Symeo LPR 1d24 Bsv101757 Manual
Symeo LPR 1d24 Bsv101757 Manual
Product Documentation
Table of Content
Content
1.2 Mounting.................................................................................................................... 6
1.3 Repairs....................................................................................................................... 6
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 2 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 3 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
Table of Figures
Figure 1: LPR®-1D24 measurement path .............................................................................. 8
Figure 2: LPR®-1D24 unit inclusive mounting bracket...........................................................10
Figure 3: Mounting of the fall protection ................................................................................11
Figure 4: LPR®-1D24 Connectors .........................................................................................13
Figure 5: M12 Connector for the power requirement ............................................................14
Figure 6: M12 Ethernet M12 .................................................................................................15
Figure 7: LPR®-1D24 Housing Dimensions ..........................................................................17
Figure 8: Network Settings ...................................................................................................19
Figure 9: Ping LPR®-1D24 unit .............................................................................................19
Figure 10: Homepage of the LPR®-1D24 unit .......................................................................20
Figure 11: Sign in on the home page of the LPR®-1D24 unit ................................................21
Figure 12: Device Menu .......................................................................................................22
Figure 13: Information overview and device status ...............................................................22
Figure 14 – Device: Device Configuration Menu ...................................................................23
Figure 15 – Device: Device Configuration - LAN Settings .....................................................24
Figure 16 – Device: Device Configuration LAN Settings - Commit the change .....................25
Figure 17 – Device: Device Configuration LAN Settings - Changes have been applied ........25
Figure 18 – Device: Device Configuration - SystemTime Settings ........................................26
Figure 19 – Device: Application Settings ..............................................................................27
Figure 20 – Device: Application Settings - Costumer Protocol Settings ................................27
Figure 21 – Device: Application Settings – General Settings ................................................28
Figure 22: Example configuration of one measurement pair Master and Slave Unit .............29
Figure 23 – Diagnostics Menu ..............................................................................................30
Figure 24 – Diagnostics: Operating System Status...............................................................31
Figure 25 – Diagnostics: Hardware Status............................................................................32
Figure 26 – Diagnostics: Distance over time.........................................................................33
Figure 27 – Diagnostics: Signal strength over distance diagram ...........................................34
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 4 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
The documentation for the LPR®-1D24 Local Positioning Radar System is published by:
SYMEO GmbH
Prof.-Messerschmitt-Str. 3
D-85579 Neubiberg
www.symeo.de
HISTORY
Version Date Description
1.00 29.01.2016 Initial Release
SYMBOLS USED
The following symbols are used throughout the documentation:
This symbol appears before instructions that must be followed at all times.
Failure to comply with these instructions will result in personal injury.
This symbol appears before instructions that must be followed at all times.
Failure to comply with these instructions will result in damage to
equipment.
This symbol appears before information of particular importance.
All rights reserved, particularly those relating to the translation, reprinting, and reproduction
by photocopying or similar processes of all or part of the documentation.
All rights reserved, particularly for purposes of the award of patents or submission of utility
models.
Delivery options and technical changes reserved.
Published by SYMEO GmbH
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 5 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
1 General Information
1.1 Safety Instructions
1.2 Mounting
1.3 Repairs
Use the original packaging or other suitable packaging for returns and
whenever the system is to be transported. This ensures protection from
crushing, impact, moisture and electrostatic discharge.
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 6 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
During mounting, make sure that no objects or liquids reach inside the
device (risk of short-circuit).
In case of emergency (e.g. damaged housing, control elements or power
cables, penetration of liquids or foreign bodies) switch off the device
immediately, disconnect from the power line the device and inform your
SYMEO service.
Protect the contacts of all sockets and plugs of the device from static
electricity. Avoid touching the contacts. If touching the contacts is
unavoidable, then one should take the following precautions: Touch a
grounded object or wear a ground strap before touching the contacts.
This will dissipate static charges.
The device must be secured against falling.
This device complies with Part 15 of the FCC Rules and with Industry
Canada license-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
General Information
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 7 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
LPR®-1D24
®
Figure 1: LPR -1D24 measurement path
In addition to the distance reading, the relative approach speed of the LPR® sensors is
available. Distance and speed can be used for internal collision avoidance decisions at
predetermined distance thresholds. Optional on-board relays will be activated. All data is
made available at standard interfaces.
