0% found this document useful (0 votes)
107 views7 pages

Gen600 1.3 - Densei Lambda

The document describes a line of programmable power supply units. It provides details on the specifications, features, and applications of the Genesys power supply family, including output power range, efficiency, regulation performance, interfaces, and safety approvals.

Uploaded by

Richard bangcaya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views7 pages

Gen600 1.3 - Densei Lambda

The document describes a line of programmable power supply units. It provides details on the specifications, features, and applications of the Genesys power supply family, including output power range, efficiency, regulation performance, interfaces, and safety approvals.

Uploaded by

Richard bangcaya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

The GenesysTM family of programmable power supplies sets a new standard for flexible, reliable,

AC/DC power systems in OEM, Industrial and Laboratory applications.

Features include:
• Highest Power Density available 1500W in 1U
• Wide Range Input 85 - 265Vac Continuous, single phase, 47/63Hz
• Active Power Factor Correction 0.99
• Output up to 600V, Current up to 200A
• Built in RS232/RS485 Interface
• Software Calibration
• Last Setting Memory
• High Resolution 16 bits ADCs & DACs
• Reliable Encoders for Voltage and Current Adjustment
• Constant Voltage/Constant Current auto crossover
• Parallel Operation with Active Current Sharing
• Independent Remote ON/OFF and Remote Enable/Disable
• External Analog Programming and Monitoring
• Reliable Modular and SMT Design
• 19" Rack Mounted ATE and OEM applications
• Five Year Warranty
• Optional Isolated Analog Programming and Monitoring
• Optional GPIB (SCPI) Interface
• LabView® drivers ( LabView® is registered trademark of National Instruments Corporation )
Worldwide Safety Agency Approvals CE Mark for LVD and EMC Regulation

Applications
Genesys™ power supplies have been designed to meet the demands of a wide variety of applications.

Test and Measurement


Last setting memory simplifies test design and requires no battery backup.
Built in RS232/RS485 gives maximum system flexibility along with 0-5V and 0-10V, selectable analog programming
Wide range of available inputs allows testing of many different devices.
Semiconductor Burn-in
Safe Start may be enabled to restart at zero output to protect load.
Wide range input (85-265VAC) with Active Power Factor correction rides through input transients easily.
Component Test
High power density, zero stacking and single wire parallel operation give maximum system flexibility
Laser Diode
OVP is directly set on Voltage Meter, assuring accurate protection settings.
Current Limit Fold Back assures load is protected from current surges.
Heater Supplies
Smooth, reliable encoders enhance front panel control.
Remote analog programming is user selectable 0-5V or 0-10V.
RF Amplifiers and Magnets
Robust design assures stable operation under a wide variety of loads.
Excellent linearity in voltage and current mode.

1|Genesys™ 750W/1500W-1U
Front Panel Description

1. AC On/Off
2. Air Intake allows zero stacking for maximum system flexibility and power density
3. Reliable encoder controls Output Voltage and sets Address.
4. Volt Meter shows Output Voltage and directly displays OVP, UVL and Address settings.
5. Amp Meter also displays baud rate.
6. Reliable encoder controls Output Current and sets baud rate.
7. Function/Status LED's

• Alarm • Foldback Mode


• Fine Control • Remote Mode
• Preview Settings • Output On

8. Pushbuttons allow flexible user configuration


Coarse and Fine Voltage and Current Adjustment of Output
Preview Settings and Set Voltage while in Current Mode or with Output OFF
Set OVP and UVL Limits
Set Current Foldback
Local/Remote Mode and select Address and Baud Rate
Output ON/OFF and Auto Start/Safe Start Mode

