GST-M200
Intelligent Fire Alarm
Control Panel
S24679
Description Installation Data
GST-M200 Intelligent Fire Alarm Control Panel (FACP) complies to The FACP can be flush-mounted or wall-mounted. Its
UL864 standard with features of easy installation, operation and appearance and the mounting method are shown here.
maintenance. All circuit boards are installed in a metal cabinet,
providing a complete fire control system for most applications.
Features and Benefits
● Single ring loop which meets Style 6 (Class A) requirement
● 240 addressable devices
● Optional 2 loops with additional loop card
● LCD display unit of 128 X 64
● History file with 1,000 events capacity
● “Walk Test”, silent or audible
● PAS (positive Alarm Sequence) per point (NFPA72 compliant)
● Auto silent timer option per NAC. The time duration is 5minutes.
● Password and key-protected nonvolatile memory
● Fully programmable from local keypad and from a pc
● Signaling Line Circuit (SLC) operates up to 4000 ft through
twisted pair with cross section 17AWG (1.02mm2)
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a
specific commitment or guarantee. We are constantly pursuing the improvement of product technology to improve product performance, for which
Gulf Security Technology Co., Ltd. we reserve the right to adjust the configuration and technical information of the related products without notice. In addition, the description of
system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special
http://www.gst.com.cn/en/index.asp circumstances in the real world, so the realization of the relevant product performance will depend on the professional investigation and analysis
and the design plan. Please contact us and we will be happy to provide you with professional advice.
Page 1/3 DS10103235-5
Terminals Typical Connections
Signaling Line Circuits (SLC) loop connection is shown below.
Cable Requirement
Loop: Minimum 17AWG, ideally 14AWG
Network: Minimum 17AWG, ideally 14AWG
Active Outputs: Minimum 16AWG, ideally 12AWG
All cables should be fire rated and follow local codes.
SLC (Signaling Line Circuit) LOOP (XT4 & XT6):
Style 6 (Class A) loop connection, provides communication
to addressable detectors.
Certificates and Compliance
NAC (Notification Appliance Circuit) XT8 (NAC1) & XT7
(NAC2):
Style Y (Class B) output port, outputs when there is fire ● Standards: UL864 / NFPA72
alarm, maximum 1.2A for each circuit.
● Certifications: UL
● WEEE & RoHS Compliant
ALARM (COM, NC, NO) (XT11): Dry contact output
energized in case of fire, rated 2.0A @ 30VDC.
FAULT (COM, NC, NO) (XT12): Dry contact output
energized in case of fault, rated 2.0A @ 30VDC.
Supervisory (COM, NC, NO) (XT13): Dry contact output
energized in case of abnormal conditions, rated 2.0A @
30VDC.
Auxiliary 24VDC (XT10): Power limited output, maximum
0.75A.
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a
specific commitment or guarantee. We are constantly pursuing the improvement of product technology to improve product performance, for which
Gulf Security Technology Co., Ltd. we reserve the right to adjust the configuration and technical information of the related products without notice. In addition, the description of
system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special
http://www.gst.com.cn/en/index.asp circumstances in the real world, so the realization of the relevant product performance will depend on the professional investigation and analysis
and the design plan. Please contact us and we will be happy to provide you with professional advice.
Page 2/3 DS10103235-5
Technical Specification Accessories and Tools
I-9102(UL) Intelligent Photoelectric Smoke Detector
Primary AC 120VAC/60Hz, 220VAC/50Hz I-9103(UL) Intelligent Rate of Rise and Fixed Temperature
Heat Detector
Power
Max. 2A
Consumption DZ-03(UL) Detector Base
DI-M9101 Intelligent Combination Heat Photoelectric Smoke
Backup Battery 20AH/24V
Detector
Loop Quantity 1 or 2 DI-M9102 Intelligent Photoelectric Smoke Detector
DI-M9103 Intelligent Rate of Rise and Fixed
Device per loop 240 per loop
Temperature Heat Detector
DB-M01 Detector base
NAC output 2 Class B, 1.2A@24VDC each
C-M9503 Loop Isolator
DC-M9504 Base Mount Short Circuit Isolator
Relay output Fixed, Alarm/Fault/Supervisory
I-M9300 Addressable Input Module
I-M9301 Addressable Output Module
Standby: 0.05A DI-M9319 Digital Zone Monitor Module
Auxiliary Power
Max.: 0.75A
DI-M9305 Digital Single Riser Output Module
DI-M9301 Digital Single Input and Output Module
Display 128 X 64, LCD DI-M9300 Digital Single Input Module
DC-M9503 Loop Isolator Module
Pc connection RS232
DI-M9204 Manual Call Point
GSTGMC-M2.2 Graphic Monitor Center
Network
RS485 or CAN
connection
Operating Accessories and Tools
0-49°C / 32-120° F ≤93%, non-condensing
Environment
Color Part No.: LC200
Red
Device name: Loop Card
Product No.: 20101370
Dimension 406(W) X 666(H) X 130(D) mm2
Part No.: P-9930
Device name: RS232
Communication Card
Product No.: 20101836
Order Information
Part No.: P-M9930ModBus
Device name: ModBus
Communication Card
Part No. GST-M200
Product No.: 20102531
Device Name Intelligent Fire Alarm Control Panel
Part No.: P-M9960A
Product No. 10103235 Device name: CAN Class A Network
Card
Product No.: 20102532
IMPORTANT: This publication is a generic version in which product information is shown for informational purposes only and does not constitute a
specific commitment or guarantee. We are constantly pursuing the improvement of product technology to improve product performance, for which
Gulf Security Technology Co., Ltd. we reserve the right to adjust the configuration and technical information of the related products without notice. In addition, the description of
system performance in this publication applies only to the usual situation. As a result, there may be a variety of unpredictable special
http://www.gst.com.cn/en/index.asp circumstances in the real world, so the realization of the relevant product performance will depend on the professional investigation and analysis
and the design plan. Please contact us and we will be happy to provide you with professional advice.
Page 3/3 DS10103235-5