC - TBD
Subtotal - Architectural: $ 132,000
Fire Protection (F#)
No Violations
Subtotal - Fire Protection: $ -

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Elizabeth Ide Elementary School

Priority
Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Plumbing (P#)
P1 Toilet (120) c IL Plumbing No floor drain installed in restroom. Required to Install floor drain. $ 3,250
Code prevent backflow of waste into building
890.1370.a.4

P2 Toilet (153) c IL Plumbing No floor drain installed in restroom. Required to Install floor drain. $ 3,250
Code prevent backflow of waste into building
890.1370.a.4

Subtotal - Plumbing: $ 6,500


Mechanical (M#)
M1 Roof, DOAS-2 c n/a Outside air filter not properly secured or installed. Adjust filter installation for proper fit. $ -
M2 Roof, HP-3 c n/a Heat pump condensing coil shows signs of hail/debris Repair coil (comb) and install hail $ 11,000
damage. guards (all units).
Subtotal - Mechanical: $ 11,000
Electrical (E#)
E1 Fire Alarm c 180 NFPA 72, Fire Alarm system is aged and fails frequently posing Replace system with voice evac 50800 sf $ 61,000
175.470 safety risk in the event of emergency
E2 Interior Lighting c 175.610. Lights in public bathrooms and gym are aged beyond Replace lighting and controls with LED 5850 sf $ 31,600
their useful life, suceptible to disrepair, and inefficient
E3 a
Subtotal - Electrical: $ 92,600

Total Construction Cost - Entire Building: $ 267,060

Total Project Cost $ 320,472

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Prairieview Elementary School

Priority
Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Exterior (X#)
X1 Exterior Entry Sidewalk c 185.50 IPMC 302.3 Significant Sidewalk heaving, cracking and spalling - Replace damaged sidewalk sections 1800sy $ 144,000
potential tripping hazard
X2 Roof x n/a Failure at shingles and membrane above gymnasium Repair roofing at damaged locations 60 sf

X3 Chiller x n/a Failure at chiller concrete pad Replace and reinforce chiller support 150 sf $ 6,750

X4 Roof gutter and downspout c 185.50 IPMC 303.2 washout occuring at outfall with debris and ice pooling at Regrade and install splashplock 1 loc $ 4,500
sidewalk, poses slip hazard
X5 Parking Lot c 175-410 c) NBC 1001.1 uneven asphalt and failures throughout and at running Repair and replace damaged asphalt sections $ 243,397
PA 88-251 Section 17- track
X6 Trash Enclosure b 185.50 IPMC 302.3 Failing masonry walls at dumpster enclosure present Reconstruct masonry surround allow $ 15,000
falling brick hazard at walkway
Subtotal - Exterior: $ 413,647
Architectural (A#)
A1 Stairwells - multiple (2) b 185.390.I.1) Masonry cracking and planar shifting at interior walls Replace and repair masonry, provide supporting lintel to 30 lf $ 2,800
and floor lines presenting possible structural deficiencies correct planar shift

A2 Classroom Windows (all) x Masonry cracking at sill, typical at most exterior Repair masonry and provide control joint at masonry sills 4'-0" lf @ approx 35 $ 52,600
classroom windows locations

A3 Toilet Rooms - multiple (4) c Illinois Accessibility ADA clearance conflicts with toilet accessories and grab replace and relocate accessories in accordance with 8 loc $ 4,800
Code bars per Illinois Accessibility Code required ADA clearances.
A4 Kitchen c IDPH Not slip resistant flooring surface Replace floor finish with food service appropriate, slip 650 sf $ 18,400
resistant tile
A5 Gymnasium/Multipurpose Room b 185.50 IPMC 305.3 Floor tile chipping,cracking, posing trip hazard to Replace flooring in Gymnasium/Multipurpose Room 7750 sf $ 218,000
Floor students.
Subtotal - Architectural: $ 296,600
Fire Protection (F#)
No Violations
Subtotal - Fire Protection: $ -
Plumbing (P#)
No Violations $ -
Subtotal - Plumbing: $ -
Mechanical (M#)
M1 BAS Controls c n/a BAS system obsolete, unable to properly control Replace BAS system 64000 $ 320,000
ventilation, heating, and cooling
Subtotal - Mechanical: $ 320,000

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Prairieview Elementary School

Priority
Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Electrical (E#)
E1 Intercom System (B198) b Intercom failures multiple rooms throughout, obsolete Replace intercom system in full $ 51,300
system with difficult maintenance
E2 Exterior Lighting c Recommended IES Mixture of lighting types creating uneven lighting Replace all remaining original with LED $ 24,900
conditions
E3 Electrical Panels - A106, C109 a NEC Insufficient Panel Clearance Move tables intruding on 3ft panel clearance $ -

E4 Fire Hood - Kitchen b NEC No shunt-trip for fire hood equipment/devices posing fire install a shunt trip device $ 6,000
safety hazard
E5 Camera Coverage c n/a Insufficient building surveillance Add security cameras to increase interior and exterior $ 20,100
surveillance coverage
E6 Intrusion Detection c n/a Alarm system not functioning Diagnose/replace $ 25,800
E7 Interior Lighting c 175.61 Lighting fixtures have reached the end of their useful life, Replace interior lighting with LED 64000 $ 387,000
are inefficient, and susceptible to disrepair.

