A.K. Sawhney, Puneet Sawhney - (17) High Voltage Measurements and Testing
A.K. Sawhney, Puneet Sawhney - (17) High Voltage Measurements and Testing
and Testing
either due to switching operations or due to some The danger to the electric installations comes from
external causes and are usually damped high the fact that this over-voltage acts across the insulation
frequency oscillations. and that the time taken by the voltage to rise to its
It has been found that even though the porcelain peak value is very small, i.e., of the order of one
insulator has satisfactorily withstood the sustained millionth of a second. This imposes very severe
low frequency high voltage tests, it breaks down at a voltage stresses on the insulators, transformer windings,
much lower voltage at high frequencies owing to circuit breakers, bushings and other equipment. If the
increased dielectric loss and heating. Thus to insure voltage stress exceeds the strength of the insulation, a
reliable operation of insulators under disturbances flash over or a puncture results causing a short circuit
caused by switching and arcing earths, they must be and power outage. If a power arc follows, there may
subjected to high frequency tests. be disastrous results in damage to the equipment
whose repair may cost considerable amount of money
High frequency tests are also carried out for
insulators used for communication purposes. and time.
Frequencies ranging from several kHz to a MHz or Since power systems are frequently exposed to
more are used for such purposes. lightning strokes and consequent voltage surge,
impulse testing is necessary for coordination of
4. Surge or Impulse Tests insulation of the system in order that these surges are
These tests are recommended with the object of not allowed to damage the insulation of the important
determining the effect of voltage surges due to associated equipment.
atmospheric disturbances of very short duration on
electrical installations and their individual parts. The 17.2 TESTING APPARATUS
dangerous over-voltages to which power systems are The following testing apparatus is used for
exposed to are caused by lightning. Lightning may sustained low frequency tests. This apparatus is
produce an over-voltage on an overhead line either by usually common for all types of high voltage tests.
a direct stroke to the line or by an indirect stroke. An (z) high voltage testing transformer,
indirect stroke occurs when a charged cloud above
(zz) equipment for voltage regulation,
and near to the line, electrostatically induces charges
of opposite sign to that of its own charge, in the line. (zzz) control gear and protective devices and
These charges are bound as long as the cloud remains (zu) equipment for voltage measurement.
In addition to above, high voltage d.c. tests, high
frequency tests and impulse (surge) tests require some
other apparatus also which will be described along
with these tests later into this chapter.
circuits supplying the test transformer. The testing between testing transformer and the test object. In
transformers are also designed with compact and well Fig. 17.2(b) the active part of the transformer is placed
insulated high voltage winding. Therefore, a single in an isolating shell, thereby avoiding the use of a
phase testing transformer may be compared with a bushing. This construction of Fig. 17.2(b) reduces the
potential transformer as regards its construction. height of the transformer, however, the heat dissipation
A single phase core type H.V. testing transformer is impaired with this arrangement. In both the arrange
is shown in Fig. 17.2. The primary winding is usually ments, tanks are filled with high quality transformer
rated for rated voltages below 1 kV, but might often be oil as most of the windings are oil-paper insulated.
split up in two or more winding sections which can be The primary winding (I.v. winding) is close to the
connected in series or parallel to increase voltage iron core and is surrounded by the h.v. winding. This
regulation capabilities. The iron core is earthed and so arrangement reduces the leakage flux and increases
are the one terminal of each of the two primary and the coupling between the two windings. The shape
secondary windings. Two possible types of and cross-section of h.v. winding is a reference to
layout of this coil : the beginning (grounded end) of
the h.v. winding is located at a side close to the core,
and the end close to a sliced metal shield, which
prevents too high field intensities at h.v. potential.
Between both ends, the single turns are arranged in
layers, which are carefully insulated from each other
by solid materials like kraft paper sheets. Adjacent
layers, therefore, form co-axial capacitors of high
values. In order to keep the potential distribution
uniform under transient conditions, the capacitances
have to be made equal. This is done by using reduced
width of insulating layers with increasing diameters.
Thus, we have trapezoidal shape for the h.v. winding.
The transformers used for insulation testing need
not be of a high kVA rating because the current taken
by the transformer is limited by inserting external
resistances when the specimen under test breaks
down. However, transformers used for cable testing
are designed to deliver large currents owing to
capacitive (charging) currents drawn by the cables.
Attention must be paid to regulation and cooling
methods employed for such transformers.
Special constructional features are incorporated in
high voltage transformers to eliminate corona effects
as far as possible. The high voltage terminal of the
secondary winding and all other metal parts which
have a high potential with respect to earth, must be
constructed in such a manner that sharp comers are
avoided. This is done to avoid excessive voltage
Fig.17.2 High voltage testing transformers. gradients which cause corona. If this arrangement is
construction are shown in Figs. 17.2(a) and 17.2(b). In not possible, corona shields (which are usually
both cases the layout arrangement of core and windings aluminium spinnings) should be provided.
is the same. Figure 17.2(a) shows a grounded metal For voltages upto about 500 kV, a single
tank, for which a h.v. bushing is necessary to bring the transformer is used. For voltages above 500 kV ; the
high voltage out of the tank. Figure 17.2(b) shows another connection of two or more transformers in cascade is
arrangement, wherein the bushing is dispensed with, more economical than the use of a single transformer
and a co-axial cable is used for high voltage because at very high voltages a single-transformer
connection which results in improved connection tends to be of very large size and is thus costly.
516 Electrical and Electronic Measurements and Instrumentation
A general arrangement of two transformers the testing transformer or an available supply is being
connected in cascade is shown in Fig. 17.3. fed to the testing transformer. A separate alternator is
normally used except in the case of small testing
establishments which carry out routine testing work.
When a separate alternator is used, the voltage
regulation is carried out by variation of the alternator
field current.
In case a separate alternator is not used, the
voltage regulation is done :
(z) by insertion of resistance in the supply
circuit,
(zz) by insertion of inductance in the supply
circuit,
(zzz) by means of a tapped transformer,
(iv) by means of a variac, and
Fig. 17.3 Cascade connection of transformers.
(y) by means of an induction regulator.
