0% found this document useful (0 votes)
38 views7 pages

Catalog

The Trip Circuit Supervision Relay monitors and supervises the integrity of circuit breaker trip coils and wiring circuits. It generates an alarm if the trip circuit is disconnected or broken. It uses two opto-couplers to sense current flow and check the circuit breaker position. A green LED indicates healthy operation while a red LED with relay drop-off shows faults like loss of voltage or broken circuits. It is used to monitor circuit breaker control circuits and detect failures.

Uploaded by

Arjun Parlikkatt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views7 pages

Catalog

The Trip Circuit Supervision Relay monitors and supervises the integrity of circuit breaker trip coils and wiring circuits. It generates an alarm if the trip circuit is disconnected or broken. It uses two opto-couplers to sense current flow and check the circuit breaker position. A green LED indicates healthy operation while a red LED with relay drop-off shows faults like loss of voltage or broken circuits. It is used to monitor circuit breaker control circuits and detect failures.

Uploaded by

Arjun Parlikkatt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

s

www.siemens.com/energy

Trip Circuit Supervision Relay (7PJ13)


Better protection and more efficiency for your power system

Answers for infrastructure and cities.


Trip Circuit Supervision Relay

7PJ13

Description current of 0.7 mA to 1.5 mA and sensing the flow of current


with two opto-couplers. The circuit breaker contact indicates
Trip Circuit Supervision Relay is an electronic-circuit based the status of relay whether the circuit breaker is in open
relay which is used to monitor and supervise the integrity position or closed position.
of circuit breaker’s trip coil and other wiring circuits of
low-voltage and medium-voltage network. Trip Circuit The front panel of Trip Circuit Supervision Relay comprises
Supervision Relay is connected with a circuit breaker to of single LED with dual colored to indicate the status of
monitor the trip circuit positions (open or closed). process.

Trip Circuit Supervision Relay generates a trip circuit failure In a healthy condition, the Green LED flashes and the output
alarm, either if the trip circuit supply is disconnected or if relay reaches the pick-up condition. In the fault condition,
the trip circuit connection is changed to an open circuit. Trip the Red LED flashes and the output relay reaches the drop-
circuit continuity is measured by supplying the supervision off condition and operates after a delay of 500 ms.

Features
The salient features of Trip Circuit Supervision Relay are:
 Universal auxiliary voltage range with very low burden
(i.e.) 24 V to 230 V AC/DC at less than 4 watts
 Universal supervision voltage range (i.e.) 24 V to
230 V DC
 Compact-in-size 48x96 mm
 Fitted with flush-mounting
 Continuous supervision of trip circuit in Pre-closed, Post-
closed condition, and latched trip condition
 Detects faults such as Auxiliary voltage loss and circuit
breakage in supervised circuits
 Indicates operational status by single LED with dual color
 Relay has been type tested in accordance with IEC60255
standards
Figure 1.1 - Block diagram of Trip Circuit Supervision Relay

2
Trip Circuit Supervision Relay

Applications Supervision in post-close condition


Trip Circuit Supervision Relay is used in the following field After the tripping circuit is completed, a small amount of
applications: sensing current flows through TS1, circuit breaker auxiliary
contacts (52a) and tripping coil. Trip Circuit Supervision
 Used for monitoring activities. The trip circuit wiring
Relay indicates a healthy condition by flashing the Green
is supervised from the positive supply to the negative
LED.
supply when the circuit breaker is in open position or
closed position. If the tripping circuit becomes an open circuit or loss of
supply voltage, the unhealthy condition of Trip Circuit
 Used for detecting and generating circuit breaker alarm,
Supervision Relay is indicated by flashing Red LED and issue
if the trip circuit supply is failed.
a control command by drop-off contacts.
 Used to generate an alarm if the trip signal is received
but the circuit breaker fails to operate.

