ABB Document No.
1LIN600201-AKR
Rev-B Dated 26.11.2015
Page 1 of 3
40/50 MVA, 132/33 kV POWER TRANSFORMER
Schedule of Technical Particulars for Transformers
1. Name of the manufacturer : ABB India Limited
2. Service : OUTDOOR
3. kVA rating
a. HV winding (kVA) : 40000/50000 kVA
b. LV winding (kVA) : 40000/50000 kVA
4. Rated voltage (line voltage)
a. HV winding kV : 132 kV
b. LV winding kV : 33 kV
5. Rated frequency (Hz) : 50 Hz
6. Number of phases : 3 Phase
7. Connections
a. HV winding : Star
b. LV winding : Star
8. Connection symbol
a. HV-LV : YNyn0
9. Tapping
a. Range : +5% to -15% in steps of
1.25% for HV variation
b. Number of steps : 16 steps (17 Positions)
c. For high voltage variation/for : For High Voltage Variation
low voltage variation
d. Location of tap Switch : At Neutral end of HV winding
e. Type : On Load Tap Changer, In tank type
10. Reference ambient air temperatures
a. Maximum ambient air temperature (C) : 50C
11. Type of cooling : ONAN/ONAF
12. Temperature rise
a. Top oil (C) : 40C
b. Windings (C) : 45C
ABB Document No. 1LIN600201-AKR
Rev-B Dated 26.11.2015
Page 2 of 3
40/50 MVA, 132/33 kV POWER TRANSFORMER
Schedule of Technical Particulars for Transformers
13. Losses (kW)
a. No load loss at rated voltage on : 25 kW Max.
Principal tapping and at rated frequency
b. Load loss at rated current at principal : 150 kW Max.
Tapping at 75C (kW) @ 50 MVA (Including auxiliary loss: 1 kW)
(AC Sinusoidal current)
c. I2R losses shall be less than 85% : Yes
of load loss excluding auxiliary loss
14. Impedance voltage at rated current for :
the principal tapping @ 50 MVA base
a. HV –LV : 15 % (-0 to +10% tol.)
15. Auxiliary Loss (kW) : Included in Item 13 (b)
16. Insulation level
i. HV winding (kV rms / kVp) : 230 / 550 (kV rms / kVp)
ii. LV winding (kV rms/ kVp) : 70 / 170 (kV rms / kVp)
iii. HV Neutral (kV rms/ kVp) : 38 / 95 (kV rms / kVp)
iv. LV Neutral (kV rms/ kVp) : 70 / 170 (kV rms / kVp)
17. Equipment for ONAN cooling
a. State:
i. Radiators on main tank : Yes
ii. Radiators paint : Painted (Epoxy + PU paint)
iii. Radiator material thickness : 1.0mm
b. MVA rating at ONAN cooling : 40 MVA
c. MVA rating at ONAF cooling : 50 MVA
18. Details of on load tap-changer
a. Make : Easun MR
b. Current rating : 500 Amps
c. Type : High speed transition resistor type
(In tank)
d. Number of steps : 16 Steps
19. Terminal arrangement
a. HV : 145 kV, 800A, OIP Condenser Bushing
25 mm/kV, (Bare bushings)
b. LV : 36 kV, 2000A, Porcelain Bushing
25mm/kV (Bare bushings)
20. Sound pressure level : 78 dB (As per NEMA TR-1)
ABB Document No. 1LIN600201-AKR
Rev-B Dated 26.11.2015
Page 3 of 3
40/50 MVA, 132/33 kV POWER TRANSFORMER
Schedule of Technical Particulars for Transformers
21. Max. Flux density at rated
Voltage & frequency : 1.6 Tesla at 100% voltage
22. Max. Current density : 3.0 A/mm2 Max.
23. Paint shade : 631 of IS-5
24. Tank Plate Thickness
a. Cover/Bottom/Sides : 12 / 16 / 10 mm
b. Radiator sheet thickness : 1.0 mm
25 Approximate Weights
Core & Windings mass : 45750 kg
Tank & Fittings mass : 16200 kg
Oil mass : 18750 kg
Total mass : 80700 kg
Transport mass (Dry Air Filled) : 67100 kg
Oil Quantity : 21050 Liters
27. Overall dimensions (LxBxH) mm : 7000 x 5200 x 5750 Approx.
28. Transport dimensions (LxBxH) mm : 6450 x 2600 x 4100 Approx.
29. Reference standard : IS: 2026
Note:
1) All accessories are of reputed Indian makes only.