A low voltage supply is given to the primary 1. Voltage control by variation of alternator
winding of transformer 1. The tank of this transformer field current. This method is applicable when a
is earthed. One end of the secondary winding of this separate alternator is used to supply the testing transfor
transformer is also earthed. A lead is taken from the mer. When the field current of an alternator is varied
other end of the secondary winding. This lead is taken its output voltage changes as shown in Fig. 17.4.
out of the transformer through a high voltage bushing
which provides insulation for full secondary voltage
between this lead and the tank (earth). The secondary
winding is tapped at a point and another lead is taken
out of the tank through the h.v. bushing. These two
leads are connected to the primary winding of
transformer 2. One end of the secondary winding of
transformer 2 is connected to the tank which is insulated
from earth for a voltage equal to the secondary voltage
of transformer 1. The other end of the secondary
winding of transformer 2 is taken out with the help of Fig. 17.4 Variation of output voltage of alternator
a lead passing through a high voltage bushing. This with field current.
lead forms the high voltage terminal of the transfor
The alternator used should give a sinusoidal
mer. The output voltage for test purpose, is taken
output voltage at no load and the distortion caused
between the h.v. terminal and earth. This is equal to
under load conditions should be small. This requires
the sum of the secondary voltages of the two transfor
the length of air gap of the machine should be large, as
mers. The output voltage can be increased further by
in that case the armature reaction is limited and also
addition of more transformers connected in cascade.
there is no saturation owing to increased reluctance
1 7.2.2 Voltage Control offered by a large air gap length.
It is very important in high voltage measurements The armature winding of the alternator should be
that the output voltage which is fed to the test specially designed and also the number and shape of
specimen is varied smoothly. Any abrupt or crude slots should be properly regulated so that the output
changes in voltage will impress voltage surges on the voltage wave shape does not contain lower order or
specimen and will also affect the accuracy of higher order (slot) harmonics.
measurements. It is equally important that the voltage The field current of the alternator is directly
regulating device should not distort the waveform of varied in the case of small alternators but in the case of
output voltage. large alternators, the field current of exciter is varied,
The method of voltage regulation depends upon which varies the output voltage of the exciter thus
whether a separate alternator is being used to supply varying the alternator field current.
High Voltage Measurements and Testing 517
Figures 17.5 and 17.6 show the two connections This is because a smooth voltage regulation from zero
employed. A potential divider arrangement is used in to full voltage is obtained. This method is usually used
both the cases and the connections are so arranged for small capacity sets of about 2-3 kVA rating.
that a small current in the reverse direction to the
normal one may be obtained. Thus for this arrange
ment zero output voltage is obtained. Referring to
Fig. 17.4, the output voltage due to residual magnetism
is OA and a field current OB (in the reverse direction)
is required to bring the output voltage down to zero.
The method suffers from many disadvantages : 5. Voltage control by variac. A variac may be
(z) The size of the coil is large when the power used to supply the h.v. transformer. The arrangement
to be handled is large. is simple and is shown in Fig. 17.10. The method has
(zz) Due to non-linear characteristics of the iron the advantage that it gives smooth voltage regulation
core of the choke coil the input voltage from zero to full value of voltage.
waveform is distorted.
(zzz) The power factor of the load is usually
leading as test specimens are insulating
materials and therefore the use of a choke
coil results in an increase in the input voltage
to the transformer with increase in load.
4. Voltage control by tapped transformer.
Figure 17.9 shows the arrangement for voltage
regulation with the help of a tapped transformer. An
inter- mediate regulating transformer is used for the Fig. 17.10 Voltage control by Variac.
purpose of tappings. The primary winding of the
tapped transformer is supplied from a l.v. supply. The 6. Voltage control by induction regulators. An
secondary winding of this transformer is provided induction regulator may be used to give a smooth
with a number of tappings with the help of which the voltage regulation. The voltage is varied by changing
voltage fed to primary of the h.v. testing transformer the position of secondary winding with respect to
can be varied. In order to avoid surges due to sudden primary winding. The connections are shown in
opening of secondary circuit of regulating transformer Fig. 17.11. If the primary and secondary windings of
when the tapping switch is moved, two contact an induction regulator have equal number of turns,
brushes are used which make contacts with adjacent the voltage supplied to the primary winding of the
tapping points. A buffer resistor or a reactance coil is high voltage transformer can be varied from zero to
used between the two contact brushes to prevent the 2 E where E is the induced voltage of each winding of
short-circuiting of a portion of the secondary winding induction regulator.
by the brushes.
Fig. 17.9 Voltage control by a tapped transformer. Fig. 17.11 Voltage control by induction regulator.
In order to obtain smooth voltage regulation a The advantages of this method are :
large number of tappings should be used. The
(z) It gives a gradual and a smooth voltage
advantages of this method are :
regulation.
(z) It has a high efficiency.
(zz) It can be used for all loads and power factors.
(zz) It gives a very small distortion of voltage
(zzz) Voltage waveform distortion can be avoided
waveform.
by using a carefully designed induction
The disadvantages are : regulator.
(z) The voltage regulation is not smooth unless (m) This method of voltage regulation is
a large number of tappings is used. particularly suited for cable testing
(zz) The equipment becomes expensive if the equipment owing to its adaptability for any
power to be handled is large. load.
High Voltage Measurements and Testing 519
17.3 CONTROL GEAR AND PROTECTIVE DEVICES The protective devices on the high voltage side of
the test transformer are :
The primary side of the high voltage transformer
is provided with : (?) Protective resistances. When the specimen
under test or sphere gap breaks down, voltage surges
(z) Main switch. It is required to isolate the testing are produced. In order to protect the high voltage
apparatus from the supply. transformer from the effects of these surges a high
(zz) Fuses. resistance or a choke is connected in series with the
secondary winding of h.v. transformer. The resistance
(zzz) Automatic circuit breaker. It is used to
is about 0.5 Q/V.
protect the testing apparatus from damage in case of
failure of supply. It is provided with a no volt coil so (z’z) Sphere gaps. A sphere gap is connected
that it automatically trips if the supply goes off. across the high voltage transformer. In case of over
voltage, the sphere gap breaks down and thus
(z’v) Over-voltage relay. It is used to protect the bypasses the surge. In order to prevent pitting of
apparatus from the effects of over voltages. This relay sphere gaps, a resistance is used to limit the current at
short circuits the no volt coil of the circuit breaker in breakdown. This resistance is about 1 ohm per volt so
case of over voltage and therefore the latter trips that the current is limited to 1 ampere at breakdown.
automatically isolating the apparatus from the Some difficulties arise in H.V. testing at power
supply.
frequencies and these are primarily due to corona effect.