Mounting Instructions
Trip Circuit Supervision Relay comprises of all the mounting
elements required for the mounting. To flush mount the Trip
Circuit Supervision Relay, the following requirements should
be satisfied:
 Cut a hole in the panel with a measurement of
45mm x 92mm (HxW).
 Carry out all the required internal wiring connections.
 Flush Trip Circuit Supervision Relay into panel and lock
with the clamps.

Supervision Operation Figure 1.3 - Supervision in post-close condition

Trip Circuit Supervision Relay contact operates in the


Supervision in latched trip condition
following 3 supervision conditions:
After the tripping circuit is completed, a small amount of
Supervision in pre-close condition sensing current flows through TS2, circuit breaker auxiliary
contacts (52b) and tripping coil. Trip Circuit Supervision
After the tripping circuit is completed, a small amount of
Relay indicates a healthy condition by flashing the Green
sensing current flows through TS1, TS2, circuit breaker
LED.
auxiliary contacts (52b), and tripping coil. Trip Circuit
Supervision Relay indicates a healthy condition by flashing If the tripping circuit becomes an open circuit or loss of
the Green LED. supply voltage, the unhealthy condition of Trip Circuit
Supervision Relay is indicated by flashing Red LED and issue
If the tripping circuit becomes an open circuit or loss of
a control command by drop-off contacts.
supply voltage, an unhealthy condition of Trip Circuit
Supervision Relay is indicated by flashing Red LED and issue
a control command by drop-off contacts.

Figure 1.2 - Supervision in pre-close condition Figure 1.4 - Supervision in latched trip condition

3
Trip Circuit Supervision Relay

MLFB (Ordering Code)


Use the following ordering information to order Trip Circuit Supervision Relay.

Variants Order Number

7 P J 1 3 2 1 - 5 A A 2 1 - 0 A A 0

Relay Type
Trip Circuit Supervision Relay 3
Number of Binary Inputs
Element 2 2
Contact Reset Type
Self Reset 1
Auxiliary Voltage Range
24 V - 230 V DC/AC 5
Contact Arrangement - NO
0 NO A
Contact Arrangement - NC
0 NC A
Contact Arrangement - CO
2 CO 2
Binary Input Range
24 V - 230 V DC 1

Figure 1.5 - MLFB of Trip Circuit Supervision Relay

Terminal Diagram
The terminal diagram is located on the top of Trip Circuit Table 1-2 Binary terminals specification
Supervision Relay housing and displays the terminal
Terminal number Terminal name Description
numbers and terminals.
K2-(1) BI1 Binary Input 1-1
(2) BI1 Binary Input 1-2
(3) - -
(4) BI2 Binary Input 2-1
(5) BI2 Binary Input 2-2
(6) - -
(7) COM-1 Common
(8) NC-1 Normal Closed
(9) NO-1 Normal Open
(10) COM-2 Common
(11) NC-2 Normal Closed
(12) NO-2 Normal Open
Figure 1.6 - Terminal Diagram of Trip Circuit Supervision Relay

Table 1-1 Auxiliary terminals specification


Terminal number Terminal name Description
K1-(1) +~ Auxiliary Voltage Positive
(2) -~ Auxiliary Voltage Negative
(3) -
(4) E Earth

4
Trip Circuit Supervision Relay

Dimensional Drawings
This section displays the different dimensional views of Trip Circuit Supervision Relay.

Front view Panel-cut out view

Top view Right-side view

Note: All dimensions are in mm.

Technical Specifications
Power Supply
Parameter Value
Auxiliary voltage range UN DC 24 V to DC 230 V
AC 24 V to AC 230 V
Auxiliary voltage operating range 75% - 115%
Input power consumption <4W
Operate time > 500 ms and < 800 ms
Reset Time < 100 ms
Rate of Operations 350 operations per hour
Mechanical life (Loaded) 10,000 Operations
(At rated current of resistive load)
Number of contacts 2 C/O contacts
Contact details Rated voltage AC 250 V
DC 250 V
Rated current AC 5 A
Make and carry for 0.5 s AC 10 A
Make and carry for 3 s AC 8 A
Break Breaking capacity for DC with circuit time-constant
L/R < 40 ms, at DC 48 V/110 V/220 V 1 A/0.25 A/0.15 A