Rear Panel Description

1. Remote/Local Output Voltage Sense Connections


2. DIP Switches select 0-5V or 0-10V Programming and other functions.
3. DB25 (Female) connector allows (Non-isolated) Analog Program and Monitor as well as other functions.
4. RS485 Out to other Genesys Power Supplies
5. RS232/RS485 IN Remote Serial Programming
6. Output Terminals are rugged bus bars for 6-60V Output, higher output voltage models have terminal block connector.
7. Exit air assures reliable operation when zero stacked
8. Wide-Range Input 85-265VAC continuous, 47/63Hz with Active Power Factor Correction (0.99)
AC Input Connector 750W: IEC320, 1500W: Screw terminal Model Shown
9. Position for Optional Isolated Analog Programming or GPIB Digital Interface model shown
|2
Genesys ™ 750W/1500W Specifications 750W 1500W
1.0 MODEL GEN 6-200 8-180 12.5-120 20-76 30-50 40-38 60-25 80-19 100-15 150-10 300-5 600-2.6 X
1.Rated output voltage(*1) V 6 8 12.5 20 30 40 60 80 100 150 300 600 X
2.Rated Output Current(*2) A 200 180 120 76 50 38 25 19 15 10 5 2.6 X
3.Rated Output Power W 1200 1440 1500 1520 1500 1520 1500 1520 1500 1500 1500 1560 X
4.Efficiency at 100/200Vac (*3) % 77/80 78/81 81/84 83/86 83/86 84/88 84/88 84/88 84/88 84/88 83/87 83/87 X X
1.0 MODEL GEN 6-100 8-90 12.5-60 20-38 30-25 40-19 60-12.5 80-9.5 100-7.5 150-5 300-2.5 600-1.3 X
1.Rated output voltage (*1) V 6 8 12.5 20 30 40 60 80 100 150 300 600 X
2.Rated Output Current (*2) A 100 90 60 38 25 19 12.5 9.5 7.5 5 2.5 1.3 X
3.Rated Output Power W 600 720 750 760 750 760 750 760 750 750 750 780 X
1.1 CONSTANT VOLTAGE MODE
1.Max.line regulation ( 0.01% of Vo+ 2mV )(*4) mV 2.6 2.8 3.3 4 5 6 8 10 12 17 32 62 X X
2.Max load regulation ( 0.01% of Vo+2mV )(*5) mV 2.6 2.8 3.3 4 5 6 8 10 12 17 32 62 X X
3.Ripple and noise p-p 20MHz mV 60 60 60 60 60 60 60 80 80 100 125 300 X X
4.Ripple r.m.s 5Hz~1MHz mV 8 8 8 8 8 8 8 8 8 10 25 60 X X
5.Remote sense compensation/line V 1 1 1 1 1.5 2 3 4 5 5 5 5 X X
6.Temp. coefficient PPM/°C 100PPM/°C from rated output voltage,following 30 minutes warm up X X
7.Up-prog. response time, 0~Vomax mS 80mS , N.L/F.L , resistive load 150mS , N.L/F.L , resistive load X X
8.Down-prog response time full-load mS 10 50 80 150 X X
9.Down-prog response time no-load mS 500 600 700 800 900 1000 1100 1200 1500 2000 2500 4000 X X
10.Transient response time (*8) Less than 1mSec for models up to and including 100V. 2msec for models above 100V X X
1.2 CONSTANT CURRENT MODE
1.Max.line regulation (0.01% of Io+ 2mA)(*4) mA 12 11 8 5.8 4.5 3.9 3.25 2.95 2.75 2.5 2.25 2.13 X
2.Max.load regulation (0.01% of Io+5mA)(*6) mA 15 14 11 8.8 7.5 6.9 6.25 5.95 5.75 5.5 5.25 5.13 X
3.Ripple r.m.s 5Hz~1MHz . (*7) mA 200 180 120 76 63 48 38 29 23 18 13 8 X
1.Max.line regulation (0.01% of Io+ 2mA)(*4) mA 2 2 2 2 2 2 2 2 2 2 2 2 X
2.Max.load regulation (0.01% of Io+5mA)(*6) mA 5 5 5 5 5 5 5 5 5 5 5 5 X
3.Ripple r.m.s 5Hz~1MHz .(*7) mA 400 360 240 152 125 95 75 57 45 35 25 12 X
4.Temp. coefficient PPM/°C 100PPM/°C from rated output voltage,following 30 minutes warm up X X
1.3 PROTECTIVE FUNCTIONS
1. OCP 0~105% Constant Current X X
2. OCP Foldback Output shut down when power supply change from CV to CC. User selectable. X X
3. OVP type Inverter shut-down, manual reset by AC input recycle or by OUT button X X
4. OVP trip point 0.5~7.5V 0.5~10V 1~15V 1~24V 2~36V 2~44V 5~66V 5~88V 5~110V 5~165V 5~330V 5~660V X X
5. Over Temp. Protection User selectable , latched or non latched X X
1.4 ANALOG PROGRAMMING AND MONITORING
1.Vout Voltage Programming 0~100%, 0~5V or 0~10V, user select. Accuracy and linearity:+/-0.5% of rated Vout. X X
2.Iout Voltage Programming 0~100%, 0~5V or 0~10V, user select. Accuracy and linearity:+/-1% of rated Iout. X X
3.Vout Resistor Programming 0~100%, 0~5/10Kohm full scale,user select.,Accuracy and linearity:+/-1% of rated Vout. X X
4.Iout Resistor Programming 0~100%, 0~5/10Kohm full scale,user select. Accuracy and linearity:+/-1.5% of rated Iout. X X
5.On/Off control (rear panel) By electrical. Voltage: 0~0.6V/2~15V,or dry contact ,user selectable logic X X
6.Output Current monitor 0~5V or 0~10V , accuracy:1% , user selectable X X
7.Output Voltage monitor 0~5V or 0~10V ,accuracy:1% ,user selectable X X
8.Power Supply OK signal 5V-OK, 0V-Fail 500ohm impedance X X
9. CV/CC indicator CV: TTL high (4~5V) source: 10mA, CC: TTL low (0~0.4V):10mA X X
10. Enable/Disable Dry contact. Open:off , Short: on. Max. voltage at Enable/Disable in: 6V X X
1.5 FRONT PANEL
1.Control functions Vout/ Iout manual adjust by separate encoders (coarse and fine adjustment selectable) X X
OVP/UVL manual adjust by Volt. Adjust encoder X X
AC on/off, Output on/off, Re-start modes (auto, safe), Foldback control (CV to CC), Go to local control X X
Address selection by Voltage (or current) adjust encoder. No of addresses:31 X X
RS232/485 and IEEE488.2 selection by IEEE enable switch and DIP switch X X
Baud rate selection: 1200,2400,4800,9600 and 19,200 bps X X
2.Display Voltage 4 digits , accuracy: 0.5%+/-1 count X X
Current 4 digits, accuracy: 0.5%+/-1 count X X
3.Indications Voltage, Current, Alarm, Fine, Preview, Foldback, Local, Output On X X

