0% found this document useful (0 votes)
147 views4 pages

UV IRS-datasheet

The document describes a UV/IRS flame detector that uses ultraviolet and infrared sensors to detect fires. It provides specifications for the detector including its operating voltage range, power consumption, temperature range, field of view, response time, and certifications. It also includes ordering information and accessories.

Uploaded by

Leinner Ramirez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views4 pages

UV IRS-datasheet

The document describes a UV/IRS flame detector that uses ultraviolet and infrared sensors to detect fires. It provides specifications for the detector including its operating voltage range, power consumption, temperature range, field of view, response time, and certifications. It also includes ordering information and accessories.

Uploaded by

Leinner Ramirez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

UV/IRS Flame Detector Product Data Sheet

FGD_PDS_UV_IRS_Flame_Detector October 2014

UV/IRS Flame Detector


Ultraviolet and Infrared Optical Sensors
The UV/IRS (Ultraviolet/Infrared) flame detector
delivers exceptional performance with many
distinct functions and features. Two precise
spectrums of radiation must be recognized and
confirmed by highly tuned sensors for the UV/
IRS to initiate a fire condition. This accurate and
reliable flame monitoring technology combined
with immunity to arc welding, hot body
radiation, lightning, and sunlight greatly reduces
costly false alarms while providing critical safety
performance to your site and personnel.

„„ Two radiation wavelengths necessary for alarm


– minimizing false alarm events „„ Field-selectable sensitivity and delay settings
„„ Low power consumption increases uptime and allows operators to fine tune at installation site
lowers overall costs „„ Wide area coverage, extended range with fast
„„ Manual and automatic testing of optical surfaces response times
„„ Designed for extreme conditions, operational „„ Analog, relay, RS 485 digital Modbus, and HART®
from -50 °C to +75 °C outputs available
„„ Global certifications and approvals „„ Three year warranty electronics/two years on
„„ Wide voltage range allows for greater stability sensors
and system compatibility

Enclosed in a rugged, explosion-proof housing, the UV/IRS The UV/IRS flame detector is simple to operate and maintain
flame detector uses the latest in modular microprocessor and while delivering all the security and performance required
Ultraviolet/Infrared sensor technology — delivering accurate for high-risk, industrial installations!
and reliable monitoring for hydrocarbon based fires. It is
capable of standalone operation or can be connected to a
variety of networked safety systems to create a dependable fire
monitoring system.

The UV/IRS flame detector has many unique features which


make it one of the industries best: an extra wide field of view
— up to 120°; user defined sensitivity and time delay settings
can be completed in the field with no special tools required;
one of the lowest power consumption levels and widest voltage
range available on the market.
UV/IRS Flame Detector October 2014

Specifications
Table 1 - UV/IRS Flame Detector
Analog Relay HART®
Operating Voltage Range 10 to 32 Vdc
Power Consumption at 24 Vdc Nom 45 mA/1.1 W Nom 45 mA/1.1 W Nom 71 mA/1.7 W
*with Heater Max 115 mA/2.76 W Max 115 mA/2.76 W Max 173 mA/3.36 W
*Nom 90 mA/2.16 W *Nom 90 mA/2.16 W *Nom 106 mA/2.22 W
* Max 165 mA/3.96 W * Max 165 mA/3.96 W * Max 223 mA/5.36 W
Power Consumption at 32 Vdc Nom 35 mA/1.12 W Nom 35 mA/1.12 W Nom 57 mA/1.72W
*with Heater Max 105 mA/3.36 W Max 105 mA/3.36 W Max 158 mA/5.06 W
*Nom 70 mA/2.24 W *Nom 70 mA/2.24 W *Nom 92 mA/2.84 W
* Max 145 mA/4.64 W * Max 145 mA/4.64 W * Max 198 mA/6.34 W
Temperature Range Certified -40 °C to +75 °C (-40 °F to +167 °F)/Operational -50 °C to +75 °C (-58 °F to +167 °F)
Field of View 120° horizontal/95° vertical
Spectral Range UV Radiation 185 to 260 nm (1850 to 2600 angstroms) | IR Radiation in the 4.4 µm range
Time Delay DIP switch selectable to 0, 3, 5, 7 seconds
Sensitivity Settings DIP switch selectable to 8, 16, 24 or 32 counts per second
Response Time < 6 seconds [depending on fuel source, fire size and distance]
Enclosure Material Red powder coated with clear anodizing, 6061 aluminum (optional 316 stainless steel), factory sealed housing
Humidity Range 0 to 95 % RH, non-condensing
Weight (with Swivel) 2.1 kg/4.5 lb (Stainless Steel option 3.4 kg/7.5 lb) - does not include junction boxes
Outputs 0 to 20 mA - Into a maximum loop Form C contacts rated 1 A at
impedance of 800 ohms 30 Vdc, 0.5 A at 125 Vac.
at 32 Vdc or 150 ohms at 11.0 Vdc Selectable energized/de-energized,
Non-isolated loop supply latching/non-latching Fire relay Fault HART®
relay factory set as energized/nonlatching,
cannot be modified
Certifications/Approvals CSA - Class I, Division 1, Groups B, C and D - Temperature code T5 - CANADA: Class I, Zone 1, Ex d IIB + H2 T5
ANSI/UL - Class I, Division 1, Groups B, C and D - Temperature code T5 - UNITED STATES: Class I, Zone 1, AEx d IIB + H2 T5
ATEX/IECEx - II 2 G Ex d II B+H2 T5 Gb INMETRO - Ex d II B+H2 T5 Gb
Factory Mutual (FM) 3260 NEMA Type 4X • IP66 - Enclosure ratings
Warranty Three years electronics/Two years sensors