(u) Interlocks. The interlocking arrangements are Corona. This is a phenomenon which occurs
used : when the voltage gradient at the surface of a high
(a) to ensure that the primary winding of h.v. voltage conductor exceeds the breakdown strength of
air. This results in ionization of surrounding air
testing transformer is switched on to a low
accompanied by a faint glow and hissing sound.
voltage,
Corona results in power loss and distortion of
(b) to make it impossible for the operator to waveform. Thus it influences the breakdown and
enter the h.v. testing enclosure while the flash-over voltages on account of surges in the circuit
supply is on. This is in the form of a gate and because of presence of ionized air in the test room.
switch. The supply to the primary winding
Steps should be taken to eliminate corona as far as
of h.v. testing transformer is through a gate
possible. Since the voltage gradient at the surface
operated switch. When the gate is open, the
decreases as the diameter increases, the conductors
switch is off and therefore the operator can
used in high voltage circuits should be made much
safely go inside the enclosure.
more larger in size than is necessitated by current
(yi) Earthing. All the metal parts which should carrying considerations. Also care should be taken to
be at earth potential must be earthed. This includes avoid sharp bends and small radii of curvature.
transformer tanks, metal framework of switchgear, Figure 17.12 shows a simple diagram of
enclosure and one end of each transformer connections of a high voltage testing set up using a
winding. separate alternator.
17.4 EQUIPMENT FOR VOLTAGE MEASUREMENT Another method of improving the uniformity of
The high voltages encountered in practice involve the field is to insert, between the main plates, a series
a large range of frequencies extending from zero in the of intermediate electrodes. A capacitance divider, thus
case of d.c. to very high frequencies of surges caused formed, preserves a uniform distribution of voltage
by lightning. Most methods of measurement of high between plates.
voltages described in the following pages are suitable An inherent feature of these instruments is the
for measurement at comparatively low frequencies. tendency for the electrostatic force to make the disc
However, some of them give satisfactory results even unstable so that an adequate elastic or electromagnetic
for surge frequencies. force trying to keep the disc in coplanar position is
The methods of measurement of voltage are necessary. Also when alternating voltages are being
divided into two categories : measured, care must be exercised to ensure that the
forced vibrations due to pulsating component of force,
(?) Methods used for measurement of rms values of
are minimized.
voltage. We are interested in measurement of
rms values of voltage because not only they The electrostatic force is usually balanced by an
have a direct bearing on the dielectric losses, opposing gravitational or electro-magnetic force. The
but through internal heating they have a lack of balance can be detected by the displacement of
close connection with dielectric constant also. the disc from its coplanar position and therefore very
sensitive methods of measuring displacement are
(n) Methods of measurement of peak values of
required in order to achieve a high degree of accuracy.
voltage. The measurement of peak values of
Automatic adjustment of balance can be done through
voltage is also necessary because of the fact
a servo-loop, the actuating signal is obtained from the
that the actual breakdown or flash-over of
output of the displacement detector. A disc may be
the specimen under test is dependent upon
loaded with a weight of approximately 90 g, or
the peak value of the applied voltage.
alternatively 360 g, corresponding to the attractive
17.4.1 Measurement of R.M.S. Values of Voltage forces on the disc at electrostatic stresses of 5 kV/mm
and 10 kV/mm and a servo-system adjusts the
1. Electrostatic Voltmeters electrode spacing till the appropriate stress is
These instruments have been described in details obtained. The voltage is then read directly from a
in chapter 9, page 282. The following instruments may micrometer scale which indicates the spacing between
be used for measuring rms values of high voltages. the electrodes.
(/) Attracted disc voltmeter. At high voltages, the Alternatively, with a given electrode spacing the
design of the attracted disc voltmeter becomes servo-system can be arranged to adjust the current in a
difficult. A large spacing between plates is necessary coil coupled to the disc. This current produces an
in order to avoid flash-over and corona. electromagnetic force which balances the electrostatic
The simple expression for voltage given by Eqn. 9.84 force and in addition stabilizes the disc powerfully in
(page 286) does not hold good and corrections have to the coplanar position. The electromagnetic system is
gravitationally calibrated.
be applied.
(n) Attracted sphere voltmeter. The tremendous
In order to overcome the above difficulty, an
classical theoretical analysis of the electrostatic field
absolute high voltage attracted disc voltmeter has
between two spherical electrodes has led to the
been evolved by making use of gas at high pressure or
development of Attracted Sphere Voltmeters. The
a high vacuum, in the region between plates. Both the
voltage measurement is based upon measurement of
designs make it possible to reach high field intensities electrostatic force between two spheres. A wide
than with air at atmospheric pressure ; consequently variety of sphere voltmeters has been produced
the spacing between the plates can be decreased with wherein forces amounting to 4.2 to 7.5 N are produced
no resultant side effects. with direct voltages which will flash over gaps of
In high vacuum, for example, a voltage difference 100 mm and 500 mm between spheres of 1 m diameter.
of 300 kV requires a spacing of only 3 cm. At the same The attractive forces between the spheres can be
time, however, the small spacing reduces the measured with a stiff elastic support. The errors
tolerances in flatness and parallelism of the plates. involved are less than 1% for voltages as high as 1 MV.
Moreover the attracted electrode needs close Another method of measuring the electrostatic
adjustment to the plane of guard ring. force is to observe the change produced in the period
High Voltage Measurements and Testing 521
of oscillation of one of the spheres, swinging over a This method assumes that the ratio of transfor
small arc. The voltage is proportional to mation remains the same (= ri) irrespective of the load
and power factor on the secondary side. Owing to this
VF? reason, the method though simple, gives wrong results.
where f = oscillating frequency with applied
voltage,
and f0 = oscillating frequency without applied
voltage.