1.6 Interface RS232&RS485 or Optional GPIB Interface 750W 1500W


Model V 6 8 12.5 20 30 40 60 80 100 150 300 600 X X
Remote Voltage Programming (16 bit)
Resolution (0.012% of Vomax) mV 0.72 0.96 1.50 2.40 3.60 4.80 7.2 9.6 12 18 36 72 X X
Accuracy (0.05%Vomax+0.05% of Vo Actual Output) mV 6.0 8.0 12.5 20 30 40 60 80 100 150 300 600 X X

Remote Current Programming (16 bit)


Resolution (0.012% of Iomax) mA 12 10.8 7.2 4.56 3.0 2.28 1.50 1.14 0.90 0.60 0.30 0.16 X
Accuracy (0.05% of Iomax+0.05% of Io Actual Output) mA 10 9 6 3.8 2.5 1.9 1.25 0.95 0.75 0.5 0.25 0.13 X
Resolution (0.012% of Iomax) mA 24 21.6 14.4 9.12 6 4.56 3.0 2.28 1.80 1.20 0.60 0.32 X
Accuracy (0.05% of Iomax+0.05% of Io Actual Output) mA 20 18 12 7.6 5 3.8 2.5 1.9 1.50 1 0.5 0.26 X

Readback Voltage
Resolution (0.012% of Vomax) mV 0.72 0.96 1.50 2.40 3.60 4.80 7.2 9.6 12 18 36 72 X X
Accuracy (0.1%Vomax+0.1% of Vo Actual Output) mV 12 16 25 40 60 80 120 160 200 300 600 1200 X X

Readback Current
Resolution (0.012% of Iomax ) mA 12 10.8 7.2 4.56 3.0 2.28 1.50 1.14 0.9 0.60 0.30 0.16 X
Accuracy (0.1% of Iomax+0.3% of Io Actual Output) mA 400 360 240 152 100 76 50 38 30 20 10 5.2 X
Resolution (0.012% of Iomax ) mA 24 21.6 14.4 9.12 6 4.56 3.0 2.28 1.80 1.20 0.60 0.32 X
Accuracy (0.1% of Iomax+0.3% of Io Actual Output) mA 800 720 480 304 200 152 100 76 60 40 20 10.4 X

OVP Programming
Resolution (0.1% of Vomax) mV 6 8 12 20 29 39 59 78 98 146 293 586 X X
Accuracy (1% of Vomax) mV 60 80 125 200 300 400 600 800 1000 1500 3000 6000 X X
*1: Minimum voltage is guaranteed to maximum 0.2% of Vomax. *3: At maximum output power. *5: From No-load to Full-load, constant input voltage.
*2: Minimum current is guaranteed to maximum 0.4% of Iomax. *4: 85~132Vac or 170~265Vac, constant load. *6: For load voltage change, equal to the unit voltage rating, constant input voltage.
*7: For 6V models the ripple is measured at 2~6V output voltage and full output current. For other models, the ripple is measured at 10~100% output voltage and full output current.
*8: Time for the output voltage to recover within 0.5% of its rated for a load change 10~90% of rated output , Output set-point:10~100%.
Accuracy -Values have been calculated at Vomax & Io max