5
Trip Circuit Supervision Relay

Binary Inputs External Interfaces


Parameter Value Parameter Value
Input voltage range DC DC 24 V to DC 230 V Power supply (1 No) Header: 4 Pin
Cabling-type: standard wire, unshielded,
Input voltage range DC tolerance 75% - 115%
max. 2.5 mm²
Input power consumption <1 W
Binary inputs (2 Nos) and Header: 12 Pin
Isolation AC 2 kV Contact outputs (2 Nos) Cabling-type: standard wire, unshielded,
max. 2.5 mm²

Type Testing
This section describes about the type testing performed with Trip Circuit Supervision Relay under different environmental
conditions.

Type Testing
Test Reference Test Levels
Insulation Resistance IEC 60255-5, Insulation resistance >100 M ohm at 500 V DC
IEC 60255-27
Hi Voltage (Dielectric) Voltage IEC 60255-5, 2 kV, 50 Hz, 1 min
IEC 60255-27 Between all terminals and with respect to earth terminal
Between Auxiliary terminal and contacts terminals
Between Auxiliary terminal and Supervision circuit terminals
Between Supervision terminals and contacts terminals
1.0 kV r.m.s AC, 1 min across changeover relay contacts
Impulse Voltage Withstand Test IEC 60255-5, 5.0 kV, 1.2/50 μs, 0.5 J
IEC 60255-27 Between all terminals and with respect to earth terminal
Between Auxiliary terminal and contacts terminals
Between Auxiliary terminal and Supervision circuit terminals
Between Supervision terminals and contacts terminals
1 MHz Burst High Frequency IEC 60255-22-1 Common-mode test voltage: 2.5 kV
Disturbance Test Differential test voltage: 1.0 kV
Ports are Auxiliary Input, Supervision Inputs, Output Contacts
Earth Test duration: 2 s
Source impedance: 200 Ohm
Immunity to Electrostatic IEC 60255-22-2 Class III, 8 kV discharge in air to all LEDs
Discharge Front insulated surface 6 kV point contact discharge to any metallic part of the front of the
product
Electrical Fast Transient IEC 60255-22-4 Test severity Amplitude:
or Power port: 4 kV, burst frequency 5 kHz
Burst Requirements Other ports: 4 kV, burst frequency 5 kHz
Surge Immunity Test IEC 60255-22-5 Time to half-value: 1.2/50 µs
Amplitude: 2 kV between all groups and case earth (CM)
Auxiliary port R=10 Ω, C=9 μF, For Input/Output port R=40, C=0.5 μF
Amplitude: 1 kV between terminals of each group (DM)
Auxiliary port R=0, C=18 μF, For Input/Output Port R=40, C=0.5 μF
Immunity to Radiated IEC 60255-22-3 Class III:
Electromagnetic Energy Test field strength, frequency band 80 MHz to 1000 MHz: 1400 MHz to 2700 MHz 10 V/m
Test using AM: 1 kHz/80%
Radiated Immunity from IEC 60255-22-3 10 V/m, 900 MHz
Digital Radio
Telephones
Immunity to Conducted IEC 60255-22-6 Disturbing test voltage:10 V unmodulated r.m.s
Disturbances Induced by Radio 0.15 MHz to 80 MHz, Source Impedance:150, 80% AM (1 kHz)
Frequency Fields
Power Frequency IEC 61000-4-8 Level 4,
Magnetic 30 A/m applied continuously
Field Immunity 300 A/m applied for 3 s
Conducted Emissions IEC 60255-25 0.15 MHz - 0.5 MHz, 79 dBµV (quasi peak), 66 dBµV (average)
0.5 MHz - 30 MHz, 73 dBµV (quasi peak), 60 dBµV (average)
Radiated Emissions IEC 60255-25 30 MHz - 230 MHz, 40 dBµV/m at 10 m measurement distance
230 MHz - 1 GHz, 47 dBµV/m at 10 m measurement distance