The values of f and f do not differ greatly as the
restoring force is gravitational in nature. However, by
using a rigid pendulum, the mass of the sphere can be
counter-balanced. The value of f is, therefore, reduced
nearly to zero so that frequency of oscillations, f, is ..A'""' '.
approximately proportional to the applied voltage. Fig. 17.13 Measurement of rms voltage by
(zzz) Oscillating ellipsoid voltmeter. This is transformer ratio method.
another system for which the attractive force between In some high voltage transformers, a separate
two electrodes can be obtained with a high degree of voltage coil is provided whose voltage is measured
accuracy from the period of oscillation of an electrode. with the help of a low voltage voltmeter. The
The voltage to be measured is applied to a pair of secondary voltage in this case is given by :
discharge free parallel plate pair of electrodes lying in vs=(Ns/Nc).vs
vertical planes and a small conducting electrode of
where N$ = number of turns of the secondary
accurate prolate spheroidal shape is suspended at its
winding,
mid-point by a long unspun silk thread so that it
hangs in the uniform field between the central parts of Nc = number of turns of the coil,
the plates with its long axis horizontal. When a voltage and Vc = Voltage across the coil.
is applied an electrostatic field is produced due to This method cannot be used for cascade arrangement
which charges of opposite polarity and of calculable of transformers. It gives an accuracy of 1 to 2 percent.
magnitude accumulate on the two ends of the
The advantage of this system lies in its
ellipsoid. The ellipsoid, therefore, tends to align its
convenience as a means of taking continuous reading
long axis along the direction of the field. The ellipsoid
after being calibrated by comparison with one of the
oscillates about its final position on account of the
direct systems of measurements.
moment of inertia. The controlling torque produced
by the silk thread is very small. Therefore frequency of 3. Potential Divider Methods
oscillations is approximately proportional to the
In this method a potential divider is connected
applied voltage. The constant of proportionality can
across the secondary winding (high voltage winding)
be calculated from the mass and dimensions of the
of high voltage testing transformer and a definite
ellipsoid and the geometry of the plate electrodes.
fraction of secondary voltage is measured by a low
The disadvantage of the ellipsoid voltmeter is that voltage electrostatic voltmeter. A C.R.O is used to
the average electrostatic stress is much smaller than
obtain records of peak values of surge voltages.
that which can be obtained when either attracted disc
or attracted sphere voltmeters are used. This is on Two types of potential divider arrangements are used:
account of the concentration of the stress at the tips of (z) Resistance potential divider, and
the ellipsoid. (zz) Capacitance potential divider.
2. Transformer Ratio Method Both these potential divider methods have been
In this method the primary voltage of the high described in Chapter 9 (see pages 286).
voltage testing transformer is measured with a low We should use these methods only when either :
voltage voltmeter (Fig. 17.13) and the secondary (a) the connection of the low voltage voltmeter
voltage is obtained as : has negligible effect on the voltage distri
bution, or.
where Vs,V = terminal voltages of secondary (F) appropriate allowance for low voltage
and primary windings respectively. voltmeter impedance is made in computing
n = turns ratio. the potential divider ratio.
522 Electrical and Electronic Measurements and Instrumentation
(i) Resistance potential divider. Upto about 10 kV (i) They are simple in construction.
an electrostatic voltmeter can be used successfully (ii) They are free from heating effects.
with an unshielded resistance potential divider with (iii ) They are comparatively free from effects o
resistance units wound on flat insulating sheets. stray magnetic fields and can be easily
However, for voltages above 10 kV, resistance shunted.
potential divider requires careful electrostatic
shielding to minimise stray capacitance effects. For
ideal shielding each point on the resistance should be
shielded at its own potential, but in practice it is
possible only to divide the total resistance Into a
number of equal sections each at its average potential.
Figure 17.14 shows an arrangement where the shield
potentials are correctly maintained by an auxiliary
potential divider.
Main potential voltmeter
s Q
Now if C2 is very large as compared to C^,
17 ^"1 + ^"2
Vs=~L^V
Suppose ZL is the impedance of the load connected moving iron or electrodynamometer milliammeters
on the secondary side as shown in Fig. 17.16(D). The for measurements of voltages upto 100 kV. Moving
requirement that transformation ratio V / v remains coil instrument is useful for d.c. only while the others
the same irrespective of the load on the secondary are used for measurement of rms values of a.c. voltages.
winding, the value of inductance L should be such that
it gives resonance with CT and C2 in parallel.
or oj2L= 1/(C1 + C2)
This is explained as under :
At load, V = 2 (I1 + I2) _ JL
coC1 coC2
Voltage across load
T7 r-f(L+i9) Fig. 17.17 Measurement of voltage by
r=vi- -- y 2 standard impedance method.
5. Potential Transformer Method
i,
- L + coL L Modern potential transformers have accuracies
wC2 1 comparable with those of good potential dividers. In
.'.Voltage ratio comparison with potential dividers they have the
advantages that:
(?) the indicating instrument is isolated from
the high voltage circuit,
(zz) within limits, the instrument impedance has
negligible effect on the ratio of transfor
qtq + C2)+I2C2 mation.
For measurement of very high voltages two stage
q [i1 + i2co2lc2] reduction by means of a combination of a potential
Substituting the value of divider and potential transformer proves very useful.
cd £ = 1/(^4- C2)in the above expression Potential transformers may be used with electro
V [I1(C1 + C2)+I2C9](C1 + C2) dynamometer, moving iron, or electrostatic instru
v C1[I1(C1 + C2)+I2C2] ments for measurement of rms values of a.c. voltages
upto 200 kV.
_ q + c2
The range may be extended by capacitor potential
transformers (see Art. 10.6.7 page 335)
, . V Ct + q
or voltage ratio — = —----- -
v q 17.4.2 Measurement of Peak Values of Voltages
1. Transformer ratio method. The measurement
This is the same value of ratio as we obtain on no load.
of rms value of voltage with this method has already
4. Standard Impedance Methods been explained. In order that the peak value of
A standard high impedance is connected across secondary voltage be measured, we must determine
the terminals of the high voltage winding. The the secondary voltage waveform. From the voltage
impedance may be a standard air capacitor or a high waveform the crest factor is evaluated.