3|Genesys™ 750W/1500W-1U
General Specifications Genesys™ 750W/1500W
2.1 INPUT CHARACTERISTICS
1. Input voltage/freq. (*1) 85~265Vac continuous, 47~63Hz, single phase
2. Power Factor 0.99 @100/200Vac, rated output power.
3. EN61000-3-2,3 compliance Complies with EN61000-3-2 class A and EN61000-3-3 at 20~100% output power.
4. Input current 100/200Vac 750W :10.5A / 5A, 1500W :21A / 11A
5. Inrush current 100/200Vac 750W :Less than 25A, 1500W :Less than 50A
6. Hold-up time More than 20mS , 100Vac , at 100% load.

2.2 POWER SUPPLY CONFIGURATION


1. Parallel Operation Up to 4 units in master/slave mode with single wire current balance connection
2. Series Operation Up to 2 units. with external diodes. 600V Max to Chassis ground

2.3 ENVIRONMENTAL CONDITIONS


1. Operating temp 0~50 °C, 100% load.
2. Storage temp -20~70°C
3. Operating humidity 30~90% RH (no condensation).
4. Storage humidity 10~95% RH (no condensation).
5. Vibration MIL-810E, method 514.4 , test cond. I-3.3.1 . The EUT is fixed to the vibrating surface.
6. Shock Less than 20G , half sine , 11mSec. Unit is unpacked.
7. Altitude Operating: 10000ft (3000m) , Non operating: 40000ft (12000m).

2.4 EMC
1.Applicable standards: EN55024
2.ESD IEC1000-4-2. Air-disch.-8KV, contact disch.-4KV
3.Fast transients IEC1000-4-4. 2KV
4.Surge immunity IEC1000-4-5. 1KV line to line, 2KV line to ground
5.Conducted immunity IEC1000-4-6, 3V
6.Radiated immunity IEC1000-4-3, 3V/m
7.Conducted emission EN55022B,FCC part 15J-B,VCCI-2
8.Radiated emission EN55022A,FCC part 15-A,VCCI-1
9.Voltage dips EN61000-4-11
10. Conducted emission EN55022B, FCC part 15-B, VCCI-2.
11. Radiated emission EN55022A, FCC part 15-A, VCCI-1.

2.5 SAFETY
1.Applicable standards: CE Mark, UL60950,EN60950 listed. Vout<60V:Output is SELV , IEEE/Isolated analog are SELV.
60<Vout<400V: Output is hazardous, IEEE/Isolated analog are SELV.
400<Vout<600V:Output is hazardous, IEEE/Isolated analog are not SELV.
2.Withstand voltage Vout<60V models :Input-Outputs (SELV): 3.0KVrms 1min, Input-Ground: 2.0KVrms 1min.
60<Vout<600V models: Input-Haz. Output: 2.5KVrms 1min, Input-SELV: 3KVrms 1min.
Hazardous Output.-SELV: 1.9KVrms 1min, Hazardous Output-Ground:1.9KVrms 1min.
Input-Ground: 2KVrms 1min.
3.Insulation resistance More than 100Mohm at 25°C , 70% RH.

2.6 MECHANICAL CONSTRUCTION


1. Cooling Forced air flow: from front to rear. No ventilation holes at the top or bottom of the chassis Variable fan speed.
2. Dimensions (WxHxD) W: 422.8mm, H: 43.6mm, D: 432.8mm (excluding connectors, encoders, handles etc..)
3. Weight 750W: 7Kg (15.4 Lbs) 1500W: 8.5Kg (18.7 Lbs)
4. AC Input connector 750W: AC Inlet IEC320.
1500W: screw terminal block, Phoenix P/N: FRONT-4-H-7.62 , with strain relief
5.Output connectors 6V to 60V models: bus-bars (hole Ø 8.5mm). 80V to 600V models :terminal block ,Phoenix P/N: FRONT-4-H-7.62

2.7 RELIABILITY SPECS


1. Warranty 5 years.

*1: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be described as 100-240Vac (50/60Hz).

Outline Drawing Genesys™ 750W/1500W Units

NOTE
1. PLUG CONNECTORS INCLUDED WITH THE POWER SUPPLY
2. CHASSIS SLIDES MOUNTING HOLES #10-32 MARKED "A"
GENERAL DEVICES P/N: CC301-00-S160 OR EQUIVALENT

|4
Genesys™ Power Parallel and Series Configurations

Parallel operation - Master/ Slave:


Active current sharing allows up to 4 units to be connected in an auto
parallel configuration for four times the output power.