ORDERING INFORMATION
UV/IRS 4–20 mA analog output
(JB-MPS-A/S included) ADDITIONAL APPROVALS: –X (ATEX/IECEx)
ENCLOSURE MATERIAL: Stainless Steel (–SS) [Aluminum is Standard]
UV/IRS-AR 4–20 mA analog output with a fire and fault alarm relay ADDITIONAL FEATURES: –H (Heated Optics)
(JB-MPR-A/S included)
UV/IRS-AH 4–20 mA analog output and HART® Ordering Matrix Example:
(JB-MPHF-A/S included)
UV/IRS-AHR-X-SS-H
UV/IRS-AHR 4–20 mA analog output and fire and fault alarm relays and HART® (Detector - Output - Additional Approval - Enclosure Material - Optional Features)
(JB-MPHFR-A/S included)

2 www.EmersonProcess.com/Safety
October 2014 UV/IRS Flame Detector

Separation Boxes & Accessories


Table 2 - Summary of Distances Table 3 - Immunity False Alarm Stimuli
Fuel Fire Size Typical Response Stimuli Immunity Range
n-heptane 1'' x 1'' < 11 s @ 140 ft Direct/indirect sunlight Total
Gasoline 1'' x 1'' < 6 s @ 120 ft (< 3 s @ 50 ft) 1500 W heater 10 ft
Methane 32'' plume < 6 s @ 100 ft Halogen, incandescent light 3 ft
Florescent light 10 ft
Arc welding 30 ft

Figure 1 - Example Field of View - Methane


32'' plume - indicated in feet - consult factory for other gases


15° 15° ¾'' NPT Detector
100
45° Head
30° 30°
45° 5.89''
80 45° 30°
60 0.25'' 2.96''
15°
40

20 0° 0.50'' 2.60''
15°
45° 30° 4.12''
Vertical Field of View
with Detector at 45°
VI Reflector UV Emitter
from Horizontal
Yellow Dot
Align with center IR Emitter
of Reflector IR Sensor
Red LED UV Sensor
Yellow LED Green LED

Table 4 - Termination Boxes


Class I, Division 1, Groups BCD - Class I, Zone 1 – Enclosure rated NEMA 4X, IP67 (See man-0081 for full specifications)
JB-MPS-A/S Termination box - analog output - switch (for remote MVI testing) and test jacks - aluminum or stainless steel

Table 5 - Accessories
LAT-120 Laser alignment tool assembly - used to define area of coverage for all flame detectors
AIR-SHIELD Air shield assembly (aluminum). supplied clean instrument air keeps lens clear in areas with heavy airbourne particulate
HPT-001 HART communicator port - intrinsically safe connection mounts to connected JB-MPHF and JB-MPHFR
FH-SHROUD Field of view restrictor anodized (red) for “S” series fire detectors (aluminum)
UN-MK-41 One inch pipe mounting kit - stainless steel
UN-MK-42 Two inch pipe mounting kit - stainless steel
UN-MK-43 Three inch pipe mounting kit - stainless steel
SSK-4 Sunshade kit/rain guard for “S” series flame, stainless steel - mounts directly to flame detector
SSK-1 Sunshade kit for “S” series flame, stainless steel - mounts directly to flame detector
TL-MP-KIT Universal test lamp kit - certified rechargeable hand-held unit - produces accurate fire simulation (UV and IR sources)
TL-MP-KIT-X Universal test lamp kit [ATEX] - certified rechargeable hand-held unit - produces accurate fire simulation (UV and IR sources)

www.EmersonProcess.com/Safety 3
UV/IRS Flame Detector Product Data Sheet
FGD_PDS_UV_IRS_Flame_Detector October 2014

©2014 Emerson Process Management. All rights reserved.

HEADQUARTERS The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount Analytical
Emerson Process Management is a mark of Emerson Process Management family of companies. All other marks are the property
Flame & Gas Detection of their respective owners.
2721 Hopewell Place NE
Calgary, Alberta, Canada T1Y 7J7 The contents of this publication are presented for information purposes only, and while
T +1 855-724-2638 (855 RAI-AND-U)
effort has been made to ensure their accuracy, they are not to be construed as warranties or
T +1 (403) 219 0688
T +1 866 347 3427 guarantees, express or implied, regarding the products or services described herein or their use
F +1 (403) 219 0694 or applicability. All sales are governed by our terms and conditions, which are available on request
[email protected] We reserve the right to modify or improve the designs or specifications of our products at any
www.emersonprocess.com/safety time without notice.

You might also like