_ . l peak voltage
resistance. The current flowing through the impedance Crest factor = ------------- —
may be measured by a thermocouple ammeter rms voltage
(Fig. 17.17) by measuring voltage across a known or peak voltage of secondary winding
resistance ; using an electro- static voltmeter or by = crest factor x nV
using a valve voltmeter.
where V? = rms voltage of primary winding,
Secondary voltage Vs = i x Z
and n = ratio of secondary to primary winding
where Z = impedance connected across the h.v. turns.
winding terminals
Sphere gaps. The breakdown voltage of a
2.
The impedance may be a series resistor. Series spark gap between two metal spheres may be used as
resistors are used in conjunction with moving coil, a measure of voltages upto the highest encountered in
524 Electrical and Electronic Measurements and Instrumentation
3. Rectified capacitor charging current method. v = Vm sin cot where V)n is the peak voltage.
This method depends upon the fact that the average Charging current at any instant
charging current of a standard air capacitor is V
proportional to the peak voltage. This charging i= - sin (cof + it / 2) = V wC cos (of
1 / (oC m
current is rectified and its average value is then
measured by a permanent magnet moving coil Referring to Fig. 17.20, average charging current
milliammeter or a d'Arsonval galvanometer.
Figure 17.19 shows the circuit for measurement of 2 t/4
J ^„wCcos(ofrff = 4Vm/C
peak voltage. C is a high voltage compressed gas
1 0
capacitor across which practically whole of the high
voltage is dropped. Specially designed rectifiers may
v T-
be used for the rectification of alternating currents. A
is the milliammeter for measurement of average
charging current. Thus V„=l„,/4Cf ...(17.1)
property that they commence to glow when the potential gradient rises above a critical value. Thus
voltage applied to them reaches a definite value called peak voltage of the measured supply must exceed the
a.c. striking voltage. critical voltage for part of a cycle before an indication
is obtained. The part of the cycle where voltage is more
than the critical is only effective in the cooling
[see Fig.l7.22(b)]. It follows that the instrument is not a
true peak voltmeter and a knowledge of waveform is
essential in order to determine the value of peak voltage.
Resistance potential dividers can be used. The complications with use of high frequencies and there
series resistance method is also satisfactory when a fore normally alternators are used to supply power at
high resistance is used in series with a current 50 Hz which is converted into d.c. by rectifiers.
operated d.c. instrument. The rectifying circuits commonly used are shown
in Figs. 17.24 to 17.27.
17.4.4 Measurement of Instantaneous Voltage
High voltage cathode ray oscilloscope with
suitable potential divider where necessary, is used for
measurement of instantaneous values. A treatment of
cathode ray oscilloscope is given in Chapter 21.
potentiometer
For the sake of clarity many essential parts of the Therefore the rectifier charges the capacitor Cj to a
rectifying equipment like smoothing circuits, voltage + Vm. The voltage of the end 'a' of transformer
protective resistors to limit the current during winding varies between + V and -V with respect to
breakdown of test specimen have not been shown. earth and therefore the voltage of point A oscillates
Figure 17.24 shows a single phase half wave between 0 and +2 V with respect to earth E.
circuit. Figure 17.25 shows a bi-phase half wave Nov/ if we connect a capacitor C2 as shown in
circuit. Figure 17.26 shows a full wave circuit and Fig. 17.28(b), this capacitor will be charged to a voltage
Fig. 17.27 shows a voltage doubler circuit. +2Vm through rectifier 2.
For high voltage working these circuits require The complete Cockcroft-Wal ton circuit is shown
many special constructional features particularly with in Fig. 17.29. It is in fact a cascade connection. As the
regards to the insulation problem. potential of A varies between zero and +2 Vm, F being
In the circuits shown the capacitor charges upto at a steady potential of +2 V the voltage applied to
peak of the voltage applied across it. It is prevented capacitor C3 via rectifier if C3 were uncharged would
from discharging through the transformer by the vary between zero and +2 Vm. Thus C3 charges upto
the peak of this voltage i.e., +2 V)n. The potential of B
rectifier but can discharge through the load (which is
therefore oscillates between +2-Vm and +4Vm. This
represented by a resistance).
gives a voltage of +2 Vm across C4, as F is already at a
These circuits are used upto a voltage of 100 kV or potential of +2V Thus C4 charges to a steady
more in some cases. potential of +2 V. The potential of G with respect to
earth becomes +4Vm. The portion BCHG of the circuit
17.7 COCKCROFT WALTON CIRCUIT
is a 3rd stage and output of the whole circuit is +6V„r
This circuit is used to get very high voltage a.c. For an n stage circuit, the output voltage would be
supply without using high voltage transformer of +2 n Vm. Therefore if we go on adding stages, higher
more than 100 kV rating. and higher voltages can be obtained.
Let us consider the circuit shown in Fig. 17.28(a).
The peak voltage on H.V. side of the high voltage
transformer is V.
The charging and leakage currents are indicated Figure 17.32 shows the connections for testing a 3
by a milliammeter as shown. A resistance of about core cable with two rectifiers.
0.25 MQ is connected in the anode circuit for
protection against surge effects.
tends to move towards the negatively charged Table 17.2 D.C. and A.C. voltaqes for cables
electrode (the sheath or one of the cores, depending Standard test Average thick
Working Voltage Ratio
upon the test), when a d.c. voltage is applied. ness of
Voltage D.C./A.C
Although the amount of such moisture is usually A.C. D.C. dielectric
small, it may yet be sufficient to cause breakdown due 11 kV 20 kV 30 kV 1.5 7.62 mm
to its concentration near the negative electrode. If the
22 kV 44 kV 75 kV 1.71 10.2 mm
applied voltage is alternating no such movement of
moisture occurs, the moisture remaining uniformly 33 kVx ' 66 kV 100 kV 1.52 12.7 mm
distributed. Again, breakdown may occur when
testing cable-samples due to surges which are 17.9 LOCALIZATION OF FAULTS IN
produced by spark-discharge and corona effects at the HIGH VOLTAGE CABLES
cable ends. These effects are more severe with a.c. than The resistance presented by high voltage cable
with d.c. under fault conditions is very high and therefore such
faults cannot be located with accuracy by the methods
For these reasons it is obvious that there are other
already described in chapter 14. In high-voltage cables
considerations beyond mere equivalence of potential
breakdown occurs at the time of application of the
gradient which must determine to what alternating
high voltage especially when the oil in the cable and
voltage a given direct voltage is equivalent from the
cable joints breaks down and therefore presents a low
point of view of insulation breakdown.