6
Trip Circuit Supervision Relay

Test Reference Test Levels


Power Supply Test IEC 60255-11 Voltage Variations: 18 V - 265 V
Voltage interruptions 18 V, 10 ms
Voltage interruptions 110 V, 50 ms
Ripple in DC voltage: Max 15% of DC value
Gradual shutdown/start-up in auxiliary power supply voltage
Reversal of DC power supply polarity
Vibration Test IEC 60255-21-1 Response Class I, 10 Hz - 150 Hz, 0.5 g, 3 axis,
Endurance Class I, 10 Hz - 150 Hz, 1.0 g, 3 axis
Shock and Bump IEC 60255-21-2 Shock response, Class I, 5 g, 11 ms
Shock withstand, Class I, 15 g, 11 ms
Bump Class I, 10 g, 16 ms
Seismic Test IEC 60255-21-3 In single axis sine sweep in X-axis sweep (@a sweep rate of 1 octave/min) vibration in the
frequency range (5 Hz - 40 Hz) at amplitude of 3.5 mm or 1.0 gn (whichever is less)
In single axis sine sweep in Y-axis sweep (@a sweep rate of 1 octave/min) vibration in the
frequency range (5 Hz - 40 Hz) at amplitude of 1.5 mm or 0.5 gn (whichever is less)
Degree of Protection IEC 60529, IP54 Front side
IEC 60255-27 IP20 Rear Terminal side
Cold Test IEC 60068-2-1 -10°C, 96 hours
Dry Heat Test IEC 60068-2-2 +55°C, 96 hours
Storage Test IEC 60068-2-1, -25°C to +70°C, 16 hours
IEC 60068-2-2
Damp Heat Test, Cyclic IEC 60068-2-30 6 days at 95% RH and +40 ºC
Rated Burden of Auxiliary and IEC60255-6 Auxiliary port burden at 24 V, 110 V, 220 V DC/AC
Supervision Circuit Supervision port burden at 24 V, 110 V, 220 V DC/AC
Contact Performance at defined IEC60255-6 10,000 mechanical operations at the rate of 350 operations per hour
rate of operation
Contact Test IEC60255-23 Making capacity, Make and carry capacity, Breaking capacity

Product Safety Test as per IEC60255-27


Test Reference Test Levels
Clearances and Creepage Clearances and creepage distances between external circuits ≥ 4 mm
Distances Test mutual and to the enclosure
IP Rating For Unit Front side IP54
For Unit Rear Terminal side IP20
Impulse Voltage • Test voltage: 5 kV After test the relay should operate
• Rise time/time to half-value: 1.2/50 µs
• Output energy: 0.5 J
AC or DC Dielectric Voltage • Test voltage between all live contacts and earth: 500 V DC After test the relay should operate
• Test duration: > 5 s
• Test voltage (AC): 2 kV
• Test frequency: 50 Hz
• Test duration: 1 min
Insulation Resistance • Test voltage: 500 V DC > 100 Mohm
• Test duration: > 5 s
Protective Bonding Resistance • Test voltage: <12 V AC/DC < 0.1 Ohm
• Test duration: 1 min
• Bonding resistance
Protective Bonding Continuity Accessible conductive parts should be bonded with the protective Low current continuity test
conductor terminal
Flammability of insulating • Terminals • IEC 60695-11-10, Class V-2, or Better
materials, components and fire • Terminal Mounting • IEC 60695-11-10, Class V-1, or Better
enclosures • Wiring • IEC 60695-11-10, Class V-1, or Better
• Components Mounting • IEC 60695-11-10, Class V-2, or Better
• Enclosure • IEC 60695-11-10, Class V-1, or Better
Single-fault Condition • Assessment of The equipment shall not present a risk of
• Insulation between circuits and parts electric shock or fire after a single-fault
• Compliance with requirements for protection against the spread test
of fire
• Overloads
• Intermittently rated resistors
• Compliance with requirements for mechanical protection

You might also like