Subtotal - Electrical: $ 515,100

Total Construction Costs- Entire Building: $ 1,545,347

Total Project Cost $ 1,854,416

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Lakeview Junior High School

Priority
. Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Exterior (X#)
X1 Tuckpointing various locations c 185.390L(1-6) Masonry Cracking - multiple locations. Allowing water Provide masonry repair and tuckpointing 180 sf $ 4,500
infiltration and could lead to structural deterioration and
mold.
X2 Roof - Area 1 c IPMC 302.2, 304.6, 304.7 Failure of membrane - bubbling multiple locations - Replace roof system with modified bitumen roof 31510sf $ 945,300
beyond useful life and warranty and has been repaired
repeatedly. Insulation saturated in areas recurrent leaks
X3 Roof - Area 2 c IPMC 302.2, 304.6, 304.7 Failure of membrane - bubbling multiple locations - Replace roof system with modified bitumen roof 10900sf $ 327,000
beyond useful life and warranty and has been repaired
repeatedly. Insulation saturated in areas recurrent leaks
X4 Roof - Area 3 c IPMC 302.2, 304.6, 304.7 to spaces
Failure ofbelow
membrane - bubbling multiple locations - Replace roof system with modified bitumen roof 11025sf $ 330,750
beyond useful life and warranty and has been repaired
repeatedly. Insulation saturated in areas recurrent leaks
X5 Metal Wall Panel c IECC Rusting throughout, possible failures at attachment TBD - replacement or prep and repaint/replace trim 10,000 sf $ 640,000
components due to rusting
X6 Parking Lot and Track c 175-410 c) NBC 1001.1 uneven asphalt and failures throughout and at running Repair and replace damaged asphalt sections 3934 SY $ 249,304
PA 88-251 Section 17- track
X7 Concrete Plaza c 185.50 IPMC 303.3 Concrete heaving at exit door causing tripping hazard Replace concrete sidewalk 886 sy $ 77,968

X8 Masonry Control Joints - Gym Walls c IECC Existing control joint sealant failing Remove and replace sealant at multiple locations allow $ 4,000

X9 Right Turn Lane x n/a Congested traffic flow exiting school property Add Outbound Right-turn Lane $ 447,562

X10 Circle drive lane x 185.50 IPMC 303.3 Asphalt paving failures at primary drive lane Remove and replace damaged asphalt $ 63,672

Subtotal - Exterior: $ 3,090,056

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Lakeview Junior High School

Priority
. Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Architectural (A#)
A1 Boiler b AHERA Asbestos insulation exposed Abate exposed asbestos allow $ 12,000

A2 Drinking Fountains - Multiple c Illinois Accessibility Mounting height not ADA compliant Adjust mounted height of drinking fountains allow $ 5,000
Code
A3 (2) locations c Illinois Accessibility Entry to group bathrooms do not allow for ADA Correct entries to provide required maneuver clearances allow $ 10,000
Code maneuvering clearance
A4 (2) locations c Illinois Accessibility Entry to locker rooms not ADA compliant (2) entrances Correct entries to provide required maneuver clearances allow $ 10,000
Code per locker room
A5 Masonry Interior Walls c 185.390L(1-6) Masonry cracking - multiple locations. Can contribute to Repair masonry and provide control/movement joints 450 lf $ 18,000
structural failure over time. where warranted

A6 Carpet Flooring x n/a worn carpet throughout, beyond warranty and useful Replace carpet throughout. ~40,000 sf $ 340,000
life in majority of building.