resistance. However, when the applied voltage is
N.A. Allen gives a table showing the ratio of d.c. withdrawn, the oil recovers its insulating property and
to a.c. test voltages, quoted by various authorities as the cable again presents high insulation resistance.
giving an equivalent breakdown test upon cables and The fault resistance may be reduced by a continued
dielectrics. For paper-insulated cables, although a application of the high voltage so as to carbonize (or
d.c./a.c. ratio of 2.5 has been used, Allen suggests that burn out) the insulation at the point of the fault. After
a ratio of 1.5 to 2.0 would be more satisfactory. the insulation resistance is so reduced ; ordinary
Owing to the fact, also, that this ratio increases loop-tests may then be applied to determine the
with increasing insulation thickness, he suggests the position of the fault.
adoption of a ratio 1.5 for cables upto 33 kV, and a A more satisfactory method which is generally
ratio of about 2.0 for voltages above this. Table 17.2 adopted is to perform the Murry loop-test at high
gives the d.c./a.c. ratio usually adopted by cable voltage obtained from either half-wave or full-wave
makers. rectifier. Figure 17.34 gives the circuit arrangement for
localization of faults in high-voltage cables. The Undamped high frequency voltages upto a
rectified supply at about 60 kV is obtained from a frequency of 30 kHz may be produced by alternators.
high-vacuum diode. A higher voltage, if desired, may Arc generators can also be used for the purpose but
be obtained with two valves. A step up high voltage they have the disadvantage that smooth voltage
transformer is used to feed the rectifier. A current regulation is not possible.
limiting high resistance and a milliammeter are Usually electronic circuits are used for production
included in the supply circuit for the limitation and of high frequency high voltages. Equipments have
measurement of the fault current respectively. An been developed which give an output of 150 kV and a
electrostatic voltmeter is used to measure the voltage frequency of 100 kHz.
at the junction point of the ratio arms. A loop is made 2. Tests with dumped high frequency oscilla
connecting together the faulty and sound cables with tions. Figure 17.35 shows a circuit for production of
the help of a short circuiting link. For varying the ratio high frequency damped oscillations. This circuit uses
arms (P, Q) a highly insulated slide-wire, having a a Tesla coil which is in the form of a high voltage
sliding contact which can be operated by a long transformer. The capacitor C;, on the primary side is
insulating handle is used. 'The spark gap is used for
the protection of the galvanometer. The procedure
adopted for the test is detailed below : The circuit is
energised and the tap at the primary of the H.V.
transformer is adjusted to give a low fault current of
the order of 5 mA at the time of break down of the
cable. The bridge is balanced by varying P/Q ratio. The
tap of the primary of H.V. transformer is then changed
to increase the fault current to about 50 mA. The
bridge is rebalanced. It may be mentioned at thp time Fir. 17.35 High frequency high voltage testing.
of break-down, a very large drop of voltage occurs
charged to a potential which causes a trigger gap to
across the protective high resistance and therefore the
breakdown with the result that the capacitor
voltage across the cable is low. However, if the fault
discharges. Due to this discharge, a train of damped
clears, the voltage across the cable would rise
high frequency oscillations is produced in the circuit
suddenly and it is on this account highly insulated containing Cp, trigger gap and the primary of the Tesla
slide-wire is used for the safety of the operator. coil. The charge and discharge of capacitor C takes
The position of the fault can be obtained using place two times in one voltage cycle. Therefore, there
equations given for Murray loop test in Chapter 14. will be 100 trains of frequency oscillations (Fig. 17.36)
(see Eqns. 14.53 and 14.54, on page 446) in a second for a 50 Hz supply.
Since the primary winding of the Tesla coil carries Normally 1/50 ps impulse voltages are used for
an oscillatory current, oscillations are induced in the testing. This voltage indicates that it rises to its peak
secondary winding. If the primary and secondary value in 1 ps and falls to 50 percent of its peak value in
windings are tuned i.e., L Cp = LCf the frequency of 50 ps.
oscillations in the secondary winding will be the same 2. Impulse flash-over voltage. 50 percent impulse
as in the primary. flash-over voltage : It is the peak value of that impulse
These damped high frequency oscillations are voltage which causes flashover of the object under test
impressed upon the test specimen as shown in for about half the number of applied impulses.
Fig. 17.35. 3. Impulse puncture voltage. The impulse
A sphere gap is used for voltage measurement puncture voltage is the peak value of that impulse
and a cathode ray oscilloscope may be used to record voltage which causes the puncture of the specimen
the waveform of secondary voltages of the Tesla coil. under test when puncture occurs on wave tail and is
the value of the voltage at the instant of puncture
17.11 SURGE (IMPULSE) TESTING when puncture occurs on the wavefront.
The following terms are defined related to surge 4. Impulse ratio for flashover. The impi
testing. ratio for flashover is the ratio of impulse flash
1. Impulse voltage. An impulse voltage is a voltage to the peak value of power fre
unidirectional voltage which rises rapidly to its flashover voltage.
maximum value and falls more or less rapidly to zero. The impulse ratio for puncture can al.'
An impulse voltage is shown in Fig. 17.37. in a similar manner.
Cj,C2,C3... are capacitors which are connected in parallel with highest resistances and rlzr2... etc.
between them g0,g1,g2 are the trigger spark gaps.
The capacitors are charged, in parallel, from a high voltage transformer through a rectifying device. At a
certain voltage depending upon their setting, the gaps break down and connect the capacitors in series.
The operation of the circuit is explained below :
The gaps g0,g]zg2 etc. are set to spark one after another. Gap gQ sparks when the charging voltage has
attained a voltage + E. All the capacitors will therefore charge in parallel through the resistors shown until they
reach a potential of + E. Their lower plates are at earth potential because of their connection to ground through
resistances.
g
High Voltage Measurements and Testing
As soon as a voltage + £ is attained, gap g() breaks down and there is momentary redistribution of charge
potential on capacitor C.. Its top plate falls to zero potential and its lower plate potential becomes -£ suddenly.