The devices are easy to install and operate. Rough alignment between the facing units is
sufficient, even for very long distances. The multi-channel radio antenna is integrated into the
robust housing. A built-in terminal server allows straightforward configuration of the unit ID,
the paired unit ID and other parameters in any browser.
Symeo LPR® radio works highly reliable under adverse conditions. Interference with any WiFi
equipment operating in parallel can be excluded at all times. A unique ID per each unit allows
operating multiple pairs in immediate vicinity.
LPR®-1D24 sensors are maintenance-free and paired sensors can be interconnected with
other pairs, providing several distances at a single interface, e.g. for crane xy position
acquired by two sensor pairs.
http://www.symeo.com/cms/upload/pdf/en/DataSheets/Symeo_Datasheet_LPR-1D24.pdf
At a suitable place, mount the LPR®-1D24 unit to a suitable pipe with the bracket. To
adjust the system, do not tighten the mounting bracket finally. Specified alignments have
to be adhered to if indicated by Symeo.
A minimum distance of 3 meters between the measuring system units must be
maintained to guarantee the specified accuracy. Mounting closer than the minimum
distance decreases the accuracy at close proximity.
The units must have the same orientation for mounting, for example both units with
connectors downwards. For outdoor use the units have to be mounted with the
connectors downwards.
Now adjust the system on the opposite side.
The two system units should be mounted opposite to each other and possibly should not
be an offset horizontal and vertical from each other or twisted.
Now fix the system by tightening the screws in the mounting bracket and the mounting
bracket on pipe in such a way that no modification is possible anymore. Flat wrench SW
13 is required.
®
Figure 2: LPR -1D24 unit inclusive mounting bracket
B: 2 x snap hooks 5 x 50 mm
C: 1 x steel cable 3 mm x 1 m
The two ring nuts must be mounted on the back of the LPR®-1D24 unit laterally on the
respective second screw from above, which are 4 mm longer than the other screws. Then
the snap hook must be attached to the ring nuts. Please put the steel cable around a pipe or
a bracket and hang it also in the snap hook (see picture below).
The backup set should be installed before the assembly of the unit to
secure it against falling.
C B
Potential free
Output power at least 25 W
Output voltage 10 V DC to 36 V DC
Short-term maximum current flow (when switched on):
o At 24 V DC: 2000 mA for 50 ms
o At 12 V DC: 2500 mA for 50 ms
B8
B7
B4 B5 B6
B2
B1
B3
B9
B9 B10 B11
®
Figure 4: LPR -1D24 Connectors
B1: Ethernet
B2: Can-Bus IN/ Profibus IN
B3: Can-Bus OUT/ Profibus OUT/ Termination (optional)
B4: Pressure equalization membrane
B5: Serial interface RS422/RS485 / Relays (optional)
B6: Power supply
B7: Mini-USB
B8: USB – A (Logging)
B9 – B11: Status LEDs
On the following pages you will find the connector type, the pin
assignment, the product code and the Symeo order number. For more
information, please see the data sheets on the attached data carrier.
5.2.1 Plugs
Recommended connector:
VDC+ Pin 1
VDC+ Pin 2
VDC- Pin 3
VDC- Pin 4
5.3.1 Plugs
Recommended connector:
The connector cable M12 – RJ45 is required for the Ethernet-connection for configuration of
the LPR® -1D24 units with M12 plug and RJ 45 connector.
o Symeo order number: MTE102007
5.4.1 Plugs
Recommended connector:
If the USB-port at the device is not used, it must be closed with the end
cap to prevent leakage.
®
Figure 7: LPR -1D24 Housing Dimensions
The minimum pipe diameter is 40 mm, the maximum pipe diameter is 75 mm.
7.1 Requirements
In order for a unit to be successfully commissioned, the LPR®-1D24 components must have
been installed correctly:
The unit has been connected to the power supply.
Data link has been established over TCP/IP.
Once these prerequisites have been fulfilled, you can connect the unit to the network and
commission the LPR®-1D24 system. How to do this is explained in the following chapters.
If the firewall settings are too restrictive, you may not get access to the
LPR®-1D24 unit. In this case deactivate the firewall temporarily.
The LPR® unit should be available via your PC now. You can check the connection with a
ping to the LPR®-1D24 unit:
Open the Command-Window:
1. Push the Windows Start Button
2. Choose Run
3. Enter cmd and click OK
4. Enter in the cmd.exe window: ping 192.168.1.99 or the IP-address of the LPR®-1D24
unit.