A7 Knob Hardware c Illinois Accessibility Knob hardware not compliant with Illinois Accessibility Replace door hardware 15 doors $ 12,750
Code, 185.370 d Code

A8 Damaged/rusted lockers x n/a Gym lockers damaged/worn. Some prevented from Replace Lockers allow $ 25,000
adequately closing/locking

A9 Sagging/stained ACT Ceiling x n/a Damaged/sagging ceiling tiles throughout Replace Tile/grid system to remain ~60,000 sf $ 210,000

A10 Vestibule at 217/137 x n/a Aluminum frame cover trim missing Replace and install new trim allow $ 500

A11 Science Classrooms x n/a Upper cabinets sagging/deteriorating replace upper cabinets ant secure to wall properly allow $ 4,800

Subtotal - Architectural: $ 648,050


Fire Protection (F#)
FP1 Sprinkler Pipe Leak b n/a Leak occuring at sprinkler service ` Replace fittings as required to eliminate leak allow $ 2,000
Subtotal - Fire Protection: $ 2,000
Plumbing (P#)
P1 Mechanical Room (A144) b IL Plumbing Code Water heater and storage tank are showing signs of Replace failing equipment and provide means of $ 71,500
890.1220 failure. properly tempering the building's hot water supply.

P2 Toilet (???) c IL Plumbing Code No floor drain installed in restroom. Required to prevent Install floor drain. $ 3,250
890.1370.a.4 backflow of waste into building

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Lakeview Junior High School

Priority
. Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
P3 Toilet (???) c IL Plumbing Code No floor drain installed in restroom. Required to prevent Install floor drain. $ 3,250
890.1370.a.4 backflow of waste into building
P4 Toilet (???) c IL Plumbing Code No floor drain installed in restroom. Required to prevent Install floor drain. $ 3,250
890.1370.a.4 backflow of waste into building
P5 Building-wide x IDPH 890.700(d) Galvanized steel piping at end of useful life throughout Replace galvanized steel piping with coper piping for $ 454,000
building. Failure would result in building-wide domestic water supply
plumbing issues
Subtotal - Plumbing: $ 535,250
Mechanical (M#)

M1 Roof c Recommended PM Multizone rooftop units have outlived their useful life Replace RT-1*** $ 249,500
603.1 according to ASHRAE standards.

M2 Roof c Recommended PM Multizone rooftop units have outlived their useful life Replace RT-2*** $ 249,500
603.1 according to ASHRAE standards.

M3 Roof c Recommended PM Multizone rooftop units have outlived their useful life Replace RT-3*** $ 272,160
603.1 according to ASHRAE standards.

M4 Roof c Recommended PM Multizone rooftop units have outlived their useful life Replace RT-5*** $ 272,160
603.1 according to ASHRAE standards.

M5 Roof c Recommended PM Multizone rooftop units have outlived their useful life Replace RT-6*** $ 272,160
603.1 according to ASHRAE standards.

M6 BAS Controls c n/a BAS system obsolete, unable to properly control Replace BAS system 71,900 $ 359,500
ventilation, heating or cooling.

Subtotal - Mechanical: $ 1,674,980

Commission No. 213060


Center Cass School District No. 66
10-Year Health/Life Safety Survey
November 5, 2021

CONDITIONS LIST
Lakeview Junior High School

Priority
. Item ID . Location(s) . Code . Rule Violated . Description of the Violation . Recommendation to Correct Violation Quantity Estimated Cost
Electrical (E#)
E1 Intercom System (B198) b Intercom failures multiple rooms throughout, obsolete Replace intercom system in full $ 73,200
system with difficult maintenance
E2 Electrical Panel (B189, C213A, C213B) a NEC Insufficient Panel clearance remove obstacles obscuring required 3-foot clearance $ -

E3 Camera Coverage c n/a Insufficient building surveillance Add security cameras to increase interior and exterior $ 29,000
surveillance coverage
E4 Exterior Emergency Lighting c Recommended IES Incomplete lighting coverage Add lighting for proper coverage $ 10,500
E5 Exterior Lighting c Recommended IES Mixture of lighting types Replace all remaining original with LED $ 13,800
E6 Receptacles in Locker Rooms (with b NEC Non-GFI fixtures Replace with GFI fixtures $ 780
access to showers)
E7 Intrusion Detection c n/a Alarm system not functioning Diagnose/replace $ 25,300
E8 Lighting Room C205 c 175.610. Lighting at one switch not functional Investigate and repair fixutres and wiring $ 200
E9 Corridor near science wing/science room c 175.610. Can lights in soffit are failing Replace with LED lighting 16 loc $ 4,200
E10 LED Lighting Upgrade c 175.610. Lighting fixtures have reached the end of their useful Replace with LED lighting 60000 sf $ 358,800
life, are inefficient, and susceptible to disrepair.

E11 Fire Alarm System b 180 NFPA 72, 175.470 Fire Alarm system is aged and fails frequently posing Replace with fire alarm system with voice evac 71900 sf $ 86,300
safety risk in the event of emergency

Subtotal - Electrical: $ 602,080

Total Construction Cost - Entire Building: $ 6,552,416


*** Additional cost to improve sistem to Variable Air-Volume System to improve energy efficiency and climate control. Project Cost Total $ 7,862,899