2) We have considered provision for NIFPES and NIFPES is not in our scope of supply.
Schedule-E1
GTP to be filled by the bidder for 220KV & 132KV class, 2 winding power transformers
1) Name of the Manufacturer and country of origin ABB India Ltd, Vadodara
2) Conforming to standard IS : 2026
3) Ratings: With ONAN/ONAF cooling-MVA 40/50
4) Rated Voltage Ratio: in KV 132/33
5) Temperature rise of top oil, in Deg. C 40
6) Temperature rise of winding measured by resistance : 45
With ONAN cooling, in Deg. C
7) Temperature rise of winding measured by resistance : 45
With ONAF cooling, in Deg. C
8) Vector group YNyn0
9) Magnetisation data at no load : Current in Amps from LV side 0.5 % of FLRC
10) Magnetisation data at no load : Power factor 0.2 Approx.
11) Magnetisation data at no load : 1.6 T
Max. flux density in Tesla at 100% rated no load voltage & rated frequency
12) Impedance at rated current and frequency at 75 Deg. C on rated MVA: 15 % (+10 % Tol.) @50
At normal tap, in % (HV to LV) MVA
13) Impedance at rated current and frequency at 75 Deg. C on rated MVA: 15.50 % Approx.
At Max. voltage tap, in % (HV to LV)
14) Impedance at rated current and frequency at 75 Deg. C on rated MVA: 14.60 % Approx.
At Min-voltage tap, in % (HV to LV)
15) Resistance at normal tap, at 75 Deg. C of : HV Winding (HV terminal to HV 0.459 ohms/ph Approx.
Neutral terminal per phase) (in ohms)
16) Resistance at normal tap at 75 Deg. C of : LV Winding (in ohms) 0.0246 ohms/ph Approx.
17) Efficiency at 75 Deg. C, taking into account input to cooling plant as loss : At 99.65 % approx.
100% full load and unity p.f - in %
18) Maximum efficiency and load at which it occurs : percentage of full load and p.f. 40.5 % load. Approx.
19) Regulation at full load & at 75 Deg. C : At Unity p.f.(lag), in % 1.42 % Approx.
20) Regulation at full load & at 75 Deg. C: At 0.8 p.f.(lag), in % 9.94 % Approx.
21) Noise level when energized at normal voltage and normal frequency at no load, in 78 dB(A)
db. As per NEMA TR-1
22a) Approximate weight : Core (in Kg) 27,200 Approx.
22b) Core Dimension Dia x Leg Height x Limb
pitch
670 x 1350 x 1410 App.
22c) Net core area in sq. metre 3339.40 cm2 (Approx.)
22d) Material of Laminations (Prime grade CRGO silicon steel M4 or higher) M4 or Better
22e) Watts per Kg of core material 0.98 App. @ 1.7 T
0.82 App. @ 1.6 T
22f) Building factor of the core 1.08 App.
23a) Approximate weight : HV Windings (in Kg) 6700 kg App.
Tap Winding weight also considered
23b) Approximate weight : LV Windings (in Kg) 3550 kg App.
23c) Total weight of copper (in Kg) 10,250 kg App.
23d) Type of Windings: HV Disc
23e) Type of Windings: LV Disc
23f) Conductor area in sq. cm and current density in Amp/sq. cm : HV 73 mm2 & 3A/ mm2 App.
23g) Conductor area in sq. cm and current density in Amp/sq. cm : LV 292 mm2 & 3A/ mm2 App.
24a) Winding insulation : HV : Type and Class/ Graded or Ungraded Graded
24b) Winding insulation : LV : Type and Class/ Graded or Ungraded Ungraded
24c) Total weight of Insulation (in Kg) 1300 kg Approx.
25) Approximate weight : Tank & Fittings (in Kg) 16200 kg Approx.