Therefore a potential of 2 £ (i.e., -E to +£) suddenly appears across gap g] and this gap then instantly breaks
down. This process is repeated, the potential of lower plates of capacitors of successive stages becoming
-2E,-3E,...,-nE, if there are n stages.
Thus if there are n stages, output voltage is -n£ if the charging (input) voltage is + £. Figures 17.43 and 17.44
show the charging and discharging circuits respectively.
/4 rl B r2 c r3 £ r4 E
__ AAA____ . __ AAA __ AAA
• t___VVv
AAA._
Ci C2 c5
H H ‘ II
Dielectric strength is not proportional to higher than the flash-over voltage. This means that in
thickness, but is relatively greater for thin sheets. It is case of a sudden over-voltage, the air at insulator
also a function of time of application, being greater surface breaks down earlier and thus the insulator is
lesser is the time. not punctured and is saved from total destruction.
Measurements of capacitance, permittivity, Therefore flash-over tests are very important in the
dielectric loss and loss angle of insulating materials is case of porcelain insulators.
very important. These measurements are usually The flash-over voltage for an insulator depends
made at high voltages. All these quantities vary with upon :
voltages used for measurements and for some (z) barometric pressure,
applications values measured at low voltages are of
(z’z) temperature,
no use at all. Schering Bridge explained on page 489
(zzz) shape of the electrostatic field,
is normally used for determination of these
quantities. (zu) humidity,
(u) nature of contact between electrodes and
17.13 HIGH VOLTAGE TESTING OF CABLES insulator.
The tests carried out in the field after the installa The various flash-over tests applied are :
tion of cables have been explained earlier in this (z) 50 percent dry impulse flash-over tests with
chapter. Here we will describe some acceptance tests 1/50 ps impulse voltage.
which convince the customer about the reliability of (zz) Dry flash-over.and dry one minute test. In this
the cable when put in service. The dielectric loss and test the voltage is gradually raised to a
loss angle of a cable rather than its breakdown specified value in approximately 10 seconds
strength are an index of its reliability in service. and is maintained for one minute. The
Therefore measurements of these quantities is voltage is then gradually raised until a
essential. flash-over occurs.
It has been found that the dielectric loss in a cable (zzz) Wet flash-over and one minute rain test. During
is not proportional to square of the voltage as is the this test the insulator is sprayed constantly
case in most dielectrics. Also the loss angle of a cable with water and the same procedure as for
does not remain constant. The dielectric loss increases dry flash-over and dry one minute test is
in proportion to some power of voltage greater than followed.
second and the power factor rises with voltage. 3. Sample tests. These include mechanical tests,
Therefore measurements of loss angles with temperature cycle tests, porosity tests, puncture tests
different voltages is made and a curve plotted etc.
between loss angle and voltage. The curve should be
4. Routine tests. These tests are applied to all
flat and if there are variations in the loss angle, the
the insulators. The insulators are initially subjected to
cable will not work satisfactorily. Also the loss angle
a low voltage which is rapidly increased till a
should not change very much with temperature.
flash-over occurs every few seconds. The voltage is
Breakdown tests of the cables with voltages applied
maintained at this value for a minimum of 5 minutes
for different intervals of time are also done and time
or if failure occurs, for five minutes after the last
versus breakdown voltage curves are plotted.
punctured piece has been removed. The voltage is
17.14 HIGH VOLTAGE TESTS ON PORCELAIN gradually reduced to |rd of its value before supply is
switched off.
INSULATORS
The following tests are applied to porcelain The porcelain insulators used for communication
purposes are tested with high frequency undamped
insulators :
oscillations.
1. Power frequency tests. The frequency used is
between 25 to 100 Hz of approximately sinusoidal 17.15 TESTING OF ELECTRIC STRENGTH
waveform with peak value of voltage not to exceed OF INSULATING OILS
1.45 times the rms value. An extract of IS specifications 6792-1972 "Method
2. Flashover tests. Porcelain insulators are for determination of Electric strength of insulating
designed in such a way that their puncture voltage is oils" is given on next page.
High Voltage Measurements and Testing 53 ?
General. This method is primarily intended for Test method. The oil is poured in the dry and
the new insulating oils at the time of their delivery. clean cell and is stirred so that the impurities are
However, in principle, it is applicable to all classes of evenly distributed and there are no visible air bubbles.
new and used oils for transformers, circuit breakers, The temperature of oil is the same as that of ambient
oil filled cables and capacitors. air preferably 27°C, but a temperature range of 15°C to
The test method consists of subjecting the oil 35°C is acceptable.
contained in a specified apparatus, to an a.c. electric An increasing a.c. voltage of frequency 40-60 Hz is
field with a continuously increasing voltage till the oil applied to the electrodes. The rate of increase of
breaks down. voltage is uniform and is approximately equal to
Test cell. The test cell is transparent and 2 kV/s starting from zero to the value producing
non-absorbent. It is made of glass or plastic and has an breakdown. The breakdown voltage is the voltage
effective volume of 200-500 ml. It is preferably closed. reached during the test at the time first spark occurs
between electrodes. The test is carried out six times on
Two types of cells are used and they are shown in
the same cell filling. The electric strength is the
Figs. 17.45 and 17.46.
arithmetic mean of the six results obtained.
Electrodes. The electrodes may be made of
Electrical apparatus. The characteristics of the
copper, brass, bronze or stainless steel. The polished
electrical apparatus comply with the following
electrodes are either spherical (12.5 to 13.0 mm
requirements.
diameter) as shown in Fig. 17.45 or spherical surfaced
of the shape and dimensions as shown in Fig. 17.46. Transformer. The test voltage is obtained by
The electrodes • are mounted 2.5 mm apart with an using a step up transformer supplied form a.c. The
accuracy of ± 0.1 mm. The axis of the electrodes is low voltage side has a frequency of 40 to 62 Hz. The
immersed to a depth of approximately 40 mm. The primary voltage is gradually increased, either
electrodes are replaced as soon as pitting caused by manually or by an automatic control device. The
discharges is observed. voltage applied to the electrodes has approximately a
Fig. 17.46 Test cell (All dimensions in mm). Results. The test report should include
(z) Reference to the standard,
sinusoidal waveform such that peak factor is within (zz) breakdown voltages obtained during each
1.34 to 1.48 i.e., J2± 5%. The transformer and test,
associated equipment are designed to produce a (zzz) average of breakdown voltages,
minimum short circuit current of 20 mA for a voltage (zu) types of electrodes,
higher than 15 kV. In order to avoid damage to (u) frequency of test voltage and
electrodes the short circuit current is limited to 1 A, if (uz) oil temperature.
necessary, by addition of external impedance.