Series operation
Up to two units may be connected in series to increase the output
voltage or to provide bipolar output. (Max 600V to Chassis Ground)

Remote Programming via RS232&RS485 Interface


Standard Serial Interface allows chain control of up to 31 power
supplies on the same bus with built in RS232&485 Interface

Programming Options (Factory installed)


Digital Programming via IEEE Interface P/N: IEEE
• IEEE 488.2 Compliant • SCPI Compliant
• Program Voltage • Program Current
• Measure Voltage • Measure Current
• Over Voltage setting and shutdown • Current Foldback shutdown
• Error and Status Messages

Isolated Analog Programming


Four Channels to Program and Monitor Voltage and Current
Isolation allows operation with floating references and difficult electrical environments.
Choose between programming with Voltage or Current.
Connection via Removable terminal block P/N: Phoenix MC1,5/8-ST-3.81

P/N: IS510 - Voltage Programming, user selectable 0-5V or 0-10V signal


Power supply Voltage and Current Programming accuracy +/-1%
Power supply Voltage and Current Monitoring accuracy +/-1.5%
P/N: IS420 - Current Programming with 4-20mA signal
Power supply Voltage and Current Programming accuracy +/-1%
Power supply Voltage and Current Monitoring accuracy +/-1.5%

5|Genesys™ 750W/1500W-1U
Power Supply Identification / Accessories
How to order
GEN 600 - 2.6 - -
Factory Options AC Cable option is 750W only
Series Output Output Option: IEEE Region: E - Europe
Name Voltage Current IS510 J - Japan
(0~600V) (0~2.6A) IS420 I - Middle East
Models 750/1500W U - North America
Output Output Output Output Output Output
Model Voltage Current Power Model Voltage Current Power
VDC (A) (W) VDC (A) (W)
GEN6-100 0~100 600 GEN60-12.5 0~12.5 750
GEN6-200 0~6V 0~200 1200 GEN60-25 0~60V 0~25 1500
GEN8-90 0~90 720 GEN80-9.5 0~9.5 760
GEN8-180 0~8V 0~180 1440 GEN80-19 0~80V 0~19 1520
GEN12.5-60 0~60 750 GEN100-7.5 0~7.5 750
GEN12.5-120 0~12.5V 0~120 1500 GEN100-15 0~100V 0~15 1500
GEN20-38 0~38 760 GEN150-5 0~5 750
GEN20-76 0~20V 0~76 1520 GEN150-10 0~150V 0~10 1500
GEN30-25 0~25 750 GEN300-2.5 0~2.5 750
GEN30-50 0~30V 0~50 1500 GEN300-5 0~300V 0~5 1500
GEN40-19 0~19 760 GEN600-1.3 0~1.3 780
GEN40-38 0~40V 0~38 1520 GEN600-2.6 0~600V 0~2.6 1560

Factory option P/N


RS232/485 Interface built in Standard -
GPIB Interface IEEE
Voltage Programming Isolated analog interface IS510
Current Programming Isolated analog interface IS420
AC Cords sets (750W only)
Region Europe Japan Middle East North America
Output Power 750W 750W 750W 750W
AC Cords 10A/250 Vac L=2m 13A/125 Vac L=2m 10A/250 Vac L=2m 13A/125 Vac L=2m
Wall Plug INT'L 7/VII SI-32 NEMA 5-15P
Power Supply IEC320-C13 IEC320-C13 IEC320-C13 IEC320-C13
Connector

Part Number P/N: GEN/E P/N: GEN/J P/N: GEN/I P/N : GEN/U

Accessories
1.Communication cable
RS232/RS485 Cable is used to connect the power supply to the PC Controller
Mode RS485 RS232 RS232

PC Connector DB-9F DB-9F DB-25F


Communication Cable Shield Ground L=2m Shield Ground L=2m FShield Ground L=2m
Power Supply Connector EIA/TIA-568A (RJ-45) EIA/TIA-568A (RJ-45) EIA/TIA-568A (RJ-45)
P/N GEN/485-9 GEN/232-9 GEN/232-25

Serial link cable*


Chaining Power Supply to Power Supply up to 31 GEN units
Mode Power Supply Connector Communication Cable P/N
RS485 EIA/TIA-568A (RJ-45) Shield Ground L=50cm GEN/RJ45
* Included with the power supply