26) Approximate weight : Total weight of Transformer without oil (in Kg) 67100 kg Approx.
(Dry Air filled)
27) Approximate required quantity of oil, in Litres 21050 Ltrs Approx.
28) Type of transformer (Shell/Core) Core
29a) Details of Tank: Material for main tank (low carbon mild steel) Low carbon Mild steel
29b) Details of Tank: Type (construction) of the tank Conventional
29c) Details of Tank: Thickness of sides (in mm) 10 mm (Approx.)
29d) Details of Tank: Thickness of Bottom (in mm) 16 mm (Approx.)
29e) Details of Tank: Thickness of Cover (in mm) 12 mm (Approx.)
29f) Details of Tank: Thickness of Radiators (in mm) 1 mm (Min)
30) Details of HV Bushings: Make, Type,Voltage & Current Rating ABB/CGL
31) Details of HVN Bushings : Make, Type, Voltage & Current Rating CJI/Mileen
32) Details of LV Bushings: Make, Type ,Voltage & Current Rating CJI/Mileen
33) Details of LV Neutral Bushings: Make, Type, Voltage & Current Rating CJI/Mileen
34) On Load Tap Changing gear : Make, Type, Voltage & Current Rating Easun-MR / 72.5 kV, 500A
35) Cooling System: Total radiating surface, in sq. metre 38 m2 App. for Tank
Surface
36) Cooling System: Total number of Radiators/ Banks for transformer and 5 Nos. Radiator/ Bank
dimensions of tubes 2700 CC Approx.
37) Cooling Equipment : Fans : Make, Type & Rating (Details) Marathon Make,
24”, 7900 Air flow, 0.24kW
37 a ) Total no. of fans 6 Nos.
37 b ) No. of working fans 4 Nos.
37 c) No. of stand by fans 2 Nos.
38) Type and size of oil/winding temperature indicator and whether supervisory alarm 150mm Dial type OTI/ WTI
contacts provided 4 Contacts
39) Type of oil level indicator and whether supervisory alarm contact for low oil level 250mm Dial type MOLG
provided Low oil level alarm
40) Type and size of Gas operated relay and whether supervisory alarm and trip GOR-3 , 1 Nos. (80NB)
contacts provided and their ratings and Nos.
41) No. of Breathers provided (No.) Two,
1 No. For Main Tank Cons.
& 1 No. for OLTC Cons.
42) Drain valves required/ fitted, in Nos and size in mm. 1 No. & 80 NB
43) Filter Valve required/ fitted : in Nos and size in mm. 2 Nos. & 50 NB
44) Sampling valve required/ fitted : in Nos and size in mm. 2 Nos. & 15 NB
45) Type and Make of Pressure relief device Spring Type, Make : Sukrut
46) No. of Pressure relief devices per transformer unit (Nos.) 2 Nos.
47) Microprocessor based Transformer Monitoring cum Tap change Control System Pradeep Sales/ A-eberle /
(Type & Make) Dynamic Rating / MR
48) Optic fibre based Temperature measurement system (Type & Make) Make : FISO / Lumasens /
Opsens / Qualitrol
49)Rapid Pressure Rise Relay (Type & Make) Not Applicable
50) Whether T/F is suitable for Bi-directional Flow of power Yes
51) Maximum axial length of the transformer from the center line of the transformer As per spec, 4 meter
bay to the extreme edge of the transformer (including accessories) in metres.
52) Whether the transformer offered is type tested within last five years No, Type test shall be
conducted on 1st unit
53) Max. No load loss at rated voltage and frequency (core loss + dielectric loss), in 25 kW (Max.)
KW
54) Max. load loss excluding cooler loss at rated current at 75 deg. C for ONAF 150 kW (Max.) Including
rating, in KW Auxiliary Losses.
55) Cooler loss (Auxiliary loss) due to operation of running fans, excluding standby, in Included in cl. 54
KW Auxiliary loss : 1kW App.
56) Loss calculations Doc. 1LIN600208-AKR
57) Impedance calculations Doc. 1LIN600208-AKR
58) Short circuit calculations Doc. 1LIN600205-AKR &
1LIN600206-AKR
59) Cooling calculations Doc. 1LIN600207-AKR