®
Figure 9: Ping LPR -1D24 unit
®
Figure 10: Homepage of the LPR -1D24 unit
The homepage of the LPR®-1D24 unit's Web User Interface will appear.
A website language selection can be made using the flags in the top right corner of the
homepage.
Click the "Sign in" button in the top right corner of the homepage. The dialog box with the
username and password field will appear (see picture below).
Enter the user name "symeo" and the password "54all2u" and press "Login". Now your
status is displayed as "Logged in".
®
Figure 11: Sign in on the home page of the LPR -1D24 unit
You can always come back to this page if you press on the Symeo symbol or the Symeo
character in the top left hand corner of this page.
7.3 Device
With this function (see picture below) you switch either to:
Device configuration
Application settings
VPN remote access settings
Firmware update
Reboot device
The device status shows you the status of the services and interfaces.
o The service status “Measurement Filter” and “Measurement Daemon” and also the
interface status “Binary protocol” must be green, otherwise please contact Symeo
customer support.
The interface status “Binary protocol” is only green if the customer is connected to the
binary port.
Following message appears in the upper left corner “Saved successfully” (see picture below).
Furthermore it will be shown in green, what has been saved (in the picture below the
hostname). Now you need to press “Commit” if you want to apply the change. The unit will
perform a reboot to apply it. If you want to discard the change, press “Reset”.
Figure 17 – Device: Device Configuration LAN Settings - Changes have been applied
All changes always have to be saved and confirmed. Only then the
changes are applied on the unit.
o must be set to custom timezone if needed timezone is not in the dropdown menu
set the IP-address of the NTP-server
With this function (see picture below) you can set the LPR®-1D24 settings:
LPR group ID
o Group identifier of one pair of LPR® units, associated together. Has to be the same on
units measuring with each other. Diverse measurement paths must also be adjusted
to different group IDs.
Web User Interface for LPR®-1D24
Copyright © SYMEO GmbH 2015
LPR-1D24_Users_Manual_FCC-IC-Edition_EN.docx Page 27 of 34
SYMEO Local Positioning Radar System
LPR®-1D24
LPR®-1D24 Station – Overview and Mounting
Measurement mode
o Measuring mode for the LPR®-1D24 unit. Any measuring pair of LPR®-1D24 units has
to consist of one Master and one Slave Unit.
FSK communication channel
o Data communication channel number. Has to be the same on all units needing to
communicate with each other.
o The lowest usable communication channel is channel 16, the highest usable channel
is channel 95, depending on the configuration of the device. A set of 20, 40 or 80
usable channels can be configured.
Measurement channel
Figure 22: Example configuration of one measurement pair Master and Slave Unit
Configuration rules:
Don’t use a group ID more than once per site.
If pairs of LPR®-units are mounted close to each other, the FSK
channels should be at least two channels apart from each other.
The bandwidth variation number should stay on the default value 0.
7.6 Diagnostics
With this function (see picture below) you chose to:
Operating System Status
Hardware Status
Record measurement data
Distance over time diagram
Signal strength over distance diagram
With this function (see picture below) the operating system status can be seen.
In case of problems, these information may be asked by Symeo support.
With this function (see picture below) system values and system voltages are displayed.
In case of problems, these information may be asked by Symeo support.
With this function (see picture below) the current distance and the current RSSI value (Signal
strength) will be displayed. Furthermore the distance over time graph.
By pointing the mouse in the graph and using the scroll wheel you can downsize or enlarge
the timeline.
This diagram shows the recorded distance-signal strength pairs since the last power-on. You
can use it to detect abnormal signal propagation routes at certain constellations of the two
LPR®-1D24 stations, as the signal strength should decrease with increasing distance.
The distance axis displays the distance between the two LPR®-1D24 stations, and the RSSI
axis the received signal strength in dB. As the signal strength at specific distances may vary,
the statistical distribution of the signal strength is also recorded. Displayed are the mean
received signal strength, the 10 % quantile and the 90 % quantile. The Quantiles give you
information about how many recorded signal strength values were lower than the
corresponding line. 10 % of the recorded signal strengths were lower than the 10 % quantile
line and 90 % were lower than the 90 % quantile line, leaving 80 % in between those two
lines. This way you get an idea of the signal strength distribution per distance without
including extreme outliers. This helps identifying distances with increased signal distortions
(e.g. due to multipath signal propagation), as the variance of the signal strength there usually
increases.