The extract of IS specification 335-1972
Protective gear. The test is carried out so as to "Specification for new insulating oils for transformers
and switch gear" is given below :
prevent high frequency oscillations as far as
possible. The electric strength (breakdown voltage) of new
insulated oil for transformers and switch gear should
In order to protect the equipment and to avoid have a minimum value of 3 kV/mm (rms). If this value
excessive decomposition of the oil at the instant of is not attained, the oil has to be treated. The
breakdown, a resistance, limiting the current is breakdown voltage after treatment should be atleast
inserted in the test cell circuit. The primary circuit of 5 kV/mm (rms).
the high voltage transformer is fitted with a circuit The maximum dielectric dissipation factor at 90°C
breaker operated by the current flowing, following the is 0.005. The resistivity is 13xlOloQm (minimum) at
breakdown of the sample, and with a delay not more 90°C and 500x 10l0Qm (minimum) at 27°C.
than 0.02 s. The circuit breaker is fitted with a no volt
Permittivity should be approximately 2.2 (- 0.001)
coil to protect equipment.
at 60°C.
High Voltage Measurements and Testing
Review Questions
1. Why is high voltage testing important for electrical the precautions taken when using sphere gaps for
power apparatus and insulating materials ? measurement of high voltages.
Describe briefly the different high voltage tests 9. Describe the rectified capacitor charging current
done on electrical apparatus. method for measurement of peak values of high
2. Describe the constructional details of a H.V. voltages. Describe its advantages and limitations.
transformer and explain the reasons for difference 10. Describe the working, advantages and disadvan
in construction of H.V. testing transformers and tages of the following types of voltmeters used for
power transformers. measurement of peak values of high voltages.
3. Explain the reasons for connecting H.V. transfor (?) Ryall crest voltmeter,
mers in cascade. Explain, with the help of a diagram,
(ii) Ionic wind voltmeter.
tlve cascade connections of two transformers.
11. Describe the Cockcroft Walton circuit for
4. Describe the different methods of voltage control
production of high voltage d.c.
used for high voltage test circuits. Explain their
applications, advantages and disadvantages. 12. Explain why transmission lines and cables, which
are used for power transmission and distribution
5. Draw the circuit diagram for high voltage testing of a.c. voltages, are tested with high voltage d.c.
at power frequencies. Explain the functions of the Describe the circuits used for high voltage d.c.
control and protective devices.
testing of cables. Describe why is it necessary to
6. Describe the different electrostatic type of establish an equivalence between d.c. and a.c. test
voltmeters used for measurement of r.m.s. value of voltages.
high voltages. Explain their advantages and 13. Describe the circuit of a single stage impulse
disadvantages. generator. Describe how surge voltages are
7. Explain the following potential divider methods generated by applying a step voltage to an RLC
for measurement of r.m.s. value of high voltages, series circuit.
(/) resistance potential divider, 14. Describe the working of Marx circuit used for
impulse testing. Explain the impulse testing of
(ii) capacitive potential divider and
transformers.
(iii) compensated capacitive potential divider.
15. Describe the various high voltage tests that are
8. Describe the use of sphere gaps for measurement carried out on porcelain insulators.
of peak voltages. Discuss the advantages and 16. Explain the method for testing the dielectric
disadvantages of using sphere gaps. Also describe strength of insulating oil according to IS specifications.
(c) the insulators may be used for communication 7. A Cockcroft Walton circuit for generation of high
purposes wherein the frequencies may be of voltage d.c. has n stages. If the voltage of the
the order of MHz secondary winding of the high voltage transformer
is Vm, the output voltage of the circuit is :
(d) all the above.
(a)nVm (b)2(«-l)Vw
3. If the sizes of power transformers and high voltage
testing transformers of equal kVA rating are (c)2(n+l)Vm (d)2nVm
compared : 8. The impulse voltage wave shape is defined as
(a) the size of a h.v. testing transformer is greater t-J t2 where :
than that of a power transformer (fl) t1 = time taken by the impulse voltage to rise to
(b) the size of a h.v. testing transformer is smaller its peak and
than that of a power transformer t2= time taken to fall to zero
(c) the size of a h.v. testing transformer is the same (b) t j = time taken by the impulse voltage to rise to
as that of a power transformer. its peak and
4. Cascade connection of transformers is normally t2 = time taken to fall to 50% of its peak
used when a single transformer cannot be used (c) = time taken by the impulse voltage to rise to
because the minimum test voltage : 50% of its peak and
(a) is about 100 kV (b) is about 500 kV
t2 = time taken to fall to zero
(c) is about 1000 kV
(d) none of the above.
(d) all the above.
9. In a Marx's circuit,
5. The voltage control circuits do not use resistance
potential dividers because : (a) the capacitors are charged in series and
discharged in series
(a) they involve a large power loss
(b) they cause distortion of waveform (b) the capacitors are charged in parallel and
discharged in parallel
(c) they do not give a smooth variation of voltage
(d) they have non-linear characteristics. (c) are charged in series and discharged in parallel
6. Sphere gaps are used for measurement of : (ii ) charged in parallel and discharged in series.
(a) instantaneous values of voltage 10. The electric strength of new insulating oil should
have a minimum strength (r.m.s.) of
(b) r.m.s. values of voltage
(a) 30 kV/mm (b) 3 kV/mm
(c) peak values of voltage
(c) 50 kV/mm (d) 5 kV/mm
(d) average values of voltage.
1. (b) 2. (d) 3. (fl) 4. (b) 5. (a) 6. (c) 7. (d) 8. (b) 9. (d) 10. (b)