26 Most Asked Electrical Engineering Interview Questions and Answers With PDF Compressed
26 Most Asked Electrical Engineering Interview Questions and Answers With PDF Compressed
Power factor (PF) is the ratio of working power (Real Power), measured in
kilowatts (kW), to apparent power, measured in kilovolt amperes (kVA).
Apparent power is also known as demand. The ideal power factor is unity,
or one.
It is because of the load with a power factor of 1.0 results in the most
efficient loading of the supply.
Static Capacitor
Synchronous Condenser
Phase Advancer
There are various ways that you can express or define electrical and
electronics engineering. But I would define it as:
A real ground is a zero potential point where all the current actually sinks to
the negative terminal of the supply.
Virtually ground means, it's not physically connected to Ground but the
voltage at that point/node is ‘0V’. The current doesn’t sink to the negative
terminal of supply from this point.
A motor starter is an electric device by which we can start and stop the
motor by turning ON/OFF. It provides protection to the motor against over
voltage and under voltage from the relay.
The main reason for using the starter is to limit the starting current and at
the same time, the starter function is to protect the motor.
8. What is the 'Q' factor in Electrical and Electronics
Engineering?
There is nothing called better. The only difference is in their use of the
application. Single-phase systems are actually more efficient than 3-
phase systems in low-power applications. Whereas, three-phase power
supplies are more efficient for large power applications.
In a star connection, the starting and the finishing point ends of the three
coils are connected together to a common point known as the neutral
point. But in Delta connection, there is no neutral point.
AC Resistance
DC Resistance
The circuit which is protected from the strokes of lightning with the help of
a protection device is known as a lightning arrester. When potentially
dangerous lightning strikes, the arrester activates and diverts the lightning
to the ground, where it will disperse harmlessly. It is installed near-critical
appliances or points of entry, such as an electrical panel or near a
generator or in buildings.
BDV test means the Breakdown Voltage Test. This test is performed for
verifying the dielectric strength of the oil of the transformer. Dielectric
Strength is the maximum capacity to resist the voltage of insulating oil.
This test demonstrates the dielectric Strength of Transformer Oil.
As per IEC, the minimum BDV of transformer oil should be 30 KV as per the
transformer oil BDV test standard.
For this, check your answer here: Why Transformers are Rated in KVA
instead of KW?
Slip in Induction Motor is the relative speed between the rotating magnetic
flux and rotating rotor expressed in terms of per unit synchronous speed.
The value of slip in induction motor is can never be zero.
The synchronous speed is the speed of the revolution of the magnetic field
in the stator winding of the motor. The synchronous speed is a given by
Ns=120f/P